Ie 150 Battery Asc 150 Storage Asc 4 Battery Modbus Client Tables 4189341294 Uk

The document provides details on the Modbus client functionalities for iE 150 Battery, ASC 150 Storage, and ASC-4 Battery, including software versions and function codes for reading and writing registers. It outlines various control commands, measurements, and configurations for both AC and DC data schemes. Additionally, it specifies the Modbus address offsets and the expected data types and ranges for different parameters.

Uploaded by

edwin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views3 pages

Ie 150 Battery Asc 150 Storage Asc 4 Battery Modbus Client Tables 4189341294 Uk

The document provides details on the Modbus client functionalities for iE 150 Battery, ASC 150 Storage, and ASC-4 Battery, including software versions and function codes for reading and writing registers. It outlines various control commands, measurements, and configurations for both AC and DC data schemes. Additionally, it specifies the Modbus address offsets and the expected data types and ranges for different parameters.

Uploaded by

edwin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

937327949.

xlsx
4189341284A
Software version 4.16.0

iE 150 Battery, ASC 150 Storage and ASC-4 Battery Modbus client

Software version
The information contained in these tables (Revision H) is applicable to:
iE 150 and ASC 150 software version 1.30.0
ASC-4 software version 4.29.0

See the ASC 150 Modbus client User manual and the ASC-4 Modbus client User manual for more information.

Row Hyperlink index


15 Modbus function codes
21 Output holding register
26 Input register

Modbus function codes


Back to index

Function code Description


04 Read a single or multiple input registers.
06 Write a value to a single output holding register.
16 Write a value to multiple consecutive output holding registers.

Output holding register (function code 06 or 16: Write)


Back to index

Function group Description


Writes one bit to activate the configuration.

0 (false) when the configuration is not activated.


Configuration 1 (true) when the configuration is activated.
Control command Activate a command.

Input register (function code 04: Read)


Function group Description
AC measurement Read the operating value of the AC measurement.
Back to index

Read one bit to see whether the alarm is activated.

0 (false) when the alarm is not activated.


Alarm 1 (true) when the alarm is activated.
Configuration Read the configured value.
DC measurement Read the operating value of the DC measurement.
Measurement Read the operating value of the measurement.
Status Read the status.

www.deif.com Page 1 of 3
937327949.xlsx
4189341284B
Software version 4.17.0

BCU/PCS data scheme


DEIF Generic is selected in ESS Protocol (parameter 7561).
* For 32-bit integers, only the first Modbus address is listed. The DEIF generic offset (parameter 7960) is 30000 (default).
** This register is only relevant for iE 150 Battery and ASC 150 Storage in a greenfield installation, with ground relay activated.

Note: To prevent problems with future expansions of the protocol, allow writing of all registers from 0 to 99, and reading of all registers from 30000 to 30099.

iE 150 and ASC 150 ASC-4


Modbus address Modbus address Function Data Scaling Modbus server address Modbus server address iE 150 Battery/
Function group (offset 30000)* (offset 1000) Bit code BCU/PCS function name Data type format (10⁻ˣ) Range Unit (function code 03) (function code 03) ASC parameter
ESS start/stop
0 = Stop
Control command 0 0 06; 16 1 = Start INT16s AB 0
ESS mode
0 = P/Q mode (grid-tie)
1 = V/f mode (island/off grid/grid forming)
Control command 1 1 06; 16 2 = Droop mode (V/f) INT16s AB 0
-100.0% to 100.0% /
-100% to 100% /
-3000.0kW to 3000.0kW /
Control command 2 2 06; 16 P set point (% of nominal power or kW) INT16s AB 1/0 -30000kW to 30000kW % / kW

-100.0% to 100.0% /
-100% to 100% /
-3000.0kvar to
3000.0kvar /
Control command 3 3 06; 16 Q set point (% of nominal reactive power or kvar) INT16s AB 1/0 -30000kvar to 30000kvar % / kvar
Control command 4 4 06; 16 Frequency set point (used for nominal f and synchronising) INT32s ABCD 3 45 to 65 Hz
Control command 6 6 06; 16 Voltage set point INT32s ABCD 1 350 to 550 V

Control command 8 8 06; 16 Droop delta frequency set point for V/f operation (island and droop) INT16s AB 3 -5 to 5 Hz
Control command 9 9 06; 16 Droop delta voltage set point for V/f operation (island and droop) INT16s AB 1 -100 to 100 V
Control command 10 10 06; 16 Heart beat (toggle 0x55AA/0xAA55 for each cycle) INT16s AB 0
Phase rotation
0 = L1L2L3
Configuration 11 11 0 06; 16 1 = L1L3L2 BOOL
Configuration 11 11 1-2 06; 16 Reserved BOOL
Configuration 11 11 3 06; 16 Activated by iE 150 Battery/ASC M-Logic "Custom input to ESS" BOOL
Configuration 11 11 4 06; 16 Activated by iE 150 Battery/ASC M-Logic "Ack. alarms on ESS" BOOL
Configuration 11 11 5 06; 16 Activated by iE 150 Battery/ASC M-Logic "Ack. Alarms on BMS" BOOL
Configuration 11 11 6 - 15 06; 16 Reserved
Ground relay
0 = Open ground relay
Control command 12 12 06; 16 1 = Close ground relay** BOOL
AC measurement 30000 1000 04 Frequency slope INT32s ABCD 1 % P/Hz 46315 40315
AC measurement 30002 1002 04 Voltage slope INT32s ABCD 1 % Q/V 46316 40316
AC measurement 30004 1004 04 Actual active power production (P) INT32s ABCD 1 kW 46102 40102
AC measurement 30006 1006 04 Actual reactive power production (Q) INT32s ABCD 1 kvar 46122 40122
AC measurement 30008 1008 04 Actual apparent power production (S) INT32s ABCD 1 kVA 46124 40124
AC measurement 30010 1010 04 Actual voltage L1-L2 INT32s ABCD 1 350 to 550 V 46336 40336
AC measurement 30012 1012 04 Actual voltage L2-L3 INT32s ABCD 1 350 to 550 V 46337 40337
AC measurement 30014 1014 04 Actual voltage L3-L1 INT32s ABCD 1 350 to 550 V 46338 40338
AC measurement 30016 1016 04 Actual frequency INT32s ABCD 3 0 to 70 Hz 46342 40342
Alarm 30018 1018 0 04 BCU/PCS warning. 0 = No alarm, 1 = Alarm activated BOOL 46343 40343 7580
Alarm 30018 1018 1 04 BCU/PCS shutdown. 0 = No alarm, 1 = Alarm activated BOOL 46343 40343 7590

ESS status
0 = Stopped / Fault
1 = Standby
2 = P/Q
3 = V/f
4 = Droop
Status 30019 1019 04 5 = Wait INT16s ABCD 1 A 46324 40324
Configuration 30020 1020 0 04 Reserved 46369 40369
P/Q set point format
0 = % (default)
Configuration 30020 1020 1 04 1 = kW/kvar BOOL 46369 40369
P/Q set point scaling
0 = 1 decimal (default)
Configuration 30020 1020 2 04 1 = 0 decimals BOOL 46369 40369
Configuration 30020 1020 3 04 Activate iE 150 Battery/ASC M-Logic "Custom output 1 from EMS" BOOL 46369 40369
Configuration 30020 1020 4 04 Activate iE 150 Battery/ASC M-Logic "Custom output 2 from EMS" BOOL 46369 40369
Configuration 30020 1020 5 04 Activate iE 150 Battery/ASC M-Logic "Custom output 3 from EMS" BOOL 46369 40369
Configuration 30020 1020 6 - 15 04 Reserved 46369 40369

www.deif.com Page 2 of 3
937327949.xlsx
4189341284B
Software version 4.17.0

BCU/BMS data scheme


DEIF Generic is selected in BMS Protocol (parameter 7681).
* For 32-bit integers, only the first Modbus address is listed. The DEIF generic offset (parameter 7960) is 30000 (default).

Note: To prevent problems with future expansions of the protocol, allow reading of all registers from 30100 to 30199.

iE 150 and ASC 150 ASC-4


Modbus address Modbus address Function Scaling Modbus server address Modbus server address iE 150 Battery/
Function group (offset 30000)* (offset 1000)* Bit code BCU/BMS function name Data type Data format (10⁻ˣ) Range Unit (function code 03) (function code 03) ASC parameter
AC measurement 30100 1100 04 Maximum charge INT32s ABCD 1 kW 46311 40311
AC measurement 30102 1102 04 Maximum discharge INT32s ABCD 1 kW 46309 40309
Measurement 30104 1104 04 State of charge (% of nominal capacity) INT16s AB 2 0 to 100 % 46300 40300
Measurement 30105 1105 04 State of health (% of nominal capacity) INT16s AB 2 0 to 100 % 46317 40317
DC measurement 30106 1106 04 DC battery voltage INT16s AB 0 V 46318 40318
DC measurement 30107 1107 04 DC battery current INT32s ABCD 1 A 46326 40326
Alarm 30109 1109 0 04 Warning. 0 = No alarm, 1= Alarm activated BOOL 46360 40360 7610
Alarm 30109 1109 1 04 Shutdown. 0 = No alarm, 1= Alarm activated BOOL 46360 40360 7620
Activate iE 150 Battery/ASC M-Logic "Custom
Configuration 30110 1110 0 04 output from BMS" 46370 40370
Configuration 30110 1110 1-15 04 Reserved 46370 40370