Quick Reference for Parameterlist for

Endusers BurnerTronic BT300


BT320...BT340

Sensors and Systems


for Combustion Engineering
Table of Contents

Table of Contents

1 VALIDITY OF THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2 LIST OF PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2.1 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2.3 Monitor Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.4 Output Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.5 O2 Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.6 CO-Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

2.7 CO Control Optimisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

2.8 CO Controller Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

2.9 CO controller UCOe monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

2.10 CO Controller CO Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

2.11 CO Control Edge Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

2.12 FAT (Burner Sequencer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

2.13 Sequencer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

2.14 Configuring channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

2.15 Acutators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

2.16 Compound. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

2.17 Monitoring Bands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

2.18 Correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

2.19 LSB / Fieldbus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

2.20 Feature Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

2
1 Validity of these Instructions

1 Validity of these Instructions


This document is a supplement to the manual of the BT300. It is valid only in combination with
the use of the concerned operating manual. The specifications in this document apply to soft-
ware version 3.3. If you have an older version of the software, this could cause other implica-
tions to your device as aspected.

3
2 List of Parameters

2 List of Parameters
2.1 System

No. Device Description Attributes


0001 BT300 Brightness of LCD display
Group: 5
Min.: 0
Max.: 10
Default: 10
Write:0
Version: 1.0.0.0
0002 BT300 LCD contrast
Group: 5
Min.: 0
Max.:25
Default: 10
Write:0
Version: 1.0.0.0
0003 BT300 Screensaver mode of UI
The screensaver is activated after the adjusted time [min] has elapsed. Group: 5
Min.: 0
Max.: 120
Default: 1
Write:1
Version: 1.0.0.0

2.2 Maintenance

No. Device Description Attributes


0010 BT300 Maintenance interval [days]
Extension of the maintenance interval in days Group: 10
0 = no check of the maintenance interval Min.: 0
1 = no additional time configurated, only warnings are indicated Max.: 65535
>1 = additional time in days after the maintenance interval has ended until the system
indicates an error Default: 0
Write: 2
Version: 1.0.0.0
0011 BT300 Time until next burner service [days]
Maintenance interval = number of days until next burner maintenance Group: 10
0 = no check of maintenance interval Min.: 0
> 0 = days until next burner maintenance
Max.: 65535
Default: 0
Write: 2
Version: 1.0.0.0

4
2 List of Parameters

2.3 Monitor Output

No. Device Description Attributes


0024 BT300 no function
no function Group: 15
Min.: 0
Max.: 999
Default: 200
Write: 2
Version: 1.0.0.0
0025 BT300 no function
no function Group: 15
Min.: 0
Max.: 999
Default: 200
Write: 2
Version: 1.0.0.0
0028 BT300 no function
no function Group: 15
Min.: 0
Max.: 999
Default: 999
Write: 2
Version: 1.0.0.0
0029 BT300 no function
no function Group: 15
Min.: 0
Max.: 999
Default: 999
Write:2
Version: 1.0.0.0

5
2 List of Parameters

2.4 Output Regulator

No. Device Description Attributes


0040 BT300 Type of output regulator. 0-OFF / 1-constant regulator / 2-controlled by atmospheric
conditions
Operating mode: Group: 20
0 = OFF Min.: 0
1 = constant control
2 = controlled by atmospheric conditions/external setpoint shift Max.: 3
3 = no function Default: 0
Write:1
Version: 1.0.0.0
0043 BT300 Max. start-up temperature
Maximum start-up temperature or pressure depending on the actual value input Group: 20
Parameter for start-up circuit. Enter the actual temperature up to which the start-up cir- Min.: 0
cuit shall be active. Max.: 999
Default: 0
Write: 0
Version: 1.0.0.0
0044 BT300 Start-up output
Start-up output in digit depending on internal firing-rate. Group: 20
Enter the burner firing-rate with which the burner shall start in the start-up circuit. Min.: 0
Max.: 999
Default: 0
Write: 0
Version: 1.0.0.0
0045 BT300 Start-up time
Start-up duration [sec] Group: 20
Enter the maximunm duration for start-up. Min.: 0
Max.: 32767
Default: 0
Write: 0
Version: 1.0.0.0
0046 BT300 Ext. output limit [digit]
External output limit in digit depending on internal firingd-rate Group: 20
Min.: 0
Max.: 999
Default: 999
Write: 0
Version: 1.0.0.0

6
2 List of Parameters

No. Device Description Attributes


0047 BT300 Soft-stop time
Burner run-out time in seconds Group: 20
0 = no soft-stop Min.: 0
Set the duration, how long the burner runs in base firing-rate until shut-down occurs Max.: 100
effectively. If the value is set to zero, the burner runs in baseload continuesly after Default: 0
shut-down.
Write: 0
Version: 1.0.0.0
0048 BT300 Controller setpoint 1 minimum
Controller setpoint 1 minimum (setpoint 1) [°C] or [bar] (xx.x) Group: 20
Enter the minimum value for the first controller setpoint (active, if input "Setpoint Min.: 0
switching" = 0) (controller is controlled by atmospheric conditions). If the burner firing- Max.: 999
rate controller is set to constant control, the value is equal to the setpoint.
Default: 75
Saving the value is possible only if the controller is set to constant control. If the con-
troller is set to be controlled by atmospheric conditions, you can preset the burner fir- Write: 0
ing-rate controller’s setpoint manually. Version: 1.0.0.0
Activation of the controller’s setpoint switching is blocked in operating mode "OFF". In
this case the burner cannot be started by shifting the start-up point.
0049 BT300 Controller setpoint 1 maximum
Controller setpoint 1 maximum (setpoint 1) [°C] or [bar] (xx.x) Group: 20
Enter the minimum value for the first controller setpoint (active, if input "Setpoint Min.: 0
switching" = 0) (controller is controlled by atmospheric conditions). If the burner firing- Max.: 999
rate controller is set to constant control, the value is equal to the setpoint.
Default: 75
Saving the value is possible only if the controller is set to constant control. If the con-
troller is set to be controlled by atmospheric conditions, you can preset the burner fir- Write: 0
ing-rate controller’s setpoint manually. Version: 1.0.0.0
Activation of the controller’s setpoint switching is blocked in operating mode "OFF". In
this case the burner cannot be started by shifting the start-up point.
0050 BT300 Controller setpoint 2 minimum
Controller setpoint 2 minimum (setpoint 1) [°C] or [bar] (xx.x) Group: 20
Enter the minimum value for the first controller setpoint (active, if input "Setpoint Min.: 0
switching" = 0) (controller is controlled by atmospheric conditions). If the burner firing- Max.: 999
rate controller is set to constant control, the value is equal to the setpoint.
Default: 60
Saving the value is possible only if the controller is set to constant control. If the con-
troller is set to be controlled by atmospheric conditions, you can preset the burner fir- Write: 0
ing-rate controller’s setpoint manually. Version: 1.0.0.0
Activation of the controller’s setpoint switching is blocked in operating mode "OFF". In
this case the burner cannot be started by shifting the start-up point.

7
2 List of Parameters

No. Device Description Attributes


0051 BT300 Controller setpoint 2 maximum
Controller setpoint 2 maximum (setpoint 1) [°C] or [bar] (xx.x) Group: 20
Enter the maximum value for the first controller setpoint (active, if input "Setpoint Min.: 0
Switching" = 0) (controller is controlled by atmospheric conditions). If the burner firing- Max.: 999
rate controller is set to constant control, the value is equal to the setpoint.
Default: 60
Saving the value is possible only if the controller is set to constant control. If the con-
troller is set to be controlled by atmospheric conditions, you can preset the burner fir- Write: 0
ing-rate controller’s setpoint manually. Version: 1.0.0.0
Activation of the controller’s setpoint switching is blocked in operating mode "OFF". In
this case the burner cannot be started by shifting the start-up point.
0052 BT300 Firing-rate controller: Lower limit [°C] [digit]
Lower limit for mode: ’controlled by atmospheric confitions’ in °C or digit. Group: 20
This is the lower limit of the outside temperature at mode ’controlled by atmospheric Min.: 0
conditions’.
Max.: 999
0 ... 249  0 ... 249 °C/32 °F ... 480 °F
250 ... 500  -250 ... 0 °C/-418 °F ... 32 °F Default: -25°C
Lower limit for mode: setpoit shift in 0,1 mA or digit. This is the lower limit for the cur- Write: 0
rent input in 0,1 mA (min = 0 max = 500) Version: 1.0.0.0
0 = 0,0 mA
40 = 4,0 mA
200 = 20,0 mA
0053 BT300 Firing-rate controller: Upper limit [°C] [digit]
Upper limit (for mode: ’controlled by atmospheric confitions’) in 0,1°C or digit. Group: 20
This is the upper limit of the outside temperature at mode ’controlled by atmospheric Min.: 0
conditions’.
Max.: 999
0 ... 249  0,0 ... 24,9 °C/32 °F ... 76,82 °F
250 ... 500  -25,0 ... 0,0 °C/-13 °F ... 32 °F Default:
+25°C
Upper limit (for mode: Setpoint shift) in 0,1mA. This is the upper limit of the current
input (min = 0, max = 500) Write: 0
0 = 0,0 mA Version: 1.0.0.0
40 = 4,0 mA
200 = 20,0 mA
0054 BT300 Switch-off hysteresis of lower control range (burner start-up point)
Enter the start-up point as a difference to the setpoint. Group: 20
Start-up point = Setpoint - parameter value. Min.: 0
p.ex.: Burner shall start at 110. Setpoint = 120, parameter value = 10, Start-up value = Max.: 65535
120 - 10 = 110. Default: 1
If the burner shall start above the setpoint, you may also enter negative values . Ther- Write: 0
fore -1 = 65535 and -999 = 64537. Parameter value = 65536 - difference.
Version: 1.0.0.0
p.ex.: Burner shall start at 125. Setpoint = 120, parameter value = 65536 - 5 = 65531,
Start-up point = 120 - (-5) = 125.
0055 BT300 Swithc-off hysteresis of upper control range
Enter the upper control range as the difference of the actual setpoint to the upper limit Group: 20
of the control range °C, bar (xx.x) or digit Min.: 0
Depending on the settings in P 061 the content is interpreted as °C (directly, without Max.: 999
point), as bar (resolution 0,1 bar - range from 0,1 up to 99,9 bar) or as digit.
Default: 10
Write: 0
Version: 1.0.0.0

8
2 List of Parameters

No. Device Description Attributes


0056 BT300 Burner OFF
Burner OFF (difference to the setpoint) [°C] or [bar] (xx.x) or [digit] Group: 20
Enter the firing-rate controller’s shut-off limit as the difference of the actual setpoint to Min.: 0
the value by which the burner shuts off. This limit must be higher than the adjusted Max.: 999
control range’s upper limit. (P 0055).
Default: 15
Depending on the settings in P 0061 the content is interpreted as °C (directly, without
point), as bar (resolution 0,1 bar - range from 0,1 up to 99,9 bar) or as digit.. Write: 0
Version: 1.0.0.0
0057 BT300 P-term of the controller
P-term of the controller Group: 20
Min.: 0
Max.: 999
Default: 120
Write:0
Version: 1.0..0.0
0058 BT300 I-term of controller
I-term of controller Group: 20
Min.: 0
Max.: 999
Default: 60
Write: 0
Version: 1.0.0.0
0059 BT300 D-term of controller
D-term of controller Group: 20
Min.: 0
Max.: 999
Default: 20
Write: 0
Version: 1.0.0.0
0060 BT300 Cycle time
Enter the cycle time in seconds. This period lies between the single control steps. It Group: 20
would be wise to set this time according to the response time of the system. Min.: 0
Max.: 60
Default: 5
Write: 0
Version: 1.0.0.0

9
2 List of Parameters

No. Device Description Attributes


0061 BT300 Representation of actual value and set-point for firing-rate controller (0=digit, 1=°C,
2=bar, 3=mA)
Define, which setpoint input of the firing-rate controller is used and how it is interpreted Group: 20
in display and parameters (definition:kind of physical quantity). Min.: 0
LCM version 1.0.0.0 and higher Max.: 5
0 = digits
1 = °C Default: 1
2 = bar Write: 1
3 = mA
Version: 1.0
(4 = °F)
(5 = psi)
LCM version 1.2.0.0 and higher and UI version 3.3.0.0 and higher
(4 = °F)
(5 = psi)
0062 BT300 4 mA corresponds to x units
Lower limit/pressure 4 mA at setpoint input are equal to x bar (adjustable in 0.1 bar Group: 20
steps). Min.: 0
Enter the lower limit of the display range. If you have configurated this input as pres-
sure input it is 4 mA. Max.: 999
This parameter is active only if P 0061 = 2 Default: 0
Write: 1
Version: 1.0.0.0
0063 BT300 20 mA corresponds to x units
Lower limit/pressure 20 mA at setpoint input are equal to x 0,1 bar (to adjust in 0.1 bar Group: 20
steps). Min.: 0
Enter the upper limit of the display range. If you have configurated this input as pres-
sure input it is 20 mA. Max.: 999
This parameter is active only if P 0061 = 2 Default: 160
Write: 1
Version: 1.0.0.0
0065 BT300 Adjustment, which input of the firing-rate controller is used for manual presetting of
the burner firing-rate
Adjust which one of the firing-rate controller ’s inputs is used for manual presetting of Group: 20
the burner firing-rate Min.: 0
0 = potentiometer Max.: 3
1 = three-point-step (TPS)
2 = 4 ... 20 mA (current loop signal) Default: 2
3 = 0 ... 10 V (voltage input) Write: 1
Version: 1.0.0.0
0066 BT300 limitation of burner firiing-rate P 48 - P 51 [°C/0.1bar]
limitation of burner firiing-rate P 48 - P 51 in Celsius degree or 0.1bar Group: 20
Min.: 0
Max.: 999
Default: 0
Write: 2
Version: 1.0.0.0

10
2 List of Parameters

No. Device Description Attributes


0067 BT300 no function
no function Group: 20
Min.: 0
Max.: 0
Default: 065535
Write: 1
Version: 1.0.0.0
0068 BT300 no function
no function Group: 20
Min.: 0
Max.: 65535
Default: 0
Write: 1
Version: 1.0.0.0

2.5 O2 Controller

No. Device Description Attributes


0100 BT300 O2 controller type (0-no O2 control / 1-standard / 2-without dead time / 3-dis-
play only / 8-switch off value/ 9-LM-value)
O2 controller type Group: 25
0 = no O2 control (output of correction value for inactive O2 control) Min.: 0
1 = default Max.: 25
2 = without presetting of burner firing-rate and optimisation curve
3 = O2 display only (display of correction’s neutral value) Default: 1
4 ... 7 = OFF Write: 1
Editable only when burner is ON Version: 3.0.0.0
0101 BT300 Activate O2 control from firing-rate position X [digit]
You can deactivate O2 control with a defined firing-rate value. Group: 25
Output = correction value for inactive O2 control Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 3.0.0.0
0102 BT300 Deactivate O2 control from firing-rate position X [digit]
You can deactivate O2 control with a defined firing-rate value. Group: 25
Output = correction value for inactive O2 control Min.: 0
Editable even when burner is ON. Max.: 999
Default: 999
Write: 1
Version: 3.0.0.0

11
2 List of Parameters

No. Device Description Attributes


0103 BT300 Max. O2-value during pre-ventilation [vol. % O2]
The system monitors the threshold values. If the values are not reached, the O2 con- Group: 25
trol will be deactivated. The controller ouputs "correction value for inactive O2 control". Min.: 0
The system checks if "O2 value during pre-ventilation" is equal to "O2 value in ambient
air" (18 vol. % O2 and >24 vol. % O2). Max.: 250
Editable even when burner is ON. Default: 24,5
Write: 2
Version: 3.0.0.0
0104 BT300 Min. O2-value during pre-ventilation [vol. % O2]
The system monitors the threshold values. After pre-ventilation the O2 value should Group: 25
reach a value less than the adjusted one wihtin 45 sec. If it doesn’t reach this value, Min.: 0
O2 control will be deactivated. The controller outputs "correction value for inactive O2
control" (P 120). Max.: 25,0
Editable even when burner is ON. Default: 16,0
Write: 2
Version: 3.0.0.0
0105 BT300 Max. O2-value after ignition [vol. % O2]
The system monitors the threshold values. After pre-ventilation the O2 value should Group: 25
reach a value equal or less than the adjusted one wihtin 45 sec. If it doesn’t reach this Min.: 0
value, O2 control will be deactivated. The controller outputs "correction value for inac-
tive O2 control" (P 120). Max.: 25,0

Editable even when burner is ON. Default: 14,0


Write: 2
Version: 3.0.0.0
0107 BT300 Safety shut-down by O2 controller / CO controller allowed (0-never / 1-air deficiency)
When a fault occurs O2 control is deactivated. Depending on the cause of error the Group: 25
system outputs the preset correction value for "inactive O2-control" or "air deficiency". Min.: 0
No burner shut-down! (value = 0)!
Max.: 1
With this parameter you can just select a shut-down of the burner at air deficiency
(value = 1). Default: 0
Editable even when burner ON. Write: 2
Version: 3.0.0.0
0109 BT300 Dead time of O2 controlled system [s]
Dead time of the controlled system in seconds. Group: 25
Target value for two pass boiler or three pass boiler: 12 seconds Min.: 3
Editable even when burner ON. Max.: 40
Default: 15
Write: 1
Version: 3.0.0.0
0110 BT300 O2: P-term
Adjust P-term in a way that the system is able to compensate the setpoint variation of Group: 25
1 to 2 vol. % O2 in 4 to 6 steps without overshoot. Min.: 1
Control pulse too short - increase P-term
Overshoot - reduce P-term Max.: 50
Default: 5
Write: 1
Version: 3.0.0.0

12
2 List of Parameters

No. Device Description Attributes


0111 BT300 Dead time reduction for O2 controlled system at high firing-rate [s]
Target value for two pass boiler or three pass boiler: 3 seconds Group: 25
You can adjust dead time depending on the firing-rate. Min.: 0
Higher gas-rate = reduction of dead time at high firing-rate Max.: 5
Editable even when burner ON. Default: 3
Write: 2
Version: 3.0.0.0
0113 BT300 Delay after ignition in [s]
Delaytime for activation of O2-control after signal ’burner burns’. Group: 25
Editable even when burner is ON Min.: 0
Max.: 9999
Default: 90
Write: 2
Version: 3.0.0.0
0114 BT300 O2 dead band in [%]
O2 dead band with active trim. If the actual value of O2 is inside the dead band, there Group: 25
is no more output of actuating pulses. Min.: 0
Editable even when burner is ON. Max.: 5,0
Default: 0,2
Write: 2
Version: 3.0.0.0
0115 BT300 Load dead band of O2 control (in points)
This parameter avoids the masking of O2 control and therfore a presetting of the Group: 25
O2 actuator at small changes of the firing-rate. Min.: 0
Editable even when burner is ON. Max.: 999
Default: 40
Write: 2
Version: 3.0.0.0
0118 BT300 Min. value for probe dynamic check / 0 = no dynamic test
Adjust the threshold for function monitoring ’probe dynamic check’. Group: 25
Factory setting: 0,2 % vol. O2 Min.: 0
0 = "dynamic probe check" OFF
Max.: 2,0
Editable even when burner is ON.
Default: 0,2
Write: 2
Version: 3.0.0.0
0120 BT300 Correction value, which is displayd with inactive O2 trim
no function Group: 25
Min.: 0
Max.: 1000
Default: 400
Write: 2
Version: 3.0.0.0

13
2 List of Parameters

No. Device Description Attributes


0121 BT300 Air deficiency - correction value
Air deficiency - correction value Group: 25
Editable even when burner is ON. Min.: 0
Max.: 999
Default: 300
Write: 2
Version: 3.0.0.0
0128 BT300 First positive monitoring band [% of base firing-rate]
Adjust the O2 monitoring bands based on O2 setpoint value in % for base firing-rate Group: 25
and high firing-rate. Min.: 0
O2 value of first positive monitoring band = O2 setpoint value + x % from setpoint value
Max.: 101
Example:
O2 setpoint value = 3 % vol. O2 Default: 60
Parameter setting = 60 % Write: 4
O2 value of first positive monitoring band =
Version: 3.0.0.0
3 % O2 + 60 % of 3 % O2 = 3% O2 + 1,8 % O2 = 4,8 % O2
Editable even when burner is ON.
0129 BT300 First positive monitoring band [% of high firing-rate]
see P 128 Group: 25
Editable even when burner is ON. Min.: 0
Max.: 101
Default: 100
Write: 4
Version: 3.0.0.0
0132 BT300 First negative monitoring band [% of base firing-rate]
Adjust the O2 monitoring bands based on O2 setpoint value in % for base firing-rate Group: 25
and high firing-rate. Min.: 0
O2 value of first negative monitoring band = O2 setpoint value - x % of setpoint value
Max.: 100
Example:
O2 setpoint value = 3 % vol. O2 Default: 40
Parameter setting = 40 % of O2 value f first negative monitoring band = Write: 4
3 % O2 - 60 % of 3 % O2 = 3% O2 - 1,2 % O2 = 1,8 % O2
Version: 3.0.0.0
Enable even when burner is ON.
0133 BT300 First negative monitoring band [% of high firing-rate]
see P 132 Group: 25
Editable even when burner is ON. Min.: 0
Max.: 100
Default: 50
Write: 4
Version: 3.0.0.0

14
2 List of Parameters

No. Device Description Attributes


0136 BT300 Second negative monitoring [% of base firing-rate]
Adjust the O2 monitoring bands based on O2 setpoint value in % for base firing-rate Group: 25
and high firing-rate. Min.: 0
O2 value of second negative monitoring band = O2 setpoint value - x % from setpoint
value Max.: 100
Example: Default: 50
O2 setpoint value = 3 % vol. O2 Write: 4
Parameter setting = 40 % of O2 value
Version: 3.0.0.0
second negative monitoring band =
3 % O2 - 60 % of 3 % O2 = 3 % O2 - 1,2 % O2 = 1,8 % O2
Editable even when burner is ON.
0137 BT300 Second negative monitoring band [% of high firing-rate]
see P 136 Group: 25
Editable even when burner is ON. Min.: 0
Max.: 100
Default: 70
Write: 4
Version: 3.0.0.0
0140 BT300 Min. deadtime with modification to learncurve
This value defines the minimum time, which is needed to update the correction curve. Group: 25
If the addition of the adjusted dead time (P 109) and the dead time reduction (P 111) is Min.: 10
smaller than the value of this this parameter, the measured correction value will not be
stored. Due to this, the curve will not be updated. Max.: 30
Standard Value for the dead time is 12 s. Default: 12
Editable even when burner is ON. Write: 4
Version: 3.0.0.0
0142 BT300 Cutt-off of the O2 controller
Value = 1 cutts-off the O2 controller. The O2 controller displays the value for inactive Group: 25
controller. Min.: 0
Editable even when burner is ON. Max.: 1
Default: 1
Write: 0
Version: 3.0.0.0

2.6 CO-Control

No. Device Description Attributes


0200 BT300 CO controller type (0-OFF, 1-gas only, 2-curve set based on P 201)
CO controller type: Group: 30
1 = default (oil = O2 control , gas = CO control) Min.: 0
2 = CO control is activated by curve (P 201 - low byte)
3 = without dynymic optimisation, else like 1 Max.: 4
4 = without dynymic optimisation, else like 2 Default: 1
Editable even when burner is ON. Write: 1
Version: 3.0.0.0

15
2 List of Parameters

No. Device Description Attributes


0201 BT300 Co-controller: Curve set specific activated by bit pattern
Curve specific activation of CO- controller Group: 30
Low Byte (active only with P 200 = 2) - corresponding bit activated: CO controller Min.: 0
active Max.: 65535
High Byte (always active) - You can determine for evry curve set, if after a CO control- Default: 514
ler shut OFF (p.ex. after fault detection of a monitoring function) O2 control is acti-
vated or not. corresponding bit activated : O2-Regler is activated Write: 4
Default calue: 514 (O2controller is activated) Version: 3.0.0.0
Editable even when burner is ON.
0202 BT300 Base firing-rate value: below this value the CO control is switched OFF [digit]
Activate CO control at this value (in digit). Group: 30
Below this value CO control is inactive. Min.: 0
Editable even when burner is ON. Max.: 999
Default: 0
Write: 1
Version: 3.0.0.0
0203 BT300 High firing-rate value: above this value CO control is switched OFF [digit]
Activate CO control at this firing-rate position (in digit). Above this value CO control is Group: 30
inactive. Min.: 0
Value = 0 - CO controller is active over the entire range.
Max.: 999
Editable even when burner is ON.
Default: 999
Write: 1
Version: 3.0.0.0
0204 BT300 Smallest permissible O2 threshold value to switch OFF the CO-control
When reaching the O2 value in P 236, a forced shutdown of the optimisation occurs. Group: 30
When reaching the O2 value in P 204 , CO control is switched off an the function "air Min.: 0
deficiency" of the O2 trim is activated.
As soon as the secure SYSTEM BUS transfers an O2 value below this parameterised Max.: 10
limit and the parameterised time in P 205 has expired, CO control is switched OFF. Default: 0,4
Editable even when burner is ON. Write: 4
Version: 3.0.0.0
0205 BT300 Smalles valid O2 value:Tolerance time during supervision [sec]
As soon as the safe SYSTEM BUS connection transferrs an O2 value below the Group: 30
parameter set limit (P 204) and the parameter set time in this parameter (P 205) has Min.: 0
elapsed, a shut down of the CO control occurs..
Max.: 30
Editable even when burner is ON.
Default: 20
Write: 4
Version: from
3.0.0.0

16
2 List of Parameters

2.7 CO Control Optimisation

No. Device Description Attributes


0206 BT300 Max. firing-rate difference to stop static optimisation [digit]
Maximum permitted firing-rate difference (in digit) at static optimisation. Group: 31
During static optimisation internal firing-rate freezes. As soon as the adjustet differ- Min.: 0
ence exceeds, the process is interrupted and internal firing-rate is released again.
Max.: 999
Value range 0 ... 999 digit difference between regular firing-rate input and internal fir-
ing-rate. Default: 40
Editable even when burner is ON. Write: 2
Version: 3.0.0.0
0208 BT300 Time value [s] to cancel a closed optimisation in the burner operation
P 208 is active only, if P 207 is set to 0. Group: 31
0 = A completed optimisation is frozen for an unlimited time. Min.: 0
1...= Time [s] to clear a completed optimisation while the burner is in operation.
(28800 s = 8 h). Max.: 65535
Editable even when burner is ON Default: 28880
Write: 4
Version: 3.0.0.0
0209 BT300 Burner standstill [min], after expiration the CO-optimization immediately is released at
burner start
If the burner is shutt-off after POWER-ON and after curve set change for a longer time Group: 31
than adjusted in this parameter, optimisation will be released in all firing-rate seg- Min.: 0
ments immediatelly after acceptance of the CO controller.
Factory settings: 60 min. Max.: 65535
Editable even when burner is ON. Default: 60
Write: 4
Version: 3.0.0.0

2.8 CO Controller Monitoring

No. Device Description Attributes


0221 BT300 Min. monitoring time [minutes] of the dynamic supervision
Tolerance time for monitoring probe dynamic. Group: 32
After the end of the monitoring time the active part of the self-test starts. Min.: 0
0 = monitoring OFF
Max.: 60
Editable when burner is ON.
Default: 15
Write: 4
Version: 3.0.0.0

17
2 List of Parameters

No. Device Description Attributes


0223 BT300 Number of tolerable unsuccessful attempts of the CO probe dynamic test at maximum
correction value
Dinamic test at correction value max. Group: 32
0 = first ineffective dynamic test shuts OFF CO control Min.: 0
1 = maximum number of ineffective dynamic tests before CO control shuts OFF
Max.: 100
Editable even when burner is ON.
Default: 4
Write: 4
Version: 3.0.0.0
0222 BT300 Least value [mV] to accept the dynamic supervision / 0=OFF
minimum requested probe dynamic in mV. Group: 32
Minimum value of the probe’s voltage variations for acceptance of the probe dynamic. Min.: 0
0 = OFF
Max.: 999
Editable even when burner is ON.
Default: 10
Write: 4
Version: 3.0.0.0
0224 BT300 Min O2 value, below this value a fault shut-down occurs
An offset of 1000 avoids a fault shut-down while a fault occurs at LAMTEC SYSTEM Group: 32
BUS and switched off measurement at Lambda Transmitter (p.ex. MAINTENANCE). Min.: 0
Editable even when burner is ON. Max.: 1025
Default: 1000,4
Write: 2
Version: 3.0.0.0
0225 BT300 Monitoring time [s] untill disturbance shut off at Min-O2 value falls short of (P224)
Editable even when burner is ON. Group: 32
Min.: 0
Max.: 65535
Default: 30
Write: 4
Version: 3.0.0.0

2.9 CO controller UCOe monitoring

No. Device Description Attributes


0226 BT300 Monitoring window for effective CO-probe voltage UCOe [+-mV]
0 = monitoring OFF Group: 33
Editable even when burner is ON. Min.: 0
Max.: 500
Default: 100
Write: 4
Version: 3.0.0.0

18
2 List of Parameters

No. Device Description Attributes


0227 BT300 Monitoring time for effective CO-probe voltage UCOe [sec]
0 = monitoring OFF Group: 33
Editable even when burner is ON. Min.: 0
Max.: 30
Default: 20
Write: 4
Version: 3.0.0.0
0228 BT300 UCOe + Offset for Parameter 228 in oil operation [percent of the CO-probe voltage]
Activation of UCOe monitoring with O2 control. Group: 33
You can activate UCOe monitoring without CO control, too. Min.: 0
0 = monitoring OFF
Max.: 200
Editable even when burner is ON.
Default: 100
Write: 4
Version: 3.0.0.0

2.10 CO Controller CO Detection

No. Device Description Attributes


0232 BT300 CO edge: increasing air after change of firing-rate direction [digit]
Number of digit which change the actual correction signal in direction increasing air Group: 34
immediately after changing the firing-rate direction. Min.: 0
High byte: Increasing air when changing the firing-rate without change of the firing-rate
direction Max.: 65535
Low byte: Increasing air when changing the firing-rate with change of the firing-rate Default: 30
direction
Write: 2
LSB initial value while changing firing-rate direction applies with master-slave configu-
ration. Version: 3.0.0.0
Editable even when burner is ON.
0233 BT300 CO edge: increasing air after optimisation is completed [digit]
Increasing air between CO edge and calculated optimisation curve (in digit) Group: 34
After finishing optimisation the correction signal runs from the corresponding optimisa- Min.: 0
tion point in direction increasing air by the adjusted digit.
Range: 0 to 200 is equal to 0 to 200 digit Max.: 200
Editable even when burner is ON. Default: 20
Write: 2
Version: 3.0.0.0

19
2 List of Parameters

2.11 CO Control Edge Signal

No. Device Description Attributes


0234 BT300 CO recognition immediately after the ignition: 0=off, >0=Digits for maximum air rise
0 = OFF Group: 34
1...= Digits for maximum air rise Min.: 0
Editable even when burner is ON. Max.: 500
Default: 200
Write: 4
Version: 3.0.0.0
0235 BT300 Max. permissible effective CO probe voltage UCOe [mV] below the CO edge
Beside the binary edge signal the CO edge is recognised as overshot, if UCOe over- Group: 35
shoots the threshold-value in P 235. Min.: 0
Editable even when burner is ON. Max.: 500
Default: 200
Write: 4
Version: 3.0.0.0
0236 BT300 O2 value forces completition of optimisation (requirement: value > P 943)
When reaching O2 value in P 236 optimisation is completed by force if P 236 > P 204. Group: 35
During dynamic tests the value may be less! Min.: 0
Editable even when burner is ON. Max.: 10
Default: 0
Write: 2
Version: 3.0.0.0
0237 BT300 Maximum O2 value to accept optimisation
Optimisation is completed and the new value is added to the CO optimisation curve Group: 35
only, if the actual O2 value is less than the threshold value in P 237. O2 values higher Min.: 0
than this threshold value will not be added to the visualisation curve.
Max.: 21
Editable even when burner is ON.
Default: 5
Write: 2
Version: 3.0.0.0
0238 BT300 CO threshold signal maximum time [sec] untill CO controller shuts off temporarily
Monitoring of the duration of an active CO edge signal. Group: 35
0 = the active edge signal does not switch OFF the CO controller temporarily or per- Min.: 0
manently
1 ... = Maximum duration [s] of the CO edge signal until the temporary shut OFF of CO Max.: 300
controller Default: 60
Editable even when buner is ON. Write: 4
Version: 3.0.0.0

20
2 List of Parameters

No. Device Description Attributes


0239 BT300 CO threshold signal maximum time [sec] untill CO Controller shuts off permanently
Duration of the monitoring of an active CO edge signal. Group: 35
1 ... = Maximum duration of the CO edge signal until CO controller shuts OFF perma- Min.: 0
nently . P 239 must be higher or equal than P 238 for a permanent shut OFF. You can
reset the permanent shut OFF with confirming manually or with restarting the burner. Max.: 300
Editable even when burner is ON. Default: 300
Write: 4
Version:
0240 BT300 Switch OFF of the CO controller
1 = shut OFF. Group: 35
Editable even when burner is ON. Min.: 0
Max.: 1
Default: 1
Write: 0
Version: 3.1.0.0

2.12 FAT (Burner Sequencer)

No. Device Description Attributes


0300 BT300 Time for forced intermittent operation in minutes (0=endless)
Time for forced intermittent operation in minutes Gruppe: 40
0 = the burner can operate infinitely without interruption Min.: 0
(available only with BT33x and BT34x) Max.: 1440
>0 = after this period the burner gets a forced interruption Default: 1430
Schreiben: 2
Version: 1.0.0.0
0301 BT300 Automatic restart (0=TRD, 1=OFF, 2=EN676)
Configuration of the automatic restart Group: 40
0 = TRD Min.: 0
1 = without automatic restart Max.: 10
2 = automatic restart accoeding to
Default: 1
Changing the parameter will lead to a restart if P 301  1 and P 328 > 0 and BT300 is
in fault condition. Write: 2
Version: 1.0.0.0
0302 BT300 Start with (1) or without (0) pilot burner for oil, (2)=oil with continuous pilot flame
0 = without pilot burner Group: 40
1 = with pilot burner Min.: 0
2 = continuous pilot flame
3 = with pilot burner - main flame scanner doesn’t detect the pilot flame during ignition Max.: 4
(operation like 1) Default: 0
4 = with continuous pilot burner - main flame scanner doesn’t detect the pilot flame
Write: 2
during ignition (operation like 2)
Version: 1.0.0.0

21
2 List of Parameters

No. Device Description Attributes


0303 BT300 Start with (1) or without (0) pilot burner for gas, (2)=gas with continuous ignition flame
Configuration oft the pilot buner for gas operation Group: 40
refer to the values in P 302 Min.: 0
Max.: 4
Default: 0
Write: 2
Version: 1.0.0.0
0304 BT300 Program check time [sec]
Set the program check time for the integral controller. If this time has elapsed after Group: 40
"Burner ON" and no ignition occured, a fault message will be indicated. If the parame- Min.: 0
ter is set to 0, no fault message will be indicated.
Max.: 9999
Default: 600
Write: 2
Version: 1.0.0.0
0305 BT300 1st safety period for oil [s]
1st safety period for oil in seconds Group: 40
Enter the first safety period for oil. Respect the actual valid standards. while setting the Min.: 1
time.Also respect theflame sensor’s time for reaction = 1s. You must deduct this time Max.: 30
from the specifications in the standards.
Default: 5
Write: 4
Version: 1.0.0.0
0306 BT300 2nd safety period for oil [s]
2nd safety period for oil in seconds or safety period with start without pilot burner Group: 40
Set the second safety period for oil in this parameter. Respect the actual, valid stand- Min.: 1
ards while setting the time. If you don’t use a pilot burner this parameter contains the
safety period. Max.: 30
Default: 5
Write: 4
Version: 1.0.0.0
0307 BT300 1st safety period for gas [s]
1st safety period for gas in seconds (ignition safety time). Group: 40
Respect the actual valid standards. while setting the time.Also respect theflame sen- Min.: 1
sor’s time for reaction = 1s. You must deduct this time from the specifications in the Max.: 30
standards.
Default: 3
Write: 4
Version: 1.0.0.0
0308 BT300 2nd safety time for gas
2nd safety period for oil in seconds or safety period with start without pilot burner. . Group: 40
Respect the actual valid standards. while setting the time.Also respect theflame sen- Min.: 1
sor’s time for reaction = 1s. You must deduct this time from the specifications in the Max.: 30
standards.
Default: 3
Write: 4
Version: 1.0.0.0

22
2 List of Parameters

No. Device Description Attributes


0309 BT300 Pre-ignition time [sec]
Transformertime in seconds Group: 40
This parameter defines how long the ignition transformer is activated befor the sole- Min.: 2
noid valve of the pilot gas or the maingas is opened (transformer’s pre-activation time). Max.: 40
The oilpump is started simultaneously. If the period is to short to build up the oilpres- Default: 3
sure in the system, you should extend this period.
Write: 1
Version: 1.0.0.0
0310 BT300 Stabilising time [sec]
Stabilasing time in seconds Group: 40
Set the stabilasing period in this parameter. This parameter defines how long the pilot Min.: 3
burner burns solely between first and second safety period (without activating the igni- Max.: 30
tion transformer and with closed maingas valves)
Default: 3
– ignition
Write: 1
– fuel change via pilot burner
Version: 1.0.0.0
0311 BT300 Leakage check time [sec]
Set the duration of thelLeakage test in this parameter. Standard vale is 20 seconds. Group: 40
You should change this parameter only if the volume of the leakage test line and the Min.: 5
switching hyteresis of the gas-pressure monitor (minimum) do not recognise the mini-
mum leakage volume that is defined in the standars (refer to the calculation example Max.: 999
in the manual). Default: 20
If the minimum leakage volume is not detected in even a shorter period than 30 sec-
Write: 2
onds, you can decrease the parameter value to safe time.
Version: 1.0.0.0
0312 BT300 Leak test before ignition (0-OFF / 1-ON)
Leak test before ignition Group: 40
0 = not necessary Min.: 0
1 = necessary
Max.: 1
Default: 1
If P312 > 0 than P 802 should be > 0.
Write: 1
Version: 1.0.0.0
0313 BT300 Leakage test, fill-intime extension [sec] main gas 1
Period for filling the leakage test line in seconds. Group: 40
You can increase the opening time for main gas 1 (2.4s) to fill-in the leakage test line Min.: 0
0 = opening time of main gas 1
1 = 2.4 s Max.: 3
1.... = increasing time for opening main gas 1 [s] (total = value P313 + 2.4s) Default: 0
Example: Write: 4
value P313 = 1 >> total = 3.4s
Version: 1.0.0.0
0315 BT300 Leakage test after switching off (0-OFF / 1-ON)
Leakage test time after operation Group: 40
0 = not necessary Min.: 0
1 = necessary
Max.: 1
If P 312 > 0 then P 802 has to be > 0.
Default: 0
Write: 1
Version: 1.0.0.0

23
2 List of Parameters

No. Device Description Attributes


0316 BT300 Pre-ventilating suppression (0-OFF / 1-active / 2-automatic / 3-automatic short)
Pre-ventilating suppression Group: 40
0 = pre-ventilating suppression is not permitted Min.: 0
1 = reserved (error 107)
2 = automatic pre-ventilation suppression permitted for all fuels when burner is inac- Max.: 5
tive for less than 24h Default: 0
3 = automatic pre-ventilation suppression permitted for all fuels when burner is inac-
Write: 1
tive for less than 24h, but all flaps are opened and closed.
4 = automatic pre-ventilation suppression permitted for gas only when burner is inac- Version: 1.0.0.0
tive for less than 24h.
5 = automatic pre-ventilation suppression permitted for oil only when burner is inactive
for less than 24h.
0318 BT300 Pre-ventilating time [sec]
Set the pre-ventilating period in this parameter during commissioning. Group: 40
P 317 defines the lower limit. Min.: 0
Max.: 999
Default: 30
Write: 1
Version: 1.0.0.0
0319 BT300 Post-ventilating time [sec]
Set the pPost-ventilating period in seconds Group: 40
A value of 1000 means an unlimited post-ventilating time. Min.: 0
Set in this parameter how long BT300 post-ventilates after switch-off. Therefore all air
flaps have to run open. Max.: 999
With a value of 0 and with fault shut-down there is nor post-ventilation. Default: 0
In post-ventilation mode the actuators are not monitored. The actuators run open not
Write: 1
till the flame has distinguished. But the time starts running as soon as the solenoid
valves are closed. Perhaps you must add the after-burnung time to the desiredpost- Version: 1.0.0.0
ventilating time.
0320 BT300 oil pumpe ON, 0=standard, 1=together with the fan
This parameter defines the moment when the oilpump is switched on. Group: 40
0 = normally at ignition Min.: 0
1 = yet when it reaches "Stand-by"
Max.: 1
Default: 0
Write: 2
Version: 1.0.0.0
0323 BT300 Irrelevance time of oil safety chain when igniting on oil [sec]
Tolerance time / irrelevance time of the safety interlock chain oil when igniting oil in Group: 40
0...10 seconds Min.: 0
Irrelevance time after ignition (extended tolerance) for the safety interlock chain oil Max.: 10
You can extend the tolerance time of the safety interlock chain during ignition to avoid Default: 1
faultshut-downs which are caused by line shocks while opening the main valves.
Input in seconds Write: 4
The time starts running when the main valves open. Version: 1.0.0.0
After ignition is completed this parameter has no effects to the system.

24
2 List of Parameters

No. Device Description Attributes


0324 BT300 Irrelevance time of gas safety chain when igniting on gas in seconds.
Tolerance time / irrelevance time of the safety interlock chain gas when igniting gas in Group: 40
0...10 seconds Min.: 0
Irrelevance time after ignition (extended tolerance) for the safety interlock chain gas Max.: 10
You can extend the tolerance time of the safety interlock chain during ignition to avoid Default: 1
faultshut-downs which are caused by line shocks while opening the main valves.
Input in seconds Write: 4
The time starts running when the main valves open. Version: 1.0.0.0
After ignition is completed this parameter has no effects to the system.
Irrelevance time starts running after opening gas valve 2 (second safety period) and
ends after the time you have set in this parameter has elapsed.
0325 BT300 Maintenance mode (control unit up to the stabilisation time only)
0 = maintenance mode OFF Group: 40
1 = maintenance mode ON Min.: 0
Set the maintenance mode in this parameter. Use the maintenance mode to adjust the Max.: 1
pilot burner or the pilot flame monitor. It enables up to 5 ignition attempts in series with-
out preventilation and leakage test. The controler runs to stabilisation time only. The Default: 0
main valves don’t run open before you haven’t reset this parameter. Write: 1
After the 5th ignition attempt the system runs pre-ventilation and leakage test automat-
Version: 1.0.0.0
ically.
But:
A total reset resets the counterfor maintenance mode automatically. That means, that
the following start is seen as the first start and pre-ventilation and leakage test is run
automatically.
Thus:
Reset faults with a common reset if possible.
0326 BT300 After-burning time (flame signal irrelevant) [sec]
The after-burning time controls how long the system waits after switching-off until the Group: 40
"Flame OFF" check starts.If you have set this time to 0 there isn’t an after-burning time Min.: 0
is configured and the "Flame OFF" check doesn’t run.
Max.: 180
Default: 10
Write: 1
Version: 1.0.0.0
0327 BT300 Behaviour of the ignition transformer during the switch-on sequence with oil
0 = normal behaviour: switching on the oil pump activates the ignition transformer Group: 40
1 = switching on the fan activates the ignition transformer and after switching off the Min.: 0
flame (post-ventilating time) the ignition transformer is switched on once more.
Max.: 1
Default: 0
Write: 2
Version:
1.0.0.0
0328 BT300 Automatic restart after fault
Delay period until the burner starts automatically. Group: 40
0 = no automatic restart Min.: 0
>0 = delay period until the burner starts automatically in seconds
Max.: 30

If P 301  1 and P328 > 0 and BT300 in fault condition, changing the parameter leads Default: 5
to an immediate restart Write: 2
Version: 1.0.0.0

25
2 List of Parameters

No. Device Description Attributes


0330 BT300 Permanent ventilation (0-OFF / 1-active)
0 = OFF Groupe: 40
1 = active Min.: 0
Keep in mind, that activation of permanent ventilation switches the fan off in case of Max.: 1
failor.
Default: 0
Write: 2
Version: 2.0.0.0

2.13 Sequencer

No. Device Description Attributes


0365 BT300 Limit by which pre-ventilation can be completed channel 1 [digit]
Pre-ventilation limit (also post-ventilation) channel 1 Group: 45
Enter the upper limit to which the channel runs open during pre-ventilation. If you enter Min.: 0
999 (default value) the channel runs to it’s upper stop. Set the pre-ventilation limit for Max.: 999
example with air dampers to shorten the pre-ventilation period (but you must assure
the exchange of air). Default: 999
Write: 1
Version: 1.0.0.0
0366 BT300 Limit by which pre-ventilation can be completed channel 2 [digit]
Pre-ventilation limit (also post-ventilation) channel 2 Group: 45
see P 365 Min.: 0
Max.: 999
Default: 999
Write: 1
Version: 1.0.0.0
0367 BT300 Limit by which pre-ventilation can be completed channel 3 [digit]
Pre-ventilation limit (also post-ventilation) channel 3 Group: 45
see P 365 Min.: 0
Max.: 999
Default: 999
Write: 1
Version: 1.0.0.0
0368 BT300 Limit by which pre-ventilation can be completed channel 4 [digit]
Pre-ventilation limit (also post-ventilation) channel 4 Group: 45
see P365 Min.: 0
Specialities channel 4 Max.: 999
Warning: Default: 999
A continuous output limits the setpoint.
Please note that you have to enter the range limits of the feedback manually. Write: 1
With continuous outputs the feedback value for the limitation is calculated and saved Version: 1.0.0.0
in the device during the automatic range-limit calculation.
At this juncture you have to keep in mind that the feedback raches the value of the lim-
itation during the automatic calculation of the range limits.
The feedback is used for the monitoring of the channel’s pre-ventilation position.
After the activation or changing of the pre-ventilation limit of a continuous channel you
have to run an automatic calculation of the range limits (refer to the device’s manual)

26
2 List of Parameters

No. Device Description Attributes


0373 BT300 Delay in ignition in seconds after recognition of ignition position
Enter how many seconds pass after the compound detects the ignition position until Group: 45
ignition is released. Min.: 0
Max.: 999
Default: 0
Write: 2
Version: 1.0.0.0
0374 BT300 Delay for base load with sep. ignition position [sec]
Enter the delay in seconds which the compound waits after ignition until he leaves igni- Group: 45
tion position to run to base load. This parameter effects only if you have programmed a Min.: 0
separate ignition position (P 803).
Max.: 999
Default: 0
Write: 2
Version: 1.0.0.0
0375 BT300 Delay time for control release [sec]
Delay for control release in seconds. Group: 45
The burner remains in base load during this delay. Min.: 0
Max.: 999
Default: 0
Write: 2
Version: 1.0.0.0
0376 BT300 Damper delay after fan ON [sec]
Delay for dampers after fan ON in seconds (only with burner sequencer) Group: 45
Enter the delay in seconds which defers the damer’s running open compared with the Min.: 0
fan release. This helps to prevent the fan motor of an increasing current consumption Max.: 15
during the star delta starting.
Default: 5
This parameter effects with permanent ventilation too.
Write: 2
Version: 1.0.0.0
0377 BT300 Firing-rate position during switching OFF (0=actual position / 1=base load before
switching OFF)
0 = switching OFF at actual firing-rate position Group: 45
1 = running to base load bevore starting the switching OFF sequence Min.: 0
Max.: 1
Default: 0
Write: 2
Version: 1.0.0.0

27
2 List of Parameters

2.14 Configuring channels

No. Device Description Attributes


0400 BT300 Function definition channel 1
Define in this parameter which type of actuator an output channel drives. Thus you Group: 50
define indirectly it’s behaviour at bandshift, at performance change and at drift com- Min.: 0
pensation. Potentially these defines special functions e.g. if a channel is configured to
recirculation or flue gas. Max.: 6

Channel functions: Default: 3


0 = OFF Write: 2
1 = reserved (error 107)
Version: 1.0.0.0
2 = fuel
3 = air damper
4 = reserved (error 107)
5 = reserved (error 107)
6 = reserved (error 107)
0401 BT300 Function definition channel 2
see P 400 Group: 50
Min.: 0
Max.: 6
Default: 2
Write: 2
Version: 1.0.0.0
0402 BT300 Function definition channel 3
see P 400 (BT320) Group: 50
* Min.: 0
Default: 0 (BT320) Max.: 6
Default: 3 (BT33x and BT34x)
Default: *
Write: 2
Version: 1.0.0.0
0403 BT300 Specification of channel 4 functions
see P 400 Group: 50
Min.: 0
Max.: 6
Default: 0
Write: 2
Version: 1.0.0.0

28
2 List of Parameters

No. Device Description Attributes


0405 BT300 Channel release for curve set 1
Switch-off bit for each curve set. If bit "x" is set, channel in curve set "x" is in use. Group: 50
Define with this parameter active channel in a curve set. All channels are activated by Min.: 0
default. With this function you can change e.g. channel activities at oil/gas operation Max.: 15
(BT34x).
Selection via bit pattern. Default: 15
Write: 2
Version: 1.0.0.0

1 = active
0 = inactive
0406 BT300 Channel release for curve set 2
with bit pattern see P 405 Group: 50
Min.: 0
Max.: 15
Default: 15
Write: 2
Version: 1.0.0.0
0415 BT300 Fuel remains CLOSED during pre-ventilation
Behaviour of the fuel channels at pre-ventilation in operation with LGN (liquified natu- Group: 50
ral gas) Min.: 0
0 = normal operation Max.: 1
1 = fuel allocated actuators remain closed at pre-ventilation
Default: 0
Fuel remains closed at pre-ventilation
Switch (ON/OFF) Write: 2
If you have set this parameter to 1 fuel allocated actuators remain clost at pre-ventila- Version: 1.0.0.0
tion. If you use BT300 in a LGN plant the fuel actuator may not run open during pre-
ventilation. In this case you must set this parameter to "ON". You must enter the range
limits manually or you must deactivate the determination of range limits.
(see P 650 seqq.)

29
2 List of Parameters

2.15 Acutators

No. Device Description Attributes


0453 BT300 Running time for continuous output channel 4 [digit/min.]
If the channel is configured as continuous, you can set in this parameter how fast this Group: 55
output may change (maximum) Min.: 0
The time you set in this parameter is just the minimum running time. Because of the
compound routine it may happen that this time my be exceeded (e.g. if you use slower Max.: 65535
flap drives in another channel). Default: 1500
Primarily this parameter is used to get some adaption while actuating frequency con-
Write: 2
verters.
The value in this parameter should match the acceleration time programmed to the Version: 1.0.0.0
frequency converter.
0455 BT300 Configuration of the actuator type channel 1
Configuration of the actuator type for every channel Group: 55
1 = actuators 0,8 Nm (665R5500...); 1,2 Nm (662R5001...) and 3 Nm (662R5003...) Min.: 1
2 = actuators 9 Nm (662R5009...)
Max.: 2
Default: 1
Write: 2
Version: 1.0.0.0
0456 BT300 Configuration of the actuator type channel 2
see P 455 Group: 55
Min.: 1
Max.: 2
Default: 1
Write: 2
Version: 1.0.0.0
0457 BT300 Configuration of the actuator type channel 3
see P 455 Group: 55
Min.: 1
Max.: 2
Default: 1
Write: 2
Version: 1.0.0.0
0458 BT300 CLOSE position of the connected damper channel 1
Position for each channel in which the connected damper is in CLOSE position. Group: 55
0 = CLOSE position on 12 o’clock Min.: 0
1 = CLOSE position on 9 o’clock for actators 1.2 Nm (662R5001...); 3 Nm
(662R5003...); 9 Nm (662R05009...) or position on 3 o’clock for actators 0.8 Nm Max.: 1
(663R550...) Default: 0
Write: 2
Version: 1.0.0.0

30
2 List of Parameters

No. Device Description Attributes


0459 BT300 CLOSE position of the connected flap of channel 2
see P 458 Group: 55
Min.: 0
Max.: 1
Default: 0
Write: 2
Version: 1.0.0.0
0460 BT300 CLOSE position of the connected flap of channel 3
see P 458 Group: 55
Min.: 0
Max.: 1
Default: 0
Write: 2
Version: 1.0.0.0
0461 BT300 Behaviour of the acuator’s protection against the permutation at power on
2 = permutation activated, execution after connecting the power supply and after every Group: 55
cold start. Min.: 0
0 = inactive
Max.: 1
Default: 0
Write: 2
Version: 1.0.0.0

2.16 Compound

No. Device Description Attributes


0508 BT300 Band shift channel 1 [digit]
Band shift at change of the firing-rate Group: 60
Enter the channel’s band shift at change of the firing-rate in digit. The electronic fuel/ Min.: 0
air ratio control evaluates the direction automatically where the band shift shall effect Max.: 50
by the configuration of the respective actuator (air upwards, fuel downwards).
The band shift effecs only if the firing-rate changes in the direction which is the leading Default: 4
air procedure (at reduction of the firing-rate fuel leads, at increasing firing-rate air Write: 2
leads).
Version: 1.0.0.0
It depends on the actuator’s effect on the Lambda which values you must enter.
0509 BT300 Band shift channel 2 [digit]
see P 508 Group: 60
Min.: 0
Max.: 50
Default: 4
Write: 2
Version: 1.0.0.0

31
2 List of Parameters

No. Device Description Attributes


0510 BT300 Band shift channel 3 [digit]
see P 508 Group: 60
Min.: 0
Max.: 50
Default: 4
Write: 2
Version: 1.0.0.0
0511 BT300 Band shift channel 4 [digit]
see P 508 Group: 60
Min.: 0
Max.: 50
Default: 4
Write: 2
Version: 1.0.0.0
0513 BT300 Running time for TPS load input [digit/min]
Running time term for TPS (three-point-step) firing-rate input Group: 60
Set in this parameter how fast the external firing-rate’s signalchanges if the firing-rate’s Min.: 0
presetting is set by TPS signal. With TPS-signal a counter creates the external firing- Max.: 65535
rate. Depending on the contact the counter counts up or down.
This parameter defines the counter’s speed. The parameter sets the counter in digits Default: 1000
per minute. If the firing-rate input is not a TPS input you must set this parameter to 0. Write: 1
Version: 1.0.0.0
0514 BT300 Minimum running time of compound
Limitation of the adjustment speed of the internal firing-rate related to the given firing- Group: 60
rate. Min.: 10
Minimum running time of the firing-rate in seconds from the ignition poit on to the
curve’s maximum firing-rate Max.: 999
Mmimimum runningtime of the compound in seconds Default: 10
Use this parameter to slow down the burner’s acceleration time or deceleration time Write: 2
between low firing-rate and full firing-rate.
Version: 1.0.0.0
0515 BT300 Channels used in overshoot
Define in this parameter which channels are used to calculate the overshoot. Because Group: 60
overshoot is generally used with TPS outputs but is never used with continuous out- Min.: 0
puts you may never chose continuous outputs. Even you should exclude actuators
with curves that are running horizontally for long periods. Max.: 15
Default: 0
Write: 2
Version: 1.0.0.0
0516 BT300 Overshoot min. value
Define the minimum value to run the actuator in a higher position than during over- Group: 60
shoot. Every channel must run this minimum distance to end the overshoot. Overshoot Min.: 0
will end as soon as every overshoot-channel meets the conditions to terminate over-
shoot Max.: 999
Default: 0
Write: 2
Version: 1.0.0.0

32
2 List of Parameters

No. Device Description Attributes


0517 BT300 Overshoot max. value [digit]
Maximum overshoot value in digit related to the internal firing-rate. Group: 60
Define the maximum value which the internal firing-rate is allowed to run higher than Min.: 5
it’s regular value. As soon as this value is reached, the overshoot is terminated. Max.: 250
Default: 5
Write: 2
Version: 1.0.0.0
0518 BT300 Value of internal firing-rate in OFF mode
Given firing-rate in operating mode OFF and operating mode FAULT Group: 60
0 = Firing-rate follows the external given value. Min.: 0
Define in this parameter which value the output "internal firing-rate" outputs in BT300
is in mode OFF. Max.: 999
Default = 200 = 4mA Default: 0
Write: 2
Version: 1.0.0.0
0519 BT300 Dead band definition +/- this value no load change effective
Dead band of the firing-rate Group: 60
Low byte = dead band of the firing-rate, if no change in direction of the firing-rate Min.: 0
High byte = dead band of the firing-rate after changing the direction of the firing-rate
Max.: 65535
Dead band of the firing-rate without changing the direction of the firing-rate = 5 digit
Dead band of the firing-rate with changing the direction of the firing-rate = 10 digit Default: 2565

Define the dead band of the firing-rate input in this Parameter. Changes of the firing- Write: 1
rate, which are in this defined range are ignored and don’t lead to a regulation of the Version: 1.0.0.0
compound. If you define the dead band of the firing-rate too small, the compound runs
irregularly becaus even for smalles changes of the firing rate the compount corrects.
With additional routines like leading air procedure at changes in the firing-rate and
overshoot (approaching of the actuators from one side) this leads to needless irregular
running. At slightly oscillating operation or disturbed firing-rate signal the actuators are
in permanent movement. If you chose a to big dead band of the firing-rate leads to an
incomplete extension of the firing-rate request or the firing-rate is not extended before
the deviation of setpoint/actual value gets higher. Then it changes in one step. This
may cause a huge oscillation of the actual value of the control path (steam pressure or
flow temperature).
You must determine the optimal value of this parameter on the plant. You should set
the parameter content lowe tha 3 digit only in exceptional cases, because this can lead
to fluctuations of the signals at the firing-rate input and thus the displacements of the
compound.
0525 BT300 Setting of number of stages for staged operation in oil mode (0 = modulated operation/
1 = 2 stages/2 = 3 stages)
0 = 1 stage = modulated operation Group: 60
1 = 2 stages Min.: 0
2 = 3 stages
Max.: 2
Default: 0
Write: 2
Version: 1.0.0.0

33
2 List of Parameters

No. Device Description Attributes


0526 BT300 Minimum time, which the fuel/air ratio control system needs to change from one stage
to another [s]
Group: 60
Min.: 0
Max.: 999
Default: 10
Write: 2
Version: 1.0.0.0
0527 BT300 Position of the air damper, at which the valve is opened for the second stage
This value affects the position of the air damper at which the second oil valve is Group: 60
opened, i.e. when switched from stage 1 to stage 2 Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0528 BT300 Position of the air damper at which the valve for the second stage is switched off
This value affects the position of the air damper at which the second oil valve is Group: 60
closed, i.e. when switched from stage 2 to stage 1 Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0529 BT300 Position of the air damper, at which the valve for the third stage is opened
This value affects the position of the air damper at which the third oil valve is opened, Group: 60
i.e. when switched from stage 2 to stage 3 Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0530 BT300 Position of the air damper at which the valve for the third stage is switched off
This value affects the position of the air damper at which the third oil valve is closed, Group: 60
i.e. when switched from stage 3 to stage 2 Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0531 BT300 Firing-rate threshold at which the valve for the second stage is switched off
Threshold for staged load operation. Group: 60
The threshold defines at which firing-rate switches to the next stage. Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0

34
2 List of Parameters

No. Device Description Attributes


0532 BT300 Firing-rate threshold at which the valve for the second stage is switched on
see P 531 Group: 60
Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0533 BT300 Firing-rate threshold at which the third stage’s valve is switched off
see P 531 Group: 60
Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0534 BT300 Firing-rate threshold at which the valve for the third stage is switched on
see P 531 Group: 60
Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0537 BT300 Minimum firing-rate during controle
The parameter is active only if it’s value is higher than 0. If the parameter’s value is Groupe: 60
equal to 0, the corresponding limit vaue is inactive. A default value of 0 effects an Min.: 0
unlimited firing-rate.
Max.: 999
Default: 0
Write: 4
Version: 1.1.0.0
0538 BT300 Maximum firing-rate during controle
The parameter is active only if it’s value is higher than 0. If the parameter’s value is Groupe: 60
equal to 0, the corresponding limit vaue is inactive. A default value of 0 effects an Min.: 0
unlimited firing-rate.
Max.: 999
Default: 999
Write:
Version: 1.1.0.0

35
2 List of Parameters

2.17 Monitoring Bands

No. Device Description Attributes


0600 BT300 Without function
Group: 65
Min.: 0
Max.: 999
Default: 20
Write: 2
Version: 1.0.0.0
0601 BT300 Switch-off time for 1st monitoring band channel 1
Monitoring band-1 tolerance time Group: 65
There you set the time for the monitoring band. It should be shorter than the monitor- Min.: 0
ing time of the dead band, to allow a differential shot down between monitoring band
and dead band. As a result for plant with TRD-regulations - 28 sec. It’s possible that Max.: 99
this time is responsible for fault at not safety-related actuators or special plant and u.U. Default: 27
get bigger.
Write: 4
Version: 3.1.0.0
0602 BT300 Switch-off time for 1st monitoring band channel 2
see P 601 Group: 65
Min.: 0
Max.: 99
Default: 27
Write: 4
Version: 3.1.0.0
0603 BT300 Switch-off time for 1st monitoring band channel 3
see P 601 Group: 65
Min.: 0
Max.: 99
Default: 27
Write: 4
Version: 3.1.0.0
0604 BT300 Switch-off time for 1st monitoring band channel 4
Tolerance time Group: 65
Set the time for the first minitoring band in this Parameter. This time has to be a bit Min.: 0
smaller than the monitoring time of the dead band to enable a differentiated shut-off
between monitoring band dead band. This would be 28 sec. for plants according to Max.: 99
TRD standards. Default: 27
This time can be possibly exceeded for non-safety-related actuators and for special
Write: 4
plants
Version: 1.0.0.0

36
2 List of Parameters

No. Device Description Attributes


0606 BT300 1st monitoring band negative, channel 1 in digit
Monitoring band-1 negative direction Group: 65
1st monitoring band negative, channel 1 in digit Min.: 0
Max.: 100
Default: 15
Write: 4
Version: 3.1.0.0
0607 BT300 1st monitoring band negative, channel 2
see P 606 Group: 65
Min.: 0
Max.: 100
Default: 15
Write: 4
Version: 3.1.0.0
0608 BT300 1st monitoring band negative, channel 3
see P 606 Group: 65
Min.: 0
Max.: 100
Default: 15
Write: 4
Version: 3.1.0.0
0609 BT300 1st monitoring band negative, channel 4 [digit]
First monitoring band in negative direction Group: 65
Monitoring band in negative direction for each channel. As larger the monitoring band Min.: 0
as larger thescope for adjustment of the compound. As smaller the monitoring band as Max.: 100
more often the compound is stopped during adjustment. Outside the monitoring band
the actuator is run by permanent signal. Inside the monitoring band it is clocked in Default: 30
dead band direction. Continuous channels don’t have a dead band. Thus the first mon- Write: 2
itoring band marks the shut-down threshold. At TPS (three-point step) dead band is
Version: 1.0.0.0
ruling the shut-down threshold..
0610 BT300 1st monitoring band negative, channel 5
Group: 65
Min.: 0
Max.: 100
Default: 15
Write: 4
Version:
0611 BT300 1st monitoring band positive, channel 1
Monitoring band 1 positive direction Group: 65
As larger the monitoring band is as larger the scope for adjustment is. As smaller the Min.: 0
monitoring band is as more often the sequencer is stopped during adjustment. Outside Max.: 100
of the monitoring band the actuator is triggered by a permanent signal. Inside the mon-
itoring band it is triggered at regular intervals in direction dead band. Because the con- Default: 15
tinuous channels don’t have a dead band, the 1st monitoring band is their only shut-off Write: 4
limit. At TPS dead band is relevant.
Version: 3.1.0.0

37
2 List of Parameters

No. Device Description Attributes


0612 BT300 1st monitoring band positive, channel 2
see P 611 Group: 65
Min.: 0
Max.: 100
Default: 15
Write: 4
Version: 3.1.0.0
0613 BT300 1st monitoring band positive, channel 3
see P 611 Group: 65
Min.: 0
Max.: 100
Default: 15
Write: 4
Version: 3.1.0.0
0614 BT300 1st monitoring band positive, channel 4
Group: 65
Min.: 0
Max.: 100
Default: 30
Write: 2
Version: 1.0.0.0
0615 BT300 1st monitoring band positive, channel 5
Group: 65
Min.: 0
Max.: 100
Default: 40
Write: 4
Version:
0616 BT300 Switch-off time for 2nd monitoring band in secs.
Group: 65
Min.: 0
Max.: 10
Default: 2
Write: 4
Version: 3.1.0.0
0617 BT300 2nd monitoring band negative, channel 1
Group: 65
Min.: 0
Max.: 100
Default: 40
Write: 4
Version: 3.1.0.0

38
2 List of Parameters

No. Device Description Attributes


0618 BT300 2nd monitoring band negative, channel 2
see P 617 Group: 65
Min.: 0
Max.: 100
Default: 40
Write: 4
Version: 3.1.0.0
0619 BT300 2nd monitoring band negative, channel 3
see P 617 Group: 65
Min.: 0
Max.: 100
Default: 40
Write: 4
Version: 3.1.0.0
0620 BT300 2nd monitoring band negative, channel 4
Second monitoring band in negative direction Group: 65
This monitoring band is used for emergency shut-down at starker deviation from Min.: 0
standard. You should accordingly define this monitoring band broad. The parameter
value will be added to the first monitoring band. Max.: 100
Default: 40
Write: 2
Version: 1.0.0.0
0622 BT300 2nd monitoring band positive, channel 1
Monitoring band 2 positive direction Group: 65
nd
2 monitoring band in positive direction. This monitoring band is used for emergency Min.: 0
shut-down for extreme control variations. You should adjust it accordingly spacious. Max.: 100
The parameter set value is added to the 1st monitoring band.
Default: 40
Write: 4
Version: 3.1.0.0
0623 BT300 2nd monitoring band positive, channel 2
see P 622 Group: 65
Min.: 0
Max.: 100
Default: 40
Write: 4
Version: 3.1.0.0
0624 BT300 2nd monitoring band positive, channel 3
see P 622 Group: 65
Min.: 0
Max.: 100
Default: 40
Write: 4
Version: 3.1.0.0

39
2 List of Parameters

No. Device Description Attributes


0625 BT300 2nd monitoring band positive, channel 4
Second monitoring band in positive direction Group: 65
This monitoring band is used for emergency shut-down at starker deviation from Min.: 0
standard. You should accordingly define this monitoring band broad. The parameter
value will be added to the first monitoring band. Max.: 100
Mind that at "flying curve set" the actuator cna reach the second monitoring band Default: 40
within 30 seconds. Otherwise you must increase the monitoring band.
Write: 2
Version: 3.1.0.0

2.18 Correction

No. Device Description Attributes


0700 BT300 Correction mask
Coose the fuel/air ratio channels on which the correction affects. Each bit represents a Group: 75
channel. Min.: 0
Max.: 999
Default: 0
Write:2
Version: 3.0.0.0

1 = active
0 = inactive
0701 BT300 Spread factor
The spread factor defines, how much the correction effects at maximum firing-rate. Gruppe: 75
The spread factor is set in 0.1 digit, i.e. a spread factor of 10 does not effect the cor- Min.: 0
rection rang.
Max.: 50
Minimum firing-rate = exactly the correction range.
Maximum firing-rate = the correction range modificated with the spread factor. Default: 10
Schreiben:2
Version: 3.0.0.0
0702 BT300 Correction range O2-controller
Correction range with active O2-controller. It is identical for all fuel/air ratio control Gruppe: 75
channels. Min.: 0
* adjustable in BURNER OPERATION Max.: 400
Default: 0
Schreiben: 1*
Version: 3.0.0.0

40
2 List of Parameters

No. Device Description Attributes


0703 BT300 Correction range CO-controller
Correction range with active CO-controller. It is identical for each fuel/air-ratio control. Group: 75
adjustable in BURNER OPERATION Min.: 0
Max.: 400
Default: 0
Write: 1*
Version: 3.0.0.0

2.19 LSB / Fieldbus

No. Device Description Attributes


0750 BT300 LSB family (LAMTEC SYSTEM BUS)
You can use this family in the LSB system range. Group: 80
0 = family 1 Min.: 0
1 = family 1 Max.: 4
2 = family 2
3 = family 3 Default: 1
4 = family 4 Write: 2
Version: 1.0.0.0
NOTE:
You must reset the device before changes in this parasmeter effect the system.

0751 BT300 LSB configuration (LAMTEC SYSTEM BUS)


not yet in use Group: 80
Min.: 0
Max.: 65535
Default: 0
Write: 2
Version: 1.0.0.0
0752 BT300 LSB device no. (LAMTEC SYSTEM BUS)
LAMTEC SYSTEM BUS group Group: 80
Min.: 0
Max.: 65535
Default: 1
Write: 2
Version: 1.0.0.0
0753 BT300 Configurate LSB analogue module
Configuration of LSB analogue modules Group: 80
Min.: 0
Max.: 65535
Default: 255
Write: 2
Version: 1.0.0.0

41
2 List of Parameters

No. Device Description Attributes


0754 BT300 LSB digital moduls (load thresholds)
not in use Group: 80
Min.: 0
Max.: 65535
Default: 255
Write: 2
Version: 1.0.0.0
0755 BT300 Bus card parameter no. 1
Parameter of the BUS cards, only available for external connected devices. Group: 80
The values are only forwarded to these external devices. they don’t effect the Burner- Min.: 0
Tronic. Refer to the description of bussystems (default values of PROFIBUS)
Parameter of the bus-card (functionality depends on the configuration of the bus-card - Max.: 999
refer to the documentation of the bus-card). Default: 0
Write: 1
Version: 1.0.0.0
0756 BT300 Bus card parameter no. 2
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 4
Write: 1
Version: 1.0.0.0
0757 BT300 Bus card parameter no. 3
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0758 BT300 Bus card parameter no. 4
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 100
Write: 1
Version: 1.0.0.0
0759 BT300 Bus card parameter no. 5
see P 755 Gruppe: 80
Min.: 0
Max.: 999
Default: 0
Schreiben: 1
Version: 1.0.0.0

42
2 List of Parameters

No. Device Description Attributes


0760 BT300 Bus card parameter no. 6
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0761 BT300 Bus card parameter no. 7
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0762 BT300 Bus card parameter no. 8
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0763 BT300 Bus card parameter no. 9
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0
0764 BT300 Bus card parameter no. 10
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version: 1.0.0.0

43
2 List of Parameters

2.20 Feature Parameter

No. Device Description Attributes


0800 BT300 Using the integral flame scanner
0: Main flame: ionisation detector Gruppe: 85
Pilot flame: none Min.: 0
1: Main flame: ionisation detector
Pilot flame: UV tube/contact Max.: 8
2: Main flame: ionisation detector Default: 0
Pilot flame: LDR photo resistance
Schreiben: 2
3: Main flame: UV tube/contact
Pilot flame: none Version: 1.0.0.0
4: Main flame: UV tube/contact
Pilot flame: ionisation detector
5: Main flame: UV tube/contact
Pilot flame: LDR photo resistance
6: Main flame: LDR photo resistance
Pilot flame: keine
7: Main flame: LDR photo resistance
Pilot flame: ionisation detector
8: Main flame: LDR photo resistance
Pilot flame: UV tube
0801 BT300 Definition of terminal assignment (0: oil operation - two-stage or modulating/1: oil oper-
ation - three-stage/2: gas operation - modulating/3: dual fuel - oil and gas operation -
modulating/4: dual fuel - oil operation two or three-stage and gas operation)
Definition of terminal assignment Group: 85
0: oil operation - two-stage or modulating Min.: 0
1: oil operation - three-stage (pilot burner not available)
2: gas operation - modulating (BT340 only) Max.: 65535
3: dual fuel - oil operation - modulating or two-stage or gas operation - modulating Default: 2
pilot burner permitted (BT340 only)
Write: 2
4: dual fuel - oil operation up to three stages (without pilot burner) and modulating gas
operation (BT340 only) Version: 1.0.0.0
0802 BT300 Running leakage check
Type of leakage check Group: 85
0: no leakage check Min.: 0
1: Leakage check starts with pre-ventilation
2: Leakage check starts after pre-ventilation has finished Max.: 2
This parameter decides whether the integrated leakage chek is active or not (only Default: 1
available if the device is configured with active control). Write: 1
If P 802  0 than P 312 should be  0 or P 315 should be  0. Version: 1.0.0.0
0808 BT300 Fuel selection (0: fuel oil / 1: fuel gas). Effects only if P 812 = 0
Fuel selection is only analysed if P 812 = 0 Group: 85
0: fuel oil Min.: 0
1: fuel gas
Max.: 1
Default: 1
Write: 2
Version: 1.0.0.0

44
2 List of Parameters

No. Device Description Attributes


0809 BT300 Setting of the output at terminal X24
Setting of the output at terminal X24 Group: 85
Min.: 0
Warning! Max.: 2
The output at terminsl X24 is not configurated in a safety-related way. You
Default: 1
may ust it only for display functions.
0: Output without function, i.e. inactive Write: 2
1: Output indicates a failure (terminal off: no failure, terminal on: failure) Version: 1.0.0.0
2: Output indicates the actual fuel (terminal Off: oil, terminal on: gas)
0812 BT300 Definition of source for fuel selection (0: fuel selection with P 808/1: fuel selection via
terminal at Dual Fuel Module)
Definition of source for fuel selection Group: 85
0 = fuel selection with P 808 Min.: 0
1 = fuel selection via terminal at Dual Fuel Module (DFM)
2 = fuel selection via LSB (p.ex. PBM) Max.: 2
Default: 0
Write: 2
Version: 1.0.0.0
0813 BT300 Deactivation/activation and threshold voltage for power-failure detection
Deactivation/activation and threshold voltage for power-failure detection Group: 85
Bit 5 = Failure indication at power-failure >= 60ms --> 0:OFF, 1:ON Min.: 0
Bits 14..8 = not used
Bits 7..0 = threshold voltage (unit: 1V RMS) Max.: 33023
Default: 32963
Write: 2
Version: 1.0.0.0

45
Copyright© 2014 LAMTEC
DLT1204-14-aEN-013

The information in this publication is subject to technical changes.

LAMTEC Meß- und Regeltechnik LAMTEC Leipzig GmbH & Co. KG Presented by:
für Feuerungen GmbH & Co. KG

Wiesenstraße 6 Portitzer Straße 69


D-69190 Walldorf D-04425 Taucha
Phone: +49 (0) 6227 / 6052-0 Phone: +49 (0) 34298 / 4875-0
Fax: +49 (0) 6227 / 6052-57 Fax: +49 (0) 34298 / 4875-99
e-mail:[email protected] Print no. DLT1204-14-aEN-013
www.lamtec.de Printed in Germany

You might also like