0% found this document useful (0 votes)
151 views37 pages

Mau 150

Uploaded by

sandro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
151 views37 pages

Mau 150

Uploaded by

sandro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 37

INSTALLATION, OPERATION & MAINTENANCE MANUAL

PRE-ENGINEERED HI-FOG® SYSTEMS


for

TOTAL COMPARTMENT PROTECTION OF


MACHINERY SPACES, TURBINE ENCLOSURES AND
SPECIAL HAZARD MACHINERY SPACES

INSTALLATION, OPERATION
AND MAINTENANCE MANUAL

FOR MAU 150

GE Oil&Gas - Project no. 1703665


PO. 440018561– RAO2322278

GE Oil&Gas - Project no. 1703666-1703667


PO. 440018562 – RAO2322278

LIBRA - PETROBRAS
BRAZIL

LIBRA Project MAU 150 Rev .0


-1-
INSTALLATION, OPERATION & MAINTENANCE MANUAL

CONTENTS

1.0 INTRODUCTION .................................................................................................... 3

2.0 SYSTEM DESCRIPTION ........................................................................................ 4


LIBRA Project: MAU 150 .................................................................................................................. 4
3.0 WARNING ............................................................................................................... 5

4.0 SAFETY MEASURE ............................................................................................... 5

5.0 DESIGN & CONFIGURATION .............................................................................. 6


5.1 Application and special note ................................................................................................... 6
5.2 Spray Heads .............................................................................................................................. 6
5.3 Distribution Network ............................................................................................................... 6
5.4. Installation ................................................................................................................................ 7
5.5. Flushing and System Filtration ............................................................................................... 7
6.0 FIELD INSTALLATION ......................................................................................... 8
6.1. Tubing ....................................................................................................................................... 8
6.2. MAU cabinet ............................................................................................................................. 8
6.3. System Filling ........................................................................................................................... 9
7.0 COMMISSIONING ................................................................................................ 12
7.1. List of operations .................................................................................................................... 12
7.2. System Operation ................................................................................................................... 13
7.3. Post Discharge ........................................................................................................................ 14
8.0 TESTING, INSPECTION & MAINTENANCE .................................................... 15
8.2. 3 Months Inspection ............................................................................................................... 15
8.3. Semi-Annual Inspection ........................................................................................................ 15
8.4. Annual Inspection .................................................................................................................. 15
8.5. Supplementary Information.................................................................................................. 16
9.0 TROUBLE SHOOTING ......................................................................................... 16
9.1 Water cylinder level signal .................................................................................................... 16
9.2 Water Mist discharge failure ................................................................................................ 16
9 APPENDIX ............................................................................................................. 17
9.1 Appendix -Gas Actuator Valve (Solenoid) ................................................................................ 17
9.2 Appendix - Water Storage Cylinder& Assembly of Header ................................................... 18
9.3 Appendix – Delta P Valve ........................................................................................................... 19
9.4 Appendix - Scheme Commissioning Test Records ................................................................... 20
9. 5 Appendix – Instrument manuals .............................................................................................. 24

LIBRA Project MAU 150 Rev .0


-2-
INSTALLATION, OPERATION & MAINTENANCE MANUAL

1.0 INTRODUCTION

1.0.1 The function of the manual is to provide Design, Installation, Operation and Maintenance
information for use by suitably qualified and authorized personnel with experience of fixed fire
protection system engineering.

1.0.2 The scope of this manual covers pre-engineered Hi-fog systems for the TURBINE
COMPARTMENTS.

1.0.3 Marioff cannot be held responsible for any pre-engineered system of the type that has not been
designed, installed, operated or maintained in accordance with the instructions and guidelines
provided in this manual.

1.0.4 Marioff Corporation Oy reserves the right to revise and improve its products and recommended
system configurations as it deems necessary without notification.

1.0.5 All the information contained herein is confidential and proprietary to Marioff Corporation Oy
and it shall not, in whole or in part, be reproduced, copied, disclosed or used as the basis for
manufacture or sale without the prior written consent of Marioff Corporation Oy. Hi-fog® is a
registered trademark of Marioff Corporation Oy. Copyright 1997. Marioff Corporation Oy.

1.0.6 CAUSION: Hi-fog® comprise high pressure gas cylinder for water pressurization. Care must be
taken to ensure that all relevant procedures are followed in accordance with recognized code of
the territory of installation.

1.0.7 Any questions concerning information presented in this manual should be addressed to:

MARIOFF Srl
Street address: Via Matteotti, 24
Mailing address: 20016 - Pero (Milan) - Italy
Telephone: ++39 02 3391 5300
Fax: ++39 02 33915293
Web site: www.marioff.it
E.mail: [email protected]
[email protected]

LIBRA Project MAU 150 Rev .0


-3-
INSTALLATION, OPERATION & MAINTENANCE MANUAL

2.0 SYSTEM DESCRIPTION

2.0.1 The Hi-fog systems described in this manual are self-contained water mist storage and
distribution system. Detection, control and release facilities provided by others and not covered
within the scope of this manual.

2.0.2 The systems are of twin-fluid, single-pipe type employing water as the suppressant and nitrogen
or air as the atomizing medium.

2.0.3 Each MAU system arrangement is configured using a water and gas (N2) supply to provide the
total suppressant requirement for at least 10 min for the total volume of protection.

2.0.4 The system is activated by remote electric actuation, being supplemented by local manual
release.

LIBRA Project: MAU 150

2.0.5 Please refer to P&ID drawing no. SOM6755361

2.0.6 Hi-fog fire extinguishing system MAU150 for LIBRA Project is designed to meet client’s
requirements to protect the Turbine Enclosures, equipped with Marioff’s spray heads type 4S
1MC 8MB 1100, in SS316.

2.0.7 The system is composed by two MAU battery (Main & Reserve). The battery is composed by
two MAU 150. The MAU 150 protects the GT enclosure. The first of two MAU 150 covers the
initial discharge. It will last for about 10 minutes. The second MAU 150 will be activated after
the first one and it will cover the extension discharge for other 10 minutes. The activation is
pneumatic by the first MAU. As soon as the N2 pressure will drop at 20 bar, the second MAU
will be activated by Delta P Valve. The total discharge time for the GT enclosure will be more
than 20 minutes.

2.0.8 The system MAU skid has two batteries (Main and Stand-By) and every battery it is composed
by 2+2 MAU150. Every battery (Main & Reserve) has 3+3 water cylinders 50 l and 1+1 N2
cylinders, 50l – 200 bar TPED. Every battery has also the damper N2 cylinder for every battery

2.0.9 The MAU units are installed in a cabinet. The cabinet has also instrumentation for the
monitoring of the status of N2 cylinders, water cylinders and activation. These instruments are
general supply in accordance with the client specification.

2.0.10 The actuation of the system (ie. Main Battery) is given by a 24VDC electric signal sent to the
solenoid valve installed on the nitrogen cylinder. When valve is opened by the solenoid a
mixture of gas and water is released into the turbine enclosure through spray heads as fine water
mist. The N2 pressure will also actuate the extended discharge by the Delta P Valve. When the
pressure will drop at about 20 bar, the extended discharge will be actuated. The N2 pressure,
from the solenoid cylinder will activate the damper cylinder by pneumatic actuator.

LIBRA Project MAU 150 Rev .0


-4-
INSTALLATION, OPERATION & MAINTENANCE MANUAL

2.0.11 Solenoids in the systems are ATEX/IECEx II 2 G/D Eexm T4/T5 using 24 VDC.

2.0.12 Actuator valves are equipped with a manual release and remain open after discharging until
pressure drops to approx. 3 bar. Discharge can be stopped during actuation by manually closing
either the nitrogen cylinder valve or isolation valve with micro switch installed outside the unit.

2.0.13 After discharge, water cylinders can be filled using the water inlet connection through “normally
closed” manual valves located in the line.

2.0.14 Unit tests can be carried out through “normally closed” manual test valves. During testing water
discharges from the water inlet plug; care should be taken to monitor and control potentially
high water speed at the outlet.

3.0 WARNING
VERY IMPORTANT

3.1. NOTE: The MAU systems will be supplied by MARIOFF Srl with the water cylinder empty.

3.2. In case the water cylinders are filled by other, not suggested, be sure that the temperature inside
the MAU cabinet shall be ALWAYS above +1°C during the handling or storage period. In case
the temperature of the storage phase is below +1°C, the water cylinders must be empty for avoid
damage to the equipment.

3.3. During the working phase the temperature inside the cabinet shall be above +4°C. An internal
Warning Sign will be attached to the cylinders in order to remember it before the shipment.

4.0 SAFETY MEASURE


4.1. The cabinet is considered a confined space, due to the presence of nitrogen cylinders. Keep the
cabinet doors open for a while before enter.

4.2. Use no sparkling tools during maintenance operation.

4.3. Close needle valve on N2 cylinders before every operation inside the cabinet.

4.4. The handling and installation of the N2 cylinders must be done by skilled personnel.

4.5. During the handling of the N2 cylinders the protection cup must be used. The protection cup can
be removed only when the N2 cylinders is installed and fixed to the MAU cabinet.

LIBRA Project MAU 150 Rev .0


-5-
INSTALLATION, OPERATION & MAINTENANCE MANUAL

5.0 DESIGN & CONFIGURATION

5.1 Application and special note

5.1.1 In this case, the enclosed risk shall be the turbine and load compartments.

5.1.2 All ventilation openings or forced ventilation arrangements shall be capable of automatic
closure or shut-down prior to water mist Hi-Fog® discharge.

5.2 Spray Heads

5.2.1 Hi-fog spray heads are precision-engineered devices, designed to deliver a water mist discharge
in a form that ensures fire suppression. The spray head comprises a single stainless steel body
designed to accommodate the spray nozzles.

5.2.2 The spray heads have been designed for water mist systems in enclosures with flammable
liquids. The relevant component tests have been conducted by and at the Factory Mutual
Research Corporation, USA.

5.2.3 Within the constraints of this manual, Hi-fog spray heads of type 4S 1MC 8MB 1100, in SS316
with no. 3 nozzles, installed in the Turbine Enclosure, two in the turbine compartment, one in
the load compartment.

5.2.4 The mounting adapter will be fitted with a test plug to facilitate pressure testing of completed
distribution network installation. The plug is removed from the system prior to the coupling of
the spray head to the mounting adapter.

5.2.5 Spray heads are fitted with a 300 m strainer to prevent any particles carried in the discharge
network from clogging the discharge orifices.

5.3 Distribution Network

5.3.1 The tubing system features a single line arrangement, using 5/8” (thk. 1,5 mm) and or ½” (thk.
1,5 mm), in stainless steel AISI 316L into the GT compartment while ½” into the load
compartment. Tubing inside FFWM skid is AISI316L imperial type.

5.3.2 The connections are usually ferrule type DIN 2353 joints or SAE 518J flange joints, which are
type approved by VdS. The couplings are made of AISI 316, and are designed with a minimum
safety factor of 4. In this case fittings required and used are compression fitting Parker A-Lok
type in AISI 316.

LIBRA Project MAU 150 Rev .0


-6-
INSTALLATION, OPERATION & MAINTENANCE MANUAL

5.3.3 Tube clamps are equipped with steel bottom and cover plates. The distance between clamps is to
be as instructed, following the normal practice for hydraulic piping.

5.3.4 All tubing for pre-engineered systems up to 150 l or 100 l of water storage, shall comprise
16/1.5 mm or 12/1.2 mm tubing. The suggested distance between the MAU cabinet and the
turbine enclosure should be 10m with tubing 5/8” or OD 16 mm. For higher distance, but
always less than 20m, OD ¾” is required. In this case the distance is higher than 10 m so the
interconnecting tubing will be ¾”. Internal the turbine enclosure the tubing has ND 12 mm / ½”
and distance about 20 m max. Systems with characteristics between these distances do not
require hydraulic calculation.

5.4. Installation

5.4.1. The system has been developed to meet the requirements of NFPA 750.

5.4.2. The positioning of the nozzles are defined by Marioff Srl Technical Department. Modifications,
unless authorized by Marioff Srl, is not permitted.

5.5. Flushing and System Filtration

5.5.1. Water used in the Hi-fog systems should be the equivalent of a potable supply. In all cases the
fill line must be routed through a 100 m filter and the chloride concentration may not exceed
50 ppm (= 50 mg/l). See attached technical data sheet for water and N2.

5.5.2. VERY IMPORTANT: The system has to be properly cleaned and flushed before it is
commissioned as reported in point 6.1.7. The cleanliness level must be maintained at all times.

5.5.3. Under no circumstances should suppression additives be applied in the stored water cylinder, 50
l.

LIBRA Project MAU 150 Rev .0


-7-
INSTALLATION, OPERATION & MAINTENANCE MANUAL

6.0 FIELD INSTALLATION

6.1. Tubing

6.1.1 System distribution tubing will be routed and installed in accordance with project specific
drawings. Do not modified the size of the tubing, in particular the connection line between the
MAU cabinet and the Turbine enclosure which must be 5/8” or ND16 mm for distance up 10 m
For distance less than 20 m, tubing ¾” must be used, as per this case.

6.1.2 Cutting, de-burring, bending, attachment of fittings and tube cleaning will take place during
field installation. All such work shall be carried out in accordance with the instructions of the
Marioff approved tube and fittings supplier.

6.1.3 VERY IMPORTANT: Cleaning shall be carried out to Standard NAS 1638, Class 9 or ISO
4406, Class 18/15.

6.1.4 All support brackets and clamps should be welded or bolted securely and at spacing compliant
with Marioff recommendations.

6.1.5 Special care must be practiced in the installation where efficient spray distribution may be
disturbed by obstructions close to the spray head. In this case the nozzle positioning has been
defined. Do not modify for any reason. In case of nozzles modification, please contact Marioff.

6.1.6 The tubing distribution system shall be pressurized before commissioning. The test pressure is
200 bar for a period of 30 minutes without loss. Loss shall be determined by loss of gauge
pressure at a low point of the distribution network or by visual examination, after temperature
stabilization. In case of leakage the joints must be repair and the test repeated. Another pressure
test, fully in accordance with NFPA750 is to pressurized the interconnecting tubing and
distribution tubing at 120 bar for 110 minutes and 180 bar for 10 minutes.

6.1.7 On completion of the pressure test procedures, all plugs from the mounting adapters should be
removed and the cleanliness of tubing network verified. Temporarily the plugs in the mounting
adapters should be replaced. Note: Grip the mounting adapter when tightening or removing
plugs to ensure that the mounting adapter to the tube connection is not disturbed.

6.2. MAU cabinet

6.2.1 The MAU cabinet will be installed on side using the supplied foundation plate to be welded to
the main structure or by expansion bolts into the concrete basement. The MAU cabinet will be
anchored by bolts and nuts. The cabinet will be installed on a plane surface.

6.2.2 The field-tubing network is to be connected to the appropriately tagged outlet port of the MAU
cabinet.

LIBRA Project MAU 150 Rev .0


-8-
INSTALLATION, OPERATION & MAINTENANCE MANUAL

6.2.3 All connections are to be made off to rack/skid mounted electrical interface points, i.e. junction
box if pre-wired or individual components if not pre-wired.

6.2.4 All appropriate functions are to be carried out as required for detection, control and releasing
devices in accordance with the relevant codes of the territory of the installation.

6.2.5 System is now mechanically and electrically installed and ready for system filling, in case the
water cylinders are empty (Note: Marioff always supply water cylinders empty).

6.3. System Filling

6.3.1 It should be ensured that the gas pressure is isolated. The water supply hose is to be connected to
the filling port on the water storage cylinder header.

LIBRA Project MAU 150 Rev .0


-9-
INSTALLATION, OPERATION & MAINTENANCE MANUAL

6.3.2 The vent plug on the right of the cylinder header of each water cylinder connected to the fill line
hose should be released. Open the ball valve and filling up the water cylinder. During this
operation be carefully to do not loose the spring and the inside check valve. In case during this
operation the operator loose some pieces, remember to change it. Spare parts of this pieces must
be always available on stock (Marioff Srl Stock Code: D32030, D32015, H20165.1, D32005,
G01235, G00095, D32020 (NP001)).

6.3.3 The filling is continued until water is seen to continuously escape from each of the unplugged
ports of the water cylinder headers. Close the water inlet valve. The plugs in the cylinder
headers should then be replaced.

LIBRA Project MAU 150 Rev .0


- 10 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

6.3.4 The water supply connection hose must be removed and the plug should be replaced in the fill
port. All plug connections should be rechecked for tightness.

6.3.5 For releasing all the air in the top of the water cylinder valve, in same cases, it is necessary to
fill up with water the line until the solenoid valve and Delta P valve. In this case water must exit
from the release orifice on the front valve. This procedure can reset the signal on water cylinder
level switch (LSL or WSL).

LIBRA Project MAU 150 Rev .0


- 11 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

7.0 COMMISSIONING

7.1. List of operations

7.1.1 The MAU cabinet must be installed correctly. The level must horizontal. The cabinet must be
anchored to the main structure using the foundation plate.

7.1.2 The tubing connecting the MAU cabinet and the turbine enclosure must be correctly installed,
using the ¾” NPT connections.

7.1.3 Check all the nozzles should be correct installed. In front of the nozzle nothing must be
installed. The water mist jet must be free to flow. In case of doubt please advice a safety
manager and in case contact Marioff.

7.1.4 Check the electrical connection at the junction box, installed on the MAU cabinet.

7.1.5 Check the selector switch installed inside the MAU cabinet will be positioned on “Main
Battery”.

7.1.6 Check the system for the activation of the solenoid valve.

7.1.7 Open the valve on the N2 cylinders.

7.1.8 Check if there are gas leakages between the cylinder and the actuator valves. In case of leakage,
close the valve on the cylinder and take the correct action.

7.1.9 Open again the valve on the N2 cylinder e re-check the leakages.

7.1.10 Check the pressure on the pressure gauge on the actuator. The pressure must be about 200 bar.

7.1.11 Marioff suggest to do a real discharge test into the enclosure turbine for checking all the system
and the correct water mist flow inside the enclosure. The activation can be done by remote
command (using the solenoid valve) or manual, according to the client choice. In case the real
discharge cannot be done, Marioff suggest to test the system using the line test. Care must be
taken during the test. No personnel must be outside the MAU cabinet near the line test outlet.

7.1.12 In case of real discharge, verify the jet flow at the nozzles. After the discharge, the nozzle must
be checked and clean. In case the filter on the nozzle is damage, the nozzle must be replaced.
Before mounting the nozzle, the line must be clean with compressed air.

7.1.13 The report of the commissioning operations must be update and keep.

LIBRA Project MAU 150 Rev .0


- 12 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

7.2. System Operation

7.2.1 The system will be operated on an automatic basis from an electrical signal input to the solenoid
actuator. The system will be also activated by a manual Push Button near the turbine enclosure
or by manual activation installed outside the MAU Cabinet.

7.2.2 Upon actuation the system will discharge on a continuous basis for the duration of discharge
(about 20 minutes for GT compartment) through the tubing distribution system and the Hi-fog
spray heads.

LIBRA Project MAU 150 Rev .0


- 13 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

7.3. Post Discharge

7.3.1 Following a discharge the MAU system is normally empty and the gas pressure has been
expelled.

7.3.2 In the event of a no-fire condition release, the most distant (in respect of the storage unit
position) Hi-fog spray head should be removed from the system and examined in respect of
discharge cleanliness. Should the removed spray head show sufficient signs of dirt collected by
the spray head filter during discharge, all spray heads should be removed for cleaning by a
Marioff authorized distributor.

7.3.3 In the event of a fire condition release, all spray heads should be removed from the system, and
replaced (Marioff Srl Stock Code: C31122.1)

7.3.4 All detection and control facilities should be reset.

7.3.5 Water storage cylinders shall be refilled in accordance with the procedure for initial filling
(Section 6.3).

7.3.6 The gas cylinder valve should be closed and the actuator valve removed from the gas cylinder
valve outlet, taking care to retain the adapter (if used). The gas cylinder valve actuator will
require to be reset (See 6.3.5).

7.3.7 Replace the rupture disc of the Delta P Valve (extended discharge battery). See Appendix 3.
(Marioff Srl Stock Code: V21013). Contact always Marioff for these parts in case the code can
be modified.

7.3.8 The gas cylinder should be removed from the mounting position and replaced with a fully
pressurized cylinder. In case other N2 cylinder are used, check the correct high for the proper
connection. In case of need leveling must be made in order to have the same high. DO NOT
BEND THE N2 TUBING DURING N2 CYLINDERS REPLACEMENT.

7.3.9 Reconnection of the replacement gas cylinder is in accordance with the instructions provided for
system commissioning.

7.3.10 The system shall be re-commissioned in accordance with the instructions provided for initial
commissioning (Section 7.1).

7.3.11 System records should be updated accordingly.

LIBRA Project MAU 150 Rev .0


- 14 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

8.0 TESTING, INSPECTION & MAINTENANCE


8.1.1 Testing, inspection and maintenance of installed Hi-fog systems shall be in accordance with the
requirements of NFPA 750 and this manual.

8.1.2 Hi-fog systems require minimum maintenance in normal service.

8.2. 3 Months Inspection


8.2.1. Visual inspect the pressure of the N2 cylinders on pressure gauge.

8.3. Semi-Annual Inspection


8.4.1. Close the gas cylinder valve. Disconnect the actuator valve, vent the line to the pressure switch
using the valve manifold.

8.3.2. Activate the solenoid valve e check the opening.

8.3.3. Replace the actuator valve to the gas cylinder valve. Close the vent.

8.3.4. Re-open the gas cylinder valve noting the requirements of Section 4 in respect of valve security.

8.3.5. Observe and record the gas cylinder pressurization level. Remove and replace if the N2 pressure
is below 170 bar (set point of the Pressure Switch/Transmitter on N2 cylinders)

8.3.6. Check the physical condition of all equipment assembled within water storage unit and the
physical integrity of tubing distribution network and spray heads.

8.3.7. Verify no modification has been made.

8.3.8. Update system records.

8.4. Annual Inspection

8.4.1. Carry out all procedures as for before point.

8.4.2. To avoid any residue or bacteria build-up in the storage cylinders, change stored water.

8.1. Close the gas cylinder valve and disconnect the actuator valve (retaining the adapter if used).

8.2. Connect the water supply fill line as for the initial fill procedure (Section 6.3).

8.4.5. Close the delivery valve to the turbine and open the drain/test valve. Allow each cylinder to
discharge water through the vent plug port(s) for a minimum of five (5) minutes to ensure a
complete water change.

8.4.6. Turn off the water supply and disconnect the water fill line hose.
LIBRA Project MAU 150 Rev .0
- 15 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

8.4.7. Replace all plugs to the water storage cylinder headers and replace the plug in the fill connection
port. Recheck tightness on all plugs.

8.4.8. Carry out a functional discharge test of the system in accordance with the commissioning
instructions.

8.4.9. Check if modification are made. In case of modifications, advice the safety manager and in case
Marioff.

8.4.10. Check if obstruction are positioned near the nozzle which can be interfere with the nozzle jet
through.

8.5. Supplementary Information

8.5.1. There follows, in the Appendix section of this manual, a series of individual plates providing
additional data, which may be read in conjunction with the text pages of this manual.

9.0 TROUBLE SHOOTING

9.1 Water cylinder level signal


In case the water cylinders level signal is not off even if the cylinders are full, take care to
eliminate all the air in the top of the cylinder head through the vent. Reduce the water filling
flow rate until the signal is off from the panel. This operation can takes several minutes.

9.2 Water Mist discharge failure


The MAU unit is a very simple apparatus, then if there is a failure during the water mist
discharge the reasons can be:
In Gas Turbine there is only a N2 discharge: this means that the water cylinders are
empty
In Gas Turbine there is no water mist discharge, this means:
1. Section ball valve closed on the main distribution line inside the Hi-Fog cabinet,
or ball valve of the drain/vent lines are open. Check the valves and their status
signal.
2. The cabinet outlet tubing connection is not connected to the GT internal line.
Check the connection on terminal point.
3. The nozzles are blocked. Check the nozzles. Take care to control is the line is
under pressure before to dismantle the nozzles.
4. Solenoid valve failure. Check the solenoid coil.

LIBRA Project MAU 150 Rev .0


- 16 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

9 APPENDIX

9.1 Appendix -Gas Actuator Valve (Solenoid)

Note: The solenoid valve code reported in the scheme is only for information.

LIBRA Project MAU 150 Rev .0


- 17 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

9.2 Appendix - Water Storage Cylinder& Assembly of Header

LIBRA Project MAU 150 Rev .0


- 18 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

9.3 Appendix – Delta P Valve

LIBRA Project MAU 150 Rev .0


- 19 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

9.4 Appendix - Scheme Commissioning Test Records

COMMISSIONING REPORT
FOR
MARIOFF HI-FOG FIRE PROTECTION SYSTEM

Project
Customer
Reference documents
Type of Unit Installed
Number of Units Installed
Space Protected
Commodity stored in space
Location of Unit
Commissioning Date
Commissioning Engineer

Comments:

LIBRA Project MAU 150 Rev .0


- 20 -
INSTALLATION, OPERATION & MAINTENANCE MANUAL

1. TUBE INSTALLATION (VISUAL INSPECTION) Completed Sign/Date


(1) Piping and fittings stainless steel SS-316L (Minimum). _________
(2) Pipe sizes nominal O.D. in accordance with specs. _________
(3) Pipework installed according to manufacturers
specs to meet the system requirements. _________
(4) Spray head locations in accordance with
manufacturers specs to meet system requirements. _________
(5) Spray heads not obstructed or blocked. _________
(6) Spray head mounting adapters capped with plugs. _________
(7) Correct signage securely mounted. _________

Comments:

2. PIPING HYDROSTATIC TESTING Completed Sign/Date

(1) Spray head mounting adapters capped. _________


(2) Initial pressure build up by the hydrostatic pump ______ bar. _________
(3) The pressure after 30 minutes ________ bar. _________
(4) Pipework free of leakage. _________
(5) System test pressure released. _________

Comments:

LIBRA Project MAU150 Rev. 0


21
INSTALLATION, OPERATION & MAINTENANCE MANUAL

3. SKID INSTALLATION (VISUAL INSPECTION) Completed Sign/Date

(1) Skid placed in a correct location. _________


(2) Skid securely mounted to deck or basement. _________
(3) 100 m filter or better mounted on water filling line. _________
(4) Water cylinders full. _________
(5) Water filling connection closed. _________
(6) Isolation valve open towards pipeline. _________
(7) Drain valve closed (if applicable). _________
(8) Gas cylinders installed and secured with brackets. _________
(9) Actuator valves correctly mounted and in stand-by for operation. _________
(10) Necessary interface connections connected properly. _________
(11) Gas cylinder valves open. _________
(12) Gas pressure gauge readings above 200 bar. _________

Comments:

4. SYSTEM FUNCTIONAL TESTING Completed Sign/Date

Note: Functional test may be carried out through spray heads or by utilizing test port
connection if discharge to protected space is not desired.

(1) Blanking plugs replaced by spray heads. _________


(2) Gas cylinder valves open. _________
(3) Actuator valve(s) manually released. _________
(4) Spray flow pattern of each spray head verified. _________
(5) Duration of discharge ________ min. _________

Comments:

LIBRA Project MAU150 Rev. 0


22
INSTALLATION, OPERATION & MAINTENANCE MANUAL

5. SYSTEM RESET (OPERATION STAND-BY) Completed Sign/Date

(1) Actuator valve(s) reset and stand-by for next operation. _________
(2) Gas cylinder(s) replaced by new full cylinder(s) and opened. _________
(3) The initial pressure in gas cylinders ________ bar. _________
(4) Water cylinders filled up and venting plugs closed. _________
(5) Filling connection closed. _________
(6) Manual valve open towards pipeline (if applicable). _________

Comments:

6. COMMISSIONING COMPLETION

Commission Engineer to sign:


Inspections, verifications and procedures included in the commission procedure have been acceptably completed,
and the system performs in accordance with system requirements.
Date :
Signature:
Position :

Installer’s Representative to sign:


We hereby acknowledge that the system has been installed in accordance with the requirements and procedures
defined in Manufacturer’s manuals and specifications. Good workmanship and standard hydraulic installation
practices are applied for the installation work.
Date: :
Signature:
Position :

Customer’s Representative to sign:


Date: :
Signature:
Position :

LIBRA Project MAU150 Rev. 0


23
INSTALLATION, OPERATION & MAINTENANCE MANUAL

9. 5 Appendix – Instrument manuals

1. Level Switch (Magnetic Proximity Sensor) Manual


2. Pressure Indicator Manual
3. Solenoid Valve: see point 9.1 in this document
4. Limit Switch Manual
5. Delta P Valve: see point 9.3 in this document.
6. Water data sheet
7. N2 data sheet
8. Pressure Switch Manual

LIBRA Project MAU150 Rev. 0


24
BA_Magn_Namur_multi.pmd 1 18.02.2009, 09:08
×ñþ á óýìñáôïò Åð öÞ ÊáôÜëçö
brn ÊáöÝ 1 + V DC
blu ìôôëå 4 – V DC
3 åëåýèåñï
2 åëåýèåñï

Ôýðïò Áñéè. ðáñáãã.

óýìö. ìå EN 60 947-5-6

Ôá ìïíôÝëá ìáãíçôéêþí áéóèçôÞñùí ðñïóÝããéóçò/


áéóèçôÞñåò êýëéíäñïé NAMUR.åßíáé áõôïáóöáëÞ
çëåêôñéêÜ ëåéôïõñãéêÜ óõóôÞìáôá óýìöùíá ìå ôï
ðñüôõðï NAMUR EN 60 947-5-6, ôá ïðïßá åðéôñÝðåôáé
íá ëåéôïõñãïýí óå åíéó÷õôÝò áðïìüíùóçò ìå
ðéóôïðïßçóç áíôéåêñçêôéêÞò óõììüñöùóçò. Åßíáé
êáôÜëëçëá ãéá åöáñìïãÝò óôçí ïìÜäá ôïìÝùí
åðéêßíäõíùí åêñÞîåùò EX II, áðü æþíç 1 (óýìö. ìå
EN 60079-0 êáé EN 60079-11).
Èåñìïêñáóßá ðåñéâÜëëïíôïò TU = –25 °C +70 °C.
ÊëÜóç èåñìïêñáóßáò T6
Åßäïò ðñïóôáóßáò
ÄéáâÜóôå ôéò ïäçãßåò ëåéôïõñãßáò ðñéí áðü ôç èÝóç óå
ëåéôïõñãßá.
Ç óýíäåóç, ç óõíáñìïëüãçóç êáé ç ñýèìéóç ðñÝðåé íá
ðñáãìáôïðïéïýíôáé ìüíï áðü åéäéêü ðñïóùðéêü.
ÊáíÝíá äïìéêü ìÝñïò áóöÜëåéáò óýìöùíá ìå ôçí ïäçãßá
ãéá ìç÷áíÝò ôçò ÅÅ.

NAMUR óýìö. ìå EN 60 947-5-6 ÷ñçóéìïðïéïýíôáé ãéá ôçí


áíß÷íåõóç ìáãíçôéêþí ðåäßùí óå ôïìåßò åðéêßíäõíïõò
åêñÞîåùí.

ÔÜóç ôñïöïäïóßáò U0max. = 16 V


Ñåýìá âñá÷õêõêëþìáôïò Ikmax. = 30 mA
Éó÷ýò Pmax. = 100 mW
Åíåñãüò åóùôåñéêÞ åðáãùãÞ Lmax. = 35 H
Åíåñãüò åóùôåñéêÞ ÷ùñçôéêüôçôá Cmax. = 15 nF

ÊáôÜ ôç óýíäåóç ôïõ áéóèçôÞñá óå ðçãÞ ôÜóçò ðñÝðåé íá


ëçöèïýí õðüøç ôá åîÞò:
á.) Ôá ìÝãéóôá óôïé÷åßá éó÷ýïò ôïõ åíéó÷õôÞ áðïìüíùóçò
â.) Ôï äéÜãñáììá óýíäåóçò ôïõ áéóèçôÞñá
ã.) Óôá ìïíôÝëá ìå âýóìá ôï êïõôß êáëùäßùí ðñÝðåé íá
åìâõóìáôùèåß ÷ùñßò ôÜóç êáé íá âéäùèåß óôáèåñÜ
Ïé áéóèçôÞñåò NAMUR èåùñïýíôáé ùò ðáèçôéêÝò óõóêåõÝò
êáé óõíåðþò äåí ÷ñåéÜæïíôáé ðåñáéôÝñù äéáéñÝôåò
áíÜóôñïöçò ôÜóçò.

Ïé ìáãíçôéêïß áéóèçôÞñåò ðñïóÝããéóçò/áéóèçôÞñåò


êýëéíäñïé SICK äåí ÷ñåéÜæïíôáé óõíôÞñçóç. Ðñïôåßíïõìå íá
åëÝã÷åôå óå ôáêôéêÜ äéáóôÞìáôá ôéò åìâõóìáôþóåéò êáé ôéò
Üëëåò óõíäÝóåéò.

BA_Magn_Namur_multi.pmd 2 18.02.2009, 09:08


C.E. s.r.l.
Compagnia Generale Elettronica
INSTALLATION ISTRUCTIONS SERIES 70
Misure - Regolazioni - Sicurezze SPDT/DPDT
MILANO - ITALIA FOR SERIES 70 PROXIMITY SWITCH
EDITION 24 september 2002
The magnetic end-runs work on the basis of magnetic SPECIFICHE - SPDT Safe, end-run connection types with cable input using the nipple, Measurement of the size to detect
attraction, reacting with iron metals or magnetic actuators blocking joint and junction box.
when these enter within the sensitive area. MODELS 71 and 72 MODELS 73 TO 77 In the illustration aside, the size of the
1) The ed-run connecting cables to the external circuit must be protected object to be detected by the end-run is
Sensitive distance: 1,02,, sensitive limit for 3/8” ø Sensitive distance: from damage deriving from mechanical stress using a conduit (either too small to be detected in a satisfying
Differential: approximately 0,5mm rigid or flexible). and durable manner.
Response time: 8 milliseconds 2,54cm at 2.000 PSI
Assembly Temperature: from -400F (-400 C) to 221 0F(1050C) 1,83mm at 5.000 PSI
Contacts: single pole, double throw, C shape. 1,52mm at 10,000 PSI

300 mm flexibl
- Establish a selected working position
- Position the end-run and/or actuator to ensure Differential: approximately 0,5mm
Response time: 8 milliseconds
that the actuator inputs into the sensitive area In the illustration aside the object has

150 mm forr conduit o


Temperature: from -400F (-400 C) to 221 0F(1050C)
- Use a surface iron actuator of suitable size not enough size or mass to be detected
Contacts: single pole, double washer, shape C

300 mm
- Avoid contact between the actuator and the end-run, in a satisfying and durable way.
Electrical data: Resistive
as it might damage the end-run

150 mm o flexibl
- Use external, standard production magnets to widen

300 mm
A B
the sensitive distance A
- The end-runs can be assembled in any position Electrical data: Resistive Tube

150 mm o flexible
C
- The series 70 end-runs are unaffected by iron-content
G
steel. They can be assembled in steel iron with no H I Blocking joint
adverse reaction. Case: stainless steel B E Position of the object to detect
- In order to achieve best performance, assemble Conduit output: 1/2” 14NPT. One position F
end-runs on non-magnetic materials Repetitivity: 0,05mm in identical working
E
Entre cable Ex-d In the illustration aside the iron object
conditions. is positioned to stop at the outer corner
- Steel positioned outside the end-runs sensitive D of the run-ends sensitive area. This is a
area does not interfere with the proximity switch Case: stainless steel F fringe position for a satisfying and
correct performance End-run sensitivity Conduit output: 1/2” – 14 NPT. One position D
E durable detection.
- When selecting and installing the end-runs, take into Series 70 Repeatability: 0,05mm. in identical working
F
account all factors potentially damaging the contact conditions.
The series 70 standard actuator is a 2,5cm. x A Case with protection type complying with IEC600079, example Eex-d case
- Select the magnetic end-run model characteristics 2,5cm x 8cm., mild steel bar with the 2,5cm x B Conduit or flexible
suitable to your requirements, working cycles, type of 2,5cm side towards the back of the end-runs. The C Blocking joint
D Box with Atex-certified terminal strip according to EN500014-18 norm
load, environment, vibrations, temperature, etc. models 73 to 77 sensitive distance is approximately E Cable fastener
- For capacitive r inductive loads, we recommend 2,54cm. The models 71 and 72 sensitive distance F Cable
G Adaptor with sealed through
using arc suppression devices such as resistors and is approximately 1,02 cm. I Adaptor for cable fastener
In the illustration aside, the iron object
condensers, thus lengthening the contact life-span. NOTE: the actuator size influences the sensitive is positioned to stop within the end-runs
Indication of valves position 2) The cables terminals connection must
- The series 70 ed-run used to detect cylinders distance. sensitive area, thus ensuring a satisfying
be carried out according to one f the
movement r valves position must be scrupulously The magnetic end-run applications are designed protection procedures described in the and durable detection.
adjusted and tested. End-runs, torque sealing values: mod. 73 to 76: for in excess of 600positions, researched and EN50014 norms and according to the
- Do not apply excessive torque stress when installing 15,88mm diameter designed for the most part of valves and assembling directive current in the
the magnetic end-run - Turn the nut of 15ft/lbs to achieve a 2.000 PSI actuators on the market, might they be rotating place of installation.
- The manufacturer recommends to use his apposite sealing of linear (hydraulic, pneumatics and electric).
- Turn the nut of 25ft/lbs to achieve a 5.000 PSI The operator is responsible for ensuring
assembly, factory-sealed kits instead of other products
sealing the adequate earthing continuity in the
available on the market. With these special factory-kits
are also supplied the specific, pressure and max torque assembly procedure selected.
Do not exceed 30ft/lbs.
parameters Pneumatic and hydraulic cylinders
- If, during installation no torque-measuring tools are
available the max sealing value can be extrapolated The proximity switch is actuated by a cylinder
by taking into account the rubber sealing medium and a piston.
- Unscrew the nut downwards, towards the washer I order to determine the threading length,
underneath, completely compressing the sealing measure the distance between the proximity
head and the cylinder ad add to it 15mm.
medium and stopping when in contact with the metal.
for the fastening nut.
The series 70 proximity switches are calibrated
for a 2,000 ad 5,000 PSI working pressure
and, upon request, for 10,000 PSI in the
models 73 to 78.
Hand screw the proximity in the cylinder
until the proximity reaches the piston.
C.E. s.r.l. - Via Giovanni da Verrazzano, 26 - 20132 Milano - tel. 02 2563197 fax 02 3590178 - e-mail:[email protected] - www.ce-srl.com Page 1/2
C.E. s.r.l.
Compagnia Generale Elettronica
INSTALLATION ISTRUCTIONS SERIES 70
Misure - Regolazioni - Sicurezze SPDT/DPDT
MILANO - ITALIA FOR SERIES 70 PROXIMITY SWITCH
EDITION 24 september 2002
Series Wiring
MAGNETIC END-RUN Series 70 DPDT
All magnetic end-runs are
Any number of magnetic end-runs can be
pure contacts, meaning they series connected, without causing any loss Models 7G 7H, 7I SPECIFICATIONS
have no tension loss when
of tension.
closed neither they lose Sensitive Distance: when using an actuator with
On the contrary, in the standard, solid-state
power when opened. same area of end-runs terminal
switches there is a tension decrease of
To install multiple units the approximately 2V between the switches
end-runs must be either 2,3mm terminal part Standard
when they are activated: this means that in a
series or parallel connected, 1,6mm terminal part 5.000 PSI
12V system and 4 switches in series, 8V are
as illustrated. 1,2mm terminal part 10.000 PSI
lost at the switches and only 2V can be used
on the load.
Differential: approximately 0,5mm
Response time: 8 milli-seconds
Temperature: from -400F (-400C) to 2210F (1050C)
Parallel Wiring Contacts: double pole, double throw, DPDT 2
When standard, solid-stat end-runs are Shape c
wired in parallel, there is a power dispersion
of approximately 100 micro-amperes Electric data: Resistive
through each end-run. This means that in
case of 10, solid-state, parallel-connected
end-runs the overall power dispersion totals
1,000 micro-amperes or 1 milli-ampere; in
other words an amount of power adequate
for an “ON” situation on a PLC. On the other
C shape hand, we can parallel-connect any number of
Double load type magnetic end-runs with no power dispersion Case: stainless steel
Circuits group and no modification to working power. Conduit output: 1/2” – 14 NPT, one position
Repetitivity: 0,05mm in identical working conditions
COLOURS FOR END-RUNS COLOURS FOR END-RUNS
WIRING SPOT CODE WIRING SPOT CODE
MODEL WIRE CABLE MODEL WIRE CABLE
Series 70 N/C - Red Serie 7G N/C - Red N/C - Red
N/C - Red
Serie 7H N/O - Blue
Double C shape
Standard N/O - Blue N/O - White N/O - Blue
(4 fili SPDT) COM - Black Serie 7 I COM 1 - Black COM 1 - Black
COM - Black
GND - Green N/C 2 - Red N/C 2 - Red
GND - Green
White stripes White stripes
DPDT
Serie 70 N/C - Rosso N/C - Red
B Shape Standard N/O - Blue
N/O 2 - Blu N/O 2 - Blu
N/O - Blu White stripes
Normally closed (3 wires SPDT) COM - Nero COM - Black
White stripes Note: when the end-run is used in SPST applications the
GND - Green or GND - Verde o wires must be parallel wired, thus distributing the load on the
Green & White Verde strisce end-runs and achieving even wearing to the advantage of a
stripes bianche longer end-run life-span.
TERMINAL WITH CONNECTOR
The connections shown are the standard ones. 7 POLES
Special wiring on request
Packaging
1-N/O2 White and Black
2-COM1 Black
4 POLES 4 POLES Every magnetic end-run is individually packed in a hit -resistant
3-N/C2 White carton box. There are no particular recommendations concerning
3 POLES 3 POLES 4-N/C1 Red
1-COM-Red and Black 1-COM-Black magnetic end-runs loading, uploading and transport
A Shape 1-COM-Green 2-N/O- Red and White 1-COM- Green 2-N/O White 5-COM2 Orange
Normally open 2 - N/C- Red and Black 3 - N/C- Red 2- N/C- Black 3-N/C Red 6- N/O1 Blue
3- N/O- Red and White 4-GND-Green 3- N/O- White 4-GND-Green (long pin) 7-GND Green
C.E. s.r.l. - Via Giovanni da Verrazzano, 26 - 20132 Milano - tel. 02 2563197 fax 02 3590178 - e-mail:[email protected] - www.ce-srl.com Page 2/2

You might also like