SOLARATOR
SERIES
Experience Uninterrupted Power with Solis Energy Storage Inverters

S6-EH3P(75-125)K10-NV-YD-H
Three Phase | High Voltage

6 Leading Features


Support flexible PV connection through DC and
AC coupling simultaneously

Support battery reserve function in multiple


scenarios
8 Unique Features


Usable PV power up to 200% inverter rated
power, improve the utilization of PV generation

Support max 21A PV input current, perfectly


match high power PV modules

• Smart Load Prioritizing – Extended support for • Compatible with 100-314Ah battery modules
critical loads
• Support faster charging with battery current
• Seamless on grid/off grid switching time <10ms up to 200A

• Support max 10 pcs in parallel mode, >6 pcs • Powerful backup overload capability – 160%
recommend Solis power distribution cabinet overload

• SMARTLOAD/GEN/INV port - Flexible connection • Support wide power range of generator


of multiple energy sources such as Grid-tied interaction from 25kVA to 125kVA
inverter, diesel generator, wind turbines,etc.
• Support 2 independent batteries connection
for flexible configuration

• 7-inch large screen uses U.S.-made ZEITLER


industrial-grade components

GINLONG TECHNOLOGIES CO., LTD.

t: +86 574 6580 2188 e: s [email protected]


w: solisinverters.com [email protected]
DATASHEET S6-EH3P(75-125)K10-NV-YD-H

Models 75K 80K 100K 125K


Input DC (PV side)
Recommended max. PV array size 150 kW 160 kW 200 kW 240 kW
Max. usable PV input power 150 kW 160 kW 200 kW 240 kW
Max. input voltage 1000 V
Rated voltage 600 V
Start-up voltage 180 V
MPPT voltage range 150 - 950 V
Max. input current 10 × 42 A
Max. short circuit current 10 × 60 A
MPPT number / Max. input strings number 10 / 20
Battery
Battery type Li-ion
Battery voltage range 300 - 950 V
Max.charge / discharge current 200 A / 100 A + 100 A
Number of battery ports 2
Max. charge / discharge current of each port 100 A
Communication CAN / RS485
Output AC (Grid side)
Rated output power 75 kW 80 kW 100 kW 125 kW
Max. apparent output power 75 kVA 80 kVA 100 kVA 125 kVA
Rated grid voltage 3/N/PE, 220 V / 380 V, 230 V / 400 V
Rated grid frequency 50 Hz / 60 Hz
Rated grid output current 114 A / 108.3 A 121.6 A / 115.5 A 152 A / 144.3 A 180.4 A / 189.9 A
Power factor > 0.99 (0.8 leading - 0.8 lagging)
THDi < 3%

y
Input AC (Grid side)

r
Max. input current 250 A
Output AC (Back-up)

a
Rated output power 75 kW 80 kW 100 kW 125 kW

n
1.2 times of rated power, 100 s

i
1.2 times of rated power, 10 mins; 1.4 times of rated power, 100 s;
Max. apparent output power 1.4 times of rated power, 10 s
1.6 times of rated power, 10 s; 2 times of rated power, 200 ms
1.6 times of rated power, 200 ms
Back-up switch time < 10 ms

im
Rated output voltage 3/N/PE, 220 V / 380 V, 230 V / 400 V

l
Rated frequency 50 Hz / 60 Hz

re
THDv (@linear load) < 2%
Efficiency
Max. efficiency 97.6%

P
EU efficiency 97.2%
BAT charged / discharged to AC max. efficiency 97.0%
Protection
Anti-islanding protection Yes
Output over current protection Yes
Short circuit protection Yes
Integrated DC switch Yes
DC reverse-polarity protection Yes
Surge protection DC Type II / AC Type II
Integrated AFCI 2.0 Yes Optional Optional (Brazil: Yes)
Protection class / Over voltage category I / II
General Data
Max. allowable phase imbalance (grid & back-up) 100%
Max. power per phase (grid & back-up) 25.00 kW 26.66 kW 33.33 kW 41.66 kW
Dimensions (W × H × D) 1174 × 814 × 400 mm
Weight 170 kg
Topology Transformerless
Operating ambient temperature range -25 ~ +60°C
Ingress protection IP66
Cooling concept Intelligent fan-cooling
Max. operation altitude 3000 m
G99, VDE-AR-N 4105/VDE V 0124, EN 50549-1&2/EN 50549-10, VDE 0126/UTE C 15/VFR:2019, NTS 631/RD 1699/RD 244/
UNE 206006/UNE 206007-1, CEI 0-21, C10/11, NRS 097-2-1, TOR, EIFS 2018.2, IEC 62116, IEC 61727, IEC 60068, IEC 61683,
Grid connection standard
EN 50530, MEA, PEA,PORTARIA Nº 140, DE 21 DE MARÇO DE 2022;
Brazil (75K: ORDINANCE (PORTARIA) NO.140, ORDINANCE NO. 515; 100K/125K: NBR 16149, NBR 16150, IEC 62116)
Safety / EMC standard IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4, EN 55011
Features
PV connection MC4 Quick connection plug
Battery connection Terminal connector
AC connection Terminal block
Display 7.0" LCD display & Bluetooth + APP
Communication CAN, RS485-115200, Ethernet, Optional: Wi-Fi, Cellular, LAN