Single Phase Hybrid Inverter Introduction
Chapter 1 Introduction
This Manual describes the specification, installation, operations and maintenance of INVT hybrid inverter.
Please read this Manual carefully to understand the safety information, functions and features of the product
before installing and using it. The information provided in this Manual is subject to update from time to time due to
product improvements. The latest version and more product information are available on our official website.
1
Single Phase Hybrid Inverter Safety Precautions
Improper use may result in risk of electric shock or burns. This Manual provides important instructions for
installation and maintenance of the product. Please read this Manual carefully before using the product, and keep it
The following are the safety symbols used in this Manual to indicate potential safety risks and important safety
instructions.
WARNING!
The warning symbol indicates important safety information that, if not followed properly,
could result in serious personal injury or even death.
RISK OF ELECTRIC SHOCK!
The electric shock hazard symbol indicates important safety information that, if not
followed, could result in electric shock.
Safety Tips!
This symbol indicates important safety information that, if not followed, could result in
serious personal injury or even death.
HIGH TEMPERATURE!
This symbol indicates safety information that, if not strictly followed, could result in burns.
WARNING!
When performing maintenance on the input and output of the inverter after disconnecting it,
wait at least 5 minutes for the inverter to discharge any remaining electrical charge.
The hybrid inverter in XD3~6KTL series has been designed and tested according to the applicable safety
regulations. This ensures the personal safety of the user. However, as an electrical equipment, the inverter could
cause electric shock or other injuries if not operated properly. Please operate the inverter in accordance with the
following requirements:
1. The wiring, installation and commissioning work should be carried out by professionals.
2. Be sure to read this Manual before operating the product. We shall not be held liable for any failure or loss
caused by improper operation.
3. Before starting the installation or maintenance work, please break the connections at the AC side, DC side
2
Single Phase Hybrid Inverter Safety Precautions
and battery side, and then wait at least 5 minutes before proceeding to avoid electric shock.
4. When the inverter is running, the temperature of the casing is high. Do not touch it to avoid getting burned.
5. All electrical installations must conform to local electrical standards. The inverter should be connected to the
power grid by professionals with the permission of the local power provider.
6. During the installation process, insulated tools and personal protective equipments should be used to ensure
personal safety. To touch the electronic components of the inverter, please wear anti-static gloves, anti-static wrist
strap or anti-static clothing so as to protect the inverter against electrostatic discharge.
7. Please install the inverter at a position that is out of the reach of children.
8. Do not plug or remove the AC/DC terminal during normal operation of the inverter.
9. The actual DC input voltage should not exceed the maximum allowable DC input voltage of the inverter.
10. Select an appropriate battery that matches the system, and set the battery type correctly. If you select a
battery that does not match the hybrid inverter, the system cannot run.
11. If the battery has been completely discharged, please strictly follow the User Manual of the battery to charge
the battery.
12. For system maintenance service, please contact our local authorized service personnel or our after-sales
personnel.
13. The hybrid inverter system should be connected to the power grid after getting permission.
14. Turn off the PV switch before installing a solar PV panel during the sunny daytime, or there could be a
serious risk of electric shock.
15. Do not connect a PV string to more than one inverter, as this could cause damage to the inverters.
16. Do not connect a device that relies on continuous and stable power supply (such as a life-sustaining medical
device), to the emergency load port.
3
Single Phase Hybrid Inverter Product Introduction
The hybrid inverter in XD series should be installed only by trained professionals who are familiar with local
regulations, standards and electrical systems and have a good knowledge of this product.
It is highly recommended that the installer read this Manual carefully, so as to learn about product installation,
troubleshooting and communication networking.
The inverter in XD series is intended to store the energy generated in the PV system or public power grid into
the battery, and also output energy to the power grid. In the case of electric power failure, the hybrid inverter can
provide energy to the load as a backup power supply.
This Manual applies to the following hybrid inverter models:
XD3KTL\XD3K6TL\XD4KTL\XD4K6TL\XD5KTL\XD6KTL
Overview:
4
Single Phase Hybrid Inverter Product Introduction
1. Be sure to read this Manual before operating the product. We shall not be held liable for any failure or loss
caused by improper operation.
2. Select an appropriate battery that matches the system, and set the battery type correctly. If you select a battery
that does not match the hybrid inverter, the system cannot run.
3. If the battery has been completely discharged, please strictly follow the User Manual of the battery to charge
the battery.
4. The wiring, installation and commissioning work should be carried out by professionals.
5. During the installation process, insulated tools and personal protective equipments should be used to ensure
personal safety. To touch the electronic components of the inverter, please wear anti-static gloves, anti-static wrist
5
Single Phase Hybrid Inverter Product Introduction
As shown in the above diagram, a complete hybrid inverter system in XD series consists mainly of the solar PV
panels, hybrid inverter, battery and power grid.
Note: The battery is an integral part of the hybrid inverter system. Please keep the installation environment well-
ventilated and take necessary measures to control the ambient temperature, so as to prevent the risk of explosion
caused by high temperature.
Battery characteristics:
Ingress protection: ≥IP65; pollution degree: PD2; indoor temperature: 0℃~40℃; RH: 5%~85%
6
Single Phase Hybrid Inverter Product Introduction
2. Allow you to set the priority of grid connection, battery type and other inverter information on the LCD
screen;
3. Dual MPPT, high current input, compatible with large solar cell module of 210mm, flexible configuration;
5. Provide a battery safety management system, supporting remote upgrade of BMS system;
7. Support over-temperature / over-current / short-circuit protection, ensuring safe, stable and reliable
8. Provide a variety of humanized communication module options (RS485, GPRS, Wi-Fi), supporting
7
Single Phase Hybrid Inverter Installation
Chapter 4 Installation
4.1 Unpacking
The inverter has been fully tested and strictly inspected before delivery, but damage may still occur during
transportation. Before unpacking, carefully check whether the product information on the purchase order and package
label is consistent, and whether the product package is in good condition. If any damage of package is detected,
contact the carrier or your dealer and provide photos of the damaged area, so as to receive the fastest and best service.
To keep the inverter idle for a long time, please place it in the original carton and protect it against moisture and
dust.
After taking the inverter out of the carton, please check the following:
(1) Whether the inverter remains in good condition;
(2) Whether you have received the User Manual and all of the connection parts and mounting parts;
(3) Whether the items you have received are free from damage and shortage;
(4) Whether the product information indicated in the nameplate on the inverter is consistent with that
indicated in the Purchase Order;
(5) Check with the List of Standard Deliverables below.
Standard deliverables for hybrid inverter:
8
Single Phase Hybrid Inverter Installation
1 Inverter 1
2 Mounting bracket 1
Quick-connect AC terminal and hexagon
3 2
screwdriver
4 Wiring terminal 1
5 DC connectors (pair) 2
8 M6 combination bolts 9
9 M4 combination screws 6
10 M6 nut 6
11 M6 flat washer 6
12 CT 1
Please check the above items carefully, and contact your dealer immediately if you have any questions.
9
Single Phase Hybrid Inverter Installation
(1) Install the inverter at such a height that allows the operator to observe the LED indicator lights of the
inverter easily.
10
Single Phase Hybrid Inverter Installation
≥1200
Fig. 4.3 Best Mounting Height
(2) Leave adequate space around the inverter to facilitate air circulation, and future handling of the
inverter. See Fig. 4.4.
≥ 500mm
≥ 500m m
≥ 500m m
0 mm
00
≥1
≥12 00mm
(3) To install more than one inverter, please keep a certain distance between the inverters and at the
top/bottom of the inverters (see Fig. 4.5), so as to facilitate heat radiation.
≥ 500mm ≥ 500mm
(4) The mounting surface should be upright (see Fig. 4.6). Install the inverter vertically or at a backward
11
Single Phase Hybrid Inverter Installation
tilt of ≤15° so as to facilitate heat radiation. Forward tilt, horizontal installation, upside-down installation,
backward tilt of >15° and sideways tilt are not allowed.
≤15°
12
Single Phase Hybrid Inverter Installation
D W
H
Fig. 4.8 Overall Dimension of Inverter
Step 1: The thickness of the wall for wall-mounted installation should be greater than or equal to 60mm. Using
a marker and a spirit level, mark the points where you need to drill the holes.
Step 2: Drill the holes (diameter: φ8; depth: ≥55mm) using a hammer drill, and then install M6×50 stainless-
steel expansion bolts.
13
Single Phase Hybrid Inverter Installation
Step 3: Fix the mounting bracket. Clean the holes, drive expansion bolts into the holes using a rubber hammer.
Tighten the nut to fix the tail of the bolt using a wrench, and then remove the nut, spring washer and flat washer. Fix
the wall mount bracket to the wall with the nuts using a tightening torque of 5N•m.
Step 3: Snap the bayonets of the inverter into the mounting bracket, and then press the inverter down to ensure
that its radiator groove fits well with the mounting bracket.
14
Single Phase Hybrid Inverter Installation
Step 4: Tighten M6×16 screws into the left and right holes of the radiator with a torque of 5 N•m so as to fix the
inverter onto the mounting bracket.
15
Single Phase Hybrid Inverter Electrical Connection
NOTE
➢ The connection modes between the N wire and PE wire and the GRID port and EPS port of the
inverter may be vary in different regions. Please consult your local regulatory requirements.
➢ The GRID port and EPS AC port of the inverter have built-in relays. When the inverter works in off-
grid state, the built-in GRID relay will be open; when the inverter works in on-grid state, the built-in
➢ When the inverter is powered on, the EPS AC port will be charged; if you need to perform
maintenance of the EPS load, please power off the inverter first in order to avoid electric shock.
NOTE
The following wiring method is applicable for Australia, New Zealand and South Africa.
16
Single Phase Hybrid Inverter Electrical Connection
NOTE
➢ Make sure the BACK-UP grounding wire is properly connected and secured; otherwise, the BACK-
UP function may fail in the case of power grid failure.
➢ The following wiring method is applicable for regions other than Australia, New Zealand and South
Africa.
17
Single Phase Hybrid Inverter Electrical Connection
5.2 PV Wiring
MC4 connectors are provided at DC input side of the hybrid inverter. Below are the connection steps.
1. Turn off the DC switch.
2. Connect the positive terminal and negative terminal of the PV module respectively to the PV+ port and PV-
port of the hybrid inverter. Make sure the actual input voltage and current fall within the allowable range.
● Maximum allowable PV input voltage: 600V (please consider changes in the voltage at the minimum
temperature).
● Maximum allowable PV input current: 16A.
5.3 AC Wiring
The AC output side is located at the bottom right of the hybrid inverter, containing an EPS port on the left and
a GRID port on the right (see Chapter 3 Product Introduction for detailed information).
Step 1: Unscrew the AC terminal, and then use an appropriate tool to remove it as shown below.
1
Step 2: Pass the cable through the rubber nut, sealing ring and threaded sleeve in turn. Connect the cable to the
corresponding terminal based on the polarity mark, and then tighten the threaded sleeve onto the AC terminal as
shown below:
18
Single Phase Hybrid Inverter Electrical Connection
2
Step 3: Connect the prepared AC terminal to the EPS port or GRID port of the hybrid inverter as shown below.
3
Note: 1. If you use the grid connection function only, connect the power grid to the GRID port of the inverter.
2. Do not connect the GRID port directly to the EPS port, as this could cause damage to the inverter.
3. Do not connect the power grid to the EPS port, as this could cause damage to the inverter.
2. Pass the cable through the rubber nut, sealing ring, threaded sleeve and waterproof cover in turn;
3. Crimp the battery cable (supplied in the original package) to the corresponding O-terminal,
4. and then connect the positive (negative) terminal of the battery to the positive (negative) end of the battery
Pressure nut
19
Single Phase Hybrid Inverter Electrical Connection
2. Power cable between the battery and the inverter: ≤1.5m in length, ≥ 16mm2 (5AWG) in cross sectional
area.
To use a lithium battery, you need to connect the BMS system of the lithium battery in the following steps:
1. Unscrew the rubber nut on the waterproof cover of the hybrid inverter;
2. Pass the LAN cable through the rubber nut, sealing ring, threaded sleeve and waterproof cover in turn;
3. Connect the RJ45 terminal of the LAN cable to the BMS port of the hybrid inverter;
4. Lock the waterproof cover with screws;
5. Screw the rubber nut reliably onto the waterproof cover.
Definition of RJ45 interface:
BMS
Pin 1
Pin 2
Pin 3
Pin 4 CAN-H
Pin 5 CAN-L
Pin 6
Pin 7 GND
Pin 8 WAKE-UP
20
Single Phase Hybrid Inverter Electrical Connection
Note: To use a lead-acid battery, you can jump directly to Section 5.5.2 without connecting the
Communication cable.
To use a lead-acid battery, you need to connect a temperature sensor to monitor the surface temperature of the
battery. Connect the temperature sensor in the following steps:
1. Unscrew the rubber nut on the waterproof cover of the hybrid inverter;
2. Pass the NTC cable through the rubber nut, sealing ring, threaded sleeve and waterproof cover in turn;
3. Connect the RJ45 terminal of the NTC cable to the DRY IO/NTC port of the hybrid inverter;
Definition of interface:
NTC DRY IO
Pin 1 NC OUT
Pin 2 NC OUT
Pin 3 GND
Pin 4 COM
Pin 5 COM
Pin 6 TEMP
Pin 7 NO OUT
Pin 8 NO OUT
21
Single Phase Hybrid Inverter Electrical Connection
Note: The probe of the temperature sensor used to monitor the ambient temperature of the lead-acid battery
should be shorter than 1.5m; if you use lithium battery instead, there is no need to install a temperature sensor.
5.6 CT Connection
The current transformer used on the inverter can help monitor the energy use of the home user. Below are the
CT connection steps.
1. Unscrew the rubber nut on the waterproof cover of the hybrid inverter;
2. Pass the CT cable through the rubber nut, sealing ring, threaded sleeve and waterproof cover in turn;
3. Connect the RJ45 terminal of the CT cable to the CT port of the hybrid inverter;
CA N2
CT cable: 5m in length, RJ45, standard LAN cable (8-pin connector at one end, connecting current
transformer at the other end). It can be extended by an extension cable to 15m if necessary. See the figure below.
22
Single Phase Hybrid Inverter Electrical Connection
Make sure the current transformer is installed in the correct direction as shown below.
Turn on the current transformer, and you will see an arrow indicating the direction of the current, as shown
above. Pass the L wire through the detection hole of the current transformer and then lock the current transformer.
Note: The direction of the arrow (from K to L) corresponds to the direction from load to grid in the L wire.
The current transformer should be placed in the distribution box.
The communication distance should be less than 30m.
Ender user can also monitor home consumption by smart meter. You can connect the communication cable of
the smart meter as described below.
Connect the smart meter to COM-2 (waterproof RS485 terminal) by plugging and tightening, as shown in the
figure below:
Note: You cannot install the smart meter and current transformer at the same time, but select either CT or
Meter as the sensor mode as described in Chapter 7.
3 4
910 1112
1 3 2 4
N On Grid
RS485
5 6 24 25 24 25
1 2
485+ 485-
COM-2
CHNT DDSU666
23
Single Phase Hybrid Inverter Electrical Connection
The hybrid inverter should be grounded reliably. The grounding wire should be ≥10mm². The grounding point
(GND) is shown below.
24
Single Phase Hybrid Inverter Commissioning
Chapter 6 Commissioning
6.1 Startup
6.2 Shutdown
To stop the operation of the hybrid inverter, please disconnect all energy sources to enter automatic shutdown.
Step 1: Turn off the PV switch.
Step 2: Turn off the BAT switch.
Step 3: Disconnect the power grid.
Both the LED light and LCD screen will be turned off.
Note: At the end of the above steps, please wait at least 5 minutes before proceeding to other operations.
25
Single Phase Hybrid Inverter Parameter Settings
On the LCD screen, you can check the current state of the system, energy flow diagram, operation information
and fault information, or set the language, charge and discharge priority and system time. The main screen shows
2. Waiting: The inverter enters self-check. If no fault is detected, the system will enter standby mode or
normal working mode.
3. On Grid: The inverter is working in on-grid state.
4. Fault: In case of a fault, the inverter will stop working and get into protected mode.
5. Programming: The inverter is currently undergoing program burning .
On the main screen, press the OK, ESC, Up or Down key to go to the Menu Info page. The Menu Info page is
shown below.
On the Menu Info page, press the Up or Down key to select a menu item. The page of each menu item is shown
below.
26
Single Phase Hybrid Inverter Parameter Settings
Here you can check the PV input voltage, current and power.
Here you can check the AC voltage, frequency and current as well as the meter power.
Here you can check the battery type, voltage, current and power as well as the battery SOC.
27
Single Phase Hybrid Inverter Parameter Settings
Here you can check the EPS voltage, frequency, current and power as well as the load power.
Here you can check the date & time, rated power, serial number, communication address and firmware version.
key to go to the
28
Single Phase Hybrid Inverter Parameter Settings
Here you can check daily and total energy generated by inverter, as well as daily battery charging/discharging
energy and total battery charging/discharging energy.
Here you can check the total number of fault logs as well as the fault code, date and time of each fault.
To access the Setting Info page, you need to enter the password. On the Menu Info page, select “Setting Info”
to go to the Input Password page.
29
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
Down key to
increase or reduce
the number.
Press the Up or
Down key to
increase or reduce
the number.
Press the Enter key.
Press the Up or
Down key to
increase or reduce
the number.
30
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
Down key to
increase or reduce
the number.
On the Setting Info page, you can set such parameters as the date & time, COM address, language, country and
priority. The Setting Info page is shown below.
31
Single Phase Hybrid Inverter Parameter Settings
key.
Press the Up or
Down key to
increase or reduce
the number.
Press the Up or
Down key to
increase or reduce
the number.
Press the Up or
Down key to
increase or reduce
the number.
32
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
Down key to
increase or reduce
the number.
Press the Up or
Down key to
increase or reduce
the number.
Press the Up or
Down key to
increase or reduce
the number.
key.
33
Single Phase Hybrid Inverter Parameter Settings
key.
Press the Up or
Down key to
increase or reduce
the number.
Press the Up or
Down key to
increase or reduce
the number.
34
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
Down key to
increase or reduce
the number.
key.
key.
35
Single Phase Hybrid Inverter Parameter Settings
key.
On the BAT & Meter Setting page, you can select the CT mode or a meter manufacturer. See the following
steps.
key.
Press the Up or
Down key to
select the CT
mode or a meter
manufacturer.
36
Single Phase Hybrid Inverter Parameter Settings
The battery parameters displayed on the Setting Info page depend on the battery manufacturer. If you select
“Lead-Acid”, the battery parameters will include Charge Voltage, Charge Current and Low Voltage. If you select a
lithium battery manufacturer, the battery parameters will include Charge Current and Discharge Current. You can
set the lead-acid battery parameters in the following steps.
key.
37
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
Down key to
select “Lead-
Acid” or a lithium
battery
manufacturer.
Press the Up or
Down key to
increase or reduce
the CV value.
Press the Up or
Down key to
increase or reduce
the CA value.
Press the Up or
Down key to
increase or reduce
the LV value.
38
Single Phase Hybrid Inverter Parameter Settings
key.
You can set the lithium battery parameters in the following steps.
key.
Press the Up or
Down key to
select a lithium
battery
manufacturer.
39
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
Down key to
increase or reduce
the maximum
charge current
value.
Press the Up or
Down key to
increase or reduce
the maximum
discharge current
value.
40
Single Phase Hybrid Inverter Parameter Settings
key.
Press the Up or
Down key to
associated with
the applicable
safety standards.
41
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
key.
Down key to
select “Enable” or
“Disable”.
42
Single Phase Hybrid Inverter Parameter Settings
Enable the off-grid mode and set the EPS voltage and frequency in the following steps.
Press the Up or
Down key to
select “Enable” or
“Disable”.
Press the Up or
Down key to
increase or reduce
value.
Press the Up or
Down key to
increase or reduce
value.
43
Single Phase Hybrid Inverter Parameter Settings
key.
Priority setting includes Battery First mode and Grid First mode.
key.
key.
44
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
Down key to
enable or disable
the AC charge
function.
Press the Up or
Down key to
select a time
interval.
Press the Up or
Down key to
enable or disable
period.
Press the Up or
Down key to
increase or reduce
45
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
Down key to
increase or reduce
SOC value.
Press the Up or
Down key to
increase or reduce
value.
key.
46
Single Phase Hybrid Inverter Parameter Settings
key.
Press the Up or
Down key to
select a time
interval.
Press the Up or
Down key to
enable or disable
period.
Press the Up or
Down key to
increase or reduce
47
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
Down key to
increase or reduce
the Stop
Discharge SOC
value.
Press the Up or
Down key to
increase or reduce
the Discharge
Power value.
key.
The auto test function will be available only if you select “Italy” on the Country Setting page. If you select any
48
Single Phase Hybrid Inverter Parameter Settings
other country, the Auto Test Setting page will indicate “Not Support!”
key.
key.
The Real value will vary with time once you start the auto test.
key.
When an item has been tested, you can see its trigger limit and test result.
The information is
updated
automatically.
When all items have been tested, you can see the auto test results as well as the trigger limits of all items.
49
Single Phase Hybrid Inverter Parameter Settings
The information is
updated
automatically.
This function can restore calibration data and configuration parameters to default parameters, as well as clear
energy data and historical fault data. Restore factory settings is as follows:
key.
Press the Up or
Down key to
enable or disable
the reset of
calibration data.
Press the Up or
Down key to
enable or disable
the clearing of
energy data.
50
Single Phase Hybrid Inverter Parameter Settings
Press the Up or
Down key to
enable or disable
the clearing of
fault history.
Press the Up or
Down key to
enable or disable
the reset of
configuration
data.
key.
51
Single Phase Hybrid Inverter System Debugging
K L A B P
J O
M Q
N R
C D E F G H I
Fig. 8-1
52
Single Phase Hybrid Inverter System Debugging
Position Description
A State
B Fault code
C RS485 communication
D CAN communication
E USB
F Smart meter
G Fault warning
H Date
I Time
J PV input
K PV power
L Hybrid inverter
N Battery power
O Grid
P Grid power
Q Critical load
R Load power
53
Single Phase Hybrid Inverter System Debugging
Fig. 8-2
Position Description
Green and yellow LED flashing: during the program burning process.
4 LCD screen
5 Return key
6 Enter key
7 Up key
8 Down key
In normal mode, the inverter may work in on-grid state or off-grid state.
On-grid State
When the hybrid inverter works in on-grid state, you can select a priority mode as needed. On the LCD screen,
you can only set one period for each priority mode; while on the App, you can set up to three periods for each priority
mode.
1. Load First: This is the default priority mode. When the system works in this mode, the PV energy will
54
Single Phase Hybrid Inverter System Debugging
be provided to the load first. When the PV energy is not sufficient to meet the load need, the battery will begin to
supply power. When the PV energy has fulfilled the load need, the excess power will be stored in the battery. If no
battery is connected or the battery is already full, the excess power will be supplied to the grid (if anti-reflux
protection is not enabled).
2. Battery First: When the system works in this mode, the battery will be charged first. To charge the
battery by AC power, you need to enable the AC Charge function and set the period and battery SOC. If the AC
Charge function is not enabled, the hybrid inverter will only charge the battery by PV energy. You can also set the
discharge power (maximum discharge percentage of the battery). In Battery First mode, the actual discharge energy
of the battery will not exceed the set percentage.
3. Grid First: When the system works in this mode, the PV energy will be supplied to the grid first. Users
can export energy to the grid during peak hours, and need to set the period and battery SOC. You can also set the
discharge power (maximum discharge percentage of the battery). In Grid First mode, the actual discharge energy of
the battery will not exceed the set percentage.
Off-grid State
In case of grid power failure, the system will automatically get into the off-grid state (you can disable this
function as instructed in Section 9.1).
In this state, the system will output voltage via the EPS port and power the load by the battery and solar PV
panel. Please note that the load at the EPS port should not exceed the maximum output power (6000W) of the inverter.
Note:
1. In Grid First mode or Battery First mode, you can only set one period on the LCD screen. If you need to set
more period,please use Solarman App.
2. To charge the battery by AC power, you need to enter your login password and then enable the AC Charge
function.
INVT hybrid inverter has an intelligent control system that can continuously monitor and adjust the state of the
system. In case of a system fault or device fault, the fault information will be displayed on the LCD screen and the
corresponding LED will be turned on.
Note:
A) See Section 10.1 for more fault information.
B) Some of the fault information is intended to remind you of possible internal faults of the inverter.
Do not turn off the power during the firmware upgrade progress. The system will automatically proceed to
working mode at the end of firmware upgrade.
55
Single Phase Hybrid Inverter System Debugging
Before activating the working mode, the system will get into the power-on self-test state. If no fault is detected,
the system will proceed to working mode; otherwise, it will get into the fault state.
When no fault is detected and a certain operating condition has not been met, the system will get into the standby
state.
To stop the operation of the hybrid inverter, please disconnect all energy sources to enter automatic shutdown.
Below are the shutdown steps:
1. Step 1: Disconnect the PV side;
2. Turn off the BAT switch;
3. Disconnect the power grid. Both the LED light and LCD screen will be turned off.
Note: At the end of the above steps, please wait at least 5 minutes before proceeding to other operations.
NOTE
At the end of the above steps, please wait at least 5 minutes before proceeding to other operations.
inverter first.
NOTE
To ensure normal operation of the inverter, please use Solarman App to set the parameters of the hybrid
inverter first.
Solarman is a mobile App that can communicate with the hybrid inverter via WiFi or GPRS. It allows you to:
1. Check the running data, software version and fault information of the inverter;
2. Set the grid parameters and communication parameters of the inverter;
3. Perform maintenance of the inverter;
4. Update the software version of the inverter.
56
Single Phase Hybrid Inverter System Debugging
For more functions of the Solarman App, please read its User Guide, which is available on
https://www.invt.com/.
57
Single Phase Hybrid Inverter System Maintenance
INVT hybrid inverter has undergone a series of tests before delivery. To maintain and extend the service life
of the inverter, you need to perform necessary routine maintenance in addition to using it in strict accordance with
this Manual.
Make sure the inverter is disconnected from the power supply. WARNING
58
Single Phase Hybrid Inverter System Maintenance
DANGER
•To perform maintenance of the inverter, please power off the inverter so as to avoid damage to the
inverter and avoid the risk of electric shock.
•When the inverter is powered off, it will take time for the internal components to discharge. Please wait
for the time period specified on the label until the inverter is fully discharged.
Step 1: Disconnect the on-grid AC circuit breaker of the inverter.
Step 3: Disconnect the EPS circuit breaker between the inverter and battery.
Step 4: Keep the inverter properly for future use, according to the storage environment requirements.
requirements of the laws and regulations of your country/region. Do not dispose of the inverter as household waste.
59
Single Phase Hybrid Inverter Troubleshooting
Chapter 10 Troubleshooting
If you are not professional at troubleshooting, contact your dealer for help. Please
wear personal protective equipment and power off the inverter before
WARNING troubleshooting!
This Chapter lists the faults by a list of fault codes, so that you can find troubleshooting actions quickly.
You can use the following methods to do troubleshooting. If they cannot help you, contact our After-sales
Service Center.
Please provide the following information to our After-sales Service Center so that we can help you more quickly.
⚫ SN of the inverter: ;
— Version 2: ;
⚫ Fault code: ;
Description of fault: .
60
Single Phase Hybrid Inverter Troubleshooting
61
Single Phase Hybrid Inverter Troubleshooting
Fault
No. Fault Type Fault Description Actions
Code
temperature
Abnormal ambient
06-04
temperature
Abnormal buck-boost
06-05
temperature
Open circuit of NTC
06-06
thermistor
Check whether the inverter and PV panel are
Insulation
Insulation monitoring grounded reliably. Power off the inverter for 5
5 monitoring 07-01
error minutes and then power it on again. If the fault
error
still exists, contact your dealer.
Driver Restart the inverter. If the fault still exists,
6 08-01 Driver error
error contact your dealer.
Communication error
09-01
from ARM to master DSP
Communication error
09-02
from master DSP to ARM Restart the inverter. If the fault still exists,
Communication error contact your dealer.
09-03
from ARM to salve DSP
Communication error
09-04
Communic from slave DSP to ARM
7
ation error Communication error
Restart the inverter. If the fault still exists,
09-05 between master and slave
contact your dealer.
chips - master chip failure
Communication error
Restart the inverter. If the fault still exists,
09-06 between master and slave
contact your dealer.
chips - slave chip failure
Communication error Restart the inverter. If the fault still exists,
09-07
between DSP and AFCI contact your dealer.
10-01 High static leakage current 1. If the fault occurs occasionally, it may
be caused by accidental abnormality of
10-02 Abrupt fault of 30mA
Leakage external cables. You can restart the inverter to
8 current 10-03 Abrupt fault of 60mA resume normal operation.
error 2. If the fault occurs frequently or lasts
10-04 Abrupt fault of 150mA long, check whether the PV string is grounded
reliably.
Relay 11-01 Open circuit of relay Restart the inverter. If the fault still exists,
9
failure 11-02 Short circuit of relay contact your dealer.
62
Single Phase Hybrid Inverter Troubleshooting
Fault
No. Fault Type Fault Description Actions
Code
Internal fan Restart the inverter. If the fault still exists,
10 12-01 Internal fan failure
failure contact your dealer.
Check whether the inverter and PV panel are
grounded reliably. Power off the inverter for 5
11 DCI error 14-01 DCI error of R-phase
minutes and then power it on again. If the fault
still exists, contact your dealer.
Inconsistent AC voltage
19-01
values
Inconsistent BUS voltage
19-02
values
Inconsistent ISO voltage
19-03
values
Consistenc Restart the inverter. If the fault still exists,
12 Inconsistent PV voltage
y error 19-04 contact your dealer.
values
19-05 Inconsistent GFCI
Bus voltage sampling
19-06
error
19-07 PV current sampling error
One-level under-voltage 1. If the fault occurs occasionally, it may be
31-01
of AC power caused by momentary abnormality of the
power grid.
The inverter will resume normal operation
One level over-voltage of
31-02 when the power grid gets back to normal.
AC power
2. If the fault occurs frequently, check whether
the power grid is connected properly.
Check whether the AC power is connected
31-03 No AC voltage
properly.
63
Single Phase Hybrid Inverter Troubleshooting
Fault
No. Fault Type Fault Description Actions
Code
31-10 Oscillation of grid voltage
One-level under-
33-01
frequency of AC power
One level over-frequency
33-02 1. If the fault occurs occasionally, it may
of AC power
be caused by momentary abnormality of the
Two-level under-
AC 33-03 power grid. The inverter will resume normal
frequency of AC power
14 frequency operation when the power grid gets back to
Two-level over-frequency
error 33-04 normal.
of AC power
2. If the fault occurs frequently, check
Startup under-frequency
33-05 whether the power grid is connected properly.
of AC power
Startup over-frequency of
33-06
AC power
Remote Remote shutdown Check whether any one is trying to shut down
15 37-01
shutdown instruction the inverter remotely.
38-01 Failure of PV string 1 Please turn off the inverter and open the input
and output switches, and turn on the inverter
16 AFCI error
38-02 Failure of PV string 2 again 5 minutes later. If the fault still exists,
contact your dealer.
Power-on Power-on self-test error of Please turn off the inverter and open the input
39-01
self-test PV string 1 and output switches, and turn on the inverter
17
error of Power-on self-test error of again 5 minutes later. If the fault still exists,
39-02
AFCI PV string 2 contact your dealer.
Please turn off the inverter and open the input
AutoTest and output switches, and turn on the inverter
18 41-01 AutoTest failure
failure again 5 minutes later. If the fault still exists,
contact your dealer.
Check whether the AC wires are connected
19 N-PE fault 42-01 N-PE voltage error
properly and reliably to the inverter.
Power-on
Please turn off the inverter and open the input
self-test
Leakage current sensor and output switches, and turn on the inverter
20 error of 43-01
failure again 5 minutes later. If the fault still exists,
leakage
contact your dealer.
current
Please turn off the inverter and open the input
PV string
and output switches, and turn on the inverter
21 detection 44-01 PV string failure
again 5 minutes later. If the fault still exists,
error
contact your dealer.
22 Auxiliary 45-01 Auxiliary power failure Please turn off the inverter and open the input
64
Single Phase Hybrid Inverter Troubleshooting
Fault
No. Fault Type Fault Description Actions
Code
power error and output switches, and turn on the inverter
again 5 minutes later. If the fault still exists,
contact your dealer.
Short
Check whether the correct wire is connected
23 circuit of 46-01 Short circuit of EPS
properly to the EPS port.
EPS
Fault
No. Fault Type Fault Description Displayed Information
Code
Please turn off the inverter and open the input
Low fan and output switches, and turn on the inverter
1 01-07 Internal fan 1
speed again 5 minutes later. If the fault still exists,
contact your dealer.
Check whether the smart meter is connected
04-01 Meter failure
Communic properly and supplies power normally.
ation of Communication error of Check whether the smart meter is connected
2 04-08
anti-reflux meter properly and supplies power normally.
meter Check whether the CT cable is connected
04-16 CT cable error
properly.
1. If the fault occurs occasionally, it may
be caused by momentary abnormality of the
Out-of- power grid. The inverter will resume normal
3 range grid 05-00 Out-of-range grid voltage operation when the power grid gets back to
voltage normal.
2. If the fault occurs frequently, check
whether the power grid is connected properly.
Short 06-01 Short circuit of PV2 Check whether the PV input is normal and
4 circuit of
06-02 Short circuit of PV1 whether the circuit is short.
PV
5 Overload 07-01 EPS overload Reduce the load at the EPS port.
65
Single Phase Hybrid Inverter Product Specifications
66
Single Phase Hybrid Inverter Product Specifications
Battery Parameters
DC input
Maximum input power (W) 4500 5400 6000 6900 7500 9000
Maximum input voltage (V) 600 600 600 600 600 600
MPPT channels 2 2 2 2 2 2
AC output
Rated output power (VA) 3000 3680 4000 4600 5000 6000
Maximum output power (VA) 3300 3680 4400 4600 5500 6000
EPS output
Maximum output power (VA) 3000 3680 4000 4600 5000 6000
Efficiency
67
Single Phase Hybrid Inverter Product Specifications
Protection
Anti-reverse / insulation
impedance / grounding Available Available Available Available Available Available
protection
Over-current & over-voltage
Available Available Available Available Available Available
protection
Battery soft start protection Available Available Available Available Available Available
General Specifications
Communication RS485 & CAN & Wi-Fi & 4G & LAN & Bluetooth
68
Hotline: +86 400 700 9997 E-mail: [email protected] Website: www.invt-solar.com