Electrical Method Statement OHTL

The document outlines the Electrical Method Statement for the construction of the New Amiral 380/230kV BSP, detailing the scope of work, responsibilities, tools, and execution methodology. It emphasizes safety measures, quality control, and deliverables required for the project. Key activities include tower earthing, conductor stringing, OPGW installation, and final commissioning.

Uploaded by

raja awais
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
47 views2 pages

Electrical Method Statement OHTL

The document outlines the Electrical Method Statement for the construction of the New Amiral 380/230kV BSP, detailing the scope of work, responsibilities, tools, and execution methodology. It emphasizes safety measures, quality control, and deliverables required for the project. Key activities include tower earthing, conductor stringing, OPGW installation, and final commissioning.

Uploaded by

raja awais
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Electrical Method Statement

Project: Construction of New Amiral 380/230kV BSP including 380kV OHTL (LILO) & 230kV UG Cable Connections
Client: National Grid SA
Contractor: [Your Company Name]
Standard References: SEC PTS-23EN324, TES-P-122.09 Rev.02, IEC 60826, IEEE 524, IEC 60383, IEC 60815

1. Scope of Work (Electrical)


- Tower earthing and bonding.
- Installation of insulators and hardware fittings.
- Stringing, sagging, and clipping of conductors.
- Stringing and jointing of OPGW (Optical Ground Wire).
- Electrical testing: tower footing resistance, continuity, insulation checks, OPGW fiber tests.
- Final commissioning and energization of 380kV OHTL.

2. Responsibilities
- Project Manager – overall responsibility.
- Electrical Site Engineer – execution and compliance with drawings/specifications.
- Quality Engineer – inspection as per ITP.
- Safety Officer – ensure adherence to National Grid Safety Rules.
- Supervisor/Foreman – direct control of stringing and erection teams.

3. Tools, Plants & Equipment


- Hydraulic cranes (for insulator strings & OPGW drums).
- Tensioner and puller machines (hydraulic, for conductor & OPGW).
- Conductor drum jacks & reel stands.
- Pilot rope winches (for pulling pilot line).
- Dynamometers & sagging equipment.
- Come-alongs, grips, and tension clamps.
- OTDR tester, fusion splicer (for OPGW).
- Earth resistance tester.
- Torque wrenches (for hardware bolts).

4. Execution Methodology (Electrical)


- Tower Earthing: Install copper-bonded earth rods, use exothermic welding, ensure TFR < 10Ω.
- Insulator & Hardware Installation: Assemble on ground, hoist, torque bolts, check insulators.
- Conductor Stringing: Pilot rope pulling, conductor pulling with tensioner, sagging per charts, clipping and jointing with
compression fittings.
- OPGW Stringing & Splicing: Pull with pulleys, splice in joint boxes, perform OTDR test (≤0.1 dB per splice).
- Electrical Testing: TFR test, continuity, insulation, clearance verification, OTDR fiber test.
- Commissioning: Final inspection, SEC/National Grid energization, acceptance testing.

5. Inspection & Quality Control


- Inspection Test Plan (ITP) to cover each activity.
- Check insulators before installation.
- Torque test hardware bolts.
- Sagging verification at tension sections.
- Tower Footing Resistance measurement logs.
- OPGW OTDR test report.
- As-Built Dossier preparation.

6. Safety Measures
- Permit to Work (PTW) system enforced.
- Maintain safe clearance from live lines.
- PPE: insulated gloves, FR clothing, helmets, harnesses.
- Ground conductors during stringing to prevent induced voltages.
- Daily Toolbox Talks and Job Hazard Analysis (JHA).

7. Deliverables
- Inspection & Test Reports (ITRs).
- OPGW OTDR test results.
- Tower Footing Resistance records.
- As-Built Drawings with final coordinates.
- Drawing Completion Certificate (DCC).
- Final handover dossier to National Grid SA.