C-9102
Conventional
Photoelectric Smoke
Detector
548d/01 0832-CPD-0521
Description Terminals and Installation Holes
C-9102 Conventional Photoelectric Smoke Detector is
adapting infrared scattering technology detecting smoke Below figures show the detector bottom and terminals of the
density. This non-addressable detector is normally used base.
together with end of line unit, connected with compatible 45mm~75mm
03
control panels to build fire detection system. It shows fire m
m
alarm by LED indicators and transmits the fire signal to the
control panel.
5mm
25mm
Special designed chamber and build in algorithm maps
reject false alarm. Mounting DZ-03
Hole
C
Features and Benefits
There are four terminals with marks on the base.
Strong environmental adaptability due to drift
1: positive IN
compensation.
2: positive OUT
Self diagnostic.
3: negative IN and OUT
Twin LED for 360°view.
2: Positive terminal of remote indicator
Remote indicator output.
4: Negative terminal of remote indicator
Dirty chamber checking
The base is suitable to be installed onto standard European
Removable sensor chamber, easy for maintenance.
embedded back box, with hole-distance 45mm to 75mm
Certified for EN 54-7:2000 + A1:2002 + A2: 2006.
Recommended Cabling
1.0mm2 or above fire cable is recommended, but subject to
local codes.
Gulf Security Technology Co., Ltd. DS2022914-2
http://www.gst.com.cn/en/index.asp
Note: Specifications are subject to change without notice.
Page 1 / 2
Application Technical Specification
Warning: The detector should be connected with fire
alarm control panel or other devices with current limit Operating Voltage 24VDC
Standby Current ≤60μA
function. Otherwise the detector may be damaged by
Alarm Current 10mA - 30mA
too heavy alarm current. Red. Quiet in normal condition.
Indicators
Illuminates steadily in alarm.
1. When the detector is connected with conventional fire Instantaneous Power-off (5s Max.,
Alarm Clear
2.5VDC Max.)
alarm control panel or I-9319 addressable zone monitor
Power-up Time ≤10s
unit, if a P-9907 AEOL is connected to the end of loop, a Max. Wind Speed 7.6m/s (1500fpm)
Polarized 2-core for zone cable.
Diode (1N5819) should be connected to the detector Wiring
Polarized 2-core for remote indicator.
base. Ambient temperature -10°C - +50°C
1) When used as the detector base, the AEOL has a Relative Humidity ≤95%, non condensing
conventional detector on it. Ingress Protection Rate IP23
Enclosure ABS, white (RAL 9016)
Diode Diode Diameter: 100mm
Dimensions
Compatible Panel
I+ I- O+ O-
Height: 56mm (with base)
+ 1 2
- 1 2
+
Mounting Hole Distance 45mm - 75mm
-
4 3
4 3 Weight About 120g
Remote Indicator
AEOL
Ordering Information and Compatible Products
2) When the AEOL is used alone, the system connection is
shown below.
Diode Part No. C-9102
Compatible Panel
I+ I- O+ O-
Device Name Conventional Photoelectric Smoke Detector
+ 1 2
- 1 2
+
Order Code 2022914
-
4 3
GST102A – GST116A Conventional Panels
3
Compatible
4
Remote Indicator Products I-9319 Zone Monitor Module
AEOL
2. When the detector is connected with conventional fire
alarm control panel or I-9319 Addressable zone monitor Accessories and Tools
unit with an end of line resistor at the end, an ordinary
Part No.: DZ-03
common detector base will be used. Device name: Standard Base
Order Code: 4044898
Compatible Panel
I+ I- O+ O- Part No.: DZ-03D
1 2
+ + -
Device name: Diode Base
EOLR Order Code: 4041136
- 4 3
Part No.: C-9314P
Remote Indicator Device name: Remote Indicator
Order Code: 2132339
Part No.: P-9907
Certificates and Compliance Device name: Active End of Line
Order Code: 2712406
Standards: CE / CPD / EN54-7
Certifications: LPCB
BS5839-1 Compliant
WEEE & RoHS Compliant
Gulf Security Technology Co., Ltd. DS2022914-2
http://www.gst.com.cn/en/index.asp
Note: Specifications are subject to change without notice.