LogiTemp Full Gauge VX 1025E Plus Manual
LogiTemp Full Gauge VX 1025E Plus Manual
PN: 219828
REV 3/22
VX-1025e plus
VX1025EPLV01-01T(UL)-18921
Ver.01
DIGITAL REFRIGERATION CONTROLLER
WITH INTEGRATED MODULE FOR AN
ELECTRONIC EXPANSION VALVE
IP 65
FRONT
You can get this in the palm of VX-1025e plus
Fast Function Switch off Electronic IEB Programming Monitoring Degree Quick coupling
your handf FG Finder application. Freezing Lock Control Expansion in Series System of protection connection
Power
Functions Valve Backup
E251415
29 ± 0,5 mm
expansion valve (EEV) control. Thus, it is able to control superheating in order to improve energy efficiency
of refrigeration systems.
A compact and integrated controller that offers a complete solution for electronic expansion valve control.
In addition to superheating control, VX-1025e plus controls room temperature, defrost, fan, lighting and
Size of the Bay for
alarms. Economic setpoint and fast-freezing functionalities are available for ambient temperature control. In inserting the device
addition, there is a battery back-up dedicated to the expansion valve closure in the event of power outage,
replacing the solenoid valves used for these applications.
VX-1025e plus can be set as “Driver Only”, controlling just the electronic expansion valve and Panel (Front View) Panel
(Side View)
superheating of the refrigeration system.
This way, it can be used as part of a larger control system, interconnecting with other controllers. CAUTION
Features serial communication output to Sitrad software, real-time clock for defrost events programming,
WHERE THE INSTALLATION LOCATION NEEDS TO BE SEALED AGAINST LIQUIDS, THE OPENING IN WHICH THE CONTROLLER
tamper-proof function smart system and control functions shutdown mode. IS TO BE INSTALLED MUST BE NO MORE THA 70.5x29mm. THE SIDE CLASPS MUST BE SECURED IN SUCH A WAY AS TO CREATE
In addition, it features a digital filter that simulates mass increase in ambient sensor (S1), delaying response A TIGHT RUBBER SEAL THAT PREVENTS ANY LIQUIDS ENTERING THE OPENING AND THE CONTROLLER.
time due to thermal inertia and preventing unecessary compressor start-ups.
Product conforming to UL Inc. (United States and Canada). 6. CONNECTION DIAGRAM
2. SAFETY RECOMMENDATIONS SITRAD
- Read this manual before installing and using this controller; A B
- Make sure that the controller assembling is done properly; S1 S2 S3 D1
- Switch off power supply during controller’s installation;
- Use appropriate Personal Protective Equipment (PPE); 11 12 13 14 15 16 17 18 19 20
- Install the vinyl adehesive protector (included) in installations prone to water splashes, such as refrigerated
counters, etc. 1 2 3 4 5 6 7 8 9 10 21 22 23 24 25
- Installation procedures must be performed only by licensed technicians, subject to codes and regulations.
BLACK
P1 OUT
P1 VCC
GND
12Vdc
YELLOW
GREY / BLUE
ORANGE
RED
COMMON
3. APPLICATIONS
Display Cases, Walk-in, Reach-in, Undercounter, Beverage Display, Chiller, Blast Freezer. - +
A @! #
Source P1
Power AUX DEFR FAN COMP Power
4. TECHNICAL SPECIFICATIONS Supply 12Vdc Supply
Power supply 12Vdc +10% COM A B A B
Brief press: The current day, month, year, day of the week, hour and minutes 8.3.6 Turn Light On /Off
/ will be shown in sequence on the display. Using option [Lamp], in the access menu, it is possible to turn the lamp on /off manually if the AUX
output is configured as a lamp ([F60]=1) and the defrosting of the tray is not configured to use the
/ Press for 2 seconds: Adjust the Setpoints AUX output([F36]= 2).
Note: When switching on the lamp manually, the time for when the lamp will be switched off after the
< Brief press: Displays maximum and minimum temperatures / pressures. door is closed [F59] will be reset.
< Press for 2 seconds: When displaying saved information, wipes the entry. 8.3.7 Adjust date and time
The date and time can be adjusted using option [ClO,], from the access menu. This option is
<
<
Press for 4 seconds: Starts Manual Defrost.
accessed with the ;(Flatec) and confirmed with the /key.
Press for 2 seconds: Stops warning alarms. In the date and time setting mode, use the<or>keys to change the value and, when ready, press/
to store the value set. If the date entered is invalid, the message [ECLO] will appear on the display.
< Press for 4 seconds: Switches to displaying the measurements / processes
briefly. 8.3.8 View date and time
By briefly pressing the /key (brief press), the date and time set on the controller will be displayed.
; Enter the Access Menu The current date ([,--d]),month ([,--m]), year ([,--y]), day of the week ([day-]), hour and
;< Press for 5 seconds: Turns off control functions. minutes ([00:00]) will be shown in sequence on the display.
Note: The controller leaves the factory with the clock disabled. To enable it follow the directions in item
<and Enters select function. 8.3.7
Example:[day1] equals Sunday.
8.3.9 View the stage of the process, the time elapsed and other 8.3.12 Record of maximum and minimum temperatures / pressures
measurements Pressing the < key (short touch) during the temperature / pressure display, the message [rEg,] will
The temporary display mode can be activated through the access menu using option [Proc] or by appear and then the minimum and maximum temperatures and pressure recorded.
pressing the > key for 4 seconds until the message [Proc] is displayed. Note: If the < key is pressed during the display of the records, the values will be reset and the
The message on the current process will alternate with the length of time ([hh:mm]) that has elapsed message [rsEt] will be displayed.
for this stage.
Stages of the process: 8.3.13 Selecting the temperature or pressure units
[init]- Initializing the Electronic Expansion Valve; To select the units that the device will use, use function [,F01] with access code [,231] and
[dEL,]- Initial Delay (delay in starting up the instrument); press the / key. Next, select the required temperature unit [,=C,] or [,=F,] using the <> keys
[Fan,]- Fan-delay (delay caused by the fan); and confirm by pressing /. After that, select the required pressure unit [PSI,] or [Bar,] using the
[rEFr]- Refrigeration; <>keys and confirm by pressing /.
[Pre,]- Pre-Defrost; Whenever the units are changed, the function settings revert to the factory value and will therefore
[dEFr]- Defrost; need to be reset.
[dRAi]- Draining;
[Off,]- Control Functions are turned off;
[dVee]- The instrument is in driver mode. 8.4 Advanced Operations
8.4.1 Schedule Defrosting
In this viewing mode, it is also possible to view other measurements (if available) by pressing the > key
or the < (short touch), depending on the list: You can configure the defrosting schedule to be equally distributed accross the day by programming
the number of defrost cycles per day. To do this, you need to set the start of the defrosting as part of a
[Proc] - Process stage and time taken; defrosting schedule, setting [F28] to 5, and configuring functions [F37] to [F42] to determine the
[t-1,] - Temperature from the ambient sensor S1; number of defrost cycles per day and their starting times.
[t-2,] - Temperature from the Evaporator sensor S2; With this, the defrost schedule makes it possible to create a program from Monday to Friday, another
[t-3,] - Temperature from the Suction Line sensor S3; program for Saturday and another for Sunday.
[tSat] - Saturation Temperature; Example: If the program for Monday to Friday consists of a preferred time of 1 pm (and the number of
[Pres] - Pressure reading (before the amount of pressure is displayed, the configured unit of defrosting cycles is 4, with an interval of 6 hours), the defrost schedule will operate at 1:00 am, at 7:00
pressure is shown:[Psi,]or[bar,]); am, at 1:00 pm and 7:00 pm on each day.
[,SH,] - Superheating Temperature;
[Vee,] - Percentage that the Electronic Expansion Valve has been opened. MONDAY TO FRIDAY
The message related to the chosen measure will alternate with the measurement value.
Note: This display will remain on the display for 15 minutes or until the / key or the ;(short touch). 13:00 19:00 01:00 07:00
Note: In this mode, alarm messages and the preferred display ([F75]) will be ignored.
8.3.10 Function Lock
The function lock provides some extra safety when using this device. When it is enabled the normal and DEFROST DEFROST DEFROST DEFROST
economic setpoints and other parameters can be viewed, but are not able to be changed ([,f78]=2)
or you can just lock the device against changes to the control functions but allow the normal and Note: If the condition for the start of the defrost cycle is set by the defrosting schedule and the clock is
economic setpoints to be amendable ([,f78]=1). To block the functions, access the [LOC,] option not set or disabled, the start of the defrost cycle will be based on time.
from the access menu using the ;(Flatec) key and confirm it by pressing the /key.
The message [no,,] will be displayed if the lock is disabled. Now press and hold the > key for the
8.4.2 Electronic Expansion Valve in Manual Mode
time configured for this function [,f79].
When enabled, the message [LOC,][On,,]will displayed. It can only be enabled if the function You can switch the mode of the electronic expansion valve between manual and automatic, using the
[,f78] is set to 1 or 2. menu provided by the [modE] option.
To disable the lock, turn the controller off and on again with the > key pressed. Keep the key pressed In manual mode, the message [Man,]is displayed, alternating with the temperature and other
until the message [LOC,][OFF,] indicates that it has been unlocked (10 seconds). messages, and the electronic expansion valve remains fixed in the position configured in ([C19]-
Note: Regardless of the values of [,F78] and [,F79] you are always able to adjust the time and Initial Valve Opening).
hour. In automatic mode, the controller checks the reading of the temperature and pressure sensors and
calculates the value of the valve opening to ensure that the refrigeration system is a energy efficient as
8.3.11 Turn off control Functions possible.
Turning off the control functions allows the controller to be used as a temperature / pressure indicator In manual mode, the controller keeps the position of the VEE fixed according o the adjustment made.
only, with the control outputs and alarms off. This feature can be enabled or disabled using the function.
Shutdown of control functions [,F80]. When enabled, the control and alarm functions are turned off
8.4.3 Change the Parameters of the Controller
([CTRL][OFF,]) or turned on ([Ctrl][ON,,]) using the menu provided by the option [Ctrl].
When the control functions are turned off, the message [OFF,] will be displayed, alternating with the The function menu can be accessed through the access menu, option [Func] or by simultaneously
temperature and other messages. It is also possible to switch off and on the control functions by pressing < and > while the pressure is being displayed. To allow these parameters to be changed,
pressing the ; for 5 seconds. enter [,F01] by pressing/(short touch) and by using the < or > keys to enter the code 123 (one
Note: When restarting the control functions, the instrument will go to the initial stage [init]. hundred and twenty-three) and confirm with the /key. To change the other functions, navigate the
menu using the < or > keys and use the same method to adjust them. To exit the menu and return to
normal activity, press / (long press) until [----]is displayed.
Note: To access the settings for the parameters of the electronic expansion valve [,c01] to
[,C21] enter code 717 and confirm with /.
Note: If the function lock is on, the controller will display the message [LOC,] on the display,
when the < or > keys are pressed, and will not allow any adjustment to the parameters.
[,F15] Time for Economic Mode to begin (Monday to Friday) 00:00 24:00(Off) hh:mm 24:00(Off) 00:00 24:00(Off) hh:mm 24:00(Off)
[,F16] Time for Economic Mode to begin (Saturday) 00:00 24:00(Off) hh:mm 24:00(Off) 00:00 24:00(Off) hh:mm 24:00(Off)
[,F17] Time for Economic Mode to begin (Sunday) 00:00 24:00(Off) hh:mm 24:00(Off) 00:00 24:00(Off) hh:mm 24:00(Off)
[,F18] Maximum temperature in economic mode 0(Off) 999 minutes 120 0(Off) 999 minutes 120
[,F19] Fast Freezing Temperature Limit -50,0 60,0 °C -25,0 -58,0 140,0 °F -13,0
[,F20] Maximum Fast Freezing time 0(Off) 999 minutes 300 0(Off) 999 minutes 300
[,F21] Minimum time for compressor to be on 0(Off) 9999 seconds 0(Off) 0(Off) 9999 seconds 0(Off)
[,F22] Minimum time for the compressor to be off 0(Off) 9999 seconds 0(Off) 0(Off) 9999 seconds 0(Off)
[,F23] Length of time the compressor is on, if there is an error from the S1 sensor 0(Off) 999 minutes 20 0(Off) 999 minutes 20
[,F24] Length of time the compressor is off, if there is an error from the S1 sensor 0(Off) 999 minutes 10 0(Off) 999 minutes 10
[,F25] Control Action if there is an error in the superheating sensors 0(Off) 1(Man) - 1(Man) 1(Off) 1(Man) - 1(Man)
[,F26] Delay time when powering up the controller 0(Off) 999 minutes 0(Off) 0(Off) 999 minutes 0(Off)
CELSIUS (°C) FAHRENHEIT (°F)
Fun Description Min Max Unit Standard Min Max Unit Standard
[,F27] Defrost type (0 = resistance / 1 = hot gas / 2 = natural) 0 2 - 0 0 2 - 0
[,F28] Condition for starting 0(Off) 5 - 1 0(Off) 5 - 1
[,F29] Interval between defrosting periods if F28=1 or the Maximum time without defrosting if F=28 2, 3 or 4 1 9999 minutes 240 1 9999 minutes 240
[,F30] Additional time to the end of the first refrigeration cycle if F28=1 0(Off) 999 minutes 0(Off) 0(Off) 999 minutes 0(Off)
[,F31] Temperature of the evaporator (sensor S2) in order to begin defrost if F28= 2, 3 or 4 -50,0 105,0 °C -20,0 -58,0 221,0 °F -4,0
[,F32] Temperature Difference in order to start defrosting (S1-S2) if F28= 3 or 4 -50,0 105,0 °C 15,0 -58,0 221,0 °F 59,0
[,F33] Time to confirm the lower temperature (sensor S2) to start the pre-defrost setting if F28=2, 3 or 4 0(Off) 999 minutes 10 0(Off) 999 minutes 10
[,F34] Defrost when the controller is powered on 0(Off) 1(On) - 1(On) 0(Off) 1(On) - 1(On)
[,F35] Smooth Defrost if F27=0 10 100(Off) - 100(Off) 10 100(Off) - 100(Off)
[,F36] Enable Tray Defrost 0(Off) - 0(Off) -
DEFROST
2 0(Off) 2 0(Off)
[,F37] Number of Defrostings per day (Monday to Friday) if F28=5 1 12 - 4 0 12 - 4
[,F38] Time to start Defrost (Monday to Friday) if F28=5 00:00 23:59 hh:mm 06:00 00:00 23:59 hh:mm 06:00
[,F39] Number of Defrostings per day (Saturday) if F28=5 1 12 - 4 0 12 - 4
[,F40] Time to start Defrost (Saturday) if F28=5 00:00 23:59 hh:mm 06:00 00:00 23:59 hh:mm 06:00
[,F41] Number of Defrostings per day (Sunday) if F28=5 1 12 - 4 0 12 - 4
[,F42] Time to start Defrost (Sunday) if F28=5 00:00 23:59 hh:mm 06:00 00:00 23:59 hh:mm 06:00
[,F43] Length of pre-defrost (collecting in gas) 0(Off) 999 minutes 0(Off) 0(Off) 999 minutes 0(Off)
[,F44] Temperature of the Evaporator (S2 sensor) to finish the defrost -50,0 105,0 °C 30,0 -58,0 221,0 °F 86,0
[,F45] Ambient temperature (S1 sensor) required to end the defrost -50,0 105,0 °C 20,0 -58,0 221,0 °F 68,0
[,F46] Maximum time on defrost (for safety) 1 999 minutes 30 1 999 minutes 30
[,F47] Draining time (from water collected from defrosting) 0(Off) 999 minutes 1 0(Off) 999 minutes 1
[,F48] Fan operation mode 0 4 - 4 0 4 - 4
[,F49] Time fan is on if F48=0 or 4 1 999 minutes 2 1 999 minutes 2
[,F50] Time fan is turned off if F48=0 (automatic timed mode) 1 999 minutes 8 1 999 minutes 8
FAN
[,F51] Length of time door is open until fan is turned off F55=1 or 2 -1(Off) 9999 seconds 0 -1(Off) 9999 seconds 0
[,F52] Fan cut off due to high temperature in the evaporator (S2 sensor) -50,0 105,0 °C 50,0 -58,0 221,0 °F 122,0
[,F53] Temperature in the evaporator to switch the fan back on after draining -50,0 105,0 °C 2,0 -58,0 221,0 °F 35,6
[,F54] Maximum length of time until the fan is switched back on after drainage (fan-delay) 0(Off) 999 minutes 1 0(Off) 999 minutes 1
[,F55] Function mode of the digital input 0(Off) 12 - 2 0(Off) 2 - 0
[,F56] Length of time door is open for instant defrost if F55=1 or 2 0(Off) 999 minutes 30 0(Off) 999 minutes 30
DOOR
[,F57] Length of time door is open until fan and compressor are turned off F55=1 or 2 0(Off) 999 minutes 5 0(Off) 999 minutes 5
[,F58] Length of time door is closed until economic mode is activated if F55=1 or 2 0(Off) 999 minutes 0(Off) 0(Off) 999 minutes 0(Off)
[,F59] Length of time door is closed until light is switched off is F55=1 or 2 and F60=1 0(Off) 999 minutes 2 0(Off) 999 minutes 2
[,F60] AUX output mode 0 2 - 1 0 2 - 1
[,F61] Low ambient temperature alarm (S1 sensor) -50,0 105,0 °C -50,0 -58,0 221,0 °F -58,0
[,F62] High ambient temperature alarm (S1 sensor) -50,0 105,0 °C 105,0 -58,0 221,0 °F 221,0
[,F63] Time to confirm the alarm by room temperature (S1) 0(Off) 999 minutes 0(Off) 0(Off) 999 minutes 0(Off)
ALARMS
[,F64] Room temperature alarm delay (power up) 0(Off) 999 minutes 10 0(Off) 999 minutes 10
[,F65] Length of time door is open to trigger alarm 0(Off) 999 minutes 5 0(Off) 999 minutes 5
[,F66] Maximum time compressor can be on without reaching the setpoint 0(Off) 999 hours 0(Off) 0(Off) 999 hours 0(Off)
[,F67] Trigger for alarm when defrosting is over based on time 0(No) 1(Yes) - 1(Yes) 0(No) 1(Yes) - 1(Yes)
[,F68] Enable buzzer 0(Off) 1(On) - 0(Off) 0(Off) 1(On) - 0(Off)
[,F69] Intensity of the digital filter on the ambient temperature sensor (S1 sensor) (Rising) 0(Off) 20 seconds 0(Off) 0(Off) 20 seconds 0(Off)
[,F70] Intensity of the digital filter on the ambient temperature sensor (S1 sensor) (Descending) 0(Off) 20 seconds 0(Off) 0(Off) 20 seconds 0(Off)
SENSORS
[,F71] Displacement of the values from the ambient sensor (S1 sensor) -20,0 20,0 °C 0,0 -36,0 36,0 °F 0,0
[,F72] Displacement of the values from the evaporator sensor (S2 sensor) -20,0 20,0 °C 0,0 -36,0 36,0 °F 0,0
[,F73] Displacement of the values from the suction line sensor (S3 sensor) -20,0 20,0 °C 0,0 -36,0 36,0 °F 0,0
[,F74] Displacement of the values (Offset) for the pressure transducer P1 -50 50 PSI 0 -3,4 3,4 BAR 0,0
[,F75] Preferred Indicator 1 7 - 1 1 7 - 1
[,F76] Ambient Temperature (S1 sensor) value locked in during defrosting 0 2 - 1 0 2 - 1
FUNCTIONS
[,F77] Maximum length of time that the temperature is locked during defrosting 0(Off) 999 minutes 15 0(Off) 999 minutes 15
[,F78] Function Lock Mode 0 2 - 0 0 2 - 0
[,F79] Function Lock Period 15 60 seconds 15 15 60 seconds 15
[,F80] Shutdown of control functions 0(Off) 2 - 0(Off) 0(Off) 2 - 0(Off)
[,F81] Address of the instrument on the RS-485 network 1 247 - 1 1 247 - 1
[,c07] Integral Time (Ti) - Low Superheating Protection 1 500 seconds 20 1 500 seconds 20
[,c08] Setpoint - LOP Protection (Low evaporation temperature) -50,0(Off) c10 °C -50,0(Off) -58,0(Off) c10 °F -58,0(Off)
[,c09] Integral Time (Ti) LOP Protection (Low evaporation temperature) 1 500 seconds 20 1 500 seconds 20
[,c10] Setpoint - MOP Protection (High evaporation temperature) c08 105,0(Off) °C 105,0(Off) c08 221,0(Off) °F 221,0(Off)
[,c11] Integral Time (Ti) - MOP Protection (High evaporation temperature) 1 500 seconds 20 1 500 seconds 20
[,c12] Time to verify the protection alarms (LoSH, LOP, MOP) 0(Off) 9999 seconds 60 0(Off) 9999 seconds 60
[,c13] State of the compressor in the event of protection alarms being triggered (ASHL, ALOP, AMOP) 0 7 - 0 0 7 - 0
[,c14] Time until the compressor switches on again after protection alarms are triggered (ASHL, ALOP, AMOP) 0(Off) 999 minutes 3 0(Off) 999 minutes 3
[,c15] Total number of steps for the valve 20 550 - 500 20 550 - 500
[,c16] Operating Speed (steps per second) 25 90 steps/ sec. 30 25 90 steps/sec. 30
[,c17] Minimum Valve Opening 0,0 c18 % 0,0 0,0 c18 % 0,0
[,c18] Maximum Valve Opening c17 100,0 % 100,0 c17 100,0 % 100,0
[,c19] Initial Valve Opening c17 c18 % 50,0 c17 c18 % 50,0
[,c20] Time valve is used after initial opening 0(Off) 300 seconds 20 0(Off) 300 seconds 20
[,c21] Time valve is used after initial opening after defrosting 0(Off) 3000 seconds 0(Off) 1 3000 seconds 0(Off)
8.5.1 Description of the Parameters F17 - Time for Economic Mode to begin (Sunday):
Time when the economic setpoint [SP-E] will be activated on Sundays.
This function can be turned off by setting it to the maximum value [OFF,].
F45 - Temperature of the Ambient Sensor (S1 sensor) to finish the defrost: F60 - AUX output mode:
If the ambient temperature (sensor S1) reaches the set value, the defrost cycle will be halted, i.e. [,,,0] - Output switched off;
Temperature controlled. [,,,1] - Light switching;
[,,,2] - Alarm switching.
F46 - Maximum time on defrost (for safety): Note: If it is set up as an alarm switch, the AUX output will be turned on in the event of the following
This function adjusts the maximum duration of a defrost cycle. If the defrosting is not complete, during alarms: open door, high / low ambient temperature, compressor on without reaching the setpoint,
this period, according to the temperature, a dot will begin flashing in the lower right corner of the display external alarm (digital input), low superheating, MOP, LOP, Internal Energy Backup error or error in the
(if it's enabled in [F67]), indicating that the time set for the defrost has ended by the required electronic expansion valve.
temperature has not been reached. This can happen when the temperature set is too high, the time limit
is insufficient, the S2 sensor is disconnected or it isn't in contact with the evaporator. F61 - Low ambient temperature alarm (S1 sensor):
This is the ambient temperature (S1), below which the instrument will trigger the low temperature
F47 - Draining time (from water collected from defrosting): alarm. The differential for switching off the alarm is set in 0.1 ° C / 0.1 ° F. During the Fast Freezing
Time required for removing excess water, i.e. for the last drops of water to drain from the evaporator. operation, the low temperature alarm is deactivated. When this process is over it is reactivated when
During this period, all outputs remain switched off. This function can be turned off by setting it to the the temperature is no longer within the range of the alarm.
minimum value [OFF,].
F62- High ambient temperature alarm (S1 sensor):
F48 - Fan operation mode: This is the ambient temperature (S1), above which the instrument will trigger the temperature alarm.
[,,,0]- Automatic according to time: the fan will be on when the compressor is on. When the The differential for the alarm to switch off is fixed at 0.1 ° C / 0.1 ° F. This alarm takes into account the
compressor is off, the fan will oscillate according to the times set in [F49] and [F50]; temperature shown on the display and is therefore determined by the temperature reading locked
[,,,1] - Automatic according to temperature: When the compressor is switched on, the fan stays on. during the defrost cycle [F76].
With the compressor off, the fan turns on when the temperature is higher than the setpoint + 60% of the
hysteresis and turns off when the temperature is lower than the setpoint + 20% of the hysteresis; F63- Time to confirm the alarm by room temperature (S1):
[,,,2]- Continuous: the fan is always on; This is the length of time, during which the ambient temperature alarm (low or high) will be inactive,
[,,,3] - Dependent: the fan operates together with the compressor; even if the conditions exist to trigger it.
[,,,4] - For a period of time after the compressor is turned off: after turning off the compressor, the
fan will remain on for the time set in [F49]. F64- Room temperature alarm delay (power up):
Note1: Modes 0 and 1 will only switch the fan on if the temperature of the S2 sensor is lower than During this time the alarm remains off while waiting for the system to go back to an operating mode. The
the temperature of the S1 sensor. (low or high) ambient temperature alarms are enabled after this time has elapsed or the setpoint
Note2: Mode 1 will activate the fan only if the temperature of sensor S2 is lower than the temperature has been reached.
configured setpoint.
F65- Length of time door is open to trigger alarm:
F49 -Time fan is on if F48=0 or 4 When the door is opened, the message [Open] appears on the display and the door open timer
This is how long the fan is on for. starts. If this time is longer than the time that is set for this function, the alarm will be triggered
F50 - Time fan is turned off if F48=0 (automatic timed mode): F66- Maximum time compressor can be on without reaching the setpoint:
This is how long the fan is off for. The alarm is triggered if the compressor remains on without reaching the setpoint, for a longer time
than the length specified in this function.
F51 - Length of time door is open until fan is turned off F55=1 or 2:
This is the length of time that the fan will continue to run after the door is opened. If you set a minimum
F67-Trigger for alarm when defrosting is over based on time:
value of [OFF,], the fan will not switch off if the door is opened. If you set a value of r [,,,0], the fan
When the defrost cycle has been running for the length of time set, but has not reached the temperature
will switch off immediately if the door is opened.
set, the user is notified via a flashing dot in the lower right corner of the display ([,,,.]).
F52 - Fan cut off due to high temperature in the evaporator (S2 sensor):
This is intended to disconnect the evaporator fan when the ambient temperature is not within the design F68- Enable Buzzer:
range for the refrigeration device, avoiding high temperatures and suction pressures that could Enables or disables the internal buzzer to sound alarms.
damage the compressor. If the evaporator temperature exceeds the set value, the fan is turned off and
will be restarted at a fixed hysteresis of 2 ° C (3.6 ° F). This is a useful function to use when, for example, F69- Intensity of the digital filter on the ambient temperature sensor (S1 sensor) (Rising):
a refrigerator is used that has been idle for days or when restocking units or counters with products. F70- Intensity of the digital filter on the ambient temperature sensor (S1 sensor) (Descending):
The value set by these functions represents the time (in seconds) in which the temperature may vary
F53 - Temperature in the evaporator to switch the fan back on after draining: 0.1ºC / 0.1 ° F either up or down.
After drainage is complete, it starts a fan-delay cycle. The compressor will start up immediately,
because the temperature in the evaporator is high, but the fan will only start after the temperature in the Note: A typical use for this type of filter is in freezers for ice cream and frozen foods. When the door is
evaporator falls below the set value. This function is used to remove the heat in the evaporator after a opened, a quantity of hot air will fall directly on the sensor, causing a rapid rise in the temperature
defrost cycle, to ensure it is not opened up immediately to the ambient temperature. reading and, often, activating the compressor unnecessarily.
F71- Displacement of the values from the ambient sensor (S1 sensor): C08- Setpoint - LOP Protection (Low evaporation temperature):
F72- Displacement of the values from the evaporator sensor (S2 sensor): When the evaporation temperature is below this value, the electronic expansion valve (VEE) will gradually
F73- Displacement of the values from the suction line sensor (S3 sensor): open to increase the evaporation temperature of the system. This process will continue until the
F74- Displacement of the values (Offset) for the pressure transducer P1: evaporation temperature reaches the value set by this function.
This allows you to compensate for possible deviations in the reading of the sensor / transducer, due to
changing the sensor or changing the cable length. C09- Integral Time (Ti) - LOP Protection (Low evaporation temperature):
Time required to correct the difference between the recorded superheating and its setpoint, as a constant
F75-Preferred Indicator: value, when the stabilized evaporation temperature is below the LOP protection setpoint.
Sets a preference for what is shown on the display:
[,,,1] : Temperature from the ambient sensor S1; C10- Setpoint - MOP Protection (Low evaporation temperature):
[,,,2] : Temperatura do sensor do evaporador S2; When the evaporation temperature is above the value set for this function, the controller will gradually
[,,,3] : Temperature from the Suction Line sensor S3; close the electronic expansion valve (VEE) to keep the evaporation temperature below the set value. This
[,,,4] : Pressure; is intended to ensure that when superheating is very low, liquid does not flow back into the compressor.
[,,,5] :Superheating Temperature;
Note: Hysteresis for the parameter [,,C8] and [,C10] is set 2°C (3,6°F).
[,,,6] : Percentage that the Electronic Expansion Valve has been opened;
[,,,7] : Current Setpoint Value (normal or economic).
C11- Integral Time (Ti) - MOP Protection (Low evaporation temperature):
Note 1: When the device is operating in driver mode (c01=[On,,]), options 1,2 and 7 must not be
Time required to correct the difference between the recorded superheating and its setpoint, as a constant
selected, otherwise the message [info] will be shown on the display, indicating that it is not
value, when the stabilized evaporation temperature is above the MOP protection setpoint.
possible to view any information.
C12- Time for checking the protection alarms (LoSH, LOP, MOP):
F76- Ambient Temperature (S1 sensor) value locked in during defrosting: This is the length of time, during which the protection alarm (LoSH, LOP, MOP) will be inactive, even if the
[,,,0] : Temperature Reading from the ambient sensor S1 conditions exist to trigger it.
[,,,1] : Reading locked in - last temperature before defrosting
[,,,2] : Display “[deFr]'' C13- State of the Compressor in the event of protection alarms being triggered (ASHL, ALOP,
This function is intended to prevent the display reflecting an increase in the ambient temperature due to AMOP):
defrosting. [,,,0]- Compressor will not switch off when ASHL, ALOP or AMOP alarms are triggered;
[,,,1]- Compressor will switch off when ASHL alarm is triggered;
F77- Maximum length of time that the temperature is locked during defrosting: [,,,2]- Compressor will switch off when ASHL or ALOP alarm is triggered;
During a defrost cycle, either the last temperature measured during the refrigeration cycle or the [,,,3]- Compressor will switch off when ASHL or AMOP alarm is triggered;
message [deFr] will be kept on the display. The display will be released when the temperature [,,,4]- Compressor will switch off when ALOP alarm is triggered;
shown is reached again or the time set for this function has been exceeded, after the start of the next [,,,5]- Compressor will switch off when ALOP or AMOP alarm is triggered;
refrigeration cycle (whichever comes first). If set to the value [Off,], the temperature display will be [,,,6]- Compressor will switch off when AMOP alarm is triggered;
frozen only while defrosting. [,,,7]- Compressor will switch off when either the ASHL, ALOP or AMOP alarms is triggered.
F78- Function Lock Mode: C14-Time until the compressor switches on again after protection alarms are triggered (ASHL,
Enables and configures the Function Lock (see item 8.3.10). ALOP, AMOP):
[,,,0]: Function Lock can't be enabled This is the length of time that the compressor remains off after an alarm is triggered, according to the
[,,,1]: Partial lock can be enabled, whereby the control functions are locked but the setpoint can still defined option [c13].
be adjusted.
[,,,2]: Functions can be completely locked. C15- Total number of steps for the valve:
This functions sets the specific number of steps that the electronic expansion valve (EEV) will use.
F79- Function Lock Period:
Sets the time in seconds after the command that the functions will be locked. C16- Operating Speed (steps per second):
[,,15]- [,,60] Time in seconds after the command that the functions will be locked. This functions sets the operating speed according to the specifications of the electronic expansion valve
(EEV).
F80- Turns Off Control Functions:
Allows the control functions to be turned off (see item 8.3.11). C17- Minimum Valve Opening:
[Off,] : Does not allow the control functions to be turned off. This is the smallest percentage that the electronic expansion valve will open.
[,,,1] : Only allows control functions to be turned on or off if the functions are unlocked.
[,,,2] : Allows control functions to be turned on or off even if the functions are locked. C18- Maximum Valve Opening:
This is the largest percentage that the electronic expansion valve will open.
F81- Address of the instrument on the RS-485 network:
C19- Initial Valve Opening:
Address of the instrument on the RS-485 network that enables it to communicate with the Sitrad
This function defines the percentage that the electronic expansion valve will open when control begins.
software.
Note: You may not have any device on the network with the same address. C20- Time valve is used after initial opening:
This is the maximum time that the electronic expansion valve will be opened as set in the [c19] function.
Electronic Expansion Valve configuration functions [c01] to [c21] (displayed if [F01]=
717) C21-Time valve is used after initial opening after defrosting:
This is the maximum time that the electronic expansion valve will be opened as set in the [c19] function,
C01- Controller is in Driver mode: after a defrost cycle.
[Off,]: The device is responsible for controlling temperature, alarms and superheating.
[On,,]: The device is only controlling superheating and alarms. 9. PID CONTROLLER
When Driver mode is active, the device turns off the temperature control functions and only controls The PID controller is made up of a combination of three control actions: Proportional action (P), Integral
superheating and alarms. When the device is turned on, the COMP output will be activated, indicating action (I) and Derivative action (D). Each action receives a weighting (adjustable via parameters) which
that the controller has been powered on. represents a gain or adjustment time. This enables the PID to perform better when controlling the process.
The FAN output will be turned on after the controller initialization stage, which indicates that the device Any control action is limited by the quality and capacity of the existing actuators in the process.
is ready to receive an external signal for the electronic expansion valve to begin controlling P - Proportional gain (Kp) - The use of proportional action in a control system enables the difference
superheating. A signal (digital input) from an external controller activates the electronic expansion (error) between the desired output (reference, setpoint) and the current value of the process, to be
valve, which will then control superheating. reduced. The proportional gain speeds up process's response, however, the increased gains can result in
The DEFR output will be activated when the instrument receives an external signal and the electronic control oscillating.
expansion valve is ready to control superheating. The AUX output will be activated if the following I - Integral time (Ti) - The integral action has an energy storage function, which allows it to remove the
alarms go off: low superheating, MOP, LOP, Internal Energy Backup error or error in the activation of the error between the reference and the output. It accumulates the error at a '' Ti '' rate, and attempts to reduce
electronic expansion valve. it to zero. Low Ti values can cause the control to oscillate, however, long Ti times tend to slow down the
Note: When DRIVER mode is on, only the VEE indication LED can be activated. process. Integral action must not be used on its own.
D - Derivative time (Td) - The use of derivative action enables the process's response time to be
C02- Enable Internal Energy Backup (IEB): increased and reduces oscillation, as it tries to anticipate the process's behavior. Low Td values tend to
[Off,] :The Internal Energy Backup (IEB) is not being used. You must therefore use a solenoid valve reduce oscillation
to ensure the fluid line is closed if there is a power cut.
[On,,] :The internal energy backup system (IEB) will be available, which helps by closing the SUMMARY TABLE - GENERAL GUIDANCE*
electronic expansion valve if there is a power cut.
PID PARAMETER OVERSHOOT STABILIZATION ERROR
C03- Proportional Increase (Kp): (peakl) TIME (The difference
(delay in stabilizing the between the setpoint
Determines the proportional increase based on the PID Control Algorithm. and the sensor)
controller)
[UEE,] Percentage that the Electronic Expansion Valve has been opened 12. CONNECTING CONTROLLERS, RS-485 SERIAL INTERFACE
AND COMPUTER
[t-1,] Temperature sensor 1
®
A B
A
B B
A
A B
A
B B
A
A B
A
B
External
B A B A link
[DEFr] Temperature locked on defrosting cycle
MT-530 super
B A
MT-530 super
Earth
Instrumento
[,,,,.] Indicates that the final defrosting temperature has not been reached *WIRING BLOCK FOR SERIAL COMMUNICATIONS
It is used to connect more than one device to the Interface. The wires must be
connected as follows: Terminal A of the device is connected to terminal A of the
Information unavailable - check the parameter. RS-485 Serial Interface
[inFo] Preferred indicator (see parameter [F75])
wiring block, which in turn, must be connected to terminal A of the Interface.
Repeat the process for terminals B and , being the cable loop (optional Hardware used to connect Full Gauge
Control devices to Sitrad®.
ground). The cash dispenser terminal must be connected to the respective
Tray is defrosting - pre-defrost and draining
@Flashing
Led stages
terminals of each instrument.
*Sold separately
13. OPTIONAL ITEMS - SOLD SEPARATELY
$piscante
Led Fast Freezing Mode Indicated
EasyProg - version 2 or higher
This is an accessory, whose main function is to store the parameters of the controllers. You can load new
[Man,] The Electronic Expansion Valve is operating in Manual Mode parameters from a controller at any time, and download them to a production line (from the same
controller), for example.
The Electronic Expansion Valve is closed as there is no
[8888] electricity
It has three types of connection for loading or clearing parameters:
- Serial RS-485: Connect it to the controller using the RS-485 network (only controllers that can access
RS-485).
[LOC,][On,,] Function Lock - USB: If connected to the computer by a USB port, it can use Sitrad's Program Editor.
- Serial TTL: The controller can connect directly to
[LOC,][OFF,] Functions Unlocked EasyProg by a Serial TTL connection.
10.3 Errors
14. ANNEXES - Reference Diagrams
[Ert1] Error in temperature sensor 1 CONTROLLER
Diagram V
X
[Ert2] Error in temperature sensor 2
[EiEb] Error in the Internal Energy Backup (IEB) system DIAGRAM VI PANEL
CONTROLLER
[ECAl] Contact Full Gauge
ENVIRONMENTAL INFORMATION
Packaging:
Full Gauge products use packaging made from entirely recycled materials. Please dispose of it through specialized
recyclers.
Product:
The components used in Full Gauge controllers can be recycled and reused if they are dismantled by specialists.
Disposal:
Do not burn or throw controllers in the domestic waste, once they have reached the end of their working life. Follow the
current legislation applicable to your area in relation to disposing of electronic waste. If you have any questions, contact Full
Gauge Controls.
Products manufactured by Full Gauge Controls, from May 2005, have a warranty period of 10 (ten) years direct from the
factory and 01 (one) year from accredited retailers, starting from the consignment date on the sales invoice. After this year,
the warranty will continue to be honored for purchases from retailers if the device is sent directly to Full Gauge Controls. This
period is valid in Brazil. Other countries provide a guarantee for 2 years. The products are guaranteed in the event of a
manufacturing fault that makes them unsuitable or inappropriate for the uses to which they were intended. The warranty is
limited to the maintenance of devices manufactured by Full Gauge Controls, regardless of any other form of costs, such as
any indemnity due to damage caused to other equipment.
WARRANTY - FULL GAUGE CONTROLS
WARRANTY EXCEPTIONS
The Warranty does not cover transport and / or insurance costs for sending products believed to have defects or to have
malfunctioned to Technical Support. The following events are also not covered: natural wear of parts, external damage
caused by falls or improper packing of products.
LOSS OF COVER
The product will automatically no longer be covered if:
-The instructions for use and assembly contained in the technical description and installation procedures listed in the
NBR5410 standard are not observed;
- It is subjected to conditions beyond the limits specified in its technical description;
- If it is opened up or repaired by a person who is not part of Full Gauge's technical team;
- The damage which has taken place was the result of a fall, blow or impact, water damage, electrical surge or atmospheric
discharge.
PN: 219828
REV 3/22