The PowerLogic® ION8600 is an advanced energy and power quality meter designed for high accuracy and flexible network connections, suitable for utilities, industry, and critical infrastructure. It features multiple mounting options, transformer loss compensation, multi-user security, and compliance monitoring with international power quality standards. The meter supports extensive communication protocols and is ideal for applications requiring accurate bidirectional energy measurement and power quality analysis.

Uploaded by

FERDINAND
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views8 pages

Ion 8600 3000BR0603R1009

The PowerLogic® ION8600 is an advanced energy and power quality meter designed for high accuracy and flexible network connections, suitable for utilities, industry, and critical infrastructure. It features multiple mounting options, transformer loss compensation, multi-user security, and compliance monitoring with international power quality standards. The meter supports extensive communication protocols and is ideal for applications requiring accurate bidirectional energy measurement and power quality analysis.

Uploaded by

FERDINAND
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Metering with higher accuracy,

power quality and flexible


network connections
PowerLogic® ION8600
energy and power quality meter

Utilities Industry Critical Infrastructure


Features
Multiple socket and switchboard form factors Transformer/line loss compensation
Meter is available in socket or switchboard form factors. The FT21 switchboard Automatically measure, compensate and correct for
case option provides all the benefits of the socket meters in a compact, transformer or line losses when meter is physically
switchboard mount, draw-out configuration. A quick disconnect system enables separated from billing point or change of ownership
removal of the meter electronics in one easy action without having to manually location.
disconnect wires, including I/O wiring.
Multi-user, multi-level security
High accuracy measurement Control and customise access to sensitive data for up
Meets stringent ANSI C12.20 Class 0.2 and IEC 62053-22 Class 0,2S to 16 users. Password protection and anti-tamper seal
measurement accuracy standards. One second loss calculation and error protection enhance meter security. Advanced security
correction capabilities establish system losses and correct for measurement functions for automatic detection, recording
errors in real time. and annunciation of:
>> PT or CT phase loss due to transformer wiring
Power quality compliance monitoring tampering or transformer failure
Measure compliance to the following international quality-of-supply standards: >> PT or CT phase reversal tampering or
>> EN50160, IEEE 519, IEEE 1159, ITI (CBEMA) installation error

Trust the quality of the results because compliance calculations are based on the >> Peak demand register resets
following international measurement standards: >> Meter power up/down
>> IEC 61000-4-7, IEC 61000-4-15

Patented ION® technology


Power quality analysis Modular, flexible architecture that offers extensive
Digital fault-recording capabilities simultaneously capture voltage and current user programmability. Uniquely addresses complex
channels for sub-cycle disturbance transients as well as multi-cycle sags/dips, monitoring and control applications.
swells and outages. Adapts to changing needs and new applications.

Complete communications: Fiber - Ethernet - Serial - Modem


Gateway functionality simplifies communications architecture and reduces
leased line or connection costs. Concurrent, independent ports communicate
with a variety of protocols such as ION, DNP 3.0, Modbus RTU, Modbus TCP,
Modbus Master (serial, TCP) and MV-90.
Intelligent metering and
control device
Providing high accuracy metering with a wide range of capabilities, the
PowerLogic® ION8600 meter is the most advanced socket-based energy and
power quality meter. Used to monitor network inter-ties, substations, and service
entrances, the PowerLogic ION8600 meter is ideal for applications that need to
accurately measure energy bidirectionally in all four quadrants.

These meters give utilities the tools to manage complex energy supply contracts
that include commitments to power quality. Integrate them with PowerLogic® ION
Enterprise® software, or other energy management and SCADA systems, through
multiple communication channels and protocols.

Typical Applications
For infrastructure, industrials and buildings For electric utilities
>> Energy savings >> Revenue metering and power quality
• Measure efficiency, reveal opportunities and • Install high-accuracy metering at all interchange points
verify savings
• Improve or verify metering accuracy at existing interchange points
• Strengthen rate negotiation with energy suppliers
• Help customers manage costs using value-added billing data
• Enable participation in load curtailment programs
• Enable customer participation in load reduction programs
(e.g. demand response)
• Verify compliance with new power quality standards
• Identify billing discrepancies
• Analyze and isolate the source of power quality problems
>> Energy availability and reliability
>> Energy availability and reliability
>> Validate that power quality complies with the energy
contract • Improve T&D network reliability
• Improve response to power quality-related • Enhance substation automation to reduce field service time
problems
• Maximize the use of existing infrastructure
Installation
Mounting options
Meter is available in socket or switchboard form factors. Socket meters fit S-Base
meter sockets and A-to-S Base adapters; supported Form factors include 9S, 35S,
36S, 39S, and 76S. Switchboard meters eliminate need for shorting blocks; they
may be ordered with an optional breakout panel that provides easy access to on-
board I/O and communications connections.

Circuit and control power connections


Socket meter mounting
Meter has 3 voltage and 3 current inputs (optional 4th current input) compatible
with 4-wire Wye, 3-wire Wye, 3-wire Delta, and single-phase systems. Direct
connect ANSI socket mount 9S, 39S, 36S and 76S systems up to 277 V ac line-to-
neutral, or a 35S system up to 480 V ac line-to-line. Meter can be powered by the
voltage source being monitored or from an auxiliary power pigtail.

Input Specification

Form 9S/36S/39S/76S steady state: Standard 57-277 (±15%) V L-N rms;


Voltage:
Form 9S/36S/39S/76S overload: Standard power supply 120-277 (± 20%)
Va, Vb, Vc, Vref V L-N rms, Low Voltage power supply 57.7-69.3 (± 20%) V L-N rms;
(9S/39S) Form 35S steady state: 120-480 (±15%) V L-L rms; Form 35S overload:
Vab, Vcb, Vref 120-480 (±20%) V L-L rms; Dielectric withstand: 2500 V rms, 60 Hz for 1
(35S) min. (ANSI C12.1-1995/C12.16-1991/C12.20-1998); Surge withstand: 6kV
peak (1.2/50 µs) voltage surge L-L and L-GND (IEC 255-4) ANSI/IEEE
Va, Vc, Vref
C37.90.1-1989 SWC and Fast Transient Common and transverse modes.
(36S/76S)
ANSI C62.41; Impedance: 5M Ω/phase (phase-Vref)
Switchboard meter mounting Accuracy range 0.005 A to 20 A autoranging; Rated nominals: 5 A and/or
Current:
Standard 10 A; Starting current: 0.005 A rms; Fault capture: 50 A (instantaneous)
peak; Overload: 500 A rms for 1 second, non-recurring; Dielectric
(IEC 5 A & 10 withstand: 2500 V ac, 60 Hz for 1 minute; Burden (switchboard): 0.20
A; ANSI current VA per phase (at 5 A); Burden (socket): 0.05 VA per phase (at 5 A);
class 10 & 20) Impedance: 0.002 Ω/phase (phase-Vref)

237.00 mm (9.33 In) Current: Optional Accuracy range 0.001 A to 10 A autoranging; Rated nominals: 1 A, 2 A
204.50 mm (8.05 In)
an 5 A; Starting current: 0.001 A rms; Fault capture: 24 A (instantaneous)
(IEC 1 A to 10 peak; Overload: 200 A rms for 1 second, non-recurring; Dielectric
A; ANSI current withstand: 2500 V ac, 60 Hz for 1 minute; Burden: 0.015 VA per phase
class 2 &10) (at 1 A); Impedance: 0.015 Ω
Rated inputs: 120-277 V ac; Type: 3-phase powered from voltage
sensing inputs; Burden: max 4 W, 6.6 VA/phase; Form 9S/39S, 36S/76S:
Control power: 120-277 V L-N rms (-15%/+20%) 47-63 Hz; Form 35S: 120-480 V L-N rms
(-15%/+20%) 47-63 Hz; Dielectric withstand: 2500 V ac rms, 60 Hz for 1
Standard power min.; Ride-through: min100 ms (6 cycles at 60 Hz at 96 V ac), 200 ms (12
supply cycles at 60 Hz at 120 V ac), 800 ms (48 cycles at 60 Hz at 240 V ac);
Socket meter (front view) Socket meter (side view)
Surge withstand: 6 kV/0.5 kA peak (100 kHz Ring Wave) ANSI C62.41 6
kV/3 kA peak (1.2/50-8/20 us) voltage surge L-L and L-GND ANSI C62.41
Rated inputs: 57-70 V ac; Type: 3-Phase supply, drawing off voltage
inputs; Burden: Typical: 3 W, 5 VA/phase, 3-Phase operation Max: 4 W,
Control power: 6.6 VA/phase, 3-phase operation; Form 9S/36S/39S/76S: 57-70
Standard low- (-15%/+20%) V L-N rms, 47-63 Hz; Form 35S: unavailable; Dielectric
voltage power withstand: 2500 V ac rms, 60 Hz for 1 min.; Ride-through: min 100 ms or
supply 6 cycles 60 Hz at 46 V ac; Surge withstand: 6 kV/0.5 kA peak (100 kHz
Ring Wave) — ANSI C62.41, 6 kV/3 kA peak (1.2/50-8/20 µs) voltage
surge L-L and L-GND ANSI C62.41
Rated inputs: 65-120 V ac (± 15%) L-N rms, 47-63 Hz or 80-160 V dc
Control power: (± 20%); Type: 1-Phase supply, powered through external cable with
grounded U-Plug; Burden: Typ. 10 VA, max 20 VA; Dielectric withstand:
Auxiliary power
2500 V ac rms, 60 Hz for 1 min.; Ride-through: min. 100 ms 6 cycles 60
cable assembly
Hz at 46 V ac; Surge withstand: 6 kV/0.5 kA peak (100 kHz Ring Wave)
ANSI C62.41 6 kV/3 kA peak (1.2/50-8/20 us) voltage surge L-L and
L-GND ANSI C62.41

Rated inputs: 160-277 V ac (±20%) L-N rms, 47-63 Hz or 200-350 V dc


Switchboard meter (front view) Switchboard meter (side view)
(± 20%); Type: 1-Phase supply, powered through external cable with
Control power: grounded U-Plug; Burden: typ. 10 VA, max 20 VA; Dielectric withstand:
2500 V ac rms, 60 Hz for 1 min.; Ride-through: min 100 ms 6 cycles, 60
Auxiliary power
Hz at 96 V ac; Surge withstand: 6 kV/0.5 kA peak (100 kHz Ring Wave)
cable assembly
ANSI C62.41 6 kV/3 kA peak (1.2/50-8/20 µs) voltage surge L-L and
L-GND ANSI C62.41
Front panel
View system data or configure meter settings. The bright, easy-to-read, backlit
Vln a 120.00 V LCD screen with adjustable contrast provides easy viewing in poor lighting
Vln b 119.91 V
conditions. Multiple programmable screens display all metered data including
Vln c 119.89 V
numeric values, timestamped values, harmonics histograms, phasor diagrams and
Vln avg 119.93 V
name plate data. Navigation buttons move between display screens and aid basic
20:36:54 12/09/2008 ABC Q1 ALT setup procedures. Protected (sealable) buttons and switches provide access for
advanced meter configuration, such as meter resets. An ANSI Type II optical serial
Example alphanumeric display
port facilitates infrared communication with the device. Two LED pulse indicators
with corresponding infrared pulsers are preconfigured for energy pulsing.
kWh deliver
00000004.460 Power and energy measurements
kWh receive
High-accuracy (1-second), high-speed (1/2-cycle) true RMS 3-phase
00065135.060
operational measurements for each phase (per phase) and all phases (total).
19:36:54 12/09/2008 ACB Q1 NORM
Accuracy ±
Example alphanumeric display Parameter
(% reading)
Voltage (line-line) (line-neutral): per phase, total, min/max,
0.1 %
unbalance, phase reversal
Current (I1, I2, I3, I4): per phase, total, neutral (39S, 76S), min/max,
unbalance phase reversal 0.1 %
Current demand2: present, min/max, predicted
Power: real (kW), reactive (kvar), apparent (kVA), per phase, total
0.2 %
Power demand2: present, min/max, predicted
Example vector diagram display
ANSI C12.20 class 0.2
Energy: real (kWh), reactive (kvarh), apparent (kVAh), bidirectional,
net, total, volt-hours, amp-hours and KQ-hours IEC 62053-22/23
(0.2S)1
Power factor: per phase, total 0.5 %

Frequency V1,V2,V3 (47-63 Hz): per phase, total 0.005 Hz

Crest factor current channels 1 %3


1 - Energy metering accurate to IEC 62053-22/23 0,2S; ANSI C12.20-1998 American National Standard
8 for Electricity Meters 0.2 and 0.5 Accuracy Classes, for current Classes 2, 10 and 20.
2 - Selectable block, sliding, or thermal (exponential) demand calculations
Example harmonics histogram display 3 - Fundamental >= 5 % nominal

Power quality
Power quality compliance monitoring for international quality-of-supply
standards plus specific data for localized and custom compliance agreements and
network connection requirements.
Analyze problems and avoid interruptions. Detect, record and report the specifics
of voltage or current imbalances and loss, frequency/power factor variations, over-
and under-voltages.
>> Sags/swells (all models): Monitor voltage waveforms for sags and swells (i.e.
ITI (CBEMA) Type 2 and Type 3 disturbances); report on each disturbance’s
magnitude and duration. Detect sub-disturbances during a sag/swell event.
>> Harmonics (all models): Individual harmonics up to the 63rd, K factor and
Total Harmonics Distortion (THD).
>> Harmonics (ION8600A): Voltage and current magnitude, phase and inter-
harmonics in accordance with IEC 61000-4-7 (up to the 40th).
>> Transient capture (ION8600A): Monitor voltage waveforms for transient activity
(i.e. ITI (CBEMA) Type 1 disturbances) to 65 µs at 60 Hz (78 µs at 50 Hz).
>> Waveform capture (ION8600A): Selectable waveform recording resolution from
Built-in web server provides browser access to extensive
16 samples/cycle to 256 samples/cycle (800 Hz to 51 kHz). Back-to-back
real-time data
waveform recording allows for extended captures.
>> EN50160, IEEE 519 and IEEE 1159 (ION8600A): Monitor compliance with
parameters for these international quality-of-supply standards.
Digital and analog inputs and outputs
Onboard meter I/O includes four Form C digital outputs and three Form A digital
inputs for a variety of applications, such as energy pulsing, control, energy
counting, status monitoring, and analog interface to SCADA.
Optional I/O Expander
The I/O Expander equips an ION meter with eight digital inputs, four Form A digital
outputs, and four Form C digital outputs, or four analog outputs in place of the four
Form A digital outputs. The I/O Expander also provides a convenient location for
the meter’s RS-232 and RS-485 communications wiring. Meter operation remains
unaffected during installation and configuration of the I/O Expander.

Input / output Specification


Excitation: SCOM self-excited, dry contact sensing, no external voltage
required; Minimum pulse width: 20 ms; Maximum input transition rate:
Digital inputs:
50 transitions/sec.; Scan time: 20 ms; Timing resolution: 1 ms with 2 ms
(S1 - S8)
accuracy; Isolation: 1000 V rms, 60 Hz 1 minute to meter; 3 additional
internal inputs available through optional on-board I/O
Optional I/O Expander
Max load voltage: 200 V ac / V dc; Max load current: 100 mA; On resistance:
Solid state
30 Ω (typical), 50 Ω (max); Off resistance: 400 M Ω (min); Isolation: 3750 V
outputs:
(C-1, C-2, C-3, RMS, 60 Hz for 1 minute to meter, 1000 V RMS, 60 Hz for 1 minute (between
C-4 ) outputs); Update rate: 20 ms; Max output transition rate: 50 transitions/s; 4
additional internal Form C outputs available through optional I/O Expander
(A-1, A-2, A-3, A-4), (Form A) supported through I/O Expander
4 analog outputs supported through I/O Expander; Output range: 0 to 20 mA
(scalable from 4 to 20 mA) or -1 to +1 mA (scalable from 0 to 1 mA); Max.
load: 500 Ω (0 to 20 mA), 10 K Ω (-1 to +1mA); Isolation: 3750 V RMS, 60 Hz
Analog outputs
for 1 minute to meter 2000 V RMS, 60 Hz for 1 minute; Accuracy: +/- 0.3% (%
of Reading) at 73.4 degrees F / 23 degrees C; Accuracy drift: 100 ppm/° K;
Update rate: 1 second

Data and event logging


The ION8600 ships with a comprehensive data-logging configuration. Data is
prioritized and stored onboard in non-volatile memory to eliminate data gaps in the
event of outages or server downtime. Dial-out capability when memory is near full;
data push capability through SMTP (email). Retrieved data is stored in an ODBC-
Optional switchboard breakout panel
compliant database when using PowerLogic ION Enterprise software. Logging
capacity is available in 2 MB, 4 MB and 10 MB configurations. The meter has data
Example logging configurations
recorders for revenue, losses, historic data, harmonics, waveforms, power system
Feature Feature Feature
data, sags/swells, transients, and event parameters.
Set A Set B Set C
Memory 10 MB 4 MB 2 MB
Multiple tariffs & time-of-use (TOU) calculations
Event 500 Events 500 Events 500 Events
20-year calendar with automatic leap-year and seasonal adjustments and clock
Data 1yr1 4yrs2 280 0.5 yr1 2 85 days1
synchronization over communications channel or GPS supports active, reactive, days 1 3 yrs2 yrs2 340 days2
Example logging configurations
and apparent energy and demand. TOU configured for 4 seasons, Waveforms 63 63 244 244 - -
5 daily profiles per season, and 4 rate periods per daily profile. Automatic
mid-season rate change. Automatic recording of maximum (peak) demand during
1 - 16 parameters recorded every 15 minutes
each tariff period.
2 - 16 parameters recorded hourly
3 - on each of 6 channels at 256 samples per cycle for
IRIG-B time synchronization option 14 cycles
IRIG-B is the industry standard for GPS time synchronization. IRIG-B applications 4 - on each of 6 channels at 16 samples per cycle for
include power quality monitoring and sequence of events recording, highly 96 cycles
accurate timestamping for revenue billing (1 ms), and system stability monitoring.

Alarm and control


Each meter has 65 setpoints configurable for 1-second or ½ -cycle operation.
Setpoint on any parameter or condition. Use them to trigger audible and visible
alarms, data logging, waveform recording, relays, and other control and reset
functions.
Communications
The meters offer multi-port access that provides secure, simultaneous data sharing
with utility systems and customers directly at the hardware level using a choice of EtherGate and ModemGate
communication standards and protocols. The meters can provide gateway functionality
Port Specification depending on communication options.
RS-232 / RS-485 Data rates: 300 – 115,200 bps (RS-485 limited to 57,600 bps); Isolation: EtherGate: provides access via Modbus TCP through
(COM 1) Optical; Duplex: Full (RS-232), Half (RS-485); Protocols: ION, Modbus the meter’s Ethernet port to devices communicating via
RTU, Modbus Master,DNP 3.0, GPS, EtherGate, ModemGate
Modbus connected to the meter’s serial ports.
Data rates: 300 – 57,600 bps; Isolation: Optical; Duplex: Half; Protocols:
RS-485 ModemGate: provides access from the telephone
ION, Modbus RTU, Modbus Master, DNP 3.0, GPS, EtherGate,
(COM 2)1 network to devices connected to the meter’s serial ports.
ModemGate
Data rate: 300 bps - 56 kbps (V.3.4, V.32 bis, V.32, V.22 bis, V.22
A/B, V.23, V.21, Bell 212A, Bell 103), automatic data rate detection
Internal modem
is supported; Error correction: V.42 LAPM, MNP 2-4, MNP 10; Data
(COM 2)2 EtherGate ModemGate
compression: V.42 bis/MNP 5; Interface: RJ11 (tip and ring); Approvals3:
FCC P68 (USA), Industry Canada CS-03 Telephone
Ethernet Serial line Serial
ANSI Type 2 optical Data rates: 1200 - 19,200 bps; Duplex: Half; Protocols: ION, DNP 3.0,
(COM 3) Modbus RTU
Interface: IEEE 802.3-1993, ISO/IEC 8802-31993 (Ethernet) 10BASE-T;
Data rates:10 Mbps, half duplex; Connectors: RJ45; Cabling: Unshielded
Ethernet
twisted-pair cable, 0.5 mm (24 AWG) max length 100 metres (109 yards);
(10BASE-T)
Isolation: Transformer isolated; min isolation voltage 1500 V ac /2250 V dc;
Protocols: Telnet, ION, Modbus TCP, DNP TCP, Modbus Master
Interface: IEEE 802.3-1993, ISO/IEC 8802-31993 (Ethernet) 10BASE-FL
(optional); Data rates:10 Mbps, half duplex; Connectors: ST; Cabling:
Ethernet Fiber optic cable, 62.5/125 μm nominal, wavelength 820 nm max length Internet connectivity
(10BASE-FL) 2000 metres (2,187 yards); Isoloation: Optical; Protocols: Telnet, ION, Exchange information using XML to integrate with
Modbus TCP, DNP TCP, Modbus Master
custom reporting, spreadsheet, database, and other
1 - If the modem is present, COM 2 serial port is unavailable.
applications.
2 - In Feature Set C, if Ethernet and modem options are chosen, no serial port is available. WebMeter: an on-board web server, provides access
3 - Also approved for use in: Austria, Belgium, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy,
Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland, UK to real-time values and PQ data through any
web-enabled device and even supports basic
Itron software support meter configuration tasks.
The meters are fully compatible with Itron software platforms including MV-90, MVP, MeterM@il: automatically emails user-configured,
MVRS, MVLT and MVCOMM, and offer a direct Ethernet connection to MV-90. high-priority alarm notifications or scheduled
system-status update messages to anyone,
Software integration anywhere within the facility or around the world.

Integrate within PowerLogic facility-level or enterprise-wide power and energy


management systems. Real-time data and data logs stored onboard can be
automatically retrieved on a scheduled basis for analysis at the system level.
Compatible with PowerLogic ION Enterprise software.
Modbus compatibility and register-based logged data supports integration and
data access by building automation, SCADA and other third-party systems.

Special features
Downloadable firmware: update your meters with the latest features by simply
downloading them from www.powerlogic.com.

General specifications
Description Specification
Operating range -40° F to 185° F (no formation of ice) (-40° C to 85° C)
Display operating range -4° F to 140° F (-20° C to 60° C)
Storage range -40° F to 185° F (-40° C to 85° C)
Relative humidity range 5% to 95% non-condensing
Safety/construction ANSI C12.20-1998 American National Standard for Electricity Meters & IEC 62052-11
ESD: IEC61000-4-2 (EN61000-4-2/IEC801-2); Radiated EM Field: IEC61000-4-3 (EN61000-4-3/IEC801-3); Electric Fast Transient: IEC61000-
4-4 (EN61000-4-4/IEC801-4); Surge: IEC61000-4-5 (EN61000-4-5/IEC801-5); Conducted: IEC61000-4-6 (EN61000-4-6/IEC801-6); Damped
Immunity
oscillatory waves: IEC61000-4-12 (EN61000-4-12/IEC801-12); Surge: ANSI C62.41; ANSI/IEEE C.37-90.1-1989 Standard surge withstand
capability tests for protective relays and relay systems
Emissions FCC Part 15 Subpart B, CISPR 22 Radiated/Conducted Emissions (Class B)
California ISO, ERCOT, and New York State; Industry Canada (AE-0924); EGR Code of Practice 4 for New Zealand; Certified by Commission
Utility approvals Federal de Electricidad and LAPEM in Mexico
Feature sets A B C
Metering
Power, energy & demand n n n
Power quality
Sag/Swell, harmonics monitoring n n n “The 2007 award recognizes Schneider Electric for its technological
Harmonics: individual, even, odd, up to 63rd 63rd 31st advancements and wide product range in the field of power quality (PQ)
Harmonics: magnitude, phase & inter-harmonics 40th - - and energy management solutions. In total, this is the fourth award that
Schneider Electric has received from Frost & Sullivan in recognition of
IEC 61000-4-15 (Flicker) n - - achievements in this arena.” Prithvi Raj, Frost & Sullivan research analyst
Symmetrical components: zero, positive, negative n n n
Transient detection, microseconds (50 Hz / 60 Hz) 78 / 65 - -
Sampling rate, maximum samples per cycle 256
Frequency accuracy 0.005 Hz
Logging and recording
Memory standard/optional 10 MB 4 MB 2 MB
Min/max logging for any parameter n n n File# 002188
Timestamp resolution in seconds 0.001
GPS time synchronisation n n n
Please contact your local sales representative for
Communications and I/O ordering information.
RS-232/485; RS-485; Ethernet; Optical; IRIG-B n n n
Visit www.powerlogic.com for more information on
Internal modem 1
other PowerLogic products, applications and system
3-port DNP 3.0 via serial, modem, Ethernet, Optical ports n n n solutions.
Modbus TCP Master / Slave (Ethernet port) n/n n/n -/n
Modbus RTU Master (serial ports) / Slave (all ports) n/n n/n -/n
EtherGate, ModemGate, MeterM@il, WebMeter n n n
Internal KYZ outputs / Form A inputs 4/3
Ext. digital status inputs/counter/solid state outputs 8/8
Setpoints, alarming, and control
65/1/2 65/1/2
Setpoints, number / minimum response time 65/1 sec
cycle cycle
Math, logic, trig, log, linearization formulas n n n
Call-out on single & multi-condition alarms n n n
Revenue metering
MV-90 on serial, modem, Ethernet ports (if present) n n n
Multi-year scheduling: hourly activity profiles n n n
Transformer/line loss compensation/ITC n/n n/n n/n

©2009 Schneider Electric. All rights reserved.

Schneider Electric - North American Operating Division


As standards, specifications and designs develop over time, always ask for confirmation
295 Tech Park Drive
LaVergne, TN 37086 of the information given in this publication. PowerLogic, ION, ION Enterprise, System
Tel: 615-287-3500 Manager, Square D, MeterM@il, and Modbus are either trademarks or registered
www.PowerLogic.com
trademarks of Schneider Electric.

Printed on recycled paper 3-09


Document Number 3000BR0603R10/09

You might also like