0% found this document useful (0 votes)
33 views11 pages

LogiTemp Full Gauge VX 1025E Plus Manual

Uploaded by

Oscar Okanto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
33 views11 pages

LogiTemp Full Gauge VX 1025E Plus Manual

Uploaded by

Oscar Okanto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

LogiTemp™

Electronic Controller System


Operations Manual

(Full Gauge Version VX-1025E Plus)

PN: 219828
REV 3/22
VX-1025e plus

VX1025EPLV01-01T(UL)-18921
Ver.01
DIGITAL REFRIGERATION CONTROLLER
WITH INTEGRATED MODULE FOR AN
ELECTRONIC EXPANSION VALVE
IP 65
FRONT
You can get this in the palm of VX-1025e plus
Fast Function Switch off Electronic IEB Programming Monitoring Degree Quick coupling
your handf FG Finder application. Freezing Lock Control Expansion in Series System of protection connection
Power
Functions Valve Backup
E251415

1. DESCRIPTION 5. INSTALLATION - PANEL AND ELECTRICAL CONNECTIONS


The VX-1025e plus is a digital temperature controller for refrigeration with a digital output for electronic
71 ± 0,5 mm

29 ± 0,5 mm
expansion valve (EEV) control. Thus, it is able to control superheating in order to improve energy efficiency
of refrigeration systems.
A compact and integrated controller that offers a complete solution for electronic expansion valve control.
In addition to superheating control, VX-1025e plus controls room temperature, defrost, fan, lighting and
Size of the Bay for
alarms. Economic setpoint and fast-freezing functionalities are available for ambient temperature control. In inserting the device

addition, there is a battery back-up dedicated to the expansion valve closure in the event of power outage,
replacing the solenoid valves used for these applications.
VX-1025e plus can be set as “Driver Only”, controlling just the electronic expansion valve and Panel (Front View) Panel
(Side View)
superheating of the refrigeration system.
This way, it can be used as part of a larger control system, interconnecting with other controllers. CAUTION
Features serial communication output to Sitrad software, real-time clock for defrost events programming,
WHERE THE INSTALLATION LOCATION NEEDS TO BE SEALED AGAINST LIQUIDS, THE OPENING IN WHICH THE CONTROLLER
tamper-proof function smart system and control functions shutdown mode. IS TO BE INSTALLED MUST BE NO MORE THA 70.5x29mm. THE SIDE CLASPS MUST BE SECURED IN SUCH A WAY AS TO CREATE
In addition, it features a digital filter that simulates mass increase in ambient sensor (S1), delaying response A TIGHT RUBBER SEAL THAT PREVENTS ANY LIQUIDS ENTERING THE OPENING AND THE CONTROLLER.
time due to thermal inertia and preventing unecessary compressor start-ups.
Product conforming to UL Inc. (United States and Canada). 6. CONNECTION DIAGRAM
2. SAFETY RECOMMENDATIONS SITRAD
- Read this manual before installing and using this controller; A B
- Make sure that the controller assembling is done properly; S1 S2 S3 D1
- Switch off power supply during controller’s installation;
- Use appropriate Personal Protective Equipment (PPE); 11 12 13 14 15 16 17 18 19 20
- Install the vinyl adehesive protector (included) in installations prone to water splashes, such as refrigerated
counters, etc. 1 2 3 4 5 6 7 8 9 10 21 22 23 24 25
- Installation procedures must be performed only by licensed technicians, subject to codes and regulations.

BLACK
P1 OUT
P1 VCC
GND
12Vdc

YELLOW
GREY / BLUE
ORANGE
RED

COMMON
3. APPLICATIONS
Display Cases, Walk-in, Reach-in, Undercounter, Beverage Display, Chiller, Blast Freezer. - +
A @! #
Source P1
Power AUX DEFR FAN COMP Power
4. TECHNICAL SPECIFICATIONS Supply 12Vdc Supply
Power supply 12Vdc +10% COM A B A B

-14 to 850 psi -1 to 58.6 bar EEV


Pressure control range
(operating range of the configurable sensor) Compatibility EEV / Models S1, S2 and S3 - Temperature Sensors
Pressure sensor input 4-20mA SB88, SB89, SB90, SB91, SB92, SB93, SB94, P1 - Pressure Transducer
Temperature control range SB108, SB110, SB114, SB118, SB124, SB130, D1 - Digital Input (Dry Contact)
-50 to 105°C / -58 to 221°F
SB132. EEV - Electronic Expansion Valve
Average consumption 600 mA
Pressure resolution 0,1 psi / 0,1 bar A
Temperature resolution Electrical connection of EEV EEV
0,1°C / 0,1°F
pressure transducer P1
Working temperature -20 to 60°C / -4 to 140°F
VCC: 12Vdc OUT: 4~20mA A
Working Humidity 10 a 90% RH (without condensation) SB68 BLACK
RED
Digital input Configurable dry contact type SB69 BROWN GREEN OR WHITE
Degree of protection IP 65 (front)
Maximum Sizes (mm) 76 x 34 x 94 (WxHxD)
B B
Bay Size (mm) X = 71±0,5 Y= 29±0,5 (See Diagram 5) NEW CONNECTION SYSTEM (QUICK CONNECTOR):
PUSH-IN WIRE CONNECTORS - QUICKLY
Output capacity
(UL certificate 60730)
120-240 Vac, 12 A Resistive, 100k cycles
120-240 Vac, 8 A General Use, 100k cycles
COMP 240 Vac, 1 HP, 100k cycles
120 Vac, 1/2 HP, 100k cycles
DEFR 120-240 Vac, 5 A Resistive
240 Vac, 1/8 HP
FAN 120 Vac, 1/10 HP Pluggable and Push-in - Quickly
- Push-in Connection:
240 Vac, 1/8 HP - Hold the wire close to its end and insert it into the
AUX / LIGHT 120 Vac, 1/10 HP required opening.
120-240Vac 5W General Use - If necessary, press the button to help make the TO DISCONNECT THE PUSH-IN
connection. CONNECTION:
- Ferrule type terminals can be used. - To disconnect the wire, press the button and
remove it.
4. DISPLAY AND KEYS - For the signal connections, the ferrule must be at
least 12mm.
In the power connectors the pin must be at least
LED indicator Defrost cycle LED indicator for the auxiliary 7mm.
Strip of the wire
outlet enabled NOTES 1 - Signal Connectors:
LED indicator Fan enabled
LED indicator for the EEV - Connections 1 to 20 must use wire of a gauge
LED indicator Compressor between 0.2 and 1,5mm² (26 and 16AWG).
Enabled LED indicator temperature unit NOTES 2 - Power Connectors:
- Connections 21 to 25 must use wire of a gauge Ferrule
between 0.2 and 2.5mm² (26 and 12AWG).
A
Up Key 6.1. Connecting the temperature sensors
Flatec Key
- Connect the wires of the S1 Sensor to terminals ‘’11 and 12'’, the wires of the S2 sensor to terminals
and ‘’13 and 14'’ and the wires of the S3 sensor to terminals ‘’15 and 16'’: the polarity is indifferent.
- The length of the sensor cables can be increased by the user themselves up to 200 meters (650 ft.),
Set Key Down Key using a 2x24 AWG PP cable.
6.2. Recommendations from NBR5410 and IEC60364 standards
VX-1025e plus a) Install surge protectors to the controller’s power supply.
b) Install transient suppressors - suppressor filter (type RC) - in the circuit to increase the working life of
the controller’s relay.
c) The sensor cables can be together, but not in the same conduit as the power supply fot the controller
or the loads.
7. INSTALLATION PROCEDURE 8.3 Basic Operation
a) Cut out the panel plate (Diagram 5 - Item 14) where the controller is going to be installed, to a size 8.3.1 Operation mode
where X = 71±0,5 mm and Y = 29±0,5 mm; To enter the setpoint adjustment menu, press / for 2 seconds. The message [,,sp] will appear on
b) Remove the side clasps (Diagram 6 - Item 14): to do this, press on the elliptical central part (with the the display, followed by the value for adjusting the normal setpoint. Use the < or > keys to change the
Full Gauge Controls Logo) and slide the clasps back; value and confirm by pressing /. Next the message [SP-E] will be displayed showing that the
c) Pass the wires through the opening (Diagram 7 - Item 14) and install the electrics as described in item economic setpoint to be changed. Again, use the < or > keys to change the value and confirm by
6; pressing. Finally, the display will read [----] to show that configuration is complete. Setpoints can
d) Insert the controller into the opening made in the panel, from the outside; also be changed individually in the access menu.
e) Replace the clasps and move them until they are pressed against the panel, securing the controller to 8.3.2 Economic Setpoint (SPE)
the housing (see arrow in Diagram 6 - Item 14); The [SP-E] uses more flexible parameters for controlling the temperature which results in better
f) Adjust the parameters as described in item 9. energy savings ([F08] - Desired temperature - Economic setpoint and [F12] - Switching differential
WARNING: Where the installation needs to be sealed tight against liquids, the opening for - Economic setpoint (hysteresis)).
the controller must be no more than 70.5x29mm. When it is activem the message [,ECO] is displayed, alternating with the temperature and other
The side clasps must be secured in such a way as to create a tight rubber seal that prevents ant messages.
liquids entering the opening and the controller. Economy mode can be activated or deactivated using the commands:
Protective Film - Diagram 9 (item 14)
This protects the controller when it is installed somewhere subject to splashing water, such as
Function Command Ação
refrigerated counters.
IMPORTANT: Only apply it after you have finished making the electrical connections: [f15][f16][f17] Time to come on Activate
a) Pull the side clasps back (Diagram 6 - item 14);
[f18] Maximum temperature in economic mode Desactive
b) Remove the protective film from the adhesive vinyl strip;
c) Apply the film to the entire upper part, folding the flaps, as indicated by the arrows - Diagram 9 (item Not dependent on time, only
[f18] Maximum temperature in economic mode = 0 (Off)
14); deactivated when door is opened
d) Replace the clasps. [f55]= [1] or [2] Indicates door is open (digital input) Keep turned off
Note: The film is transparent, so that the electrical layout of the device can be seen. [f55]= [7] or [8] External key (digital input) Activate / Deactivate

8. OPERATIONS [f58] Time to activate after door is closed Activate


8.1 Access Menu Map - Determined by the Access Menu ([ECO,]) Activate / Deactivate
Press the Access key ;(short touch) to navigate through the menu functions. Each press will display - Error measuring ambient temperature (S1) Keep turned off
the next function in the series. To confirm press the /key (short touch). The menu function map is - On switching on the instrument Deactivate
below: - Fast Freezing Deactive
TURN OFF
SELECT FUNCTION EXIT FUNCTIONS CONTROL FUNCTIONS 8.3.3 Manual defrost
; The defrosting process can be activated / deactivated manually through the access menu, using the
; ; [defr]option or by pressing the < key for 4 secondds or by using an external switch connected to
digital input ([F55] = 11 or 12). Activation or deactivation is indicated by the message
[defr][On,,]or [defr][OFF,]respectively.
DEFROST (ON/OFF) LOCK FUNCTIONS 8.3.4 How to determine when defrosting is complete using the
; ; temperature
a) - Set the condition for starting defrosting as based on time, [F28] = 1;
b) - Reset the functions related to the end of defrosting to their maximum value:
- Refrigeration time (Interval between defrosting periods) [F29] = 9999min.
FAST FREEZING (ON/OFF) VIEW PROCESSES - Temperature of the Evaporator to finish the defrost [F44] = 105°C / 221°F
- Maximum time on defrost (for safety) [F46] = 999min.
; ; c) - Wait a while until a layer of ice has formed on the evaporator.
d) - Defrost manually (using the ; key, go to [dEFr] and press / or press the < key for 4
seconds).
ECONOMIC SETPOINT (ON/OFF) ADJUST DATE AND TIME
e) - Monitor it melting .
f) - Wait until all the ice on the evaporator has melted to determine when the defrosting is over.
; ; g) - When the defrosting has finished, check the temperature in the evaporator (S2) using the >key
(see item 8.3.9).
h) - Using the reading for S2, adjust the temperature to end the defrosting:
- Temperature of the evaporator to finish the defrost [F44]= Temp. S2
MANUAL MODE ON/OFF
SUPERHEATING SETPOINT
i) - As a safety measure, reset the maximum defrost duration, according to the type of defrosting set.
Example:
; ; - Electric defrost (by resistance) [F46] = 45min.
- Hot gas defrost [F46] = 20min.
j)- Finally, adjust the refrigeration time (Interval between defrosts) [F29] to the desired value.

8.3.5 Fast Freezing


LIGHT NORMAL SETTING ECONOMIC SETPOINT
In fast freezing mode, the refrigeration output is permanently on and therefore the refrigeration or
; ; ; freezing process is accelerated. This operating mode can be activated or deactivated in the access
menu, using option [Fast] or an external switch connected to the digital input ([F55]= 9 or 10). It
can also be switched off automatically according to temperature [F19] or time [F20]. While fast
freezing is on, the connected compressor display will flash rapidly and defrosting will continue. If, on
8.2 List of key functions activating the fast freezing mode, the controller identifies that there is a defrost cycle programmed to
The keys listed act as shortcuts for the following functions: start during this period of time, the defrost will be run first and then it will go into fast freezing mode.

Brief press: The current day, month, year, day of the week, hour and minutes 8.3.6 Turn Light On /Off
/ will be shown in sequence on the display. Using option [Lamp], in the access menu, it is possible to turn the lamp on /off manually if the AUX
output is configured as a lamp ([F60]=1) and the defrosting of the tray is not configured to use the
/ Press for 2 seconds: Adjust the Setpoints AUX output([F36]= 2).
Note: When switching on the lamp manually, the time for when the lamp will be switched off after the
< Brief press: Displays maximum and minimum temperatures / pressures. door is closed [F59] will be reset.

< Press for 2 seconds: When displaying saved information, wipes the entry. 8.3.7 Adjust date and time
The date and time can be adjusted using option [ClO,], from the access menu. This option is
<
<
Press for 4 seconds: Starts Manual Defrost.
accessed with the ;(Flatec) and confirmed with the /key.
Press for 2 seconds: Stops warning alarms. In the date and time setting mode, use the<or>keys to change the value and, when ready, press/
to store the value set. If the date entered is invalid, the message [ECLO] will appear on the display.
< Press for 4 seconds: Switches to displaying the measurements / processes
briefly. 8.3.8 View date and time
By briefly pressing the /key (brief press), the date and time set on the controller will be displayed.
; Enter the Access Menu The current date ([,--d]),month ([,--m]), year ([,--y]), day of the week ([day-]), hour and
;< Press for 5 seconds: Turns off control functions. minutes ([00:00]) will be shown in sequence on the display.
Note: The controller leaves the factory with the clock disabled. To enable it follow the directions in item
<and Enters select function. 8.3.7
Example:[day1] equals Sunday.
8.3.9 View the stage of the process, the time elapsed and other 8.3.12 Record of maximum and minimum temperatures / pressures
measurements Pressing the < key (short touch) during the temperature / pressure display, the message [rEg,] will
The temporary display mode can be activated through the access menu using option [Proc] or by appear and then the minimum and maximum temperatures and pressure recorded.
pressing the > key for 4 seconds until the message [Proc] is displayed. Note: If the < key is pressed during the display of the records, the values will be reset and the
The message on the current process will alternate with the length of time ([hh:mm]) that has elapsed message [rsEt] will be displayed.
for this stage.
Stages of the process: 8.3.13 Selecting the temperature or pressure units
[init]- Initializing the Electronic Expansion Valve; To select the units that the device will use, use function [,F01] with access code [,231] and
[dEL,]- Initial Delay (delay in starting up the instrument); press the / key. Next, select the required temperature unit [,=C,] or [,=F,] using the <> keys
[Fan,]- Fan-delay (delay caused by the fan); and confirm by pressing /. After that, select the required pressure unit [PSI,] or [Bar,] using the
[rEFr]- Refrigeration; <>keys and confirm by pressing /.
[Pre,]- Pre-Defrost; Whenever the units are changed, the function settings revert to the factory value and will therefore
[dEFr]- Defrost; need to be reset.
[dRAi]- Draining;
[Off,]- Control Functions are turned off;
[dVee]- The instrument is in driver mode. 8.4 Advanced Operations
8.4.1 Schedule Defrosting
In this viewing mode, it is also possible to view other measurements (if available) by pressing the > key
or the < (short touch), depending on the list: You can configure the defrosting schedule to be equally distributed accross the day by programming
the number of defrost cycles per day. To do this, you need to set the start of the defrosting as part of a
[Proc] - Process stage and time taken; defrosting schedule, setting [F28] to 5, and configuring functions [F37] to [F42] to determine the
[t-1,] - Temperature from the ambient sensor S1; number of defrost cycles per day and their starting times.
[t-2,] - Temperature from the Evaporator sensor S2; With this, the defrost schedule makes it possible to create a program from Monday to Friday, another
[t-3,] - Temperature from the Suction Line sensor S3; program for Saturday and another for Sunday.
[tSat] - Saturation Temperature; Example: If the program for Monday to Friday consists of a preferred time of 1 pm (and the number of
[Pres] - Pressure reading (before the amount of pressure is displayed, the configured unit of defrosting cycles is 4, with an interval of 6 hours), the defrost schedule will operate at 1:00 am, at 7:00
pressure is shown:[Psi,]or[bar,]); am, at 1:00 pm and 7:00 pm on each day.
[,SH,] - Superheating Temperature;
[Vee,] - Percentage that the Electronic Expansion Valve has been opened. MONDAY TO FRIDAY
The message related to the chosen measure will alternate with the measurement value.
Note: This display will remain on the display for 15 minutes or until the / key or the ;(short touch). 13:00 19:00 01:00 07:00
Note: In this mode, alarm messages and the preferred display ([F75]) will be ignored.
8.3.10 Function Lock
The function lock provides some extra safety when using this device. When it is enabled the normal and DEFROST DEFROST DEFROST DEFROST
economic setpoints and other parameters can be viewed, but are not able to be changed ([,f78]=2)
or you can just lock the device against changes to the control functions but allow the normal and Note: If the condition for the start of the defrost cycle is set by the defrosting schedule and the clock is
economic setpoints to be amendable ([,f78]=1). To block the functions, access the [LOC,] option not set or disabled, the start of the defrost cycle will be based on time.
from the access menu using the ;(Flatec) key and confirm it by pressing the /key.
The message [no,,] will be displayed if the lock is disabled. Now press and hold the > key for the
8.4.2 Electronic Expansion Valve in Manual Mode
time configured for this function [,f79].
When enabled, the message [LOC,][On,,]will displayed. It can only be enabled if the function You can switch the mode of the electronic expansion valve between manual and automatic, using the
[,f78] is set to 1 or 2. menu provided by the [modE] option.
To disable the lock, turn the controller off and on again with the > key pressed. Keep the key pressed In manual mode, the message [Man,]is displayed, alternating with the temperature and other
until the message [LOC,][OFF,] indicates that it has been unlocked (10 seconds). messages, and the electronic expansion valve remains fixed in the position configured in ([C19]-
Note: Regardless of the values of [,F78] and [,F79] you are always able to adjust the time and Initial Valve Opening).
hour. In automatic mode, the controller checks the reading of the temperature and pressure sensors and
calculates the value of the valve opening to ensure that the refrigeration system is a energy efficient as
8.3.11 Turn off control Functions possible.
Turning off the control functions allows the controller to be used as a temperature / pressure indicator In manual mode, the controller keeps the position of the VEE fixed according o the adjustment made.
only, with the control outputs and alarms off. This feature can be enabled or disabled using the function.
Shutdown of control functions [,F80]. When enabled, the control and alarm functions are turned off
8.4.3 Change the Parameters of the Controller
([CTRL][OFF,]) or turned on ([Ctrl][ON,,]) using the menu provided by the option [Ctrl].
When the control functions are turned off, the message [OFF,] will be displayed, alternating with the The function menu can be accessed through the access menu, option [Func] or by simultaneously
temperature and other messages. It is also possible to switch off and on the control functions by pressing < and > while the pressure is being displayed. To allow these parameters to be changed,
pressing the ; for 5 seconds. enter [,F01] by pressing/(short touch) and by using the < or > keys to enter the code 123 (one
Note: When restarting the control functions, the instrument will go to the initial stage [init]. hundred and twenty-three) and confirm with the /key. To change the other functions, navigate the
menu using the < or > keys and use the same method to adjust them. To exit the menu and return to
normal activity, press / (long press) until [----]is displayed.
Note: To access the settings for the parameters of the electronic expansion valve [,c01] to
[,C21] enter code 717 and confirm with /.
Note: If the function lock is on, the controller will display the message [LOC,] on the display,
when the < or > keys are pressed, and will not allow any adjustment to the parameters.

8.5 Table of Parameters


CELSIUS (°C) FAHRENHEIT (°F)
Fun Description Min Max Unit Standard Min Max Unit Standard
[,F01] Access code 0 999 - 0 0 999 - 0
SUPEHEATING

[,F02] Type of Application 1 20 - 1 1 20 - 1


[,F03] Superheating Setpoint 0,0 50,0 °C 8,0 0,0 90,0 °F 14,4
[,F04] Liquid Refrigerant 1 23 - 5 1 23 - 5
[,F05] Lower Pressure Limit of the P1 transducer (Pressure at 4mA) -14,5 850,0 PSI -14,5 -1,0 58,6 BAR -1,0
[,F06] Upper Pressure Limit of the P1 transducer (Pressure at 20mA) -14,5 850,0 PSI 174,0 -1,0 58,6 BAR 12,0
[,F07] Desired Temperature - Normal Setpoint F09 F10 °C -15,0 F09 F10 °F 5,0
[,F08] Desired Temperature - Economic Setpoint F09 F10 °C -10,0 F09 F10 °F 14,0
[,F09] Minimum Setpoint allowed by the end user -50,0 F10 °C -50,0 -58,0 F10 °F -58,0
[,F10] Maximum Setpoint allowed by the end user F09 105,0 °C 105,0 F09 221,0 °F 221,0
[,F11] Switching differential - Normal setpoint (hysteresis) 0,1 20,0 °C 2,0 0,1 36,0 °F 3,6
[,F12] Switching differential - Normal setpoint (hysteresis) 0,1 20,0 °C 2,0 0,1 36,0 °F 3,6
[,F13] Pump Down Pressure -14,5 (Off) F06 PSI -14,5 (Off) -1,0 (Off) F06 BAR -1,0 (Off)
[,F14] Maximum Time for Pump Down 0(Off) 600 seconds 30 0(Off) 600 seconds 30
REFRIGERATION

[,F15] Time for Economic Mode to begin (Monday to Friday) 00:00 24:00(Off) hh:mm 24:00(Off) 00:00 24:00(Off) hh:mm 24:00(Off)
[,F16] Time for Economic Mode to begin (Saturday) 00:00 24:00(Off) hh:mm 24:00(Off) 00:00 24:00(Off) hh:mm 24:00(Off)
[,F17] Time for Economic Mode to begin (Sunday) 00:00 24:00(Off) hh:mm 24:00(Off) 00:00 24:00(Off) hh:mm 24:00(Off)
[,F18] Maximum temperature in economic mode 0(Off) 999 minutes 120 0(Off) 999 minutes 120
[,F19] Fast Freezing Temperature Limit -50,0 60,0 °C -25,0 -58,0 140,0 °F -13,0
[,F20] Maximum Fast Freezing time 0(Off) 999 minutes 300 0(Off) 999 minutes 300
[,F21] Minimum time for compressor to be on 0(Off) 9999 seconds 0(Off) 0(Off) 9999 seconds 0(Off)
[,F22] Minimum time for the compressor to be off 0(Off) 9999 seconds 0(Off) 0(Off) 9999 seconds 0(Off)
[,F23] Length of time the compressor is on, if there is an error from the S1 sensor 0(Off) 999 minutes 20 0(Off) 999 minutes 20
[,F24] Length of time the compressor is off, if there is an error from the S1 sensor 0(Off) 999 minutes 10 0(Off) 999 minutes 10
[,F25] Control Action if there is an error in the superheating sensors 0(Off) 1(Man) - 1(Man) 1(Off) 1(Man) - 1(Man)
[,F26] Delay time when powering up the controller 0(Off) 999 minutes 0(Off) 0(Off) 999 minutes 0(Off)
CELSIUS (°C) FAHRENHEIT (°F)
Fun Description Min Max Unit Standard Min Max Unit Standard
[,F27] Defrost type (0 = resistance / 1 = hot gas / 2 = natural) 0 2 - 0 0 2 - 0
[,F28] Condition for starting 0(Off) 5 - 1 0(Off) 5 - 1
[,F29] Interval between defrosting periods if F28=1 or the Maximum time without defrosting if F=28 2, 3 or 4 1 9999 minutes 240 1 9999 minutes 240
[,F30] Additional time to the end of the first refrigeration cycle if F28=1 0(Off) 999 minutes 0(Off) 0(Off) 999 minutes 0(Off)
[,F31] Temperature of the evaporator (sensor S2) in order to begin defrost if F28= 2, 3 or 4 -50,0 105,0 °C -20,0 -58,0 221,0 °F -4,0
[,F32] Temperature Difference in order to start defrosting (S1-S2) if F28= 3 or 4 -50,0 105,0 °C 15,0 -58,0 221,0 °F 59,0
[,F33] Time to confirm the lower temperature (sensor S2) to start the pre-defrost setting if F28=2, 3 or 4 0(Off) 999 minutes 10 0(Off) 999 minutes 10
[,F34] Defrost when the controller is powered on 0(Off) 1(On) - 1(On) 0(Off) 1(On) - 1(On)
[,F35] Smooth Defrost if F27=0 10 100(Off) - 100(Off) 10 100(Off) - 100(Off)
[,F36] Enable Tray Defrost 0(Off) - 0(Off) -
DEFROST

2 0(Off) 2 0(Off)
[,F37] Number of Defrostings per day (Monday to Friday) if F28=5 1 12 - 4 0 12 - 4
[,F38] Time to start Defrost (Monday to Friday) if F28=5 00:00 23:59 hh:mm 06:00 00:00 23:59 hh:mm 06:00
[,F39] Number of Defrostings per day (Saturday) if F28=5 1 12 - 4 0 12 - 4
[,F40] Time to start Defrost (Saturday) if F28=5 00:00 23:59 hh:mm 06:00 00:00 23:59 hh:mm 06:00
[,F41] Number of Defrostings per day (Sunday) if F28=5 1 12 - 4 0 12 - 4
[,F42] Time to start Defrost (Sunday) if F28=5 00:00 23:59 hh:mm 06:00 00:00 23:59 hh:mm 06:00
[,F43] Length of pre-defrost (collecting in gas) 0(Off) 999 minutes 0(Off) 0(Off) 999 minutes 0(Off)
[,F44] Temperature of the Evaporator (S2 sensor) to finish the defrost -50,0 105,0 °C 30,0 -58,0 221,0 °F 86,0
[,F45] Ambient temperature (S1 sensor) required to end the defrost -50,0 105,0 °C 20,0 -58,0 221,0 °F 68,0
[,F46] Maximum time on defrost (for safety) 1 999 minutes 30 1 999 minutes 30
[,F47] Draining time (from water collected from defrosting) 0(Off) 999 minutes 1 0(Off) 999 minutes 1
[,F48] Fan operation mode 0 4 - 4 0 4 - 4
[,F49] Time fan is on if F48=0 or 4 1 999 minutes 2 1 999 minutes 2
[,F50] Time fan is turned off if F48=0 (automatic timed mode) 1 999 minutes 8 1 999 minutes 8
FAN

[,F51] Length of time door is open until fan is turned off F55=1 or 2 -1(Off) 9999 seconds 0 -1(Off) 9999 seconds 0
[,F52] Fan cut off due to high temperature in the evaporator (S2 sensor) -50,0 105,0 °C 50,0 -58,0 221,0 °F 122,0
[,F53] Temperature in the evaporator to switch the fan back on after draining -50,0 105,0 °C 2,0 -58,0 221,0 °F 35,6
[,F54] Maximum length of time until the fan is switched back on after drainage (fan-delay) 0(Off) 999 minutes 1 0(Off) 999 minutes 1
[,F55] Function mode of the digital input 0(Off) 12 - 2 0(Off) 2 - 0
[,F56] Length of time door is open for instant defrost if F55=1 or 2 0(Off) 999 minutes 30 0(Off) 999 minutes 30
DOOR

[,F57] Length of time door is open until fan and compressor are turned off F55=1 or 2 0(Off) 999 minutes 5 0(Off) 999 minutes 5
[,F58] Length of time door is closed until economic mode is activated if F55=1 or 2 0(Off) 999 minutes 0(Off) 0(Off) 999 minutes 0(Off)
[,F59] Length of time door is closed until light is switched off is F55=1 or 2 and F60=1 0(Off) 999 minutes 2 0(Off) 999 minutes 2
[,F60] AUX output mode 0 2 - 1 0 2 - 1
[,F61] Low ambient temperature alarm (S1 sensor) -50,0 105,0 °C -50,0 -58,0 221,0 °F -58,0
[,F62] High ambient temperature alarm (S1 sensor) -50,0 105,0 °C 105,0 -58,0 221,0 °F 221,0
[,F63] Time to confirm the alarm by room temperature (S1) 0(Off) 999 minutes 0(Off) 0(Off) 999 minutes 0(Off)
ALARMS

[,F64] Room temperature alarm delay (power up) 0(Off) 999 minutes 10 0(Off) 999 minutes 10
[,F65] Length of time door is open to trigger alarm 0(Off) 999 minutes 5 0(Off) 999 minutes 5
[,F66] Maximum time compressor can be on without reaching the setpoint 0(Off) 999 hours 0(Off) 0(Off) 999 hours 0(Off)
[,F67] Trigger for alarm when defrosting is over based on time 0(No) 1(Yes) - 1(Yes) 0(No) 1(Yes) - 1(Yes)
[,F68] Enable buzzer 0(Off) 1(On) - 0(Off) 0(Off) 1(On) - 0(Off)
[,F69] Intensity of the digital filter on the ambient temperature sensor (S1 sensor) (Rising) 0(Off) 20 seconds 0(Off) 0(Off) 20 seconds 0(Off)
[,F70] Intensity of the digital filter on the ambient temperature sensor (S1 sensor) (Descending) 0(Off) 20 seconds 0(Off) 0(Off) 20 seconds 0(Off)
SENSORS

[,F71] Displacement of the values from the ambient sensor (S1 sensor) -20,0 20,0 °C 0,0 -36,0 36,0 °F 0,0
[,F72] Displacement of the values from the evaporator sensor (S2 sensor) -20,0 20,0 °C 0,0 -36,0 36,0 °F 0,0
[,F73] Displacement of the values from the suction line sensor (S3 sensor) -20,0 20,0 °C 0,0 -36,0 36,0 °F 0,0
[,F74] Displacement of the values (Offset) for the pressure transducer P1 -50 50 PSI 0 -3,4 3,4 BAR 0,0
[,F75] Preferred Indicator 1 7 - 1 1 7 - 1
[,F76] Ambient Temperature (S1 sensor) value locked in during defrosting 0 2 - 1 0 2 - 1
FUNCTIONS

[,F77] Maximum length of time that the temperature is locked during defrosting 0(Off) 999 minutes 15 0(Off) 999 minutes 15
[,F78] Function Lock Mode 0 2 - 0 0 2 - 0
[,F79] Function Lock Period 15 60 seconds 15 15 60 seconds 15
[,F80] Shutdown of control functions 0(Off) 2 - 0(Off) 0(Off) 2 - 0(Off)
[,F81] Address of the instrument on the RS-485 network 1 247 - 1 1 247 - 1

Electronic Expansion Valve configuration functions (displayed if [F01] = 717)

CELSIUS (°C) FAHRENHEIT (°F)


Fun Description Min Max Unit Standard Min Max Unit Standard
[,F01] Access code 0 999 - 0 0 999 - 0
[,c01] Controller in Driver mode 0(Off) 1(On) - 0(Off) 0(Off) 1(On) - 0(Off)
[,c02] Enable Internal Energy Backup (IEB) 0(Off) 1(On) - 1(On) 0(Off) 1(On) - 1(On)
[,c03] Proportional Increase (Kp) 1,0 100,0 - 10,0 1,0 100,0 - 10,0
[,c04] Integral Time (Ti) 0(Off) 500 seconds 200 0(Off) 500 seconds 200
[,c05] Derivative Time (dT) 0(Off) 500 seconds 0(Off) 0(Off) 500 seconds 0(Off)
[,c06] Setpoint - LoSH Protection (Low superheating) 0,0 F03 °C 4,0 0,0 F03 °F 7,2
ELECTRONIC EXPANSION VALVE

[,c07] Integral Time (Ti) - Low Superheating Protection 1 500 seconds 20 1 500 seconds 20
[,c08] Setpoint - LOP Protection (Low evaporation temperature) -50,0(Off) c10 °C -50,0(Off) -58,0(Off) c10 °F -58,0(Off)
[,c09] Integral Time (Ti) LOP Protection (Low evaporation temperature) 1 500 seconds 20 1 500 seconds 20
[,c10] Setpoint - MOP Protection (High evaporation temperature) c08 105,0(Off) °C 105,0(Off) c08 221,0(Off) °F 221,0(Off)
[,c11] Integral Time (Ti) - MOP Protection (High evaporation temperature) 1 500 seconds 20 1 500 seconds 20
[,c12] Time to verify the protection alarms (LoSH, LOP, MOP) 0(Off) 9999 seconds 60 0(Off) 9999 seconds 60
[,c13] State of the compressor in the event of protection alarms being triggered (ASHL, ALOP, AMOP) 0 7 - 0 0 7 - 0
[,c14] Time until the compressor switches on again after protection alarms are triggered (ASHL, ALOP, AMOP) 0(Off) 999 minutes 3 0(Off) 999 minutes 3
[,c15] Total number of steps for the valve 20 550 - 500 20 550 - 500
[,c16] Operating Speed (steps per second) 25 90 steps/ sec. 30 25 90 steps/sec. 30
[,c17] Minimum Valve Opening 0,0 c18 % 0,0 0,0 c18 % 0,0
[,c18] Maximum Valve Opening c17 100,0 % 100,0 c17 100,0 % 100,0
[,c19] Initial Valve Opening c17 c18 % 50,0 c17 c18 % 50,0
[,c20] Time valve is used after initial opening 0(Off) 300 seconds 20 0(Off) 300 seconds 20
[,c21] Time valve is used after initial opening after defrosting 0(Off) 3000 seconds 0(Off) 1 3000 seconds 0(Off)
8.5.1 Description of the Parameters F17 - Time for Economic Mode to begin (Sunday):
Time when the economic setpoint [SP-E] will be activated on Sundays.
This function can be turned off by setting it to the maximum value [OFF,].

F01 - Access Code: F18 - Maximum temperature in economic mode:


This is required to change the settings of the parameters. This code does not need to be entered to view Allows you to set the maximum length of time economy mode will operate for. After this time, the
the adjusted parameters. setpoint returns to economy mode in normal operation. If this is set to [OFF,] this time will be ignored.
Allows you to enter the access codes provided:
[,123]- Enables you to change the table parameters; F19 - Fast Freezing Temperature Limit:
[,231]- Enables you to configure the units of measurement for temperature and pressure; This is the minimum temperature that the instrument can reach during the Fast Freezing process.
[,717]- Enables you to change the settings for the parameters of the electronic expansion valve.
F20 - Maximum Fast Freezing time:
F02 - Type of application: This the duration of the Fast Freezing process.
It allows you to choose the type of application that the device will control. Pre-programmed values for
the PID control of the electronic expansion valve are loaded, according to the chosen option:
F21 - Minimum time for compressor to be on:
[,,,1] - Cold chamber - slow performance;
This is the minimum amount of time the compressor will be on, i.e. The period of time between the last
[,,,2] to [,,20] - Reserved.
section and the next time it is stopped. This helps to avoid power surges from the electricity grid.
F03 - Superheating Setpoint:
This is the reference value for control of superheating. F22 - Minimum time for compressor to be off:
Superheating indicates how much vapor is over the saturation temperature (boiling point) at a given This is the minimum amount of time the compressor will be off, i.e. The period of time between the last
pressure. time it stops and the next section. This helps to relieve the discharge pressure and increases the
A pressure transducer in the suction line and a temperature sensor are required at the evaporator outlet working life of the compressor.
(useful) or at the compressor inlet (total).
Superheating = Suction temperature - satured vapor temperature (fluid curve). F23 - Length of time the compressor is on, if there is an error with the ambient S1 sensor:
F24 - Length of time the compressor is off, if there is an error with the ambient S1 sensor:
F04 - Liquid refrigerant: If the ambient sensor (S1 sensor) is disconnected or goes out of the measurement range, the
Allows you to choose which refrigerant will be used in the superheating calculation/; compressor will switch on or off according to the parameters set in these functions.
[,,,1]- R22
[,,,2]- R32 F25 - Control Action if there is an error in the superheating sensors:
[,,,3]- R134A [OFF,] - Control turned off. Keeps the electronic expansion valve closed and all control outputs off,
[,,,4]- R290 except the AUX output if it is configured as an alarm output.
[,,,5]- R404A [Man,] - Keeps the expansion valve set to the position configured in (C19 - Initial Valve Opening)
[,,,6]- R407A and all control outputs operate normally.
[,,,7]- R407C
[,,,8]- R407F F26 - Delay time when powering up the controller:
[,,,9]- R410A When the instrument is turned on, it can remain disabled for a while, delaying the start of the process.
[,,10]- R422A During this time, it only works as a temperature / pressure gauge. Helps to avoid high demands for
[,,11]- R422D power, when power returns after a power cut, where several pieces of equipment are all on the same
[,,12]- R427A connection. Therefore, you can set different times for each device. This delay can relate to the
[,,13]- R441A compressor or defrosting (where defrosting is part of the sequence)
[,,14]- R448A
[,,15]- R449A F27 - Defrost type (0=coils / 1 = hot gas / 2 = natural):
[,,16]- R450A
[,,,0] - Electrical Defrosting (using coils), which only applies to the defrost outlet.
[,,17]- R452A
[,,,1] - Hot Gas Defrosting, which only applies to the compressor and defrosting outlets.
[,,18]- R507A
[,,,2] - Natural defrosting, which only applies to the fan outlet.
[,,19]- R513A
[,,20]- R600A
[,,21]- R744 F28 - Condition for starting defrosting:
[,,22]- R1234YF [Off,] - No automatic defrosting, only manual defrosting;
[,,23]- R1234ZE (E) [,,,1] - Set time to start defrosting;
[,,,2] - Set temperature to start defrosting;
F05 - Lower Pressure Limit of the P1 transducer (Pressure at 4mA): [,,,3] - Set temperature difference (S1-S2) to start defrosting;
The pressure on the pressure sensor when it has a current of 4mA at its output. [,,,4] - Set temperature and temperature difference (S1-S2) to start defrosting;
[,,,5] - Schedule Defrosting.
F06 - Upper Pressure Limit of the P1 transducer (Pressure at 20mA):
The pressure on the pressure sensor when it has a current of 20mA at its output. F29 - Interval between defrosting periods if F28=1 or the Maximum time without defrosting if
F28=3 or 4:
F07 - Desired Temperature - Normal Setpoint: It determines how often and after how long defrosting take place, based on the time of the last
It is the control temperature of the normal operating mode. When the temperature of the S1 sensor defrosting. If the controller is configured to defrost according to temperature ([F28]= 2, 3 or 4),
(ambient) is lower than the value set for this function the compressor will be turned off. this time acts as a level of safety in situations in which the evaporator temperature (S2 sensor)
does not reach the values programmed in [F31] or [F32]. This function determines the
F08 - Desired Temperature - Economic Setpoint: maximum time that the controller will wait before carrying out defrosting.
It is the control temperature when the economic operating mode is on. When the temperature of the S1
sensor (ambient) is lower than the value set for this function the compressor will be turned off. F30 - Additional time to the end of the first refrigeration cycle if [F28] = 1:
This is to set a longer period of time for the first refrigeration cycle. Where there are setups with several
F09 - Minimum setpoint allowed by the end user: pieces of euipment, you can avoid high demand peaks by ensuring that defrosting takes place at
F10 - Maximum setpoint allowed by the end user: different times by assigning different values to this function.
Limits set in order to avoid excessivelt high or low temperatures being accidentally set for the
temperature setpoint, which could lead to high energy consumption by keeping the system on F31 - Temperature of the evaporator (S2 sensor) in order to begin defrosting if F28=2, 3 or 4.
continuously. When the temperature of the evaporator (S2 sensor) reaches a value using this function, the controller
will wait for the length of time before beginning defrosting.
F11 - Switching differential - Normal setpoint (hysteresis):
F12 - Switching differential - Economic setpoint (hysteresis) F32 - Temperature Difference in order to start defrosting (S1-S2) if F28=3 or 4.
This is the temperature difference between switching off and restarting refrigeration in economic When the difference between the temperature of the ambient sensor (S1 sensor) and the temperature
operating mode. of the evaporator (S2 sensor) reaches a value using this function, the controller will wait for the length of
time before beginning defrosting.
F13 - Pump Down pressure :
When reaching the temperature setpoint ([F07] or [F08]), the compressor will not be turned off if F33 - Time to confirm the lower temperature (sensor S2) to start the pre-defrost setting if F28=2,
the pressure on the P1 transducer is higher than the value set for this function. Instead it will remain on 3 or 4
until the pressure reduces this value. If the controller is configured to defrost according to temperature, the moment the temperature reaches
This function can be turned off by setting it to the minimum value [OFF,]. the set value, it will run a delay before starting the pre-defrost stage. If the temperature remains low,
while this stage is running, the pre-defrost process is started. If it doesn’t and the temperature rises
F14 - Maximum Time for Pump Down: above the set value, the system will return to a refrigeration cycle.
This is the maximum time that the compressor will remain on during the Pump Down process (for
safety). After this period the compressor is switched off. If this function is set to a minimum value off 0 F34 - Defrost when the controller is powered on
[OFF,], the compressor will be turned off only if the pressure on the P1 transducer is less than [F13]. This enables a defrosting to be conducted when the controller is powered on. For example, when the
Note: In the event of an error in the S1 ambient temperature or the P1 transducer pressure sensor, the electricity returns after a power cut.
Pump Down feature will be disabled.
F35 - Smooth Defrost if F27=0:
F15- Time for Economic Mode to begin (Monday to Friday): Smooth Defrost mode provides a smoother defrosting, saving energy and preventing the ambient
Time when the economic setpoint [SP-E] will be activated on working days. temperature from rising as much as in a standard defrost. In this mode, the defrost output remains on
This function can be turned off by setting it to the maximum value [OFF,]. as long as the evaporator temperature (S2 sensor) is less than 2°C (35.6°F) and, after passing that
temperature, the output remains on for the percentage of time configured in this function, within a 2-
F16- Time for Economic Mode to begin (Saturday) minute period.
Time when the economic setpoint[SP-E] will be activated on Saturdays..
This function can be turned off by setting it to the maximum value [OFF,].
F36 - Enable Tray Defrost: F54 - Maximum length of time until the fan is switched back on after drainage (fan-delay):
[OFF,]- Deactives Tray Defrosting; For safety, if the temperature in the evaporator does not reach the value set by function [F53] or the
[,,,1]- Defrosting the tray using the FAN outlet; S2 sensor is disconnected, the fan will only come on after the time set for this function has expired.
[,,,2]- Defrosting the tray using the AUX outlet;
The chosen output acts as a second defrosting output. This output is activated during the pre-defrost,
F55 - Function mode of the digital input:
defrost and drain periods. The functionality related to the control of this output (FAN or AUX) will be
[,,,0] - Digital Input deactivated;
disregarded.
[,,,1] - NO Contact: Door Sensor;
[,,,2] - NC Contact: Door Sensor;
F37 - Number of Defrostings per day (Monday to Friday) if F28=5
[,,,3] - NO Contact: External Alarm;
Defrosting is set to take place at equal intervals according to the number programmed per day, always
[,,,4]- NC Contact: External Alarm;
taking preferred times into account. It can be adjusted using values of 1, 2, 3, 4, 6, 8 or 12.
[,,,5] - NO Contact: Switch off the Control System;
This function is to program this for Monday to Friday. [,,,6] - NC Contact: Switch off the Control System;
[,,,7] - NO Pulsator: Economic Mode;
F38 - Time to start Defrost (Monday to Friday) if F28=5 [,,,8] - NC Pulsator: Economic Mode;
Enables the preferred start time of one of the daily defrost cycles to be adjusted. [,,,9] - NO Pulsator: Fast Freezing;
This function is to program this for Monday to Friday. [,,10] - NC Pulsator: Fast Freezing;
[,,11]- NO Pulsator: Defrosting;
F39 - Number of Defrostings per day (Saturday) if F28=5 [,,12]-NC Pulsator: Defrosting.
Defrosting is set to take place at equal intervals according to the number programmed per day, always Note: With the instrument operating in driver mode (c01 = [On,,]), the digital input will be
taking preferred times into account. It can be adjusted using values of 1, 2, 3, 4, 6, 8 or 12. This functions automatically configured as an external signal input (compressor) in order to enable the electronic
is to program this for Saturday expansion valve.ddddddddddddddddddddddddddddddddddddddddddddddddddddddddddd
Obs: In options 5 and 6, the Sitrad supervisory system has priority over the digital input. Thus, if Sitrad
F40 - Time to start Defrost (Saturday) if F28 = 5: sends a command to turn on / off the control functions, the digital input is temporarily disabled and a
Enables the preferred start time of one of the daily defrost cycles to be adjusted. This function is to transition in its state will be necessary to enable it again.
program this for Saturday.
F56 - Length of time door is open for instant defrost if F55=1 or 2:
F41 - Number of Defrostings per day (Sunday) if F28=5: If the door is kept open for a period longer than that defined in this function, instant defrosting will take
Defrosting is set to take place at equal intervals according to the number programmed per day, always place, as long as the temperature in the evaporator (S2 sensor) is less than [F44] and the ambient
taking preferred times into account. It can be adjusted using values of 1, 2, 3, 4, 6, 8 or 12. This function temperature (S1 sensor) is less than [F45].
is to program this for Sunday.
F57 - Length of time door is open until fan and compressor are turned off F55=1 or 2:
F42 - Time to start Defrost (Sunday) if F28=5 For safety, if the door remains open longer than the time set here, both the compressor and fan will be
Enables the preferred start time of one of the daily defrost cycles to be adjusted. This function is to switched off.
program this for Sunday.
F58 - Length of time door is closed until economic mode is activated if F55= 1 or 2:
F43 - Length of pre-defrost (collecting in gas): With the door closed, this parameter defines how long until economic mode is activated. Setpoint is
When the defrost starts, the controller will only use the fan during this time, in order to take advantage of switched to the economic setpoint.
the residual energy of the gas.
F59 - Length of time door is closed until light is switched off if F55= 1 or 2 and F60=1:
F44 - Temperature of the Evaporator (S2 sensor) to finish the defrost: With the door closed, this parameter defines how long it will be until the lamp is turned off. Helps save
If the temperature in the evaporator (sensor S2) reaches the set value, the defrost cycle will be halted, electricity. With this function set to the minimum value [OFF,], all functions related to lamp activation
i.e. Temperature controlled. This way it improves the defrosting process. are ignored and the output remains off.

F45 - Temperature of the Ambient Sensor (S1 sensor) to finish the defrost: F60 - AUX output mode:
If the ambient temperature (sensor S1) reaches the set value, the defrost cycle will be halted, i.e. [,,,0] - Output switched off;
Temperature controlled. [,,,1] - Light switching;
[,,,2] - Alarm switching.
F46 - Maximum time on defrost (for safety): Note: If it is set up as an alarm switch, the AUX output will be turned on in the event of the following
This function adjusts the maximum duration of a defrost cycle. If the defrosting is not complete, during alarms: open door, high / low ambient temperature, compressor on without reaching the setpoint,
this period, according to the temperature, a dot will begin flashing in the lower right corner of the display external alarm (digital input), low superheating, MOP, LOP, Internal Energy Backup error or error in the
(if it's enabled in [F67]), indicating that the time set for the defrost has ended by the required electronic expansion valve.
temperature has not been reached. This can happen when the temperature set is too high, the time limit
is insufficient, the S2 sensor is disconnected or it isn't in contact with the evaporator. F61 - Low ambient temperature alarm (S1 sensor):
This is the ambient temperature (S1), below which the instrument will trigger the low temperature
F47 - Draining time (from water collected from defrosting): alarm. The differential for switching off the alarm is set in 0.1 ° C / 0.1 ° F. During the Fast Freezing
Time required for removing excess water, i.e. for the last drops of water to drain from the evaporator. operation, the low temperature alarm is deactivated. When this process is over it is reactivated when
During this period, all outputs remain switched off. This function can be turned off by setting it to the the temperature is no longer within the range of the alarm.
minimum value [OFF,].
F62- High ambient temperature alarm (S1 sensor):
F48 - Fan operation mode: This is the ambient temperature (S1), above which the instrument will trigger the temperature alarm.
[,,,0]- Automatic according to time: the fan will be on when the compressor is on. When the The differential for the alarm to switch off is fixed at 0.1 ° C / 0.1 ° F. This alarm takes into account the
compressor is off, the fan will oscillate according to the times set in [F49] and [F50]; temperature shown on the display and is therefore determined by the temperature reading locked
[,,,1] - Automatic according to temperature: When the compressor is switched on, the fan stays on. during the defrost cycle [F76].
With the compressor off, the fan turns on when the temperature is higher than the setpoint + 60% of the
hysteresis and turns off when the temperature is lower than the setpoint + 20% of the hysteresis; F63- Time to confirm the alarm by room temperature (S1):
[,,,2]- Continuous: the fan is always on; This is the length of time, during which the ambient temperature alarm (low or high) will be inactive,
[,,,3] - Dependent: the fan operates together with the compressor; even if the conditions exist to trigger it.
[,,,4] - For a period of time after the compressor is turned off: after turning off the compressor, the
fan will remain on for the time set in [F49]. F64- Room temperature alarm delay (power up):
Note1: Modes 0 and 1 will only switch the fan on if the temperature of the S2 sensor is lower than During this time the alarm remains off while waiting for the system to go back to an operating mode. The
the temperature of the S1 sensor. (low or high) ambient temperature alarms are enabled after this time has elapsed or the setpoint
Note2: Mode 1 will activate the fan only if the temperature of sensor S2 is lower than the temperature has been reached.
configured setpoint.
F65- Length of time door is open to trigger alarm:
F49 -Time fan is on if F48=0 or 4 When the door is opened, the message [Open] appears on the display and the door open timer
This is how long the fan is on for. starts. If this time is longer than the time that is set for this function, the alarm will be triggered
F50 - Time fan is turned off if F48=0 (automatic timed mode): F66- Maximum time compressor can be on without reaching the setpoint:
This is how long the fan is off for. The alarm is triggered if the compressor remains on without reaching the setpoint, for a longer time
than the length specified in this function.
F51 - Length of time door is open until fan is turned off F55=1 or 2:
This is the length of time that the fan will continue to run after the door is opened. If you set a minimum
F67-Trigger for alarm when defrosting is over based on time:
value of [OFF,], the fan will not switch off if the door is opened. If you set a value of r [,,,0], the fan
When the defrost cycle has been running for the length of time set, but has not reached the temperature
will switch off immediately if the door is opened.
set, the user is notified via a flashing dot in the lower right corner of the display ([,,,.]).
F52 - Fan cut off due to high temperature in the evaporator (S2 sensor):
This is intended to disconnect the evaporator fan when the ambient temperature is not within the design F68- Enable Buzzer:
range for the refrigeration device, avoiding high temperatures and suction pressures that could Enables or disables the internal buzzer to sound alarms.
damage the compressor. If the evaporator temperature exceeds the set value, the fan is turned off and
will be restarted at a fixed hysteresis of 2 ° C (3.6 ° F). This is a useful function to use when, for example, F69- Intensity of the digital filter on the ambient temperature sensor (S1 sensor) (Rising):
a refrigerator is used that has been idle for days or when restocking units or counters with products. F70- Intensity of the digital filter on the ambient temperature sensor (S1 sensor) (Descending):
The value set by these functions represents the time (in seconds) in which the temperature may vary
F53 - Temperature in the evaporator to switch the fan back on after draining: 0.1ºC / 0.1 ° F either up or down.
After drainage is complete, it starts a fan-delay cycle. The compressor will start up immediately,
because the temperature in the evaporator is high, but the fan will only start after the temperature in the Note: A typical use for this type of filter is in freezers for ice cream and frozen foods. When the door is
evaporator falls below the set value. This function is used to remove the heat in the evaporator after a opened, a quantity of hot air will fall directly on the sensor, causing a rapid rise in the temperature
defrost cycle, to ensure it is not opened up immediately to the ambient temperature. reading and, often, activating the compressor unnecessarily.
F71- Displacement of the values from the ambient sensor (S1 sensor): C08- Setpoint - LOP Protection (Low evaporation temperature):
F72- Displacement of the values from the evaporator sensor (S2 sensor): When the evaporation temperature is below this value, the electronic expansion valve (VEE) will gradually
F73- Displacement of the values from the suction line sensor (S3 sensor): open to increase the evaporation temperature of the system. This process will continue until the
F74- Displacement of the values (Offset) for the pressure transducer P1: evaporation temperature reaches the value set by this function.
This allows you to compensate for possible deviations in the reading of the sensor / transducer, due to
changing the sensor or changing the cable length. C09- Integral Time (Ti) - LOP Protection (Low evaporation temperature):
Time required to correct the difference between the recorded superheating and its setpoint, as a constant
F75-Preferred Indicator: value, when the stabilized evaporation temperature is below the LOP protection setpoint.
Sets a preference for what is shown on the display:
[,,,1] : Temperature from the ambient sensor S1; C10- Setpoint - MOP Protection (Low evaporation temperature):
[,,,2] : Temperatura do sensor do evaporador S2; When the evaporation temperature is above the value set for this function, the controller will gradually
[,,,3] : Temperature from the Suction Line sensor S3; close the electronic expansion valve (VEE) to keep the evaporation temperature below the set value. This
[,,,4] : Pressure; is intended to ensure that when superheating is very low, liquid does not flow back into the compressor.
[,,,5] :Superheating Temperature;
Note: Hysteresis for the parameter [,,C8] and [,C10] is set 2°C (3,6°F).
[,,,6] : Percentage that the Electronic Expansion Valve has been opened;
[,,,7] : Current Setpoint Value (normal or economic).
C11- Integral Time (Ti) - MOP Protection (Low evaporation temperature):
Note 1: When the device is operating in driver mode (c01=[On,,]), options 1,2 and 7 must not be
Time required to correct the difference between the recorded superheating and its setpoint, as a constant
selected, otherwise the message [info] will be shown on the display, indicating that it is not
value, when the stabilized evaporation temperature is above the MOP protection setpoint.
possible to view any information.
C12- Time for checking the protection alarms (LoSH, LOP, MOP):
F76- Ambient Temperature (S1 sensor) value locked in during defrosting: This is the length of time, during which the protection alarm (LoSH, LOP, MOP) will be inactive, even if the
[,,,0] : Temperature Reading from the ambient sensor S1 conditions exist to trigger it.
[,,,1] : Reading locked in - last temperature before defrosting
[,,,2] : Display “[deFr]'' C13- State of the Compressor in the event of protection alarms being triggered (ASHL, ALOP,
This function is intended to prevent the display reflecting an increase in the ambient temperature due to AMOP):
defrosting. [,,,0]- Compressor will not switch off when ASHL, ALOP or AMOP alarms are triggered;
[,,,1]- Compressor will switch off when ASHL alarm is triggered;
F77- Maximum length of time that the temperature is locked during defrosting: [,,,2]- Compressor will switch off when ASHL or ALOP alarm is triggered;
During a defrost cycle, either the last temperature measured during the refrigeration cycle or the [,,,3]- Compressor will switch off when ASHL or AMOP alarm is triggered;
message [deFr] will be kept on the display. The display will be released when the temperature [,,,4]- Compressor will switch off when ALOP alarm is triggered;
shown is reached again or the time set for this function has been exceeded, after the start of the next [,,,5]- Compressor will switch off when ALOP or AMOP alarm is triggered;
refrigeration cycle (whichever comes first). If set to the value [Off,], the temperature display will be [,,,6]- Compressor will switch off when AMOP alarm is triggered;
frozen only while defrosting. [,,,7]- Compressor will switch off when either the ASHL, ALOP or AMOP alarms is triggered.

F78- Function Lock Mode: C14-Time until the compressor switches on again after protection alarms are triggered (ASHL,
Enables and configures the Function Lock (see item 8.3.10). ALOP, AMOP):
[,,,0]: Function Lock can't be enabled This is the length of time that the compressor remains off after an alarm is triggered, according to the
[,,,1]: Partial lock can be enabled, whereby the control functions are locked but the setpoint can still defined option [c13].
be adjusted.
[,,,2]: Functions can be completely locked. C15- Total number of steps for the valve:
This functions sets the specific number of steps that the electronic expansion valve (EEV) will use.
F79- Function Lock Period:
Sets the time in seconds after the command that the functions will be locked. C16- Operating Speed (steps per second):
[,,15]- [,,60] Time in seconds after the command that the functions will be locked. This functions sets the operating speed according to the specifications of the electronic expansion valve
(EEV).
F80- Turns Off Control Functions:
Allows the control functions to be turned off (see item 8.3.11). C17- Minimum Valve Opening:
[Off,] : Does not allow the control functions to be turned off. This is the smallest percentage that the electronic expansion valve will open.
[,,,1] : Only allows control functions to be turned on or off if the functions are unlocked.
[,,,2] : Allows control functions to be turned on or off even if the functions are locked. C18- Maximum Valve Opening:
This is the largest percentage that the electronic expansion valve will open.
F81- Address of the instrument on the RS-485 network:
C19- Initial Valve Opening:
Address of the instrument on the RS-485 network that enables it to communicate with the Sitrad
This function defines the percentage that the electronic expansion valve will open when control begins.
software.
Note: You may not have any device on the network with the same address. C20- Time valve is used after initial opening:
This is the maximum time that the electronic expansion valve will be opened as set in the [c19] function.
Electronic Expansion Valve configuration functions [c01] to [c21] (displayed if [F01]=
717) C21-Time valve is used after initial opening after defrosting:
This is the maximum time that the electronic expansion valve will be opened as set in the [c19] function,
C01- Controller is in Driver mode: after a defrost cycle.
[Off,]: The device is responsible for controlling temperature, alarms and superheating.
[On,,]: The device is only controlling superheating and alarms. 9. PID CONTROLLER
When Driver mode is active, the device turns off the temperature control functions and only controls The PID controller is made up of a combination of three control actions: Proportional action (P), Integral
superheating and alarms. When the device is turned on, the COMP output will be activated, indicating action (I) and Derivative action (D). Each action receives a weighting (adjustable via parameters) which
that the controller has been powered on. represents a gain or adjustment time. This enables the PID to perform better when controlling the process.
The FAN output will be turned on after the controller initialization stage, which indicates that the device Any control action is limited by the quality and capacity of the existing actuators in the process.
is ready to receive an external signal for the electronic expansion valve to begin controlling P - Proportional gain (Kp) - The use of proportional action in a control system enables the difference
superheating. A signal (digital input) from an external controller activates the electronic expansion (error) between the desired output (reference, setpoint) and the current value of the process, to be
valve, which will then control superheating. reduced. The proportional gain speeds up process's response, however, the increased gains can result in
The DEFR output will be activated when the instrument receives an external signal and the electronic control oscillating.
expansion valve is ready to control superheating. The AUX output will be activated if the following I - Integral time (Ti) - The integral action has an energy storage function, which allows it to remove the
alarms go off: low superheating, MOP, LOP, Internal Energy Backup error or error in the activation of the error between the reference and the output. It accumulates the error at a '' Ti '' rate, and attempts to reduce
electronic expansion valve. it to zero. Low Ti values can cause the control to oscillate, however, long Ti times tend to slow down the
Note: When DRIVER mode is on, only the VEE indication LED can be activated. process. Integral action must not be used on its own.
D - Derivative time (Td) - The use of derivative action enables the process's response time to be
C02- Enable Internal Energy Backup (IEB): increased and reduces oscillation, as it tries to anticipate the process's behavior. Low Td values tend to
[Off,] :The Internal Energy Backup (IEB) is not being used. You must therefore use a solenoid valve reduce oscillation
to ensure the fluid line is closed if there is a power cut.
[On,,] :The internal energy backup system (IEB) will be available, which helps by closing the SUMMARY TABLE - GENERAL GUIDANCE*
electronic expansion valve if there is a power cut.
PID PARAMETER OVERSHOOT STABILIZATION ERROR
C03- Proportional Increase (Kp): (peakl) TIME (The difference
(delay in stabilizing the between the setpoint
Determines the proportional increase based on the PID Control Algorithm. and the sensor)
controller)

C04- Integral Time (Ti):


Increase KP** Increase Little Effect Reduce
Determines the Integral Time based on the PID Control Algorithm.

C05- Derivative Time (dT): Reduce Ti Increase Increase Null error


Determines the Derivative Time based on the PID Control Algorithm.
Increase Td Reduce Reduce No effect
C06- Setpoint - LoSH Protection (low superheating):
When the superheating temperature is below this value, the low superheat alarm will gradually close
the electronic expansion valve (VEE). Note: Change the parameters individually, check the response and then modify another parameter.
Note: Hysteresis for the parameter is set 1°C (1,8°F). Proceed with caution, use Sitrad Pro to monitor the behavior of the process, analyze and modify the
control parameters.
C07- Integral Time (Ti) - Low Superheating Protection: * This guide is widely applied in the technical literature on PID controllers, however processes with latency
Time required to correct the difference between the recorded superheating and its setpoint value, when in their response may differ from the indication in the table. The technician responsible for the process
the stabilized superheating temperature is below the LoSH protection setpoint (value defined by must correct small deviations manually.
[,C06]. ** In specific applications, the behavior can be opposite to that indicated.
10. WARNINGS / ALARMS / ERRORS 11. GLOSSARY
- °C: Temperature in degrees Celsius.
10.1 Warnings - °F: Temperature in degrees Fahrenheit
- Defr (defrost): Defrosting
[oPEn] Door open - LOC: Locked.
- No: No.
Pressure reading (before the amount of pressure is displayed, the - OFF: Turned Off / Deactivated
[PrES] configured unit of pressure is shown: Psi or Bar) - ON: Turned On / Activated.
- Refr: Refrigeration.
- SET: set or configure.
[,SH,] Superheating Temperature - EEV: Electronic Expansion Valve

[UEE,] Percentage that the Electronic Expansion Valve has been opened 12. CONNECTING CONTROLLERS, RS-485 SERIAL INTERFACE
AND COMPUTER
[t-1,] Temperature sensor 1
®

[t-2,] Temperature sensor 2 ®


Keep Sitrad update at
website: http://www.sitrad.com.br

[t-3,] Temperature sensor 3 Video on installing Sitrad


cab be downloaded at:
http://www.fullgauge.com.br/
[tSAt] Saturation Temperature videos/treinamentos-sitrad

[ECO,] Operating on the Economic Setpoint


A A
CONV. 32
B B or
RS-485 Network CONV. 256
[ClO,]
A B
Adjust / View the date and time B
A

A B
A
B B
A

A B
A
B B
A

A B
A
B

External
B A B A link
[DEFr] Temperature locked on defrosting cycle
MT-530 super
B A

MT-530 super
Earth

Instrumento

[,,,,.] Indicates that the final defrosting temperature has not been reached *WIRING BLOCK FOR SERIAL COMMUNICATIONS
It is used to connect more than one device to the Interface. The wires must be
connected as follows: Terminal A of the device is connected to terminal A of the
Information unavailable - check the parameter. RS-485 Serial Interface
[inFo] Preferred indicator (see parameter [F75])
wiring block, which in turn, must be connected to terminal A of the Interface.
Repeat the process for terminals B and , being the cable loop (optional Hardware used to connect Full Gauge
Control devices to Sitrad®.
ground). The cash dispenser terminal must be connected to the respective
Tray is defrosting - pre-defrost and draining
@Flashing
Led stages
terminals of each instrument.
*Sold separately
13. OPTIONAL ITEMS - SOLD SEPARATELY
$piscante
Led Fast Freezing Mode Indicated
EasyProg - version 2 or higher
This is an accessory, whose main function is to store the parameters of the controllers. You can load new
[Man,] The Electronic Expansion Valve is operating in Manual Mode parameters from a controller at any time, and download them to a production line (from the same
controller), for example.
The Electronic Expansion Valve is closed as there is no
[8888] electricity
It has three types of connection for loading or clearing parameters:
- Serial RS-485: Connect it to the controller using the RS-485 network (only controllers that can access
RS-485).
[LOC,][On,,] Function Lock - USB: If connected to the computer by a USB port, it can use Sitrad's Program Editor.
- Serial TTL: The controller can connect directly to
[LOC,][OFF,] Functions Unlocked EasyProg by a Serial TTL connection.

[Off,] Control functions off EASYPROG

10.2 Alarms IMPORTANT


IN ORDER TO COMMUNICATE WITH
[AoPn] Open door alarm EASYPROG, THE EQUIPMENT MUST
NOT BE LINKED TO SITRAD SOFTWARE.
[Athi] High ambient temperature alarm
Extended Panel
[atLO] Low ambient temperature alarm Full Gauge Controls extended panel allows controllers to be installed in Evolution and Ri lines, whose
maximum size is 76x34x77mm (the opening must measure 71x29mm for the extended panel to be
Alarm because the compressor is on and has not reached the installed), as the opening does not need to be precise for the device to be properly installed. The panel
[Alrc] setpoint has space to be branded with the company logo and contact information, and it has 10A switches (250 V
ac) that can be used for switching on internal lighting, ventilation or fan systems.
[inib] Audible alarm deactivated

[Alre] Digital input alarm (external alarm)

[ASHL] Low superheating alarm

[AlOp] Low evaporation temperature alarm

[AmoP] High evaporation temperature alarm

10.3 Errors
14. ANNEXES - Reference Diagrams
[Ert1] Error in temperature sensor 1 CONTROLLER
Diagram V
X
[Ert2] Error in temperature sensor 2

[Ert3] Error in temperature sensor 3

[ErP1] Error in the pressure transducer


Y

[ErSH] Error in the superheating calculation

[EClO] Clock not set


PANEL

[EiEb] Error in the Internal Energy Backup (IEB) system DIAGRAM VI PANEL
CONTROLLER
[ECAl] Contact Full Gauge

[PPPP] Reset function values


Error with the Electronic Expansion Valve.
To clear the error it is necessary to swicth off and swicht on the
[ErUE] controller to restart the unit. To ensure it is properly and safely
(* Also please check coil valve if wiring connections are properly installed, connect all leads before
connected or if are connected). CLASPS
putting the controller in position.
15. WARRANTY

ENVIRONMENTAL INFORMATION
Packaging:
Full Gauge products use packaging made from entirely recycled materials. Please dispose of it through specialized
recyclers.

Product:
The components used in Full Gauge controllers can be recycled and reused if they are dismantled by specialists.

Disposal:
Do not burn or throw controllers in the domestic waste, once they have reached the end of their working life. Follow the
current legislation applicable to your area in relation to disposing of electronic waste. If you have any questions, contact Full
Gauge Controls.

Products manufactured by Full Gauge Controls, from May 2005, have a warranty period of 10 (ten) years direct from the
factory and 01 (one) year from accredited retailers, starting from the consignment date on the sales invoice. After this year,
the warranty will continue to be honored for purchases from retailers if the device is sent directly to Full Gauge Controls. This
period is valid in Brazil. Other countries provide a guarantee for 2 years. The products are guaranteed in the event of a
manufacturing fault that makes them unsuitable or inappropriate for the uses to which they were intended. The warranty is
limited to the maintenance of devices manufactured by Full Gauge Controls, regardless of any other form of costs, such as
any indemnity due to damage caused to other equipment.
WARRANTY - FULL GAUGE CONTROLS

WARRANTY EXCEPTIONS

The Warranty does not cover transport and / or insurance costs for sending products believed to have defects or to have
malfunctioned to Technical Support. The following events are also not covered: natural wear of parts, external damage
caused by falls or improper packing of products.

LOSS OF COVER
The product will automatically no longer be covered if:
-The instructions for use and assembly contained in the technical description and installation procedures listed in the
NBR5410 standard are not observed;
- It is subjected to conditions beyond the limits specified in its technical description;
- If it is opened up or repaired by a person who is not part of Full Gauge's technical team;
- The damage which has taken place was the result of a fall, blow or impact, water damage, electrical surge or atmospheric
discharge.

USING THE WARRANTY


To take advantage of the warranty, the customer must send the product properly packed, together with the
corresponding purchase invoice, to Full Gauge Controls. The delivery cost for the product is borne by the client. You will
also need to send as much information as possible regarding the defect that has been detected, thus making it possible to
streamline the analysis, testing and servicing.
These processes and any eventual maintenance of the product will only be carried out by Full Gauge Controls' Technical
Support, at the Company's head office - Rua Júlio de Castilhos, 250 - Zip Code 92120-030 - Canoas - Rio Grande do Sul -
Brazil. Rev. 03

Copyright 2021 Full Gauge Controls All rights reserved


Refrigerated Solutions Group
891 County Road U
Hudson, WI 54016

800-955-5253 Norlake Foodservice Sales


800-477-5253 Norlake Scientific Sales
800-388-5253 Norlake Parts/Service
800-647-1284 Master-Bilt Sales
800-684-8988 Master-Bilt Parts/Service
Email: [email protected]

PN: 219828
REV 3/22

You might also like