Manual For Level Fmr57
Manual For Level Fmr57
Application
T
Continuous, non-contact level measurement in
powdery to granular bulk solids
Features FMR56:
• Attractively-priced basic device for standard process
conditions, as for example in bulk cargo silos and
storage tanks
• PP-cladded horn antenna
Your benefits
• Reliable measurement even for changing product and
D
process conditions
• Integrated data memory (HistoROM) for high
availability
• Intuitive operating menu in national languages for
easy commissioning
• Simple integration into control or asset management
systems
• Exact diagnostic and process information to assist fast
decisions
• International approvals for use in hazardous areas
• 5-point linearity protocol
• SIL2 according to IEC 61508, SIL3 in case of
homogeneous or heterogeneous redundancy
• System integration via HART/PROFIBUS PA (Profile
3.02)/FOUNDATION Fieldbus
TI01042F/00/EN/01.12
71162681
Table of contents Micropilot FMR56, FMR57
Table of contents
T
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Operation with remote display and operating module FHX50 . . 68
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
System integration via Fieldgate . . . . . . . . . . . . . . . . . . . . . 72
Linearization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Protocol-specific data . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Certificates and approvals . . . . . . . . . . . . . . . . . . . . 73
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device plug connectors . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
14
21
22
24
F
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C-Tick symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dual seal according to ANSI/ISA 12.27.01 . . . . . . . . . . . . . .
Functional Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AD2000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure Equipment Directive . . . . . . . . . . . . . . . . . . . . . .
73
73
73
73
73
73
73
A
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Marine certificate (in preparation) . . . . . . . . . . . . . . . . . . . 73
Power supply failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Radio standard EN302729-1/2 . . . . . . . . . . . . . . . . . . . . . 73
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Radio standard EN302372-1/2 . . . . . . . . . . . . . . . . . . . . . 74
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
FCC / Industry Canada . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
CRN approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Track record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Other standards and guidelines . . . . . . . . . . . . . . . . . . . . . 75
R
Performance characteristics . . . . . . . . . . . . . . . . . . . 27
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . 27
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . 76
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . 27
5-point linearity protocol (in preparation) . . . . . . . . . . . . . . . 76
Measured value resolution . . . . . . . . . . . . . . . . . . . . . . . . 27
Customized parametrization . . . . . . . . . . . . . . . . . . . . . . . 77
Reaction time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Influence of ambient temperature . . . . . . . . . . . . . . . . . . . 28
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
D
Symbol Meaning
DANGER!
DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious
A0011189-EN
or fatal injury.
WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious
A0011190-EN
or fatal injury.
CAUTION!
CAUTION This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor
A0011191-EN
or medium injury.
NOTICE!
T
NOTICE This symbol contains information on procedures and other facts which do not result in personal
A0011192-EN
injury.
Electrical symbols
Symbol Meaning
A0011197
A0011198
Direct current
Alternating current
F
A terminal to which DC voltage is applied or through which direct current flows.
A terminal to which alternating voltage is applied or through which alternating current flows.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
A0011200
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential
A0011201
equalization line or a star grounding system depending on national or company codes of practice.
Symbol Meaning
Allowed
Indicates procedures, processes or actions that are allowed.
A0011182
Preferred
Indicates procedures, processes or actions that are preferred.
A0011183
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0011194
100%
D
E
F
T
L
0%
å1
F
Setup parameters of the Micropilot
A0017872
A
R Reference point of the measurement (lower edge of the flange or threaded connection)
E Empty calibration ( = zero)
F Full calibration (= span)
D Measured distance
L Level (L = E - D)
Input
The reflected radar impulses are received by the antenna and transmitted into the electronics. A
R
microprocessor evaluates the signal and identifies the level echo caused by the reflection of the radar impulse
at the product surface. The unambiguous signal identification is accomplished by the PulseMaster® eXact
software together with the Multi-echo tracking algorithms, based on many years of experience with time-of-
flight technology.
The distance D to the product surface is proportional to the time of flight t of the impulse:
D = c · t/2,
D
Output
The Micropilot is commissioned by entering an empty distance "E" (=zero), a full distance "F" (=span) and
application parameters. The application parameters are automatically adapt into the instrument to the
process conditions. For models with a current output, the factory adjustment for zero point "E" and span "F"
is 4 mA and 20 mA. For digital outputs and the display module, the factory adjustment for zero point "E" and
span "F" is 0 % and 100 %.
A linearization with max. 32 points, based on a table entered either manually or semi-automatically, can be
activated locally or remotely. This function provides a measurement in engineering units and a linear output
signal for spheres, horizontal cylindrical tanks and vessels with conical outlet.
T
Engineering Procurement Installation Commissioning Operation Maintenance Retirement
A0013773-EN
å2 Life cycle
Engineering
• Universal measuring principle
• Measurement unaffected by medium properties
F
• Hardware and software developed according to SIL IEC 61508
Procurement
A
• Endress+Hauser being the world market leader in level measurement guarantees asset protection
• Worldwide support and service
Installation
• Special tools are not required
• Reverse polarity protection
• Modern, detachable terminals
• Main electronics protected by a separate connection compartment
Commissioning
R
• Fast, menu-guided commissioning in only a few steps on site or from the control room
• Plain text display in national languages reduces the risk of error or confusion
• Direct local access of all parameters
• Short instruction manual at the device
Operation
• Multi-echo tracking: Reliable measurement through self-learning echo-search algorithms taking into
account the short-term and long-term history in order to check the found echoes for plausibility and to
D
Input
Measured variable The measured variable is the distance between the reference point and the product surface.
Subject to the empty distance entered "E" the level is calculated.
Alternatively, the level can be converted into other variables (volume, mass) by means of linearization (32
points).
T
Usable measuring range
Reduction of the max. possible measuring range through:
• Media with poor reflection properties (= small DC). For examples refer to table below.
• Angle of repose
• Extremely loose surfaces of bulk solids, e.g. bulk solids with low bulk weight for pneumatic filling.
• Build-up, above all of moist products.
Media group
B
DK (er)
1.6 to 1.9
1.9 to 2.5
F
Examples
• Plastic granulate
• White lime, special cement
• Sugar
19 to 16 dB
16 to 13 dB
A
C 2.5 to 4 • Grain, seeds 13 to 10 dB
• Ground stones
• Sand
• Coal
The respective lower group applies for very loose or loosened bulk solids.
D
T
F
A
R
D
Output
Output signal HART
T
FOUNDATION Fieldbus (in preparation)
Galvanic isolation
Switch output
F
Yes
For HART devices, the switch output is available as an option. See product structure, feature 20:
"Power Supply, Output", option B: "2-wire; 4-20mA HART, switch output"
A
Devices with PROFIBUS PA and FOUNDATION Fieldbus always have a switch output.
Switch output
Switching behavior Binary (conductive or non-conductive), switches when the programmable switch point is
reached
R
Insulation voltage floating, Insulation voltage 1 350 VDC to power supply aund 500 VAC to ground
Switch point freely programmable, separately for switch-on and switch-off point
Switching delay freely programmable from 0 to 100 sec. , separately for switch-on and switch-off point
Linearization The linearization function of the device allows the conversion of the measured value into any unit of length
or volume. Linearization tables for calculating the volume in cylindrical tanks are pre-programmed. Other
tables of up to 32 value pairs can be entered manually or semi-automatically.
T
Galvanic isolation All circuits for the outputs are galvanically isolated from each other.
Manufacturer ID 17 (0x11)
Device type ID
HART specification
6.0
F
Information and files under:
• www.endress.com
• www.hartcomm.org
A
HART load Min. 250 W
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• Electronic temperature
• Relative echo amplitude
• Analog output adv. diagnostics
R
Measured values for SV, TV, FV (second, third and fourth variable)
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
D
• Area of incoupling
Manufacturer ID 17 (0x11)
T
• Sensor block save history on
• Status output
FInstallation check of the PRFIBUS segment and the Micropilot FMR5x via the
terminal voltage and telegram surveillance.
• PROFIBUS Up-/Download
Up to 10 times faster writing and reading of parameters via PROFIBUS up-/
download
• Condensed Status
Simple and self-explanatory diagnostic information by categorization of occurring
A
diagnostic messages.
Manufacturer ID 0x452B48
Number of VCRs 44
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Slot time 4
T
Transducer Blocks
Block Content Output values
Setup Transducer Block Contains all parameters for a standard commissioning • Level or volume 1)
procedure (Channel 1)
• Distance (Channel 2)
F
Contains all parameters for a more detailed configuration no output values
no output values
A
Expert Configuration Contains parameters which require detailed knowledge no output values
Transducer Block of the functionalities of the device
Expert Information Contains information about the state of the device no output values
Transducer Block
Service Sensor Transducer Contains parameters which can only be operated by no output values
Block Endress+Hauser service personnel
Service Information Contains information on the state of device which is no output values
R
Data Transfer Transducer Contains parameters which allow to backup the device no output values
Block configuration in the display module and to restore it into
the device.
Function Blocks
Block Content Number of Number of Execution Functionality
permanent instantiable time
blocks blocks
Resource Block The Resource Block contains all the data 1 0 - enhanced
that uniquely identifies the field device.
It is an electronic version of a nameplate
of the device.
T
input. The non-linear function is
determined by a single look-up table
with 21 arbitrary x-y pairs.
Integrator
Block
F
receives its inputs from AI blocks. The
block performs maximum, minimum,
middle, average and ‘first good’ signal
selection.
Block
Up to 20 blocks can be instantiated in the device altogether, including the blocks already instantiated
on delivery.
D
Power supply
Terminal assignment 2-wire: 4-20mA HART
2- w
4-2 ire le
0 v el
HA mA
[21 RT
4-2
0m
A ]
ope
A
n Sp
a
711 re pa
HA 20mA
08x rt
xx
RT
4...
+
1 -
T
1 2 4 5 6
mm
2
10
+ +
–
–
4...20 mA
1
3
2 4 5 F 7
B
[16
]
1-c
han
nel
ove
rvo
ltag
ep
+
1 -
4-2 2
0m
A
A
rote
ctio
n
+ + 711
286
– 17
–
4...20 mA
3
A0011294
R
10
9
8
2- w
4-2 ire
0
HA mA
[02 RT
PF
S
A /03
] ope
n Sp
a
711 re pa
HA 20 mA
08x rt
3+ ++ xx
31 --
RT
4...
42 +
7
1 -
mm
2 6
4-
10
T
+ +
–
-
³250W 4...20 mA
1 2 3 4 5 B
3+ 11 +
+
–
4-
F +
[17
]
2-c
han
3 -
4-2 4
nel
0m
ove
A/
rvo
ltag
ep
ro
711
+
1 -
4-2 2
FIE 0mA
LD
BU
S
/
tec
286
t ion
19
A
-
³250W 4...20 mA
1 2 3 4 5
A0013759
1 Active barrier with power supply (e.g. RN221N): Observe terminal voltage (® ä 22)
2 HART communication resistor (³250 W): Observe maximum load (® ä 22)
3 Connection for Commubox FXA195 or FieldXpert SFX100 (via VIATOR Bluetooth modem)
4 Analog display device: Observe maximum load (® ä 22)
5 Cable screen; observe cable specification (® ä 25)
6 Terminals for 4-20mA HART (passive)
7 Terminals for switch output (open collector)
D
14
13
12
2- w
4-2 ire le
0 v el
HA mA
[04 RT
4-2
0m
A /05
]
A
ope
A
n Sp
20m
a
711 re pa
HA 20mA
08x rt
xx
+
4 ...
3 -
RT
11
4 ...
4 +
1 -
mm
2
+
10
+
1 –
-
T
4...20 mA
9 8
+ +
2 –
-
4...20 mA
3 5 6 7 4
9
+
–
4...20 mA
8
F +
-
10
B
2-c
han
nel
+
3 -
4-2 4
0m
ove
A/
4-
FIE 20mA
2
+
1 -
A
[17 rvo LD /
] ltag
ep
B U
ro S
tec
tion
+ + 711
28 6
2 – 19
-
4...20 mA
3 5 6 7 4
A0013923
R
This version is also suited for single-channel operation. In this case, current output 1 (terminals 1 and
2) must be used.
13
12
11
2- w
4-2 ire
0
HA mA
[08 RT
A ]
= V
ope
48
n Sp
4...
a
711 re pa
HA 20 mA
08x rt
10.
L+ xx
1 L-
RT
4...
2 +
10 9
3 -
mm
4 8
10
7
T
+
-
³250W 4...20 mA
6
1 2 3 4 5
A0011340
å6
1
2
3
4
5
6
Evaluation unit, e.g. PLC
F
Terminal assignment 4-wire; 4-20mA HART (10.4 to 48 VDC)
!CAUTION
To ensure electrical safety:
► Do not disconnect the protective connection (7).
► Disconnect the supply voltage before disconnecting the protective earth (8).
Connect protective earth to the internal ground terminal (8) before connecting the supply voltage. If
D
necessary, connect the potential matching line to the external ground terminal (12).
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the
protective earth conductor of the supply cable. Instead, the functional grounding must also be
connected to the process connection (flange or threaded connection) or to the external ground
terminal.
An easily accessible power switch must be installed in the proximity of the device. The power switch
must be marked as a disconnector for the device (IEC/EN61010).
13
12
11
2- w
4-2 ire
0
HA mA
[09 RT
A ]
~
3V
ope
n
..25
Sp
a
711 re pa
HA 20 mA
9 0.
08x rt
xx
L
1 N
RT
4...
2 +
10 9
3 -
mm
4 8
10
7
T
+
-
³250W 4...20 mA
6
1 2 3 4 5
A0018965
å7
1
2
3
4
5
6
Evaluation unit, e.g. PLC
F
Terminal assignment 4-wire; 4-20mA HART (90 to 253 VAC)
!CAUTION
To ensure electrical safety:
► Do not disconnect the protective connection (7).
► Disconnect the supply voltage before disconnecting the protective earth (8).
Connect protective earth to the internal ground terminal (8) before connecting the supply voltage. If
D
necessary, connect the potential matching line to the external ground terminal (12).
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the
protective earth conductor of the supply cable. Instead, the functional grounding must also be
connected to the process connection (flange or threaded connection) or to the external ground
terminal.
An easily accessible power switch must be installed in the proximity of the device. The power switch
must be marked as a disconnector for the device (IEC/EN61010).
2-
F4IEwire
-20L lev
mD
ABU el
FA
P IE/F S
06 / L D
[2 F B PFS
A 07 ]
2 U S
op en Sp
a
7110 re pa
US
0283x4 rt
3+ ++ x5x7
B
31 --
/LFDF
PIAE
42 +
F
2
1 2-
mm
4-
10
3
1
T
B
3+ 6 +
3 -
1
4-
F [17
]
2-c
4-2
han
nel
4
0m
ove
A/
rvo
F
ltag
IEL
ep
+
1 -
4-2 2
0m
DB /
rote
711
286
US
ctio
A
19
A
A0011341
+
1
3+ 2
3+
+
-
4-
4-
A0015909 A0015910
T
Suitable relays (examples):
2 Digital input
• Solid-state relay: Phoenix Contact OV-24DC/480AC/5 with mounting
rail connector UMK-1 OM-R/AMS
• Electromechanical relay: Phoenix Contact PLC-RSC-12DC/21
F
A
R
D
Device plug connectors For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected without
opening the housing.
1 Signal +
4 3 –
2 not connected
1 + 2 nc 3 Signal -
4 Ground
A0011175
T
Pin Meaning
1 3 1 Signal -
2 Signal +
2 4 3 Screen
4 Not connected
A0011176
F
A
R
D
"Power Supply, "Approval" 2) Terminal voltage U at Maximum load R, depending on the supply voltage U0 at the
Output" 1) the device supply unit
Ex ia / IS 10.4 to 30 V 3)
T
0
10 20 30 35 U0 [V]
10.4 21.4
A0017140
4)
• Ex d(ia) / XP 12 to 35 V R [W]
• Ex ic(ia)
• Ex nA(ia) 500
• Ex ta / DIP
Ex ia + Ex d(ia) / IS + XP 12 to 30 V 4)
F 0
A
10 20 30 35 U0 [V]
12 23
A0019136
4) For ambient temperatures Ta £ -20 °C (-4 °F) a minimum voltage of 16 V is required for the satrtup of the device at the MIN error current (3.6 mA).
"Power Supply, Output" 1) "Approval" 2) Terminal voltage U at Maximum load R, depending on the supply voltage U0 at the
the device supply unit
• Ex nA(ia) 500
• Ex ic
• Ex ic(ia)
• Ex d(ia) / XP
• Ex ta / DIP
• CSA GP
• Ex ia / IS 12 to 30 V 3)
0
• Ex ia + Ex d(ia) / IS + XP
10 20 30 35 U0 [V]
12 23
A0019136
"Power Supply, Output" 1) "Approval" 2) Terminal voltage U at the Maximum load R, depending on the supply voltage U0 at the
device supply unit
500
0
10 20 30 U0 [V]
12 23
A0017055
T
2) Feature 010 of the product structure
3) For ambient temperatures Ta £ -30 °C (-22 °F) a minimum voltage of 16 V is required for the satrtup of the device at the MIN error current (3.6 mA).
F
USS < 10 mV
A
R
D
T
• Ex ic
• Ex ic(ia)
• Ex d(ia) / XP
• Ex ta / DIP
• CSA GP
3)
• Ex ia / IS 9 to 30 V
• Ex ia + Ex d(ia) / IS + XP
1)
2)
3)
Feature 020 of the product structure
Feature 010 of the product structure
F
Input voltages up to 35 V will not spoil the device.
Polarity sensitive No
A
FISCO/FNICO compliant Yes
according to IEC 60079-27
Nominal current 3.6 to 22 mA, the start-up current for multidrop mode can be parametrized (is set to
3.6 mA on delivery)
Nominal current 14 mA
Ui 17.5 V
Ii 550 mA
Pi 5.5 W
Ci 5 nF
Li 10 mH
T
Power supply failure • Configuration is retained in the HistoROM (EEPROM).
• Error messages (incl. value of operated hours counter) are stored.
Terminals
Instructions" (XA, ZD).
F
• Without integrated overvoltage protection
Plug-in spring terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• With integrated overvoltage protection
Screw terminals for wire cross-sections 0.2 to 2.5 mm2 (24 to 14 AWG)
A
Cable entries • Cable gland (not for Ex d):
– Plastics M20x1.5 for cable Æ 5 to 10 mm (0.2 to 0.39 in): non-Ex, ATEX/IECEx/NEPSI Ex ia/ic
– Metal M20x1.5 for cable Æ 7 to 10 mm (0.28 to 0.39 in): dust-Ex, FM IS, CSA IS, CSA GP, Ex nA
• Thread for cable entry:
– ½" NPT
– G ½"
– M20 × 1.5
R
Cable specification • Standard device cable is sufficient for the power supply of the device.
• Minimum cross-section: (® ä 25)
• For ambient temperature TU³60 °C (140 °F): use cable for temperature TU +20 K.
HART
D
Overvoltage protection If the measuring device is used for level measurement in flammable liquids which requires the use of
overvoltage protection according to DIN EN 60079-14, standard for test procedures 60060-1 (10 kA, pulse
8/20 ms), overvoltage protection has to be ensured by an integrated or external overvoltage protection
module.
Technical data
T
Capacitance at 1 MHz < 1.5 pF
• HAW562: TI01012K
• HAW569: TI01013K
F
For detailed information please refer to the following documents:
A
R
D
Performance characteristics
Reference operating • Temperature = +24 °C (+75 °F) ±5 °C (±9 °F)
conditions • Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.45 psi)
• Humidity = 60 % ±15 %
• Reflector: metal plate with a minimum diameter of 1 m (40 in)
• No major interference reflections inside the signal beam
Maximum measured error Typical data under reference operating conditions: DIN EN 61298-2, percentage values in relation to the
span.
digital analog 1)
T
hysteresis
F
R
A
20 (0.79)
D [mm] ([in])
3 (0.12)
0
R
-3 (-12)
-20 (-0.79)
A0019034
Reaction time The reaction time can be parametrized. The following step response times (as per DIN EN 61298-2) 1)are
valid if the damping is switched off:
Influence of ambient The measurements are carried out in accordance with EN 61298-3
temperature • Digital (HART, PROFIBUS PA): average TK = 5 mm/10 K; maximum 15 mm
• Analog (current output):
– zero point (4 mA): average TK = 0.02 %/10 K
– span (20 mA): average TK = 0.05 %/10 K
T
F
A
R
D
1) According to DIN EN 61298-2 the response time is the time which passes after a sudden change of the input signal until the output signal for the first time
assumes 90% of the steady-state value.
Installation
Installation conditions Mounting position
T
• Not above the fill stream (3).
• It is recommended to us a weather protection
cover (1) in order to protect the device from
direct sun or rain.
• In extremely dusty applications, the integrated
air purge connection can prevent clogging of the
antenna (® ä 45).
F
A
A0016883
R
D
Vessel installations
T
F
A0018946
A
R
D
T
F A0016889
A
Measurement in a plastic vessel
If the outer wall of the vessel is made of a non-conductive material (e.g. GRP), microwaves can also be
reflected off interfering installations outside the signal beam (e.g. metallic pipes (1), ladders (2), grates
(3), ...). Therefore, there should be no such interfering installations in the signal beam. Please contact
Endress+Hauser for further information.
R
D
3
1
T
F A0017125
A
R
D
Optimization options
• Antenna size
The bigger the antenna, the smaller the beam angle a and the fewer interference echoes (® ä 34).
• Mapping
The measurement can be optimized by means of electronic suppression of interference echoes.
• Antenna alignment
Take into account the marker on the flange or threaded connection (® ä 39).
• Metallic screens mounted at a slope (3)
They spread the radar signals and can, therefore, reduce interference echoes.
• Variable flange seal (FMR56)
Using the variable flange seal, the device can be aligned in the direction of the product surface. For details
refer to Operating Instructions BA01048F, chapter "Accessories".
• Alignment device for FMR57
In FMR57 with alignment device, the sensor can be optimally aimed within the vessel and thus
interference echoes can be avoided. The maximum angle b is ±15°.
In particular, sensor alignment serves to:
– prevent interference reflections
T
– extend the maximum possible measuring range in conical outlets.
F
A
R
D
Beam angle
a
W = 2 . D . tan _
2
D
a
T
A0016891
The beam angle is defined as the angle a where the energy density of the radar waves reaches half the value
of the maximum energy density (3-dB-width). Microwaves are also emitted outside the signal beam and can
be reflected off interfering installations.
Antenna size
Beam angle a
F
Beam diameter W as a function of beam angle a and measuring distance D:
FMR56
80 mm (3 in)
10°
100 mm (4 in)
8°
A
Measuring distance (D) Beamwidth diameter (W)
T
60 m (197 ft) 4.19 m (14 ft) 3.70 m (12 ft)
F
A
R
D
Measuring conditions • The measuring range begins, where the beam hits the bottom. Particularly with conical outlets the level
cannot be detected below this point. The maximum measuring range can be increased in such applications
by using an alignment device (® ä 44).
• In case of media with a low dielectric constant (er = 1.5 to 2.5) 2), the bottom can be visible through the
medium at low levels. In order to guarantee the required accuracy in these cases, it is recommended to
position the zero-point at a distance C above the bottom (see figure).
• In principle it is possible to measure up to the tip of the antenna with Micropilot. However, due to
considerations regarding abrasion and build-up and depending on the orientation of the product surface
(angle of repose), the end of the measuring range should be at a distance of A (see figure) from the tip of
the antenna. If required, and if some conditions (high DC value, flat angle of repose) are met, shorter
distances can be achieved.
T
A
100%
F
B
A
C
0%
A0016916
R
FMR56
400(15.7) 50 to 150(1.97 to 5.91)
FMR57
D
2) Dielectric constants of important media commonly used in the industry are summarized in the document SD106F, which can be downloaded from the
Endress+Hauser web page (www.endress.com).
T
°
90
°
90
°
90
F 90
°
90
°
A0019434
A
Nozzle mounting
R
H
øD
D
A0016868
å 13 Nozzle height and diameter for horn antenna with slip-on flange (FMR50/FMR56)
D 80 mm (3.15 in) 100 mm (3.94 in) 150 mm (5.91 in) 100 mm (3.94 in) 150 mm (5.91 in)
T
A0016865
Align the antenna vertically to the product surface using the mounting bracket.
NOTICE
F
The mounting bracket has no conductive connection to the transmitter housing.
Danger of electrostatic charge
► Connect the mounting bracket to the local potential equalization system.
A
R
D
Alignment
• Ideally, the horn antenna should be installed vertically. To avoid interference reflections or for optimum
alignment within the vessel, the Micropilot with optional alignment device can be inclined by 15° in all
directions (® ä 45).
• A marking at the boss enables axial alignment of the antenna. This marking must be aligned towards the
tank wall.
T
°
90
°
90
°
90
90
°
Nozzle mounting
F 90
°
A0019434
A
The horn antenna should protrude from the nozzle. If this is not possible for mechanical reasons, larger
nozzle heights can be accepted.
R
H
D
øD
A0016825
Threaded connection
• Tighten with the hexagonal nut only.
• Tool : Hexagonal wrench 60 mm
• Maximum permissible torque: 60 Nm (44 lbf ft)
T
F
A
R
D
Alignment
Ideally, the parabolic antenna should be installed vertically. To avoid interference reflections or for optimum
alignment within the vessel, the Micropilot with optional alignment device can be swiveled by 15° in all
directions (® ä 44).
Nozzle mounting
• Ideally, the parabolic antenna should protrude from the nozzle (1). Particularly when using the alignment
device, please ensure that the parabolic reflector is protruding from the nozzle/roof so as not to inhibit
alignment.
• For applications with higher nozzle it may be necessary to install the parabolic antenna completely in the
nozzle (2).
The maximum height of the nozzle (Hmax) to the parabolic mirror should not exceed 500 mm (19.7 in).
Interfering edges within the nozzle should be avoided.
T
1 2
F
Hmax
øD
A
A0016827
D
R
Standard installation
T
1
H
1 Nozzle
F øD
A0018874
A
Antenna size ÆD H 1)
T
2
1
2
Parabolic reflector
4 bolts
A0018878
T
±15° ±15°
A0016931
F
A
R
D
T
A0016932
F
Torque for air purge connection: 6 Nm (4.4 lbf ft)
• Pulsed operation
max. pressure of purge air: 6 bar (87 psi)
• Permanent operation
recommended pressure range of the purge air: 200 to 500 mbar (3 to 7.25 psi)
Make sure to use dry purge air.
A
In general, air purging should only be used as much as necessary, since too much air purging may
cause mechanical damage.
R
D
1
2
A0019142
If process temperatures are high, the device must be included in normal tank insulation to prevent the
T
electronics heating up as a result of heat radiation or convection. The insulation may not exceed beyond the
neck of the housing.
F
A
R
D
Environment
Ambient temperature range Measuring device –40 to +80 °C (–40 to +176 °F); –50 °C (–58 °F) with manufacturer declaration on
request
Local display –20 to +70 °C (–4 to +158 °F), the readability of the display may be impaired at
temperatures outside the temperature range.
Ambient temperature limits The following diagrams take into account only function requirements. There may be further restrictions
for certified device versions. Please refere to the separate Safety Instructions (® ä 84).
T
With a temperature (Tp) at the process connection the admissible ambient temperature (Ta) is reduced
according to the following diagram (temperature derating):
K
F
2-wire; 4-20 mA HART, switch output
FMR56 Ta
Housing: GT19 (Plastics PBT) P1 P2
Temperature unit: °C (°F) P3
R
Tp
P5 P4
A0019351
FMR56 Ta
Housing: GT20 (Alu, coated) P1 P2
Temperature unit: °C (°F) P3
Tp
P5 P4
A0019351
T
C -40 80 80 80 80 80 80 -40 -40 -40 - -
Channel 2 not used (-40) (176) (176) (176) (176) (176) (176) (-40) (-40) (-40)
E, G
Switch output used
K, L
-40
(-40)
-40
(-40)
78
(172)
77
(171)
78
(172)
77
(171)
78
(172)
77
(171)
80
(176)
80
(176) F 78
(172)
77
(171)
80
(176)
80
(176)
-40
(-40)
-40
(-40)
-40
(-40)
-40
(-40)
-40
(-40)
-40
(-40)
-
-
-
-
A
FMR57 Ta
Seal: Viton GLT P1 P2
Housing: GT18 (316 L) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
R
FMR57 Ta
Seal: Viton GLT P1 P2
Housing: GT19 (Plastics PBT) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
T
C -40 82 82 82 200 53 200 -40 -40 -40 - -
Channel 2 not used (-40) (180) (180) (180) (392) (127) (392) (-40) (-40) (-40)
E, G
Switch output used
FMR57
Seal: Viton GLT
-40
(-40)
63
(145)
63
(145)
63
(145)
F200
(392)
40
(104)
200
(392)
-40
(-40)
-40
(-40)
P1
Ta
-40
(-40)
-
P2
-
A
Housing: GT20 (Alu, coated) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
FMR57 Ta
Seal: Graphite P1 P2
Housing: GT18 (316 L) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
T
C -40 82 82 82 400 51 400 -40 -40 -40 - -
Channel 2 not used (-40) (180) (180) (180) (752) (124) (752) (-40) (-40) (-40)
E, G
Switch output used
K, L
-40
(-40)
-40
(-40)
78
(172)
77
(171)
78
(172)
77
(171)
78
(172)
77
(171)
400
(752)
400
(752) F 49
(120)
48
(118)
400
(752)
400
(752)
-40
(-40)
-40
(-40)
-40
(-40)
-40
(-40)
-40
(-40)
-40
(-40)
-
-
-
-
A
FMR57 Ta
Seal: Graphite P1 P2
Housing: GT19 (Plastics PBT) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
R
FMR57 Ta
Seal: Graphite P1 P2
Housing: GT20 (Alu, coated) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
T
C -40 82 82 82 400 59 400 -40 -40 -40 - -
Channel 2 not used (-40) (180) (180) (180) (752) (138) (752) (-40) (-40) (-40)
E, G
Switch output used
K, L
-40
(-40)
-40
(-40)
78
(172)
77
(171)
78
(172)
77
(171)
78
(172)
77
(171) F400
(752)
400
(752)
55
(131)
54
(129)
400
(752)
400
(752)
-40
(-40)
-40
(-40)
-40
(-40)
-40
(-40)
-40
(-40)
-40
(-40)
-
-
-
-
A
Storage temperature –40 to +80 °C (–40 to +176 °F)
Degree of protection IP68 NEMA6P applies for M12 PROFIBUS PA plugs only when the PROFIBUS
cable is plugged in and is also rated IP68 NEMA6P.
Cleaning the antenna The antenna can get contaminated, depending on the application. The emission and reception of microwaves
can thus eventually be hindered. The degree of contamination leading to an error depends on the medium
and the reflectivity, mainly determined by the dielectric constant er.
If the medium tends to cause contamination and deposits, cleaning on a regular basis is recommended. In
the case of FRM57, the integrated air purge connection can be used for this (® ä 45). Care has to be taken
not to damage the antenna in the process of a mechanical or hose-down cleaning. The material compatibility
has to be considered if cleaning agents are used! The maximum permitted temperature at the flange should
not be exceeded.
3) This restriction is valid if the following options of the product structure have been selected at the same time: 030("Display, Operation") = C("SD02") or
E("SD03"); 040("Housing") = A("GT19").
Electromagnetic compatibility Electromagnetic compatibility to all relevant requirements of the EN 61326- series and NAMUR
(EMC) recommendation EMC (NE21). For details see declaration of conformity. 4).
If only the analogue signal is used, unshielded interconnection lines are sufficient for the installation. In case
of using the digital signal (HART/ PA/ FF) use shielded interconnection lines. Use a shielded cable when
working with a digital communications signal.
Max. fluctuations during EMC- tests: < 0.5 % of the span. As an exception to this, the maximum
fluctuations may amount to 2 % of the span for devices with plastic housing and see-through lid (integrated
display and operating module SD02 or SD03) if strong electromagnetic interferences in the frequenency
range of 1 to 2 GHz are present.
T
F
A
R
D
Process
Process temperature range Sensor Seal Process temperature range
T
This range may be reduced by the selected process connection. The pressure rating (PN) specified on
the flanges refers to a reference temperature of 20 °C, for ASME flanges 100 °F. Pay attention to
pressure-temperature dependencies.
Please refer to the following standards for the pressure values permitted for higher temperatures:
• EN 1092-1: 2001 Tab. 18
With regard to their temperature stability properties, the materials 1.4435 and 1.4404 are grouped
under 13E0 in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
Dielectric constant
• JIS B 2220
• For liquids
F
• ASME B 16.5a - 1998 Tab. 2-2.2 F316
• ASME B 16.5a - 1998 Tab. 2.3.8 N10276
Mechanical construction
Dimensions Dimensions of the electronics housing
R100 98 (3.86)*
78 (3.07) 90 (3.54)
)
.07
(ø4
3.5
141.9 (5.59)
ø108.5 (ø4.27)
ø10
144 (5.67)
115.25 (4.54)
T
A0011666
R100
F 78 (3.07)
99.5 (3.92)*
90 (3.54)
7)
4.1
6 (ø
A
ø10
163 (6.42)
ø106 (ø4.17)
134.5 (5.3)
R
A0011346
R100
D
97 (3.82)*
78 (3.07) 90 (3.54)
7)
0
ø4.
(
3.5
ø111 (ø4.37) - 1°
141.5 (5.57)
ø10
144 (5.67)
ø108.5 (ø4.27)
117.1 (4.61)
A0011665
b
R
øc
ød
mm (in)
T
A0017747
⌀c
⌀d
15 mm (0.59 in)
127 mm (5 in)
A B
øi
øj
n
f
g øh
18.5 (0.73)
20 (0.79)
p
øa øi
e
øb øj
øc øk
ød
T
148 (5.83)
øh 8x
24(0.94)
F
20 (0.79)
35.5 (1.4)
ø240.7 (9.48)
øk
mm (in)
A0017742
A Horn DN80 (3")/DN100 (4"); flange DN80/DN100 (with slotted hole) with slip-on flange
A
suitable for DN80 PN16 / ANSI 3" 150 lbs / 10K 80
suitable for DN100 PN16 / ANSI 4" 150 lbs / 10K 100
B Horn DN80; flange DN100/DN150 with adapter ring
suitable for DN100 PN16 / ANSI 4" 150 lbs / 10K 100
suitable for DN150 PN16 / ANSI 6" 150 lbs / 10K 150
C Horn DN100 (4"); flange DN150 with adapter ring
suitable for DN150 PN16 / ANSI 6" 150 lbs / 10K 150
R Reference point of the measurement
R
A B
162.5 (6.4)
205 (8.07)
mm (in)
A0017746
T
A Mounting bracket with alignment for roof mounting
B Mounting bracket with alignment for wall mounting
F
A
R
D
A B C D
111 (4.37)
111(4.37)
8(0.31)
b
R
L2
L2
23(0.31)
43 (1.69)
ø40
(1.57)
L
ø40
L
(1.57)
ød ød
øD
T
øD øD
E F G
111 (4.37)
111 (4.37)
8(0.31)
b
R
F
L2
L2
L1
L1
øF øF
A
øD øD
øD
H I J K
201 (7.91)
201 (7.91)
207 (7.91)
R 8(0.31)
8(0.31)
(1.97)
50
R
(1.97)
(197)
23(0.31)
50
43 (1.69)
50
D
ød ød ød
øD øD
øD mm (in)
A0017814
A Horn antenna, standard version with alignment device and UNI flange
B Horn antenna, standard version with UNI flange
C Horn antenna, standard version with standard flange
D Horn antenna, standard version with threaded connection
E Parabolic antenna with alignment device and UNI flange
F Parabolic antenna with UNI flange
G Parabolic antenna, standard version with standard flange
H Horn antenna, high temperature version with alignment device and UNI flange
I Horn antenna, high temperature version with standard flange
Horn antenna
Dimension 80 mm (3") 100 mm (4")
Parabolic antenna
Dimension 200 mm (8") 250 mm (10")
T
L2 50 mm (1.97 in) 37 mm (1.46 in)
Dimension
b
Version F
Flanges according to EN1092-1 (suitable for DIN2527)
DN80
20 mm (0.79 in)
DN100
20 mm (0.79 in)
A
16 bar
⌀D ⌀200 mm (7.87 in) ⌀220 mm (8.66 in)
150 lbs
⌀D ⌀190.5 mm (7.5 in) ⌀228.6 mm (9 in)
10 K
⌀D ⌀185 mm (7.28 in) ⌀210 mm (8.27 in)
4x90° 2
ø19 (0.75) ø26 (1.02)
4x
90
°
4x
60
°
90
6x
°
1 ø26 (1.02)
A A A A
ø23 (0.91)
ø175 (6.89)
T
ø185.5 (7.3) ø294.5 (11.6)
ø225 (8.86) ø340 (13.4)
3
8 (0.31)
A-A
°
60
ø80.3(3.16)
F 6x
A
ø29 (1.14)
A
A
ø358 (14.1)
mm(in) ø405 (15.9)
A0018947
R
• DN200 PN16
• 10K 200
The number of bolts has sometimes been reduced. The bolt-holes have been enlarged for adaption of
dimensions, therefore, the flange needs to be properly aligned to the counterflange before the bolts are
tightened.
A A
ø85(3.35)
A-A
40 (1.57)
T
8 (0.31)
1 2
1
2
3
Viton seal
Endress+Hauser UNI flange DN100/200/250
Clamping screw 3 x M8, shifty at 120°
F ±15° mm(in)
A0018948
A
For the high temperature version of the FMR57 (sales option 090: "Seal", option D4 "Graphite,
-40...400°C /-40...752°F"), there is no Viton seal (1) at the alignment device.
Weight Housing
Part Weight
R
Materials Housing
2.1 1 2.2 5
4 3 9 8 7 6
A0013788
T
Housing GT18 - stainless steel, corrosion-resistant
7
• Adapter: 316L (1.4435)
2.1 Cover of the electronics compartment • Cable gland: polyamide (PA), nickel-plated brass (CuZn)
• Cover: • Adapter: 316L (1.4435)
– PA (see-through cover)
– PBT (non-transparent cover)
• Cover seal: EPDM
2.2 Cover of the terminal compartment 6 Dummy plug: nickel-plated brass (CuZn)
• Cover: PBT
• Cover seal: EPDM 7 Pressure relief stopper: nickel-plated brass (CuZn)
9 Identification
Nameplate: sticker
2.2 Cover of the terminal compartment 6 Dummy plug: nickel-plated brass (CuZn)
• Cover: AlSi10Mg(<0.1% Cu)
• Cover seal: EPDM 7 Pressure relief stopper: nickel-plated brass (CuZn)
T
4 Turn housing 9 Identification
• Screw: A4-70 Nameplate: sticker
• Clamp: 316L (1.4404)
FMR56
A F B C
A
1
2 2 2
3 3 3
4 5
R
6 6 6
A0018950
Screw A2
Nordlock washer A4
3 Horn PBT
4 Slip-on flange PP
Screw A2
Seal FKM
6 Focusing lense PP
Seal VMQ
FMR57
A B C D E F
2 2 5 2
3 4 4 3 4
7 7 7
6 6 6
8 8 9
T
G H I J
1 1 1
3
7
6
4
7
6
F 4
5
7
6
A
8 8 8
A0018958
Screws A2
T
Adapter Horn/Parabolic 316L (1.4404)
Screws A4
9
Seal
Parabolic reflector
Screws
Feed
F Standard: FKM
316L (1.4404)
A4
PTFE
High temperature: Graphite
A
Seal FKM
3.1
3.2
D
2.1 4
2.2
2.2 5.1
2.1 5.2
4
6
A0015473
T
F
A
R
D
Operability
Operating concept Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Quick and safe commissioning
• Guided menus ("Make-it-run" wizards) for applications
• Menu guidance with brief explanations of the individual parameter functions
Reliable operation
• Local operation in different languages (see product structure, feature "Additional Operation Language")
• Standardized operation at the device and in the operating tools
• Data storage device (HistoROM) for process and measuring device data with event logbook available at all
times - even if electronics modules are replaced
Efficient diagnostics increase measurement reliability
T
• Remedy information is integrated in plain text
• Diverse simulation options and line recorder functions
Local operation Order code for "Display; Operation", option C "SD02" Order code for "Display; Operation", option E "SD03"
(in preparation)
1 1
–
+
E
F –
+
E
A
A0015544 A0015546
Display elements
• 4-line display
R
• In the case of order code for "Display; Operation", option E: white background lighting; switches to red in
event of device errors (in preparation)
• Format for displaying measured variables and status variables can be individually configured
• Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside the temperature range.
Operating elements
• In the case of order code "Display; Operation", Option C: local operation with 3 push buttons ( , , )
D
• In the case of order code for "Display; Operation", option E: external operation via touch control; 3 optical
keys: , , (in preparation)
E
A0013137
T
9
3
2
F 6 8
A
1 4 5 7
A0013764
2 3
PROFIBUS DP
ENDRESS + HAUSER
PROFIBUS PA
T
T
5
4 4 4
A0015775
1 Segment coupler
2
3
4
5
PLC (Progrommable Logic Controller)
Transmitter
Additional functions (valves etc.)
F
Computer with Profiboard/Proficard and operating tool (e.g. FieldCare)
A
R
D
IN
BT
FF-HSE
T
1
FF-H1 SB 2
PS BT
LD 4
3
BT ENDRESS + HAUSER
PS
F FF-H1
– + E
BT
A
1
2
A0017188
BT Bus Terminator
1 FFblue Bluetooth modem
2 Field Xpert SFX100
3 FieldCare
4 NI-FF interface card
3 –
+
E
T
2 1
A0014019
1 Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface)
2 Commubox FXA291
3
F
Computer with "FieldCare" operating tool
A
R
D
T
ENDRESS+HAUSER
RN 221N
ENDRESS+HAUSER
RN 221N
1
F 1 2
FXN 520
A
20...45 VDC
-
R
.
A0011278
The number of instruments which can be connected in mutidrop mode can be calculated by the
"FieldNetCalc" program. A description of this program can be found in Technical Information TI 400F
(Multidrop Conncector FXN520). The program is available form your Endress+Hauser sales
organisation or in the internet at: www.de.endress.com/Download (text search = "Fieldnetcalc").
C-Tick symbol The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".
Ex approval • ATEX
• IEC Ex
• CSA (in Vorbereitung)
• FM (in Vorbereitung)
• NEPSI (in Vorbereitung)
• TIIS (in Vorbereitung)
T
Additional safety instructions must be observed for applications in hazardous areas. They are contained in
the separate "Safety Instructions" (XA) document, which is included in the scope of delivery. Reference is
made to the XA on the nameplate of the device.
Details on the available certificats as well as the associated XAs can be found in the Associated
documentation chapter in the Safety instructions section: (® ä 84).
Dual seal according to The devices Micropilot FMR5x have been designed according to ANSI/ISA 12.27.01 as dual seal devices,
ANSI/ISA 12.27.01
F
allowing the user to waive the use and save the cost of installing external secondary process seals in the
conduit as required by the process sealing sections of ANSI/NFPA 70 (NEC) and CSA 22.1 (CEC). These
instruments comply with the North-American installation practice and provide a very safe and cost-saving
installation for pressurized applications with hazardous fluids.
Further information can be found in the control drawings of the relevant devices.
A
Functional Safety Used for level monitoring (MIN, MAX, range) up to SIL 3 (homogeneous or inhomogeneous redundancy),
independently assessed by TÜV Rhineland as per IEC 61508. Other information see documentation
SD01087F: "Functional Safety Manual".
AD2000 The pressure retaining material 316L (1.4435/1.4404) corresponds to AD2000 - W2/W10.
Pressure Equipment Directive The Micropilot is not subject to the scope of the Pressure Equipment Directive 97/23/EC, as it does not
R
Radio standard The devices Micropilot FMR50, FMR51, FMR52, FMR56 and FMR57 are conform with the LPR (Level
D
EN302729-1/2 Probing Radar) standard EN302729-1/2. The devices are allowed to be used inside or outside of closed bins
or tanks in countries of th EU and the EFTA. Precondition is that the country itself already has implemented
the directive.
At present, the following countries have already implemented the directive:
Belgium, Bulgaria, Germany, Denmark, Estonia, France, Greece, Great Britain, Ireland, Iceland, Italy,
Liechtenstein, Lithuania, Latvia, Malta, Netherland, Norway, Austria, Poland, Romania, Sweden,
Switzerland, Slovakia, Spain, Czech Republic and Cyprus.
All countries not mentioned above are at present in the implementation phase.
For the use of the devices outside of closed bins or tanks, the following has to be observed:
1. The installation has to be done by trained personnel.
2. The antenna of the device has to be mounted on a fixed place and vertically to the bottom.
3. The mounting place has to be in a distance of at least 4 km to the mentioned astronomical stations or
an appropriate permission has to be issued by the national authority. If the device is mounted at a
distance of 4 to 40 km from the stations mentioned, the maximum mounting height is restricted to
15 m (49 ft).
Astronomical stations
Country Name of the station Geographical latitude Geographical longitude
T
Knockin 52°47'24" N 02°59'45" W
Poland
Russia
Krakow Fort Skala
Dmitrov
Kalyazin
Pushchino
F 50°03'18" N
56°26'00" N
57°13'22" N
54°49'00" N
19°49'36" E
37°27'00" E
37°54'01" E
37°40'00" E
A
Zelenchukskaya 43°49'53" N 41°35'32" E
Radio standard The devices Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56 and FMR57 are conform with
EN302372-1/2 the TLPR (Tanks Level Probing Radar) standard EN302372-1/2 and can always be used in closed tanks or
D
bins. For installation, points a to f in Annex B of EN302372-1 have to be taken into account.
FCC / Industry Canada This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Canada CNR-Gen Section 7.1.3
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the
following two conditions: (1) This device may not interference, and (2) this device must accept any
interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de
licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de
brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le
brouillage est susceptible d'en compromettre le fonctionnement.
[Any] changes or modifications not expressly approved by the party responsible for compliance could void the
user's authority to operate the equipment.
Track record FMR5x is the upgrade model of the corresponding FMR2xx series.
T
Software of field devices and signal-processing devices with digital electronics
• NAMUR NE 107
Status classification as per NE107
• NAMUR NE 131
Requirements for field devices for standard applications
• IEC61508
Functional safety of electrical/electronic/programmable electronic safety-related systems
F
A
R
D
Ordering information
Ordering information Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com ® Select country ®
Instruments ® Select device ® Product page function: Configure this product
• From your Endress+Hauser Sales Center: www.endress.com/worldwide
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as measuring
range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
5-point linearity protocol (in The following notes must be taken into account if option F4 ("5 point linearity protocol") has been
preparation) selected in feature 550 ("Calibration").
T
The five points of the linearity protocol are evenly distributetd across the measuring range (0% to 100%). In
order to define the measuring range, Empty calibration (E) and Full calibration (F) have to be specified 5).
The following restrictions have to be taken into account when defining E and F:
F
A
200 (7.87)
E
A F
mm (in)
A0017983
R
Minimum distance between reference point (R) and Minimum span Maximum value for "empty
100% level calibration"
The selected values of Empty calibration and Full calibration are only used to record the linearity
protocol and are reset to their antenna specific default values thereafter. If values different from the
default are required, they must be ordered as a customized parametrization (® ä 77).
5) If E and F are not specified, antenna dependent default values will be used instead.
Customized parametrization If the option IJ "Customized parametrization HART", IK "Customized parametrization PA" or IL "Customized
parametrization FF" has been selected in feature 570 "Service", customer specific presettings can be selected
for the following parameters:
T
Setup ® Adv. Setup ® Current output 1/2 ® Failure mode HART • Min
• Max
• Last valid value
F
A
R
D
Accessories
Device-specific
Accessory accessories
Description
222 (8.74)
T
mm (in)
A0015466
298.5 (11.8)
255.1 (10)
F
273.8 (10.8)
164 (6.46)
b
55°
35°
65
)
(6.1
A 155
mm (in)
A0015472
The weather protection cover can be ordered together with the device (product structure, feature 620 "Accessory Enclosed",
option PB "Weather Protection Cover").
Alternatively, it can be separately ordered as an accessory; order code 71132889.
D
Accessory Description
4°
ød
øD
1
2
h
±8°
hmax
hmin
T
A0018871
Order code
compatible with
F
The material and process conditions of the adjustable flange seal must fit the process properties (temperature, pressure,
resistance).
DN80
71074263
• DN80 PN10-40
DN100
71074264
• DN100 PN10-40
DN150
71074265
• DN150 PN10-40
A
• ANSI3" 150lbs • ANSI 4" 150lbs • ANSI 6"150lbs
• JIS 10K 80A • JIS 10K 100A • JIS 10K 150A
Material EPDM
Accessory Description
162.5 (6.4)
205 (8.07)
mm (in)
A0017746
T
å 26 Mounting bracket for FMR50/FMR56 with horn antenna
A Mounting at ceiling
B Mounting at wall
Material
– Mounting bracket: 304 (1.4301)
– Screws: A2
Accessory
Description
F
A
R
A0019128
D
• Material:
– Plastics PBT
– 316L (in preparation)
• Suitable for the display modules:
– SD02 (push buttons)
– SD03 (touch control) (in preparation)
• Connection cable:
– Cable with M12 plug; supplied with the FHX50; up to 30 m (98 ft)
– Customer supplied standard cable; up to 60 m (196 ft)
• If the remote display is to be used, the Micropilot must be ordered in the version "Prepared for display FHX50" (feature
030, option L or M). For the FHX50, on the other hand, the option A: "Prepared for display FHX50" has to be selected in
feature 050: "Option Measurement Device".
• If a Micropilot has not been ordered in the version "Prepared for display FHX50", but is nevertheless to be equipped with
an FHX50, it is essential to select the option B: "Not prepared for display FHX50" in feature 050: "Option Measurement
Device" of the FHX50. In this case, a retrofit kit, needed to prepare the Micropilot for the remote display, is supplied
together with the FHX50.
For details refer to the document SD01007F.
Accessory Description
ød
ø96 (3.78)
³ DN100 237 (9.33) mm (in)
A0019143
T
Danger of explosion
Avoid electrostatic charging of the horn protection.
Accessory Description
F ød
A
³ DN150
ø116 (4.57)
R
450 (17.72)
mm (in)
A0019144
Danger of explosion
Avoid electrostatic charging of the horn protection.
Accessory Description
Commubox FXA291 Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser Common
Data Interface) to the USB interface of a computer.
For details refer to Technical Information TI00405C
Accessory Description
HART Loop Converter Evaluates the dynamic HART variables and converts them to analog current signals or
HMX50 limit values.
For details refer to Technical Information TI00429F and Operating Instructions
BA00371F
Accessory Description
T
Accessory Description
Fieldgate FXA320 Gateway for remote monitoring of connected 4-20mA measuring devices via web
browser.
For details refer to Technical Information TI00025S and Operating Instructions
BA00053S
Accessory
Fieldgate FXA520
Description
F
Gateway for remote diagnosis and parametrization of connected HART measuring devices
via web browser.
For details refer to Technical Information TI00025S and Operating Instructions
BA00051S
A
Accessory Description
Field Xpert SFX100 Compact, flexible and robust industry handheld terminal for remote parametrization and
measured value inspection via the HART output or via FOUNDATION Fieldbus .
For details refer to Operating Instructions BA00060S
R
Graphic Data Manager The graphic data manager Memograph M provides information on all the relevant process
Memograph M variables. Measured values are recorded correctly, limit values are monitored and
measuring points analyzed. The data are stored in the 256 MB internal memory and also
on an SD card or USB stick.
For details refer to Technical Information TI00133R and Operating Instructions
BA00247R
RN221N Active barrier with power supply for safe separation of 4 to 20 mA current circuits.
Provides bi-directional HART transmission.
For details refer to Technical Information TI00073R and Operating Instructions
BA00202R
RNS221 Transmitter supply for 2-wire sensors or transmitters exclusively for non-Ex areas.
Provides bi-directional communication using the HART communication sockets.
For details refer to Technical Information TI00081R and Operating Instructions
KA00110R
T
F
A
R
D
Documentation
The following document types are available:
• On the CD supplied with the device
• In the Download Area of the Endress+Hauser Internet site: www.endress.com ® Download
T
(in preparation)
Brief Operating Instructions KA01131F/00/EN
Supplementary
documentation
Device
Fieldgate FXA520
Technical Information
Technical Information
Document code
TI369F/00/EN
TI402F/00/EN
A
Operating Instructions BA256F/00/EN
Safety Instructions (XA) Depending on the approval, the following Safety Instructions (XA) are supplied with the device. They are an
integral part of the Operating Instructions.
R
Feature 010 Approval Available for Safety Instructions HART Safety Instructions
PROFIBUS
FOUNDATION Fieldbus
BD ATEX: II 1/2/3 G Ex ic [ia Ga] IIC T6-T1 Ga/Gb/Gc FMR57 XA00678F XA00686F
BL ATEX: II 1/2/3 G Ex nA [ia Ga] IIC T6-T1 Ga/Gb/Gc FMR57 XA00678F XA00686F
Feature 010 Approval Available for Safety Instructions HART Safety Instructions
PROFIBUS
FOUNDATION Fieldbus
T
IF IECEx: Ex ta IIIC Txx°C Da/Db • FMR56 XA00682F XA00690F
• FMR57
IL
I2
I3
IECEx: Ex nA [ia Ga] IIC T6-T1 Ga/Gb/Gc
• FMR56
• FMR57
• FMR56
• FMR57
XA00678F
XA00683F
XA00684F
XA00686F
XA00691F
XA00692F
A
For certified devices the relevant Safety Instructions (XA) are indicated on the nameplate.
If the device is prepared for the remote display FHX50 (product structure: feature 030: Display, Operation",
option L or M), the Ex marking of some certificates changes according to the following table 6):
6) The marking of certificates not mentioned in this table are not affected by the FHX50.
Registered trademarks
HARTÒ
Registered trademark of the HART Communication Foundation, Austin, USA
PROFIBUSÒ
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
FOUNDATIONTM Fieldbus
Registered trademark of the Fieldbus Foundation, Austin, Texas, USA
KALREZÒ, VITONÒ
Registered trademark of DuPont Performance Elastomers L.L.C., Wilmington, USA
TEFLONÒ
Registered trademark of E.I. DuPont de Nemours & Co., Wilmington, USA
TRI CLAMPÒ
Registered trademark of Alfa Laval Inc., Kenosha, USA
T
Patents
This product may be protected by at least one of the following patents.
Further patents are pending.
US Patents
5.948.979
6.087.978
6.140.940
F EP Patents
882 957
955 527
-
A
6.155.112 834 722
- 882 955
6.606.904 -
R
6.640.628 -
- 1 389 337
6.779.397 -
D
7.201.050 -
7.412.337 -
7.552.634 -
7.730.760 -
7.819.002 -
- 1 774 616
7.966.141 -
8.040.274 -
8.049.371 -
Instruments International
D
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
Tel.+41 61 715 81 00
Fax+41 61 715 25 00
www.endress.com
[email protected]
TI01042F/00/EN/01.12
71162681
CCS/EH-COSIMA ProMoDo