RCS-931A (M) X Instruction Manual en Demostic General X R1.01 (En XLBH0105.0086.0002)
RCS-931A (M) X Instruction Manual en Demostic General X R1.01 (En XLBH0105.0086.0002)
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER!
It means that death, severe personal injury, or considerable equipment damage will occur if safety
precautions are disregarded.
WARNING!
It means that death, severe personal, or considerable equipment damage could occur if safety
precautions are disregarded.
CAUTION!
It means that light personal injury or equipment damage may occur if safety precautions are
disregarded. This particularly applies to damage to the device and to resulting damage of the
protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
Earth
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Copyright
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
Table of Contents
Preface ....................................................................................................................................... i
Introduction ........................................................................................................................ i
2.7.8 Auto-reclosing................................................................................................. 11
8.2.7 VERSION.......................................................................................................... 98
Chapter 1 Introduction
1.1 Application
RCS-931 is a digital line differential protection with the main and back-up protection functions,
which mainly is designed for transmission line of 220kV and above. It can be applied in the
overhead lines and underground cables.
The main protection of RCS-931 comprises of phase segregated differential protection using
phase current and DPFC current, and zero-sequence current differential protection, which can
clear the fault without delay for the whole line. DPFC distance protection can reach to extremely
fast speed for the fault near the busbar.
RCS-931 can implement single-phase or three-phases tripping and configure auto-reclosing that
can implement 1-pole AR, 3-poles AR and 1/3-pole AR.
BUS
52
51GVT 79 25 FR
LINE
Where:
79: Auto-reclosing
25: Synchrocheck
Note!
1.2 Function
LINE CURRENT DIFFERENTIAL PROTECTION
Note!
BACKUP PROTECTION
ADDITIONAL PROTECTION
synchro-checking (25)
Event Recorder including 64 binary input change reports, 64 self-supervision reports and 256
miscellaneous reports.
Disturbance recorder including 64 fault reports, and 24 oscillograms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
Fault location
GPS clock synchronization - second pulse, minute pulse, RS-485 difference level and IRIG-B
synchronization
High-speed 64 Kbit/s PCM channel or 2048 Kbit/s dedicated optical fiber channel for
differential protection data exchanging
COMMUNICATIONS
1 RS-232 or RS-485 (can be set by jumper) communication rear ports for printer
1.3 Features
Quickly clearing the internal fault for whole line, the time is less than 10 ms for fault where is
near the busbar, less than 15ms for fault where is in the center of line and less than 25ms for
fault where is in the remote end.
The unique DPFC distance element is integrated in the protective device, which can clear the
internal fault quickly with high sensitivity and high speed and is not influenced by power
swing.
Self-adaptive floating threshold which only reflects deviation of power frequency component
can defend system imbalance and system disturbance. Hence, it is both rather reliable and
very fast, and it is very sensitive but does not pickup frequently.
Plug connectors from the relay rear panel to the terminal blocks on the rack or cabinet, which
makes the on-site commissioning and replacement much easier than what you do the
commissioning using the traditional screw terminals on the rear panel.
Two independent data acquisition paths, one for fault detector element and another for
protections and logic functions, to prevent any undesired trip.
The CT ratio of two terminals could be different. Different ratio of various CT on each terminal
could be regulated by configurable coefficients in software.
The communication channel could be monitored automatically. Bit error rate could be
displayed online. Differential protection will be blocked during channel failure.
The relay could send and receive tripping command to and from same type protection of
opposite terminal via fiber optical channel.
Friendly HMI interface with LCD and 9 button keypad on the front panel.
24 samples per cycle, all task including data measurement, protection calculation, logic
discrimination, event recording and protection logic calculation could be done within one
sampling interval.
2. Analog voltage
Port number 2
Connector type RJ-45
Transmission rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103: 1997 or IEC 61850
Safety level Isolation to ELV level
Port number 2
Connector type SC
Ethernet
Transmission rate 100Mbits
Transmission standard 100Base-TX
Transmission distance <1500m
Optical
Optical fibre type Multi-mode or single-mode
(Optional)
Wave length 853/1310nm for multi-mode
1310/1550nm for single-mode
Fibre size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC 60870-5-103: 1997 or IEC 61850
Safety level Isolation to ELV level
Per IEC60068-2-1:1990
Dry cold test
Test Ad for 16 h at -25°C
Per IEC60068-2-2:1974
Dry heat test
Test Bd for 16 h at +55°C
Per IEC60068-2-30:1980
Damp heat test, cyclic Test Db Two (12+12) hour cycles 95%RH, low temperature +25°C,
high temperature +55°C
Radiated amplitude-modulated
Spot frequency
Radiated amplitude-modulated
Radiated pulse-modulated
2.6 Certifications
ISO9001: 2000
ISO14001:2004
OHSAS18001: 1999
CMMI L2
Accuracy: ≤1%Setting+40ms
Accuracy: ≤1%Setting+40ms
Tolerance will be higher in case of single-phase fault with high ground resistance.
2.7.8 Auto-reclosing
Phase difference tolerance for synchronism checking: <±3°
If any of the above fault detection elements operates, the GFD will operate to provide DC power
supply to the output relays to enable the output circuit.
The criterion:
Where:
If the DPFC overcurrent fault detector element operates, DC power supply will be provided to
output relay for 7 seconds.
where:
3I0: zero sequence current derived internally at the terminal from the three-phase currents
3I0Cal: zero sequence current calculated depending on the summation of IA, IB and IC (i.e.,
3I0Cal=IA+IB+IC)
If the zero sequence overcurrent fault detector element operates, DC power supply will be
provided to output relay for 7 seconds.
When CT circuit failure is detected, this element will be disabled and an alarm [Alm_CTS] will be
issued.
Note!
The zero sequence current should be connected to the protective device; otherwise all
relevant protection elements will be blocked.
If the circuit breaker pole discrepancy fault detector element operates, DC power supply will be
provided to output relay for 15 seconds.
Note!
opposite end of line, the transfer trip fault detector element operates, and DC power supply will be
provided to output relay for 500ms.
jX
Zzd
Zk
R
Zs+Zk
-Zs
Figure 3.3-1 shows the operation characteristic of the DPFC distance element on R-X plane when
a fault occurs in forward direction, which is the circle with the –Zs as the center and the│Zs+Zzd│
as the radius. When measured impedance Zk is in the circle, the DPFC distance element will
operate. The DPFC distance element have a large capability of enduring fault resistance. When
there is infeed current from power source at the other end in the fault resistance, the phase of Δ
IN is the same as Δ I and the phase of voltage of fault resistance is same as Δ I, so the fault
resistance appears resistive and is in parallel with R axes. The overreaching problem that results
from infeed current can be prevented.
jX
Z's
Zzd
-Zk
Figure 3.3-2 shows the operation characteristic of the DPFC distance element on R-X plane when
a fault occurs in reverse direction, which is the circle with the Z′s as the center and the │Z′s-Zzd│
as the radius. The region of operation is in the quadrant 1 but the measured impedance –Zk is
always in the quadrant 3, so the DPFC distance element will not operate and have the definite
directionality.
Note!
The DPFC distance protection can be enabled or disabled by corresponding logic setting
and binary input. Please refer to section 7.3.
Note!
DPFC current differential element and phase current differential element are phase
segregated current differential protection.
EM EN
52 52
Ia,Ib,Ic
RCS-931 RCS-931
Where:
Φ: phase A, B or C.
4U N
I H : Max([I_H_Diff], 4 I Cap , )
X c1
Note!
The real capacitance current is the differential current not compensated under normal
condition.
Note!
When RCS-931 is applied for long transmission line, Xc1 is the real positive sequence
capacitive impedance of line. However, for short transmission line, both the real
capacitance current and 4UN/Xc1 are small, so the DPFC current differential element has a
high sensitivity. In order to decrease the sensitivity of DPFC current differential element, it
can be achieved through decreasing Xc1 properly or increasing the setting [I_H_Diff].
I CD 0.75 I R
(Equation
I CD I H
3.4-2)
Where:
2. Stage 2
I CD 0.75 I R
(Equation
I CD I L
3.4-3)
Where:
1.5U N
I L : Max([I_L_Diff], 1.5 I Cap , )
X c1
When the above criteria is met, the stage 2 of phase current differential element will operate after
40ms delay.
criteria is
I CD0 0.75 I R 0
I
CD0 I QD 0
(Equation
I CDBC 0.15 I R 0
I
CDBC I L
3.4-4)
Where:
I QD0 : the pick-up setting of zero-sequence overcurrent fault detector element [I_ROC_FD].
0.6U N
I L : Max( I QD0 , 0.6 I Cap , )
X c1
If the alarm, [Alm_VTS] or [Alm_Xc], is issued, the capacitance current compensation will be
disabled automatically. The operation criteria is changed to:
I CD0 0.75 I R 0
I
CD0 I QD 0
(Equation 3.4-5)
I CD 0.15 I R
I
CD I L
1.5U N
I L : Max([I_L_Diff], 1.5 I Cap , )
X c1
When the above criteria is met, the zero sequence differential current element will operate after
100 ms delay.
sensitivity of zero-sequence current differential element when a ground fault associated with fault
resistance occurs, capacitance current must be compensated to eliminate the effect that
capacitance current has on differential current. The traditional method of compensating
capacitance current can only compensate steady-state capacitance current. However, during the
transient period, such as closing circuit breaker to no-load line, clearing external fault and so on,
there are large transient capacitance current in the line. The traditional method can not
compensate the capacitance current completely, hence, a new method is available in the RCS-931,
which can compensate transient component of capacitance current.
Phase capacitance current of line can be derived from “∏” equivalent circuit. For normal operation
condition, closing circuit breaker to no-load line and clearing external fault, not only steady-state
component of capacitance current but also transient component of capacitance current can be
compensated.
Because a part of capacitance current has been compensated by shunt reactor, reactance current
IL must be subtracted from capacitance current calculated above
Because capacitance current is very small, the sensitivity of current differential protection can still
meet the requirement. The function, capacitance current compensation, will be disabled
automatically if differential current is smaller than 01IN.
3.4.5 CT Supervision
If CT circuit failure occurs, an alarm [Alm_CTS] will be issued. When CT circuit failure occurs on
an end, the fault detector element and current differential protection on this end might operate at
once. However, fault detector element on another end will not operate, so no permissive signal is
sent to the opposite end of line. Hence, the current differential protection will not maloperate.
Meanwhile, RCS-931 of the healthy end will issue alarm [Alm_Diff] which will be treated as the
same as the alarm [Alm_CTS].
When CT circuit fails, and fault detector element operates caused by an internal fault or system
disturbance, the differential protection will be blocked if the logic setting [En_CTSBlkDiff] is set as
“1” and will operate if it is set as “0” and the differential current of corresponding phase is higher
than the setting [I_Diff_CTS].
3.4.6 CT Saturation
CT transient saturation might occur concurrently with external fault . Since the equipment adopts
high restraint factor and self-adaptive floating restraint threshold, it will not operate even in serious
saturation case.
[ID_Local] is greater than [ID_Remote] is chosen as a master. The master end sends sampling
information to the slave end with regular interval while the slave adjusts its sampling interval at
any time. The slave end sends three-phase current sampling value to the master if the
synchronism condition is met. Otherwise synchronism program is initiated until the synchronism
condition is met.
1) The routine of both direction shall be same to each other, so the time delays of both direction
are the same.
2) The maximum one-way channel propagation delay shall be less than 15 ms.
64Kbit/s or 2Mbit/s
TX RX
Pig Tail Pig Tail
RX TX
RCS-931
RCS-931
The protective device sends data and receive data based on independant clock respectively,
which are called transmit clock (i.e. clock Tx) and receive clock (i.e. clock Rx) respectively. Clock
Rx is fixed to be extracted from data frame, which can ensure no slip code and and not to receive
error data code. Clock Tx has two options:
1) Use internal crystal clock, which is called internal clock. (master clock)
Depend on the difference of clock used by RCS-931 of two ends, there are three modes.
1. Master-master mode
clock Tx clock Tx
64 kbit/s 64 kbit/s
clock Rx clock Rx
2. Slave-slave mode
Tx Tx
64 Kbit/s 64 Kbit/s
clock Tx clock Tx
(master) (slave)
64 Kbit/s 64 Kbit/s
clock Rx clock Rx
Rx Rx
RCS-931 installed RCS-931 installed
on the end on the other end
3. Master-slave mode
One of them uses internal clock, the other should use external clock. (not recommended)
Depending on the logic setting [En_InnClock], RCS-931 line differential relay selects the
communication clock mode. The inner clock is enabled automatically when the logic setting
[En_InnClock] is set as “1”. Contrarily, the outer clock is enabled automatically when the logic
setting [En_InnClock] is set to “0”.
Set both of the settings [En_InnClock] as “1” for protection equipments of two terminal.
Set both of the settings [En_InnClock] as “0” for protection equipments of two terminal.
3) using 2048 Kbit/s dedicated optical fibre channel for data exchanging.
Set both of the settings [En_InnClock] as “1” for protection equipments of two terminal.
When the protection message is switched-in to 2048 Kbit/s board of SDH through coaxial
cable and the retiming function of 2048 Kbit/s channel of SDH is forbid, setting the setting
[En_InnClock] as “1” for protection equipment of two terminal. (recommended)
When the protection message is switched-in to 2048 Kbit/s board of SDH through coaxial
cable and the retiming function of 2048 Kbit/s channel of SDH is initiated, setting the setting
[En_InnClock] as “0” for protection equipments of two terminal.
When the protection message is switched-in to 2048 Kbit/s board of SDH through switching
channel, the setting of the setting [En_InnClock] must be matched with other equipment used
to switch channel.
Propagation speed
64 Kbit/s 2048 Kbit/s
Jumper option
JP301-OFF, JP302-OFF -16dBm -16dBm
JP301-ON, JP302-OFF -9dBm -12dBm
JP301-OFF, JP302-ON -7dBm -9dBm
JP301-ON, JP302-ON -5dBm -8dBm
Propagation speed
64 Kbit/s 2048 Kbit/s
Jumper option
JP302-OFF -13.0±2.0dBm
Sending power
JP302-ON -3.0±2.0dBm
Propagation JP201-OFF 64 Kbit/s
speed JP201-ON 2048 Kbit/s
Note!
When using dedicated optical fibre channel, if the transmission distance is longer than
50km, the transmitted power must be enchanced to make received power larger than
receiver sensitivity with some margin (3~10 dB) by setting corresponding jumper.
Note!
When transmission distance is longer than 80km using dedicated optical fibre channel,
please notice before ordering and it will be considered as special project using 1550nm
laser diode.
Note!
When using multiplex channel, jumper needn’t be set and sending power is default.
BI_52b_Phb &
BI_52b_Phc
&
Max(IA, IB, IC)>0.06In
[En_DiffP] &
Channel abnormal
& ≥1 &
IA>[I_H_Diff] or [I_L_Diff]
1. The current differential protection will be enabled only if virtual binary input [VEBI_DiffP] and
logic setting [En_DiffP] are set as “1”.
2. DPFC current differential element, phase current differential element and zero-sequence
current differential element is phase segregated, including Phase A, phase B and phase C.
3. Permissive signal for current differential protection on remote end will be sent if the circuit
breaker is on open position or the differential relay controlled by fault detection operates.
4. At the moment of CT circuit failure, fault detector element and current differential protection
on faulty end might operate, but fault detector element on healthy end will not operate and
permissive signal will not be sent from the healthy to the faulty end. So RCS-931 will not
maloperate.
However, if internal fault occurs or the fault detector operates due to system disturbance, CT
circuit is failure in the same time, there are two possibilities:
If the logic setting [En_CTSBlkDiff] (differential protection being blocked during CT circuit
failure) is set as “1”, the differential protection will be blocked.
If the logic setting [En_CTSBlkDiff] is set as “0” and the differential current of the faulty phase
is more than the differential current setting [I_Diff_CTS] during CT circuit failure, the
differential protection will operate with alarm signal being issued at the same time.
The distance protection provides the fast and reliable protection for overhead lines and power
cables in all kinds of power networks. For each independent distance element zone, full scheme
design provides continuous measurement of impedance separately in three independent
phase-to-phase measuring loops as well as in three independent phase-to-ground measuring
loops.
Phase-to-phase distance element is suitable as a basic protection function against two- and
three-phase faults in all kinds of networks, regardless of the treatment of the neutral point.
Independent setting for each zone separately makes it possible to create fast and selective
protection in power systems.
Phase-to-ground distance element serves as basic earth fault protection in networks with solidly
or low impedance grounded networks. Independent setting for each zone separately makes it
possible to create fast and selective protection in power systems.
Polarized positive sequence voltage is used for distance protection so that faults with high
resistance can also be cleared easily. In case of short lines, in order to enhance performance
against high fault resistance, the impedance characteristic of the zone 1 and zone 2 could be
inclined toward quadrant 1.
Zero sequence reactance character is used for phase-to-ground distance element so that
overreach due to resistance earth fault could be avoided.
If the positive sequence polarized voltage is high enough, directionality of the distance protection
using positive sequence polarized voltage is very good. However, when close-in three phase fault
happens, the positive sequence voltage may reduce to 10% or less, the distance protection will go
to low voltage program (please refer to section 3.5.1) in which memorized positive sequence
polarized voltage is used instead.
Threshold will be set forward for zones 1 and 2 of distance element before it operates, so that
directionality could be assured for three-phase fault very close to busbar. And this threshold will
be changed to reverse direction after it operates, so that forward close-in three phase fault can be
fully cleared. As to the zone 3 of the distance element, direction of the threshold is always reverse,
because it acts as a backup protection for busbar.
Note!
When VT circuit failure happens, the alarm [Alm_VTS] displayed, all distance protection
will be disabled.
Distance element with memorized polarization is an algorithm used when positive sequence
voltage reduces to 10% or less. There are only two possibilities for this condition: power swing or
three phase short circuit fault.
As the power swing will be identified by power swing blocking function, only three phase short
circuit should be considered and discussed herein.
Because three phase-to-ground impedance and three phase-to-phase impedance are equal in
case of three phase short circuit fault, so only phase-to-ground impedance should be measured.
Impedance of all three phase are usually equal. But in order to ensure fast tripping even in the
case of transition from bus fault to three phase line fault, all of three phase impedance are
calculated and operation of any phase element will lead to three phase tripping.
3.5.1.2 Design
Distance element with memorized polarization compares phasor angle of operating voltage and
polarized voltage.
This does not mean it will operate incorrectly during reverse direction fault but means it will
operate correctly during forward fault even if the fault occurs just on the outlet because that is
derived supposing forward direction fault. If power angle δ does not equal to 0, the circle with the
line connecting ends of Z ZD and Z S as a chord will move toward quadrant 1or 2.
jX
ZZD
ZK
ZS
Figure 3.5-2 shows operation characteristic of measured impedance Z K on R-X plane. This
characteristic is a circle with line connecting ends of Z ZD and Z ' S as the diameter. It will
operate only when Z K is in the circle. Therefore directionality of the protection is explicit.
jX
Z'S
ZZD
R
ZK
The conditions mentioned above are before fading of memorized voltage, in another word, they
are transient characteristic.
When the memorized voltage fade, Figure 3.5-3 shows operation characteristic of measured
impedance ZK on R-X plane for forward direction fault as well as that of -ZK for reverse direction
fault. Since the circle covers the origin, the equipment will be just on the margin of operation for
fault on the bus or line outlet. In order to prevent the mal-operation for bus fault, especially the
three phase bus fault with arc resistance, zone1 and 2 of distance element is equipped with a
positive threshold. Voltage value of the threshold is equal to maximum voltage drop of the arc.
Moreover, when zone 1 or 2 of distance element operates, phase of the threshold voltage will be
inverted so that the origin can be enclosed in the characteristic circle to ensure the fault can be
fully cleared. In order to ensure backup protection of zone 3, phase of threshold voltage is always
inverted and the origin is always enclosed in the characteristic circle.
jX
ZZD
ZK
Figure 3.5-3 Steady state characteristic of three phase short circuit fault
jX
ZS
In short line case, in order to improve the relay performance against high fault resistance, phase
shift θ1 is used for polarized voltage. This phase shift could move the directional impedance
characteristic toward quadrant 1 as is shown in Figure 3.5-4. Value of θ1 can be set to 0°, 15°or
30°.
This relay could measure high fault resistance and keep a very satisfied performance under high
fault resistance condition. However, if there is a considerable power source in remote end, an
overreach caused by infeed from remote end during resistance earth fault may occur. In order to
prevent overreach, the following zero sequence reactance relay is introduced.
Typical zero-sequence reactance characteristic is shown as the straight line A in Figure 3.5-4.
Therefore, directional impedance characteristic integrating with the zero sequence characteristic
are adaptive with the fault resistance.
The no-memorized positive sequence voltage is used as polarized voltage because during earth
fault, positive sequence voltage is mainly formed by healthy phase and the phase of positive
sequence voltage is kept as it was before the fault. So characteristic of zone 3 of phase–to-earth
distance element is the same as the transient characteristic of distance element with memorized
polarization and have a very good directionality.
Phase shift θ2 is introduced here for polarized voltage in zones 1 and 2 just like θ1 in case of
phase-to-ground distance element. It is used also for improving performance against high fault
resistance in short line case. Value of θ2 can be set as 0°or 15°or 30°.
If three-phase short circuit fault occurs, since the polarized voltage has not been memorized, its
operation characteristic is a circle passing through the origin (Please refer to Figure 3.5-3). If the
positive sequence voltage is low, the fault will be measured by impedance element with
memorized polarization. There is neither problem about dead zone nor loss of directionality for
bus fault in this case.
Because zone 3 phase-to-phase distance element intends to provide backup protection for
backward busbar fault, the threshold of it is always inverted and it will operate when backward
busbar fault happens.
jX
B ZZD A
RZD
Φ
R
RZD
In order to ensure distance relay not affected by load impendence, the phase-to-phase and
phase-to-ground blinders are used. As shown in Figure 3.5-5, the slope of blinder is same to
positive sequence sensitivity angle Φ, RZD is the setting [R_Blinder]. The operation region is
between line A and line B. The logic setting [En_Blinder] can decide whether the blinder is
enabled or not.
Power swing blocking for distance element will be released if any of the following PSBR elements
operate.
If any of the following condition is matched, FD PSBR will operate for 160ms.
1) Positive sequence current is lower than the setting [I_OC_PSB] before general fault detector
element operates.
2) Positive sequence current is higher than the setting [I_OC_PSB] before general fault detector
element operates, but the duration is less than 10ms.
I0+I2>m×I1
The “m” is a internal fixed coefficient which can ensure UF PSBR operate during power swing with
internal unsymmetrical fault, while not operate during power swing or power swing with external
fault.
If a three-phase fault occurs and FD PSBR is invalid (160ms after GFD operates), neither FD
PSBR nor UF PSBR will be able to operate to release the distance protection. Thus, SF PSBR is
provided for this case specially. This detection is based on measuring the voltage at power swing
center:
UOS=U1×COSΦ
Where:
When three-phase circuit breaker is in the unsymmetrical state, PD PSBR will operate if any of the
following conditions is met.
1) The faulty phase selected by fault phase selection element is not the phase tripped.
2) The difference of current deviation of power frequency component between two unfaulty
phases increases to certain value all of a sudden.
UF PSBR ≥1 &
≥1
PD PSBR
10ms 0
I1 > [I_OC_PSB]
0 160ms
&
Fault Detector ≥1
&
& PSBR_Z1/2
Zone 2
Figure 3.5-6 Logic diagram of PSBR for zone 1 and zone 2 of distance element
The logic setting [En_PSB] is common for zone 1, 2 of distance element. If the logic setting
[En_PSB] is set as “0”, zone 1 and zone 2 of distance element is not blocked by PSBR and PSBR
for zone 1 and zone 2 of distance element will operate right now (i.e. output state of [PSBR_Z1/2]
is “1”).
If the logic setting [En_PSB] is set as “1”, zone 1, 2 of distance element is controlled by PSBR.
After zone 2 of distance element operates and PSBR condition is also met, PSBR for zone 1 and
zone 2 of distance element will operate (i.e., output state of [PSBR_Z1/2] is “1”).
Z < [Z_PG1]
&
[En_ZPG1] ≥1
& [Op_Z1]
Z < [Z_PP1]
&
[En_ZPP1]
[PSBR_Z1/2]
[En_ZPG2]
& [t_PG2]
Z < [Z_PG2]
&
≥1 [Op_Z2]
&
Z < [Z_PP2]
& [t_PP2]
[En_ZPP2]
[En_ZPG3]
& [t_PG3]
Z < [Z_PG3]
≥1 [Op_Z3]
Z < [Z_PP3]
& [t_PP3]
[En_ZPP3]
If the logic setting [En_Blinder] is set as “1”, the reach of distance protection will be restricted on a
long line or during heavy load condition.
The conventional distance protection can manage the fault clearance of earth-faults in most of the
cases. In some applications, especially applications with long lines, the clearance can be
improved by use of an instantaneous zero-sequence overcurrent protection. Those are for
instance:
1. In the case of high infeed of fault current from the opposite end of the line, this might increase
the fault resistance seen by the distance relay to such a value that the instantaneous zone of
the distance protection will not operate.
2. In applications with series compensated lines, where the capacitor is located at the end of the
line and very strong infeed of fault current from that end, will result in a difficult problem for the
distance protection to perform a selective fault clearance. This due to the voltage reversal that
might occur.
3I0>[I_ROC_FD]
&
3I0Cal>[I_ROC_FD]
& ROC DIR+
F0+
F0-
& ROC DIR-
T1
3I0Cal > [I_ROC2] & Op_ROC2
&
≥1
T2-500ms 500ms
[En_Dir_ROC3] &
Where:
T1: [t_ROC2] (the time delay of stage 2 of directional zero-sequence overcurrent protection)
T2: [t_ROC3] (the time delay of stage 3 of directional zero-sequence overcurrent protection)
When bus VT circuit failure happens, the distance protection will be disabled. As a substitute,
phase overcurrent protection and zero-sequence overcurrent protection will be put into work
automatically in this case if the binary inputs [EBI_DistP] and [EBI_ROC] are energized.
3I0>[I_ROC_FD]
&
3I0Cal>[I_ROC_FD]
&
3I0Cal>[I_ROC_VTS]
[t_OC/ROC_VTS]
≥1 Op_OC_VTS
VT circuit failure
&
IP>[I_OC_VTS]
Figure 3.6-2 Logic diagram of zero-sequence/phase overcurrent protection when VT circuit failure
If the logic setting [Opt_Dly_ROC3] is set as “1”, the stage 3 of directional zero-sequence
overcurrent protection will operate with a time delay of the setting [t_ROC3] before the protective
device trips and the time delay will reduce 500ms after the protective device trips.
All stages of directional zero-sequence overcurrent protection are under the control of
zero-sequence overcurrent element, so the current setting for each stage should be greater than
[I_ROC_FD]. For pilot directional zero-sequence protection, the setting [I_ROC_FD] is used as
current setting in the reverse direction and the setting [I_ROC_TeleP] is used as current setting in
the forward direction.
The SOTF (switch onto fault) protection is a complementary function to the distance protection
and to the directional zero-sequence overcurrent protection. With the SOTF protection, a fast trip
is achieved for a fault on the whole line, when the line is being energized. It shall be responsive to
The SOTF protection shall be controlled by an reclosing logic using both voltage and current level
detectors. It shall be enabled for a period when the circuit is energized either manually or via a
auto-reclosing system.
3-Pole AR
≥1
& 100ms 0
Manually closing
& ≥1 Op_ROC_SOTF
3I0Cal > [I_ROC_SOTF]
& 60ms 0
1-Pole AR
Zero-sequence SOTF protection will operate to trip three-phase circuit breaker with a time delay
of 60ms when 1-pole auto-reclosing.
Zero-sequence SOTF protection will operate to trip three-phase circuit breaker with a time delay
of 100ms if 3I0Cal is greater than setting [I_ROC_SOTF] when 3-pole auto-reclosing or closing
manually.
[En_LineVT]
&
1-pole AR or 3-pole AR
&
Z < [Z_PG2]
&
[PSBR_Z1/2]
≥1
&
Z < [Z_PP2]
≥1
&
[En_Z2SOTF_AR3P]
≥1
&
[En_Z3SOTF_AR3P]
10ms
Z < [Z_PG3] &
≥1
≥1 Op_Z_SOTF
Z < [Z_PP3]
≥1 25ms
&
Manually reclosing
3-pole AR
Zone 3 of distance element for SOTF will operate to trip three-phase circuit breaker when
reclosing manually.
Zone 2 and 3 of distance element for SOTF without PSBR logic will operate to trip three-phase
circuit breaker if the logic setting [En_Z2SOTF_AR3P] and [En_Z3SOTF_AR3P] are set as “1”
when 3-pole auto-reclosing.
Zone 2 of distance element for SOTF with PSBR logic will operate to trip three-phase circuit
breaker when 1-pole or 3-pole auto-reclosing if the logic setting [En_Z2SOTF_AR3P] is set as “0”.
The logic makes the relay ideal for single-phase tripping applications.
If ΔUOΦMAX is several times higher than the other two deviation of phase operation voltages, the
single-phase fault is ensured, otherwise, the multiplex-phase fault is ensured.
Region A
60° -60°
Region B Region C
180°
The operation of the contact based pole discordance logic is based on checking the position of the
circuit breaker through six of its auxiliary contacts: three parallel connected normally open
contacts are connected in series with three parallel connected normally closed contacts.
Pole disagreement procedure comprises of the protection of pole disagreement state and switch
onto fault protection. When the following conditions are met, pole disagreement state is ensured
delay 30ms.
1. Trip confirmation
5. When tripped phase current is greater than 0.06IN or corresponding phase [BI_52b_Phx]=0 (x
can be a, b or c), SOTF protection is initiated for 200ms
2. When threes currents, IA, IB and IC, are greater than 0.06IN or [BI_52b_Pha]=0,
[BI_52b_Phb]=0, [BI_52b_Phc]=0, SOTF protection is initiated for 200ms
When the primay system is in the single-phasing, three-phase trip signal will be sent with a time
delay of 200ms if the following conditions are met.
Trip phase A
Trip phase C
Trigger TJABC
&
relay
En_3P_Trip
&
3-Pole AR
Op_DiffP
≥1
Op_Z_DPFC
Op_ROC2
&
[En_ROC2_Blk_AR] ≥1
Op_Z1
Op_Z2 (phase-to-phase) ≥1
&
[En_ZPP2_Blk_AR] ≥1
Op_Z2 (phase-to-ground)
&
[En_ZPG2_Blk_AR]
IA>0.06In
IB>0.06In
IC>0.06In
&
Select Multi Phases ≥1
200ms 0
&
&
IP>0.06In
Phase selection failure
When any of the following protection element operates, phase-selective trip will be implemented.
≥1
1-pole tripping and not dropping off
Op_Perisist1P ≥1
≥1
Op_OC_VTS
Op_Z3
≥1
Op_ROC3
Op_Z2 (phase-to-phase)
& ≥1
[En_ZPP2_Blk_AR]
Op_Z2 (phase-to-groud)
&
[En_ZPG2_Blk_AR]
Op_ROC2
&
[En_ROC2_Blk_AR]
EBI_Lockout
If phase selection element fails and operation element can not drop off, three-pole tripping
command caused by phase selection failure will be sent after 200ms delay.
When any of the following protection element operates, three-phase tripping signal will be sent
directly.
5. SOTF
Three-phase tripping will be used if two or three phases are selected by the phase selection
element.
Any fault occurs under following conditions, three-phase tripping signal will be sent directly.
Op_Perisist1P ≥1
≥1
Op_OC_VTS
Op_Z3
≥1
Op_ROC3
Op_Z2 (phase-to-phase)
& ≥1
[En_ZPP2_Blk_AR]
Op_Z2 (phase-to-groud)
&
[En_ZPG2_Blk_AR]
Op_ROC2
&
[En_ROC2_Blk_AR]
[En_PhSF_Blk_AR]
&
Op_PhSelFail
EBI_Lockout ≥1 Blocking AR
VT circuit failure
When a serious fault occurs, auto-reclosing will be blocked under following conditions:
11. Three-pole trip with auto-reclosing blocked can be selected by logic setting
[En_PhSF_Blk_AR], [En_PDP_Blk_AR], [En_MPF_Blk_AR] and [En_3PF_Blk_AR].
3.11 Auto-Reclosing
3.11.1 General Description
To maintain the integrity of the overall electrical transmission system, protective relays are
installed on the transmission system to isolate faulted segments during system disturbances.
Faults caused by lightning, wind, or tree branches could be temporary in nature and may
disappear once the circuit is de-energized. Automatic reclosing systems are put into place to
re-energize and restore the faulted section of the transmission system once the fault is
extinguished (providing it is a temporary fault). For certain transmission systems, reclosing is used
to improve system stability by restoring critical transmission paths as soon as possible.
3.11.2 Design
Auto-reclosing of RCS-931 is one shot mode, which can implement single-pole automatic
reclosing, three-pole automatic reclosing and single-pole and three-pole automatic reclosing.
In any case, auto-reclosing is performed only once. If the fault still exists after reclosing, the line
will be tripped without any future reclosing, in other words, lockout. Only single shot auto-reclosing
during the time from AR initiated to dropped off.
To start this reclaiming process, the following conditions should be met in the same time:
circuit breaker is not at open position, binary input [BI_52b_Pha]=0, [BI_52b_Phb] and
[BI_52b_Phc]=0
no lockout signals: binary input [EBI_Lockout]=0 and virtual binary input [VEBI_Lockout]=0
no low air pressure blocking signal from circuit breaker operating mechanism,
[BI_LowPres_AR]=0
Note!
After circuit breaker is closed, the general fault detector described in section 3.1 may pick
up, which will delay the reclaiming process for about 7 seconds.
Note!
Before auto-reclosure has been initiated, the low pressure blocking signal will be ignored
for 200ms; after auto-reclosure has been initiated, the low pressure blocking signal will be
ignored at all.
Note!
When current differential protection is enabled, at the same time, the optic fibre channel is
normal, automatic reclosing is not blocked if single-pole reclosing is enabled or three-pole
relcosing with no check is enabled, even if VT circuit is failure.
3.11.4 Initiating
After automatic reclosure gets ready, the reclsoing process can be initiated by:
Three-pole tripping whether it coming from internal or external is confirmed and the currents
of all three phases shall be checked to confirm that they are all zero.
Single-pole tripping whether it coming from internal or external is confirmed and any current
of all three phases shall be checked to confirm that it is zero.
For dead bus check, the bus voltage shall be less than 0.3Un, no matter phase-to-ground or
phase-to-phase voltage is used.
For dead line check, the voltage shall be less than 0.3Un, and no line VT circuit failure happens
( [Alm_VTS_Ux]=0 ), no matter phase-to-ground or phase-to-phase voltage is used.
If the line voltage and bus voltage are both higher than 0.4Un, synchronism could be checked.
The include angle between busbar voltage and line voltage is Φ under normal condition. The
auto-reclosing is permitted if phase angle difference between line voltage and bus voltage is
within the setting range [phi_SynChk_AR].
3.11.8 Lockout
Under the following conditions, the auto-reclosure will be locked out.
breaker control circuit failure, either trip or closing coils are unhealthy
stage 2 of directional zero-sequence overcurrent protection operates to trip three phases and
logic setting [En_ROC2_Blk_AR] is set as “1”
reclosing conditions are not met yet till the incomplete sequence time expires.
Whenever all of the listed events disappear, the auto-reclosure will resume normal function.
[BI_52b_Phb] ≥1
&
[BI_52b_Phc]
≥1
[En_CB_Init_AR]
[BI_52b_Pha]
[BI_52b_Phb] & ≥1
& &
[BI_52b_Phc]
& &
[En_CB_Init_AR]
[En_3P_AR]
≥1
[En_1/3P_AR]
[En_NoChk_AR]
&
≥1
&
[En_DeadChk_AR]
[En_SynChk_AR]
&
Line VT circuit failure & &
&
Line: UP<30V
≥1
Bus: UP<40V
&
Line: UP>40V
SYN
[BI_52b_Pha]
[BI_52b_Phb] ≥1
&
[BI_52b_Phc]
& Tcd 0 0 120ms
Op_AR
Fault detector
&
200ms 0
[BI_LowPres_AR] ≥1
Disable AR
Lockout AR
Where:
+DC
Transfer trip
TJA-1
BI BO
Optical fibre TJB-1
Transfer trip
TJC-1
RX
TX
RCS-9XX RCS-9XX
M N
Transfer signal 1
YC1-1
RX
TX
+DC BO
YC1-2
Optical fibre
Transfer signal 1
BI
RX
TX
Transfer signal 2
Transfer signal 2
YC2-1
BO
YC2-2
RCS-9XX RCS-9XX
M N
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a fault is detected during initialization when DC power supply is provided to the equipment,
the equipment will be blocked out, which means relay is out of service. Therefore you must
re-energize the relays or reset CPU module by restarting equipment to make relay back into
service.
When a failure is detected by the automatic supervision, it is followed with an LCD message, LED
indication and alarm contact outputs. At the same time event recording will record the failure alarm
which can be viewed in event recording report and be printed.
A common abnormality may block a certain number of protections functions while the other
functions can still work. However, if serious hardware failure or abnormality were detected, all
protection functions will be blocked and the LED “HEALTHY” will be extinguished and blocking
signal will be given by contacts output BSJ. The protective device then cannot work normally and
maintenance is required to eliminate the failure.
Note!
If the protective device is blocked or alarm signal is sent during operation, please do find
out its reason with the help of self-diagnose record. If the reason can not be found at site,
please notice the factory NR. Please Do not simply press button “TARGET RESET” on the
protection panel or re-power on the protective device.
If a failure is detected in the DC power supply circuit, [Alm_Pwr_DC] alarm will be issued and the
relay will be blocked.
When any general fault detector picks up for longer than 10s, an alarm will be issued
[Alm_PersistFD] without equipment blocked.
If these 30 setting groups are not all set, when the equipment is provided DC power supply first,
an alarm [Alm_InvalidGrp] will be issued. If the secondary rated current of CT (I2n) in equipment
settings is changed and the protection settings is not confirmed or some settings in protection
settings exceed setting range, an alarm [Alm_InvalidGrp] will be issued.
If either of the binary input [BI_ExTrp1P_AR] and [BI_ExTrp3P_AR] is energized and the duration
exceed 10s, an alarm [Alm_ExTrp_BI] will be issued.
If three binary inputs, [BI_52b_Pha], [BI_52b_Phb] and [BI_52b_Phc] are all energized, but there
is still current detected in the line or the states of three binary inputs, [BI_52b_Pha], [BI_52b_Phb]
and [BI_52b_Phc], are different, i.e., the circuit breaker is in pole disagreement, an alarm
[Alm_52b] will be issued after 10s.
In normal operation program of the RCS-931, the phasor summation of bus three phase voltage is
checked frequently, if this phasor summation detected is higher than 0.08Un and fault detection
element does not operate, VTS will, after 1.25s, output an alarm [Alm_VTS].
If the phasor summation detected is lower than 0.08Un but the bus positive voltage 3U1 is less
than Un, VTS will also issue an alarm [Alm_VTS] after 1.25s when logic setting [En_LineVT] is set
to “0”, otherwise, VTS will also issue an alarm [Alm_VTS] after 1.25s when circuit breaker is
closed ([BI_52b_Pha]=0, [BI_52b_Phb]=0, [BI_52b_Phc]=0) or there is current existing on line.
Resetting of all the above measures and resetting of the display and alarm are automatically
performed 10s after all three phases voltage resume to normal condition.
When line voltage transformer circuit failure is detected, function of synchronism check and dead
line check in auto-reclosing logic will be disabled.
After line voltage resumes to normal condition, the alarm and its subsequences will be reset
automatically after 10s.
The protective device gains zero-sequence current from two sources, which is either measured
via a neutral current input transformer (measured zero-sequence current: 3I0) or derived internally
from the summation of three-phase currents (calculated zero-sequence current: 3I0Cal).
If 3I0 is less than 0.75 times 3I0Cal or 3I0Cal is less than 0.75 times 3I0, after 200 ms, an alarm
[Alm_CTS] will be issued.
If 3I0Cal exists (3I0>0.1In) but 3U0Cal derived is nearly zero (3U0Cal<0.03Un) and there is a phase
whose current is zero at least, after 10s, an alarm [Alm_CTS] will be issued.
When CT circuit failure is detected, CTS will have the following influence on protection.
3U0Cal: zero-sequence voltage calculated depending on the summation of UA, UB and UC. (i.e.,
3U0Cal=UA+UB+UC)
Note!
When differential protection is disabled and persists for 400ms, an alarm [Alm_Ch] will be issued
and persist for 3s.
If no correct data is received within 100ms, after that, an alarm [Alm_Data_Ch] will be issued and
If 40 frame messages are failed in CRC check within 1s, an alarm [Alm_CRC_Ch] will be issued.
If differential current is greater than 0.1In and 80 percent of differential current is greater than
capacitive current calculated , an alarm [Alm_Xc] will be issued after 400ms delay.
When protective fault detection picks up, if any of these alarms including [Alm_ID_Ch],
[Alm_Data_Ch], [Alm_CRC_Ch], [Alm_Diff] and [Alm_Ch] is issued, the current differential
protection will be blocked and an alarm [Alm_OutDiffP] will be issued.
5.1 Metering
RCS-931 performs continuous measurement of the analogue input quantities. The relay samples
24 points per cycle and calculates the RMS value in each interval and updated the LCD display in
every 0.5 second. The measurement data can be displayed on the LCD of the relay front panel or
on the local via software RCSPC or remote PC. Navigate the menu to view the sampling value
through LCD screen. Access path in menu is:
MENU
1: VALUES VALUES
2: REPORT
1: DSP METERING
3: PRINT
2: CPU METERING
4: SETTINGS
3: PHASE ANGLE
5: CLOCK
4: BI STATE
6: VERSION
5: COMM CH
0: EXIT
0: EXIT
1. RMS Values
Measured directly
Magnitude of phase current coming from the other end (Ioa, Iob, Ioc)
Calculated by DSP
Access path: Press key “▲” to enter main menu firstly. Select the item “VALUES“ and press key
“ENT” to enter submenu “CPU METERING“ or “MON METERING”, and then press key “ENT”.
The corresponding metering values mentioned above are displayed on the LCD.
2. Phase angle
Measured directly
Access path: Press key “▲” to enter main menu firstly. Select the item “VALUES” and press key
“ENT” to enter submenu “PHASE ANGLE”, and then press key “ENT”. The corresponding phase
angles mentioned above are displayed on the LCD.
5.2 Recording
5.2.1 General Description
The RCS-931 provides the following recording functions:
Event recorder
Disturbance recorder
These records are displayed on the LCD of the relay front panel or on the local or remote PC.
Navigate the menu to view the report through LCD screen. Access path in menu is:
MENU
1: VALUES
2: REPORT REPORT
3: PRINT
1: TRP REPORT
4: SETTINGS
2: ALM REPORT
5: CLOCK
3: BI CHG REPORT
6: VERSION
4: MISC REPORT
0: EXIT
0: EXIT
Event recorder includes abnormal report, change of binary input report, miscellaneous report and
channel status report. The equipment can store 64 records of each kind for abnormal report and
change of binary input report, 256 records of each kind for miscellaneous report and channel
status report in non-volatile memory.
The protective device is under automatic supervision all the time. If there are any failure or
anbnormal condition detected, such as, chip damaged, VT circuit failure and so on, it will be
logged in event recorder.
When there is binary input is energized or de-energized, i.e., its state has changed from “0” to “1”
or from “1” to “0”, it will be logged as an event recorder.
If operator implements some operation, such as reboot protective device, modify setting, and so
on, they will be logged as an event recorder.
Use the disturbance recorder to achieve a better understanding of the behavior of the power
network and related primary and secondary equipment during and after a disturbance. An
analysis of the recorded data provides valuable information that can be used to improve existing
equipment. This information can also be used when planning for and designing new installations.
5.2.3.2 Design
Disturbance recorder is consisted of fault report and fault waveform. Disturbance recorder is
initiated by fault detector element.
The protective device can store up to 64 records of fault report in non-volatile memory. If a new
fault occurs when 64 faults have been stored, the oldest fault report is overwritten by the latest
one.
Sequence number
Each operation will be recorded with a sequence number in the fault report and displayed on LCD
screen.
The time resolution is 1ms using the relay internal clock synchronized via GPS if connected.
Initiating date and time is the moment when a protective fault detection operates.
Operating time
An operating time (not including the operating time of output relays) is recorded in the report.
Faulty phase
Fault location
In order to get accurate result of fault location, the following settings shall be set correctly:
protective elements
For the details of designation of each protective element, please refer to section 8.3.2 Display
tripping report
The protective device can store up to 24 fault waveforms including current, voltage and so on and
file format is compatible with COMTRADE.
The equipment can save 24 pieces of fault waveform oscillogram. If a new fault occurs when 24
fault waveform records have been stored, the latest waveform record overwrites the oldest one.
The equipment stores actual samples that are taken at a rate of 24 samples per cycle.
The recording time before fault detection initiation is fixed at 2 cycles (40 ms at 50Hz). The
recording time after fault detector initiation is fixed at 6 cycles (120 ms at 50Hz) without protection
operation or with protection operation within 6 cycles. If any protection element operates after 6
cycles, then the recording time will be prolonged to another 8 cycles (160ms at 50Hz) in order to
show continuous 8 cycle waveform after the protection element operates.
6.1 General
RCS-931 is made of a 4U height 19” chassis for panel flush mounting. Components mounted on
its front include a 128×64 dot matrix LCD, a 9 button keypad, 8 LED indicators, a signal reset
button, a 9 pin connector for communication with PC and a 15 pin connector for analog quantity
inputs by HELP-90A during commissioning. A monolithic micro controller is installed in the
equipment for these functions. Shown as Figure 6.1-1 front view of RCS-931.
HEALTHY
VT ALARM
RCS-931 AR READY
GRP
LINE DIFFERENTIAL RELAY CH ALARM
TRIP A ENT
ESC
TRIP B
TRIP C
RECLOSE
NR ELECTRIC CO.,LTD.
TARGET RESET
The 8 LED indicators are, from top to bottom, operation (HEALTHY), VT supervision (VT ALARM),
auto-reclosing reclaimed (AR READY), channel supervision (CH ALARM), protection operates
(TRIP A, TRIP B and TRIP C), auto-reclosing operates (RECLOSE). A button of target reset is
below these indicators.
As to buttons of the keypad, ENT is “enter”, GRP is “group number” and ESC is “escape”.
ON
OFF
RCS-931 comprises following 11 plug-in modules. Figure 6.1-2 is rear view of the equipment and
shows disposition of these modules.
3I0 derived is used for calculation of zero-sequence directional element and zero-sequence
overcurrent element, but 3I0 measured is used for zero-sequence current fault detector element.
So 3I0 measured shall be connected to the equipment, otherwise all relevant zero sequence
current protection will be disabled. Maximum linear range of the current converter is 30In. Table
6.2-2 lists the pin number and its definition of AI module.
UA, UB, and UC are phase voltage input to AI module. UX is the line voltage and used for
synchronism check, it could be any phase-to-ground voltage or phase-to-phase voltage, and
terminal 213 is the polarity mark. If the auto-recloser is disabled or enabled but without any check,
the voltage UX should be disconnected. Terminal 215 is ground point. It shall be connected to
ground bus.
CPU
RX
TX
Event recorder, fault oscillograph recorder (could be printed via serial port)
Sampling rate of the equipment is 24 point per cycle. Parallel real time data is calculated for
algorithm and logic of protection at every sampling point. So very high inherent reliability and
security are ensured to the equipment.
An optical transceiver is installed in this module. It exchanges AC current data and status signal
with remote end via 64 Kbit/s or 2048kbit/s dedicated optical channel or multiplex PCM
equipment.
7 RS-485 A
To GPS for clock synchronism
8 RS-485 B
Type RS-485 RS-485 RS-485 RS-485/RS-232
9 RS-485 GND
10 Printer RX
To printer or controller
11 Printer TX Physical Layer Twisted pair wire Twisted pair wire Twisted pair wire Twisted pair wire
12 Printer Ground
Figure 6.2-3 Rear view of type A and external connections of COM module
Op.Fib.RX1
Optic Fibre
To supervisory system
COM
Op.Fib.TX1
RX
TX Op.Fib.RX2
Optic Fibre PORT 1 PORT 2 PORT 3 PORT 4
To supervisory system
RX
Op.Fib.TX2
TX Type RS-485 RS-485 RS-485 RS-485/RS-232
Physical Layer Optic fibre Optic fibre Twisted pair wire Twisted pair wire
1 RS-485 A
To GPS for clock synchronism
2 RS-485 B
3 RS-485 GND
4 Printer RX
To printer or controller
5 Printer TX
6 Printer Ground
Figure 6.2-4 Rear view of type B and external connections of COM module
Ethernet 1 To supervisory system
10/100 TX
Ethernet 2 To supervisory system
COM 10/100 TX
Ethernet 3 To supervisory system
10/100 TX
Ethernet 4
To supervisory system PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7
10/100 TX
RS-485/
Type Ethernet Ethernet Ethernet Ethernet RS-485 RS-485
RS-232
1 RS-485A
To supervisory system
2 RS-485B
Twisted pair Twisted pair Twisted pair Twisted pair Twisted pair Twisted pair Twisted pair
3 RS-485GND Physical Layer
wire wire wire wire wire wire wire
4 RS-485A
To GPS for clock synchronism
5 RS-485B
6 RS-485GND
7 Printer RX
To printer or controller
8 Printer TX
9 Printer Ground
Figure 6.2-5 Rear view of type E and external connections of COM module
All ports used to communicate with SAS support IEC60870-5-103 protocol, moreover, Ethernet
port in COM modules of type 5E also supports IEC61850. From Figure 6.2-3 to Figure 6.2-5
shows rear view of these types and their external connections.
All type are equipped with a RS-485 port for receiving second pulse signal (PPS-pulse per second)
from GPS and a port for printer. Printer port could be configured as RS-232 or RS-485 by setting
corresponding jumpers on the PCB (RS-232 default). If logic setting [En_Net_Print] is set to “1” ,
printer port must be set as RS-485. Transmission rate of printer port can be set by the setting
[Printer_Baud] and should be the same with baud rate of the printer.
Note!
For the port used to printer or controller, it can be configured as RS-485 or RS-232 by
setting corresponding jumper of module COM. The port is configured as RS-232 by
shorting PIN 1 and PIN 2 and as RS-485 by shorting PIN 2 and PIN 3. As shown in Figure
6.2-6
RS-485 RS-232
1. Receiving PPS (pulse per second) and PPM (pulse per minute) via external contact
1. Terminal 614
The positive pole of opto-coupler, which should be connected with the positive pole of DC power
supply (Terminal 104). It is used to supervise whether DC power supply is normal or not. The
positive pole of DC module should be connected to common of all binary inputs.
2. Terminal 615
The negative pole of opto-coupler, which should be connected with the negative pole of DC power
supply (Terminal 105).
3. Terminal 601
It is used to receive clock synchronism signal from GPS or other equipment used clock
synchronism, the binary input [BI_Pulse_GPS] will change from “0” to “1” once per second or per
minute depended on the setting [GPS_Pulse]. When setting [GPS_Pulse] is set to “1”, the
equipment receives PPM (pulse per minute), otherwise, receives PPS (pulse per second). Clock
synchronism via RS-485 bus is recommended. Only one of them can be selected.
4. Terminal 602
It is used to manually to trigger printing latest report when the equipment is configured as manual
printing mode by logic setting [En_Auto_Print]=0. The printer button is located on the panel
usually. If the equipment is configured as automatic printing mode ([En_Auto_Print]=1), report will
be printed automatically as soon as it is formed.
5. Terminal 603
It is used to block monitoring direction communication when the protective device is maintained. A
link located on the panel is used for that. When the equipment is in maintenance or
commissioning status, this link should be closed. All of the reports will not be sent via
communication port then, but local displaying and printing are still working. This link should be
open during normal operation condition.
6. Terminal 604
It is used to manually reset latching signal relay and LCD displaying. The reset is done by
pressing a button on the panel or by remote command via communication channel.
7. Terminal 605
8. Terminal 606
9. Terminal 607
It is used to select mode of auto-reclosing through switch associated with binary input
[EBI_Opt2_AR] when logic setting [En_SetOpt_AR] is set as “0”.
It is used to select mode of auto-reclosing through switch associated with binary input
[EBI_Opt1_AR] when logic setting [En_SetOpt_AR] is set as “0”.
Table 6.2-3 shows the relation between the state of binary input and AR mode.
When binary inputs [EBI_Opt1_AR] and [EBI_Opt2_AR] are both energized, auto-reclosing is
disabled of the protective device but selection of faulty phase is still valid. When logic setting
[En_SetOpt_AR] is set to “1”, the binary inputs [EBI_Opt1_AR] and [EBI_Opt2_AR] are disabled.
601 BI_Pulse_GPS
602 BI_Print
603 BI_BlkComm
604 BI_RstTarg
605 EBI_DiffP
606 EBI_DistP
607 EBI_ROC
608 EBI_Opt1_AR
609 EBI_Opt2_AR
610 EBI_Lockout
617 BI_ExTrp1P_AR
618 BI_ExTrp3P_AR
622 BI_52b_Pha
623 BI_52b_Phb
624 BI_52b_Phc
625 BI_LowPres_AR
626 BI_Send_TT
627 BI_Send_TS1
628 BI_Send_TS2
Internal connected
It is common connected with tripping contact from other protective device, such as busbar
protection or breaker failure protection and so on. The auto-reclosing is blocked and 3-pole
tripping command is sent when it is energized even if single-phase fault occurs in the line.
It is common connected with single-phase tripping contact from other protective device, such as
1. Terminal 618
It is common connected with three-phase tripping contact from other protective device, such as
line protection. Auto-relcosing will be initiated when it is energized.
2. Terminal 622
It is normally closed auxiliary contact of phase A of circuit breaker and is used to indicate the
status of circuit. It is provided by interposing relay, for example, CZX-12R.
3. Terminal 623
It is normally closed auxiliary contact of phase B of circuit breaker and is used to indicate the
status of circuit. It is provided by interposing relay, for example, CZX-12R.
4. Terminal 624
It is normally closed auxiliary contact of phase B of circuit breaker and is used to indicate the
status of circuit. It is provided by interposing relay, for example, CZX-12R.
5. Terminal 625
It is connected with auxiliary contact of circuit breaker, which is used to supervise closing pressure
of circuit breaker. The auto-reclosing will be blocked after 200ms when it is energized. If
auto-reclosing of protective device is disabled, it need not be connected.
6. Terminal 626
It is common connected with tripping contact from other protective device, such as breaker failure
protection. It is used to transfer tripping signal and trip remote circuit breaker through the channel.
7. Terminal 627
It is common connected with tripping contact from other protective device, such as breaker failure
protection. It is used to transfer signal and trip remote circuit breaker through the channel
associated with auxiliary criterion of other protective device, for example, RCS-925 voltage relay.
8. Terminal 628
It is common connected with tripping contact from other protective device, such as breaker failure
protection. It is used to transfer signal and trip remote circuit breaker through the channel
associated with auxiliary criterion of other protective device, for example, RCS-925 voltage relay.
Note!
Pin 701 is not connected with Pin 717 and Pin 711 is not connected with Pin 727 inside of
BI module. Hence, Once the module is used, Pin 701 and 717 should be both connected
to positive pole of power supply and Pin 711 and 727 should be both connected to
negative pole of power supply.
The binary inputs connected to the second BI module should be not connected to the first
BI module again and vice versa.
BO_Fail_1
02 10
BO_Alm_Abnor_1 BO_Alm_Ch_1
03 12
BO_Trp BO_Recv1_TS_1
04 14
BO_Cls
05 16
BO_Recv1_TS_2
01 18
11 BO_Trp1P_1
BO_Alm_Ch_2 20
13 BO_Trp3P_1
BO_Recv2_TS_1 21
09 BO_BlkAR_1
22
15
BO_Recv2_TS_2 19
17
Auto-reclosing 2
27 Remote signal
BO_Fail_2
07
BO_Alm_Abnor_2
08
06
For local signal, they are magnetic latching signals, so they can be reset by pressing “TARGET
RESET” button to energize binary input [BI_RstTarg] or reset command from SAS via
communication channel.
When DC power supply of protective device is lost or there is internal fault occurs in the protective
device, protective device will be blocked. Failure alarm signal will be issued by closing the
normally closed contact BO_Fail_1, BO_Fail_2 and BO_Fail_3.
When protective device is in abnormal condition but still running, such as VT circuit failure, CT
circuit failure, and so on, protective device is not blocked. Abnormal alarm signal will be issued by
closing the normally open contact BO_Alm_Abnor_1 and BO_Alm_Abnor_2.
When there is any protective element operating to trip three-phase circuit breaker or single-phase
circuit breaker, trip signal will be issued by closing the normally open contact BO_Trp1P_1,
BO_Trp1P_2 and BO_Trp1P_3. BO_Trp1P_1 and BO_Trp1P_2 can be used to initiate
auto-reclosing of other protective device by connecting with binary input [BI_ExTrp1P_AR].
When there is any protective element operating to trip three-phase circuit breaker, trip signal will
be issued by closing the normally open contact BO_Trp3P_1, BO_Trp3P_2 and BO_Trp3P_3.
BO_Trp3P_1 and BO_Trp3P_2 can be used to initiate auto-reclosing of other protective device by
connecting with binary input [BI_ExTrp3P_AR].
When the conditions that is used to block auto-reclosing is met, the normally open contact
BO_Lockout_1, BO_Lockout_2 and BO_Lockout_3 will be closed, for example, zone 2 of
Transfer signal relay retransmits transfer signals and provides two normally open contacts
respectively. When the binary input [VBI_Recv1_TS] or [VBI_Recv2_TS] is energized, these
contacts BO_Recv1_TS_1 and BO_Recv1_TS_2 or BO_Recv2_TS_1 and BO_Recv2_TS_2 will
be closed.
Channel alarm relay outputs channel alarm signal and provides two normally open contacts.
When the protective device does not receive the signal from remote end, data frame is abnormal
during data transmission, the settings related with channel of protective device on both ends are
wrong, including [Equip_ID], [ID_Local], [ID_Remote] and [En_InnClock], or error rate of channel
is greater than 0.1%, these contacts will be closed.
BO_TrpA_1 BO_TrpA_2
05 08
BO_TrpB_1 BO_TrpB_2
07 10
BO_TrpC_1 BO_TrpC_2
09 12
02 04
BO_TrpA_3 BO_TrpA_4
19 23
BO_TrpB_3 BO_TrpB_4
21 25
BO_TrpC_3 BO_TrpC_4
22 26
20 24
BO_TrpA BO_Cls_1
15 11
BO_TrpB
17
BO_TrpC
18 01
16 Reclosing 2
BO_Cls_3 BO_Cls_2
27 29
28 30
This module output five sets of trip contacts and three sets of AR contacts that are all operate
instantaneously. The first set of trip contact and AR contact are connected to trip coil and closing
coil of CZX respectively. Others are used to send remote signal, fault recorder and initiate BFP.
When there are two circuit breakers to trip, the second set of trip contact and AR contact are used
for the second circuit breaker.
BO_TrpA_5 BO_TrpA_6
05 08
BO_TrpB_5 BO_TrpB_6
07 10
BO_TrpC_5 BO_TrpC_6
09 12
02 04
BO_TrpA_7 BO_TrpA_8
15 19
BO_TrpB_7 BO_TrpB_8
17 21
BO_TrpC_7 BO_TrpC_8
18 22
16 20
Chapter 7 Settings
The equipment has 30 setting groups for protection to coordinate with the mode of power system
operation, one of which is assigned to be active. However, equipment parameters are common for
all protection setting groups.
Note!
All current settings in this chapter are secondary current converted from primary current
by CT ratio. Zero sequence current or voltage setting is configured according to 3I0 or 3U0
and negative sequence current setting according to I2 or U2.
Settings Description
1. Active_Grp
Thirty setting groups are provided for selecting, group number from 0 to 29. Equipment setup is
shared for 30 setting groups and only protection settings are independent.
2. Comm_Addr
Communication address between the equipment with the SCADA or RTU via RS-485;
3. COM1_Baud
4. COM2_Baud
5. Printer_Baud
6. Debug_Baud
Baud rate of front communication port for setting and testing via the software RCSPC;
7. fn
8. U1n
9. U2n
10. I1n
11. I2n
12. Equip_ID
13. En_Net_Print
“1” means that the printer is shared, otherwise, it should be set to “0”;
14. En_Auto_Print
“1” means that tripping report will be automatically printed after protection operating, otherwise, it
should be set to “0”;
15. Protocol
Communication protocol;
0: IEC-60870-5-103 or IEC-61850
16. GPS_Pulse
“1” means minute pulse for time synchronism, “0” means second pulse for time synchronism.
17. En_Remote_Cfg
“1” means that settings can be remotely configured via SCADA or RTU, otherwise, it should be set
to “0”.
Overview
Settings Description
1. I_DPFC_OC_FD
Setting principle: This value should be greater than maximum variation of load current and
typically 0.2 In. For line with wide variation of load current like those for electric railway, heavy
rolling mill or aluminum-smelting, the setting should be increased properly so that frequent starting
of the equipment could be avoided.
2. I_ROC_FD
Setting principle: It shall be greater than maximum zero-sequence unbalance current. Setting it
based on same primary current on both ends.
3. Z_DPFC
4. K_CT
The ratio of CTs on two terminals of the line could be different. it could be corrected by setting
[k_CT].
Setting principle: Suppose CT ratio, Terminal M: kM=IM1n : IM2n; Terminal N: is and kN=IN1n : IN2n
IM1n: primary rated current of terminal M, IM2n: secondary rated current of terminal M
IN1n: primary rated current of terminal N, IN2n: secondary rated current of terminal N
Terminal M: [K_CT]=1.00
For example:
5. I_H_Diff
Setting principle: Set it not less than 4 times of capacitance current and usually not less than 0.2
In. Sensitivity of this setting should be checked by short circuit current of internal fault. Equivalent
currents of the settings on both ends should be the same.
6. I_L_Diff
Setting principle: Set it not less than 1.5 times of capacitance current and usually not less than 0.1
In. Sensitivity of this setting should be checked by minimum short circuit current of internal fault.
Equivalent currents of the settings on both ends should be the same.
7. I_Diff_CTS
The operating value of the differential protection for VT circuit failure when it is not blocked by
CTS.
Setting step: 1
Used to confirm that equipments at both ends of line are compatible. The end of which setting
[ID_Local] should be same as the [ID_Remote] of the other and the greater [ID_Local] between
the two ends is chosen as a master end for sampling synchronism, the other is a slave end. If the
setting [ID_Local] is set as same as [ID_Remote], that means the equipment in loopback testing
state.
9. K0
Setting principle: K0 = (Z0L–Z1L)/3Z1L, where Z0L and Z1L are zero and positive sequence
impedance of the line respectively. Actual measurement value is suggested adopted, but
calculated value with 0.05 subtracted from can also be used if there is not actual measurement
value.
10. I_OC_PSB
Setting principle: This current setting should be greater than maximum load current of the line.
11. Z_PG1
Setting principle: Setting of this zone should be 0.8~0.85 times the impedance of the line and
should be decreased properly for line with mutual inductance.
12. Z_PP1
Setting principle: Setting of this zone should be 0.8~0.85 times the impedance of the line.
13. Z_PG2, Z_PG3, Z_PP2, Z_PP3, t_PG2, t_PG3, t_PP2 and t_PP3
Setting principle: Setting of the impedance and time delay of these zones should meet
requirements between various zones and operation should be ensured even for fault at end of the
line.
14. R_Blinder
Setting principle: It should be less than the minimum impedance measured during heavy load
conditions
Setting step: 1°
Phase angle of positive and zero sequence impedance of the line. Set as they should be.
16. phi_Shift_ZPG
Phase shift of zone 1 and 2 phase-to-ground distance element. Recommended value: 30°for
length of the line < 10 km, 15°for length ≥10 km and 0°for length ≥40 km.
17. phi_Shift_ZPP
Phase shift of zone 1 and 2 phase-to-phase distance element. Recommended value: 30°for
length of the line < 2 km, 15°for length ≥2 km and 0°for length ≥10 km.
19. I_ROC_SOTF
Setting principle: This setting should ensure sufficient sensitivity to ground fault at end of the line.
20. I_OC_VTS
21. I_ROC_VTS
22. t_OC/ROC_VTS
Time setting of phase and zero sequence overcurrent elements for VTS.
23. phi_SynChk_AR
Setting step: 1°
Synchronism check angle for auto-reclosing. Permissive difference between busbar voltage and
Positive sequence and zero sequence reactance and resistance of the line. Parameter of the
transmission line, used for calculation of fault location.
Setting step: 1Ω
For EHV long line, capacitance current of line is very great, so capacitance current compensation
must be adopted. It is worth of attention that XC1L must be smaller than XC0L. Table 7.2-2 can be
as a reference.
Table 7.2-2 Capacitive impedance and current of overhead per 100KM based on different voltage
However, when capacitance current of line is smaller than 0.1In, capacitance current
compensation is disabled automatically. XC1L and XC0L can be set according to the following
rule.
If the ratio of CTs on two terminals of the line are different, the terminal setting [K_CT] set to “1”
according to the above rule and the other terminal can be calculated according to CT ratio.
27. LineLength
Total length of the line. The actual total length of the line km, used for calculation of fault location.
28. Line_ID
Number of the line. The actual identification number of the transmission line in site, only used for
printing report.
Note!
For impedance setting, even if some zones of distance element are disabled, these
[Z_PP3]≥[Z_PP2]≥[Z_PP1];
[Z_PG3]≥[Z_PG2]≥[Z_PG1];
Impedance setting of zone 3 of distance element should be sensitive to fault at end of the
line.
Note!
All zero sequence current settings should be greater than that of zero-sequence current
fault detector element. These settings must meet the following relation:
[I_ROC2]≥[I_ROC3]≥[I_ROC_FD];
Overview
Settings Description
1. En_Z_DPFC
1: enable
0: disable
For short transmission line, if the secondary value of line impedance is less than 1/IN, DPFC
distance protection should be disabled.
2. En_DiffP
1: enable
0: disable
3. En_CTSBlkDiff
If this setting is set as “1”, current differential protection shall be blocked during CT circuit failure.
4. En_InnClock
If the setting is set to “1”, inner clock is used. Please refer to section 3.4.9.
5. En_FD_Ctrl_TT
If the setting is set to “1”, transfer tripping controlled by local fault detector. Local trip circuit could
be active by remote command (i.e. [BI_Recv_TT]=1) only when local fault detector initiates. if do
not use transfer tripping, the setting should be set to “1”.
6. En_LineVT
If three-phase voltage used for protection measurement comes from line side (for example, 3/2
breaker), it should be set as “1”. If three-phase voltage comes from busbar side, it should be set
as “0”.
7. En_PSB
The function of power swing blocking for zone 1,2 distance element;
“1”: enable; when power swing occurs, zone 1,2 distance element shall be blocked.
“0”: disable;
The zone 1(2, 3) of phase-to-ground distance element enabled and zone 1(2, 3) of
phase-to-phase distance relay enabled, if these setting are set to “1”, in the same time, virtual
binary input [VEBI_DistP] should be set as “1”. If none of them is met, the distance protection shall
be disabled.
9. En_Blinder
“1”: enable
“0”: disable
If the setting is set as “1”, zone2, 3 of distance element for auto-reclosing SOTF is enabled. If the
power swing does not occur after reclosing, the corresponding zone of distance protection which
is not controlled by power swing block will trip after a shorter time delay than [t_PG2] or [t_PP2]
and [t_PG3] or [t_PP3].
11. En_Dir_ROC3
If the setting is set as “1”, stage 3 of directional zero-sequence overcurrent protection is controlled
by direction element.
12. Opt_Dly_ROC3
If the setting is set as “1”, stage 3 of zero sequence overcurrent protection for auto-reclosing
SOTF will be enabled.
13. En_3P_Trip
If it is set as “1”, three-pole tripping will be implemented for any fault but auto-reclosing is not
blocked.
14. En_AR
If the setting is set as “1”, and all conditions of lockout auto-reclosing are not met, auto-reclosing
enabled.
15. En_SynChk_AR
1: enable
0: disable
16. En_DeadChk_AR
1: enable
0: disable
17. En_NoChk_AR
1: enable
0: disable
[En_SynChk_AR], [En_DeadChk_AR] and [En_NoChk_AR] are valid only when the logic setting
[En_AR] is set as “1”. Please refer to section 3.11.5. They can be used either individually or
combinedly. For example, logic settings [En_DeadChk_AR] and [En_SynChk_AR] can be set as
“1” in the same time.
18. En_CB_Init_AR
If the setting is set as “1”, auto-reclosing will be initiate by position of circuit breaker. Please refer
to section 3.11.4.
19. En_ZPP2_Blk_AR
“1”: enable;
“0”: disable;
“1”: enable;
“0”: disable;
21. En_ROC2_Blk_AR
“1”: enable;
“0”: disable;
22. En_PhSF_Blk_AR
If the settings is set as “1”, auto-reclosing will be blocked when selection of faulty phase fails.
23. En_PDP_Blk_AR
If the settings is set as “1”, auto-reclosing will be blocked in pole discrepancy condition.
24. En_MPF_Blk_AR
If the setting is set as “1”, auto-reclosing will be blocked when multi-phase fault happens.
25. En_3PF_Blk_AR
If the setting is set as “1”, auto-reclosing will be blocked when three-phase fault happens.
26. En_SetOpt_AR
When the setting is set as “1”, AR mode can be selected by logic settings [En_1P_AR],
single-pole AR, [En_3P_AR], three-pole AR, and [En_1/3P_AR], single-pole and three-pole AR.
Conversely, if it is set as “0”, AR mode can be selected by switch on the panel. Please refer to
Table 6.2-3.
If these setting are set as “1”, corresponding auto-reclosing mode is selected. Please refer to
setting [En_SetOpt_AR].
Except for virtual binary input [VEBI_Lockout], logic relation between these virtual binary inputs
mentioned in the table and corresponding logic setting is AND. If it is set as 1, auto-reclosing will
be locked out. It should be set as 0 generally.
These virtual binary inputs provide a convenient way for the operator to put the function in service
or out of service remotely away from an unattended substation.
7.5 IP Address
The setting is used to set the communication rate of COM module, please see Table 7.5-1 for
details.
This chapter describes human machine interface (HMI), HMI menu tree and LCD display. At the
same time how to input settings through keypad is described in details.
No. Item
1 LCD display
2 Status indication LEDs
3 ENT, ESC, GRP and Navigation buttons
4 DB9 port and DB15 port
5 Device type, name and Manufacturer
A 128×64 dot matrix backlight LCD display visible in dim lighting conditions, which is used for
programming, monitoring, fault diagnostics and setting, etc. when there is a trip or alarm condition,
diagnostic messages are displayed.
The LED
Numeric keypad and command keys allow for full access to the relay
HEALTHY
VT ALARM
AR READY
RCS-931
GRP
CH ALARM
LINE DIFFERENTIAL RELAY TRIP A
ESC
TRIP B
TRIP C
RECLOSE
TARGET RESET
+
GR
ENT
ESC
Pressing any button in idle mode will activate the HMI display.
2. Exit the present level in the menu tree. This means, it cancels the present function or the
present menu selection and moves one step higher (back) in the menu tree.
The “ENT” button mainly provides an Enter/Execute function. It activates, for example, the
selected menu tree branch. Further it is used to confirm settings and to acknowledge different
actions.
The “GRP” button mainly provides the function of change active setting group.
The left and right arrow buttons (“◄” and “►”) mainly provides the following functions:
1. Position the cursor in a horizontal direction, for instance, to move between digits in a number
during the parameter setting.
The up and down arrow buttons (“▲” and “▼”) mainly provides the following functions:
The plus and minus button (“+” and “-”) mainly provides the following functions:
Note!
Any setting change operation should start with simply pressing “+”, “◄”, “▲”,and “-” in
sequence, as a password. Without the operation, modifying settings is invalid.
Report delete operation should executed by pressing “+”, “-”, “+”, “-”, “ENT” in sequence
after exiting the main menu.
HEALTHY
VT ALARM
AR READY
CH ALARM
TRIP A
TRIP B
TRIP C
RECLOSE
TARGET RESET
Note!
The LED “HEALTHY” can only be lit by supplying DC to equipment and without alarms to
block equipment.
The LEDs “TRIP A”, “TRIP B”, “TRIP C” and “RECLOSE” will be lit up once the
corresponding relays operate and remain lit even after the trip commands go off. The
LEDs can be turned off by pressing “TAEGET RESET” button on faceplate, or by pressing
the RESET button on the protection panel to energized binary input [BI_RstTarg].
The LEDs “VT ALARM” and “CH ALARM” is lit as long as alarm signal is present. When
alarm signals disappear, they can turn off automatically after time delay.
1 2
No. Item
1 DB9 RS232 port for communication with a PC for local communication.
2 DB 15 port for communication with HELP-90A tester.
In order to enter the main menu, please press “▲” arrow button under the default display
condition. If the current display is the latest report display, please press “TARGET RESET” button
to return to the default display condition, and then press “▲” arrow button to enter the main menu.
Please use the “▲” and ”▼“ button to scroll between the submenus, press “ENT” to enter the item
chosen or press “ESC” to directly return to the upper level.
MENU
1:VALUES 4:SETTINGS
6:VERSION
3:PRINT
1: SETTINGS
2: TRP REPORT
3: ALM REPORT
4: BI CHG REPORT
5: PRESENT VALUES
6: VERSION
7: CH RECORD
8: MISC REPORT
9: UNACT SETTINGS 0:EXIT
0: EXIT
8.2.2 VALUES
This menu displays the sampling value of current and voltage, and status binary input value which
fully reflect the operation status of the equipment. Under normal conditions these displayed values
should be consistent with the real values injected.
DSP METERING
This submenu displays the values of current and voltage sampled and calculated by the DSP chip.
Three phase current, zero sequence current and negative sequence current
CPU METERING
This submenu displays the values of current and/or voltage sampled and calculated by the CPU
chip. These values includes:
Ua, Ub and Uc
Three phase current, zero sequence current and negative sequence current
PHASE ANGLE
The phase angles between current on local end and current on remote end
BI STATE
This submenu displays the status of binary inputs. If a certain binary input appears to be “1”, it
means that an external binary input signal is energized or a corresponding function/element of the
equipment is enabled. On the other hand if a certain binary input appears to be “0”, it means that
the external binary input signal is de-energized or the corresponding function/element of the
equipment is disabled.
COMM CH
This submenu displays the status of communication channel. Please refer to section 10.10.9.
8.2.3 REPORT
This menu displays the information recorded by the RCS-931 for the tripping reports, alarm
message reports and status change of binary input reports etc.. All the reports are stored in
non-volatile memory.
Please use “▲” and “▼” to choose the report under concern, and press “ENT” to display the
chosen report.
In the report display submenu, the latest report shall be displayed first. Press “-” button to display
the previous report, and press “+” to display the next report.
In case that a report is too long to be fully displayed on the LCD, you should press “▲” or “▼” to
display the other parts of the report.
8.2.4 PRINT
The settings list, wave recorder, tripping report, operation report, and abnormality report and
status change of binary input can be printed by this submenu.
Please use “▲” and “▼” to choose the item under concern, and press “ENT” to execute printing.
8.2.5 SETTINGS
Use this menu to select and set the different parameters for protection and control functions in the
RCS-931. There are 30 selectable and editable setting groups, each independent of the other, to
structure desired functions and applications.
Please use “▲” or “▼” to choose the setting under concern, and press “◄” or “►” to move the
cursor to the digit to be changed. Press “+” or “-” button to change the data and then press “ENT”
to confirm the setting change.
If the setting change shall be terminated , simply press “ESC” to return, and the setting will remain
unchanged.
8.2.6 CLOCK
The internal clock for the RCS-931 can be viewed here. The time is displayed in the form
YYYY-MM-DD and hh:mm:ss. All values are presented in digits.
Please use “▲” , “▼”, “◄” or “►” to move the cursor to the digit to be changed. Press “+” or “-”
button to change the data and then press “ENT” to confirm the change.
If the setting change shall be terminated , simply press “ESC” to return, and the setting will remain
unchanged.
8.2.7 VERSION
This menu displays the version, verification code and creating time of the software applied in the
equipment.
01 - 02 21 : 20 : 50
I = 000.00 A
U = 000.00 V
ActiveGrp 01
01-02 21:20:50: shows that the current time and date in format: MM-DD hh;mm:ss.
:shows the communication of both ports with SCADA system are normal
“.”: shows the communication of the first port with SCADA system is normal
“-”: shows the communication of the second port with SCADA system is normal
OP 000 07-02-27
14 : 21 : 51 : 115 MS
1. Op_TT
00173 MS
OP 000 07-02-27
14 : 21 : 51 : 115 MS
2. Fault Location
A 0017.0 KM
07-02-27: shows that the date of the tripping operation in format YY-MM-DD.
00173 MS: shows the operation time of the tripping element exclude the operation time of output
relay.
ALM052 07-02-26
12 : 06 : 03 : 063 MS
Alm_VTS
BI 034 07-02-26
12 : 06 : 03 : 441 MS
BI_Recv_TT
0→1
BI_Recv_TT 0→1: shows binary input name and status change action.
12 : 19 : 17 : 698 ms
Setting_Chgd
SETTINGS
1. EQUIP SETUP
2. PROT SETTINGS
3. VEBI SETTINGS
Press key “▼” to select the item “PROT SETTINGS” by scrolling the cursor downward. Press key
“ENT” to display the setting symbols and parameters of the submenu. Please press key “▲” or
“▼” to locate the setting. Simply press “ESC” to return without changing, and press “ENT” to input
password to ensure the change.
Group 01 Setting
I_DPFC_OC_FD
000.50 A
I_ROC_FD
Press key “▼” to select the item “UNACT SETTINGS” by scrolling the cursor downward. Press
key “ENT” to enter the submenu. Selecting a target setting group inactive to modify without the
equipment blocked.
Event recorder
Event recording are recorded in form of report and can be viewed through LCD or by printing.
Disturbance recorder
Disturbance recording is recorded in form of both report and waveform, so report can be display
as event report. However waveform must to be printed or displayed with proper software.
These recording reports can also be displayed through software by the local or remote PC.
Press “▲” enter the main menu at first. Press key “▼” to select the item “REPORT” by scrolling
the cursor downward, and then pressing key “ENT” will enter the submenu. Press key “▼” to
select the target item by scrolling the cursor downward, and press key “ENT” to the next
submenu.
REPORT
1. TRP REPORT
2. ALM REPORT
3. BI CHG REPORT
Then press key “▼” to select “TRP REPORT”, “ALM REPORT” or “BI CHG REPORT” by scrolling
the cursor downward. Press key “ENT” to display the report selected. The latest report will be
displayed firstly. Pressing key “+”or “-” will display next or previous report. If the report cannot be
fully displayed in one screen, key “▲” or “▼” can be used to display the rest of it. Simply press
key “ESC” or “ENT” to return the upper submenu. Take the “ALM REPORT” as an example.
ALM052 07-02-26
12 : 06 : 03 : 063 MS
Alm_VTS
1. SETTINGS
2. TRP REPORT
3. ALM REPORT
Then press key “▼” to select “SETTINGS”, “TRP REPORT”, “ALM REPORT”, “BI CHG
REPORT”, “PRESENT VALUES”, “VERSION” “CH RECORD”, “MISC REPORT” or “UNACT
SETTINGS” by scrolling the cursor downward. Press key “ENT” to print the report selected.
Press key “+” or “-” to select next or previous report and press key “ENT”. Simply press key “ESC”
to return the upper submenu.
Select Report
000 → 053
Press “ENT” to print if there is a printer connected to the relay. If no printer is connected, the
following information will be shown “NO Printer”.
Password : „„
Press keys “+”, “◄”, “▲” and “–” sequentially, then the equipment will check the password
automatically. If the password input is correct, modification of setting will be confirmed and the
interface will return to submenu.
If one or some settings input are detected to be off-limits, the cursor will locate where the first
wrong setting is and the LCD will display “xxxxx SetInvalid”. (For example, “I_DPFC_OC_FD
SetInvalid”)
Note!
If the active group number or protection system parameter is changed, protective settings
will be invalid and have to be configured again.
Press key “▲” to enter the main menu at first. Move cursor to the item “SETTINGS” and press key
“ENT” to enter submenu. Press key “▼” and move cursor to the item “COPY SETTINGS” item and
press “ENT” to display following interface.
COPY SETTINGS
Active Grp : 00
Target Grp : 01
Press key “+” and “-” to change digit where the cursor stays. Press “ENT” to confirm, then settings
group 0 will be totally copied to settings group 1.
Active Grp : 00
Change to : 01
Press key “+” and “-” to change digit where the cursor stays. Press “ENT” to confirm. If the new
active setting group is valid, LCD will display main configuration diagram. Otherwise, an alarm
[Alm_InvalidGrp] will be issued and LED “HEALTHY” will be turned off. Then please modify this
group settings to make them valid.
SetRefreshing „
Press <ENT>
Note!
You have no choice to select which kind of records or which one record to be deleted but
to delete all records.
Press key “ENT” to delete all records and LCD will display “RptClearing...” then the reports will be
deleted, or press key “ESC” to exit to main menu without deletion.
CLOCK
DATE : 2005 06 25
TIME : 09 08 39
Press keys “▲”, “▼”, “◄” and “►” to select the digit to be modified. Pressing key “+” and “-” to
modify data. Pressing key “ESC” to return without modification. Pressing key “ENT” to confirm the
modification and return to main menu.
RCS-931AM
Project : 080047
Ver : 3.00
CRC : FCA3
RCS-931AM
CRC : FCA3
2008-04-01 09 : 31
SUBQ : 00038210
2008-04-01 09:31: shows the creating time of the program in format of YY-MM-DD HH:MM
Note!
What above figure shows is just an example to introduce the meaning of LCD display of
software version, the actual version for user is application-specific.
Chapter 9 Communications
The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever
protocol is selected. The advantage of this type of connection is that up to 32 protective devices
can be “daisy chained” together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the
relay.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (refer to Figure 9.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
EIA RS-485
Master 120 Ohm
120 Ohm
The EIA RS-485 standard requires that each device is directly connected to the physical cable
that is the communications bus. Stubs and tees are expressly forbidden, such as star topologies.
Loop bus topologies are not part of the EIA RS-485 standard and are forbidden by it also.
Two-core screened cable is recommended. The specification of the cable will be dependent on
the application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length
must not exceed 500m. The screen must be continuous and connected to ground at one end,
normally at the master connection point; it is important to avoid circulating currents, especially
when the cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’s chassis. This is for both safety and noise reasons.
9.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur
when all the slaves are in receive mode and the master is slow to turn from receive mode to
transmit mode. This may be because the master purposefully waits in receive mode, or even in a
high impedance state, until it has something to transmit. Jabber causes the receiving device(s) to
miss the first bits of the first character in the packet, which results in the slave rejecting the
message and consequentially not responding. Symptoms of these are poor response times (due
to retries), increasing message error counters, erratic communications, and even a complete
failure to communicate.
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.
Note!
It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will
result in an excessive bias voltage that may damage the devices connected to the bus.
As the field voltage is much higher than that required, NR cannot assume responsibility for
any damage that may occur to a device connected to the network as a result of incorrect
application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic
inputs) as this may cause noise to be passed to the communication network.
Each equipment is connected with an exchanger via communication cable, and thereby it forms a
star structure network. Dual-network is recommended in order to increase reliability. SCADA is
also connected to the exchanger and will play a role of master station, so the every equipment
which has been connected to the exchanger will play a role of slave unit.
SCADA
Exchanger A
Exchanger B
To use the rear port with IEC60870-5-103 communication, the relevant settings of the protective
device must be configured. To do this use the keypad and LCD user interface. In the submenu
“EQUIP SETUP”, set the parameters [Protocol] as “0”, [COM1_Baud] and [COM2_Baud] as
“9600”. For using the Ethernet port with IEC60870-5-103 communication, the IP address and
submask of each Ethernet port can be set in the submenu “IP ADDRESS”. Please refer to section
7.5 for further details.
The IEC60870-5-103 interface over serial port (RS-485) is a master/slave interface with the
protective device as the slave device. It is properly developed by NR.
Initialization (reset)
Time synchronization
General interrogation
General commands
Disturbance records
The link layer strictly abides by the rules defined in the IEC60870-5-103.
9.3.2 Initialization
Whenever the protective device has been powered up, or if the communication parameters have
been changed, a reset command is required to initialize the communications. The protective
device will respond to either of the two reset commands (Reset CU or Reset FCB), the difference
is that the Reset CU will clear any unsent messages in the transmit buffer.
The protective device will respond to the reset command with an identification message ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.
If the protective device clock is synchronized using the IRIG-B input then it will not be possible to
set the protective device time using the IEC60870-5-103 interface. An attempt to set the time via
the interface will cause the protective device to create an event with the current date and time
taken from the IRIG-B synchronized internal clock.
The following table contains a complete listing of all events produced by the protective device.
178 21 1 Op_DiffP
178 22 1 Op_TT
178 182 1 Op_Z_DPFC
178 16 1 EBI_Opt1_AR
178 17 1 EBI_Opt2_AR
178 8 1 EBI_Lockout
178 70 1 BI_ExTrp1P_AR
178 71 1 BI_ExTrp3P_AR
178 161 1 BI_52b_Pha
178 162 1 BI_52b_Phb
178 163 1 BI_52b_Phc
178 205 1 BI_LowPress_AR
178 32 1 BI_Send_TT
178 74 1 BI_Send_TS1
178 75 1 BI_Send_TS2
178 33 1 BI_Recv_TT
178 76 1 BI_Recv_TT1
178 77 1 BI_Recv_TT2
178 131 1 VEBI_DiffP
178 132 1 VEBI_DistP
178 133 1 VEBI_ROC
178 134 1 VEBI_Lockout
178 201 1 VEBI_DiffP_Rmt
ASDU 1
178 194 1 Alm_RAM
178 195 1 Alm_ROM
178 196 1 Alm_EEPROM
178 49 1 Alm_InvalidGrp
178 50 1 Alm_Smpl_CPU
178 189 1 Alm_PersisI0
178 214 1 Alm_PersisFD
178 51 1 Alm_Smpl_DSP
178 200 1 Alm_TrpOut
178 222 1 Alm_Setting
178 44 1 Alm_Pwr_DC
178 202 1 Alm_Pwr_Opto
178 241 1 Alm_VTS
178 240 1 Alm_VTS_Ux
178 206 1 Alm_CTS
178 210 1 Alm_52b
178 186 1 Alm_Data_Ch
178 187 1 Alm_CRC_Ch
178 199 1 Alm_ID_Ch
178 212 1 Alm_Ch
Refer the IEC60870-5-103 standard can get the enough details about general interrogation.
Note!
If the setting [En_Remote_Cfg] in the submenu “EQUIP SETUP” is set as “0”, to modify
protection settings remotely will not be allowed. Moreover, equipment parameters are not
allowed to be modified remotely whether the item [En_Remote_Cfg] is “1” or “0”.
The disturbance records are stored in uncompressed format and can be extracted using the
standard mechanisms described in IEC60870-5-103.
ACC Content
1 Ia
2 Ib
3 Ic
4 3I0
5 Ua
6 Ub
7 Uc
8 3U0
IEC 61850-5: Communications and requirements for functions and device models
related to IEDs
IEC 61850-7-1: Basic communication structure for substation and feeder equipment–
Principles and models
IEC 61850-7-2: Basic communication structure for substation and feeder equipment -
Abstract communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment–
Common data classes
IEC 61850-7-4: Basic communication structure for substation and feeder equipment–
Compatible logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
1. MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. Actual MMS protocol services are mapped to IEC 61850 abstract services in
IEC61850-8-1.
2. Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation
computers running HMI programs or SOE logging software. Servers are usually substation
equipment such as protection relays, meters, RTUs, transformer, tap changers, or bay controllers.
3. Peer-to-peer
Each IED represents one IEC61850 physical device. The physical device contains one logical
device, and the logical device contains many logical nodes. The logical node LPHD contains
information about the IED physical device. The logical node LLN0 contains information about the
IED logical device.
The GGIO logical node is available in the RCS-900 series relays to provide access to digital status
points (including general I/O inputs and warnings) and associated timestamps and quality flags.
The data content must be configured before the data can be used. GGIO provides digital status
points for access by clients. It is intended that clients use GGIO in order to access digital status
values from the RCS-900 series relays. Clients can utilize the IEC61850 buffered reporting
features available from GGIO in order to build sequence of events (SOE) logs and HMI display
screens. Buffered reporting should generally be used for SOE logs since the buffering capability
reduces the chances of missing data state changes. All needed status data objects are
transmitted to HMI clients via buffered reporting, and the corresponding buffered reporting control
block (BRCB) is defined in LLN0.
Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data
from a IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2
provides data from CT/VT source 2 (usually for monitor and display purpose). All these analog
data objects are transmitted to HMI clients via unbuffered reporting periodically, and the
corresponding unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical
nodes provide the following data for each source:
MMXU.ST.Hz: frequency
The following list describes the protection elements for all RCS-900 series relays. The specified
relay will contain a subset of protection elements from this list.
PTUC: undercurrent
PTOC: phase overcurrent, zero sequence overcurrent and overcurrent when CTS
PTUV: undervoltage
PTUF: underfrequency
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For the
RCS-900 series relay protection elements, these flags take their values from related module for
the corresponding element. Similar to digital status values, the protection trip information is
reported via BRCB, and it also locates in LLN0.
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defines for the whole device; the
common settings include all the setting items of communication settings. System settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked and those commands make effective until the item Loc is changed to false. In
RCS-900 series relays, besides the logical nodes we describe above, there are some other logical
nodes below in the IEDs:
LPHD: Physical device information, the logical node to model common issues for physical
device.
PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or
more protection functions to a common “trip” to be transmitted to XCBR. In addition or
alternatively, any combination of “operate” outputs of protection functions may be combined
to a new “operate” of PTRC.
RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers
to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System”
(IEC 60255-24). All enabled channels are included in the recording, independently of the
trigger mode.
IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.
- Bit 1: Data-change
- Bit 4: Integrity
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
MMS file services are supported to allow transfer of oscillography, event record or other files from
a RCS-900 series relay.
9.5.4.3 Timestamps
The timestamp values associated with all IEC61850 data items represent the time of the last
change of either the value or quality flags of the data item.
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.
IEC61850 specifies the type of peer-to-peer data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also Devices that transmit GOOSE messages
also function as servers. Each GOOSE publisher contains a “GOOSE control block” to configure
and control the transmission.
The transmission is also controlled via device setting “GOOSE Group ID” in the setting submenu
“EQUIP SETUP”. The “GOOSE Group ID” setting item defines a definite IED group in which the
IED can communicate with each other via GOOSE protocol, and if GOOSE Group ID is configured
to “0”, GOOSE service is blocked in this IED. IEC61850 recommends a default priority value of 4
for GOOSE. Ethernet traffic that does not contain a priority tag has a default priority of 1. More
details are specified in IEC61850 part 8-1. IEC61850 recommends that the Ether-type Application
ID number be configured according to the GOOSE source.
The RCS-900 series relays support IEC61850 Generic Object Oriented Substation Event
(GOOSE) communication. All GOOSE messages contain IEC61850 data collected into a dataset.
It is this dataset that is transferred using GOOSE message services. The GOOSE related dataset
is configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between RCS-900 series relays.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must
be correct to achieve the successful transfer of data. It is critical that the configured datasets at
the transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
Where:
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
M16 Time M M Y
M17 File transfer O O Y
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
S56 TimeActivated-Operate O
File transfer
S57 GetFile M/O Y
S58 SetFile O Y
S59 DeleteFile O
S60 GetFileAttributeValues M/O Y
Time
SNTP M Y
The RCS-900 series relays support IEC61850 logical nodes as indicated in the following table.
Note that the actual instantiation of each logical node is determined by the product order code.
10.1 Introduction
The chapter contains instructions on how to install, commission and maintenance the protection
equipment. It can also be used as a reference if a periodic test is performed. The chapter covers
procedures for mechanical and electrical installation, energizing and checking of external circuitry,
setting and configuration as well as verifying settings and performing a directionality test.
1) The “Safety information” presents warning and note signs, which the user should draw
attention to.
2) The “Overview” gives an overview over the major task when installing and commissioning
the protection equipment.
3) The “Unpacking and checking the protection equipment” contains instructions on how to
receive the protection equipment.
4) The “Installing the protection equipment” contains instructions on how to install the
protection equipment.
5) The “Checking the external circuit” contains instructions on how to check that the
protection equipment is properly connected to the protection system.
6) The “Energizing the protection equipment” contains instructions on how to start-up the
protection equipment.
7) The “Setting the protection equipment” contains instructions on how to download settings
and configuration to the protection equipment.
9) The “Verifying settings by secondary injection” contains instructions on how to verify that
each included function operates correctly according to the set value.
10) The “Verifying the internal configuration” contains instructions on how verify that the
protection equipment is properly configured.
The chapter is addressing the installation, commissioning and maintenance personnel responsible
for taking the protection into normal service and out of service. The installation personnel must
have a basic knowledge in handling electronic equipment. The commissioning and maintenance
personnel must be well experienced in using protection equipment, test equipment, protection
functions and the configured functional logics in the protection.
careful during certain operations in order to avoid human injuries or damage to equipment.
Warning signs
Warning!
Strictly follow the company and country safety regulations. Working in a high voltage
environment requires serious approach to avoid human injuries and damage to
equipment.
Do not touch circuitry during operation. Potentially lethal voltages and currents are
present.
Always avoid to touch the circuitry when the cover is removed. The product contains
electronic circuitries which can be damaged if exposed to static electricity (ESD). The
electronic circuitries also contain high voltage which is lethal to humans.
Always use suitable isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present.
Never unmount the front or back cover from a powered equipment or from a protection
equipment connected to powered circuitry. Potentially lethal voltages and currents are
present.
Caution signs
Caution!
Always transport modules using certified conductive bags. Always handle modules using
a conductive wrist strap connected to protective ground and on a suitable antistatic
surface. Electrostatic discharge (ESD) may cause damage to the module.
Do not connect live wires to the protection equipment. Internal circuitry may be
damaged.
Always use a conductive wrist strap connected to protective ground when replacing
modules. Electrostatic discharge (ESD) may damage the module and protection
equipment circuitry.
Take care to avoid electrical shock if accessing wiring and connection protection
equipment when installing and commissioning.
Note signs
Note!
Changing the active setting group will inevitably change the protection equipment’s
operation. Be careful and check regulations before making the change.
The protection assembly is designed for a maximum continuous current of four times
rated value.
Activating the other setting group without proper configuration may seriously affect the
protection equipment’s operation.
10.3 Overview
The settings for each function must be calculated before the commissioning task can start. A
configuration, made in the configuration and programming tool, must also be available if the
protection equipment does not have a factory configuration downloaded.
The protection equipment is unpacked and visually checked. It is preferably mounted in a cubicle.
The connection to the protection system has to be checked in order to verify that the installation
was successful.
The installation and commissioning task starts with configuring the digital communication modules,
if included. The protection equipment can then be configured and set, which means that settings
and a configuration has to be applied if the protection equipment does not have a factory
configuration downloaded. Then the operation of each included function according to applied
settings has to be verified by secondary injection. A complete check of the configuration can then
be made. A conformity test of the secondary system has also to be done. When the primary
system has been energized a directionality check should be made.
Carefully examine the protection panel, protection equipment inside and other parts
inside to see that no physical damage has occurred since installation.
Panel wiring:
Check the conducting wire used in the panel to assure that their cross section meet the
requirement. Carefully examine the wiring to see that they are no connection failure exists.
Label:
Check all the isolator links, terminal blocks, ferrules, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable:
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator links and push buttons work normally
and smoothly.
3. Check that all items are included in accordance with the delivery documents.
The user is requested to check that all software functions are included according to the delivery
documents after the terminal has been energized.
These product checks cover all aspects of the protection, which should be checked to ensure that
the protection not only has not been physically damaged prior to commissioning but also functions
correctly and all input quantity measurements are within the stated tolerances.
Sufficient space must be available in front of and at rear of the protection panel to allow access for
maintenance and future modifications. Flush mounted protection equipment should be mounted
so that equipment modules can be added and replaced without excessive demounting.
10.5.2 Dimensions
The equipment adopts IEC standard chassis and is rack with modular structure. It uses an integral
faceplate and plug terminal block on backboard for external connections. This protective device is
IEC 4U high and 19” wide. Figure 10.5-1 shows its dimensions and Figure 10.5-2 shows the panel
cut-out.
482.6
291 465.0
101.6
177.0
465.0
101.6
179.0
4-
Ф6.8
450.0
All these influences can influence the operation of electronic apparatus. On the other hand,
electronic apparatus can transmit interference that can disrupt the operation of other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
Note!
All these precautions can only be effective if the station ground is of good quality.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
Note!
If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (refer to Figure 10.5-3).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
Note!
For metallic connections please observe the voltage difference of both materials
according to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a grounding
strip (braided copper).
Door or hinged
equipment frame
Cubicle ground
rail close to floor
Braided
copper strip
Station
ground
Conducting
connection
There are some ground terminals on some connectors of the relays, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this relay. So, the ground terminal on the rear
panel (refer to Figure 10.5-4) is the only ground terminal of this device.
The grounding strips must therefore be of (preferably tinned) braided copper and not round
copper conductors, as the cross-section of round copper would have to be too large.
Data of braided copper strip: threaded M4, 4.0mm2. Proper terminations must be fitted to both
ends (press/pinch fit and tinned) with a hole for bolting them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
Press/pinch fit
cable terminal
Braided
copper strip Terminal bolt
Contact surface
When using screened cabling always use 360° full screen cable bushing to ensure screen
coupling. Ensure that all signals of the single circuit are in the same single cable. Avoid mixing
current and voltage measuring signals in the same cable. Also use separate cables for control and
measuring circuits.
Auxiliary power cords cross can be directly screwed fixed on the rear panel of DC board. Refer to
section 6.2.1
Welding terminals. Those devices are supplied with sufficient M4 screws for making connections
to the rear mounted terminal blocks using ring terminals, with a recommended maximum of two
ring terminals per relay terminal.
To meet the insulation requirements of the terminal block, for the sake of safety, an insulating
sleeve should be fitted over the ring terminal after crimping.
The wire used for all connections to the welding terminal blocks and heavy duty terminal blocks,
except the EIA(RS)485 port, should have a minimum voltage rating of 300Vrms.
It is recommended that the auxiliary power circuit wiring should be protected by using a 16A high
rupture capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits
must never be open.
Connect the unit to the grounding bar of the cubicle with green/yellow conductor; connected to the
protective Earthing terminal at the back of the DC board. Refer to section 6.2.1. Attend that the
earth wire must be as short as possible. All cautions have to be taken to ensure the best electrical
conductivity, particularly the contact quality, stainless conductor. The impedance between the
relay Earthing terminal and the Earth must be less than 20mΩ under 12Volt, 50Hz. What matters
is that the device has to be only grounded at one point. Loop grounding from unit to unit is not
allowed.
Connectors are generally color coded; connect blue or dark grey cable connectors to blue or dark
grey (receive) back-side connectors. Connect black or grey cable connectors to black or grey
(transmit) back-side connectors.
Fiber optical cables are sensitive to handling. Do not bend too sharply. The minimum curvature
radius is 15 cm for plastic fibers and 25 cm for glass fibers. If cable straps are used, apply with
loose fit.
Note!
Always hold the connector, never the cable, when connecting or disconnecting optical
fibres. Do not twist, pull or bend the fibre. Invisible damage may increase fibre damping
thus making communication impossible.
When using galvanic connection between protective relay and communication equipment or
point-to-point galvanic connection between two protective relays it is essential that the cable
installation is carefully done. This is true regardless of type of module used, only the possible
length of the cable differs. The factors that must be taken into account is the susceptibility for
noise disturbance, due to that the levels of the communication signal are very low. For a best
result, a cable with twisted pairs with screen should be used.
*
A
*
B 52
*
C
209 210 211 212 213 214 201 202 203 204 205 206 207 208
RM SIG
615 DC (-) - BO_Fail_1 902 BO_Fail_2 908
CENT SIG
601 BI_Pulse_GPS + BO_Alm_Abnor_1 903 BO_Alm_Abnor_2 907
AR1
604 BI_RstTarg + COM 910 BO_Trp3P_1 921
Transfer Signal 1
AR2
BO_Recv1_TS_2
608 EBI_Opt1_AR + 918 BO_Trp3P_2 925
BI
Load Shedding
617 BI_ExTrp1P_AR + BO_Recv2_TS_1 913 BO_Trp1P_3 928
623 BI_52b_Phb +
624 BI_52b_Phc +
COM A01 COM A02
625 BI_LowPres_AR +
AR1
BO_C_Trp_1 A09
COM A28
COM A16
BO_TrpA_2 A08
BO
TRIP
BO_TrpA A15
BO_TrpB_2 A10
BO_TrpB A17
DC Power Supply
101 DC+
BO_TrpC A18
BO_TrpC_2 A12
102 DC-
COM A24
103 COM A20
PWR
PC
TRIP
3 3
GROUND BUS 4 4
501 RS485A
FIBRE R
COM Interface (SU)
5 5
COM1
502 RS485B
6 6
FIBRE T
503 GND
7 7
504 RS485A
ETHERNET
8 8
COM2
505 RS485B
9 9
506 GND
COM
RS232 DB 9
Serial Port
507 RS485A
GPS
508 RS485B
DB 15
509 GND
AI FOR TEST
510 RS485A/RS232R
PTINTER
LCD
PTR
HMI
511 RS485B/RS232T
KEYPAD
512 GROUND
Check that the wiring is in strict accordance with the supplied wiring diagram.
Polarity check
Grounding check
The polarity check verifies the integrity of the circuits and the phase relationship. The check
should be performed as close as possible to the relay. The primary injection test verifies the CT
ration and the wiring all the way through from the primary system to the relay. Injection must be
performed for each phase-to-neutral circuit and each phase-to-phase pair. In each case currents
in all phases and the neutral line are measured.
Check that the value of the auxiliary supply voltage remains with the permissible range under all
operating conditions. Check that the polarity is correct according to the instruction manual on the
rear plate of DC board. Refer to section 6.2.1.
Preferably, disconnect the binary input connector form the binary input cards. Check all connected
signals so that both input level and polarity are in accordance with the relay’s specifications.
Note!
The binary inputs may be energized from an external dc auxiliary supply (e.g. the station
battery) in some installations. Check that this is not the case before connecting the field
voltage otherwise damage to the protection may result. The status of each binary input
can be viewed using either RCSPC software installed in a portable PC or by checking the
front man-machine interface LCD. When each binary input is energized the display will
change to indicate the new state of the inputs.
Preferably, disconnect the binary output connector form the binary output cards. Check all
connected signals so that both load and polarity are in accordance with the relay’s specifications.
The user must energies the power supply to the relay to start it up. This could be done in a
numerous of ways, from energizing a whole cubicle to energizing a single relay. The user should
reconfigurate the relay settings. The relay time must be set. The self-supervision function should
also be checked to verify that the relay unit operates properly. The user could also check the
software version, the relay’s serial number, the installed modules, and their ordering number to
ensure that the relay is according to delivery and ordering specifications.
Download from a PC or laptop with RCSPC software or remotely by SCADA. Front port
communication has to be established before the settings can be downloaded.
To change settings through the local HMI need a password which is “+”, “◄”, “▲” and “-”
keyboard on the front panel.
Unless previously agreed to the contrary, the customer will be responsible for determining the
application-specific settings to be applied to the protection and for testing of any scheme logic
applied by external wiring and/or configuration of the protection’s internal programmable scheme
logic.
It is not the intention of the test to verify the operation of the complete system from the relay to the
remote location, just the protection’s rear communications port and any protocol converter
necessary.
Calculated settings
The relay has to be set before the testing can start. Only the functions that are used should be
tested.
All used setting groups should be tested. The user can release the functions to be tested and
prevent other functions from operation by setting the corresponding parameters. The user could
also energize the binary input [BI_BlkComm] to disable communication function to ensure that no
events are reported to remote station during the test.
The setting checks ensure that all of the application-specific protection settings (i.e. both the
protection’s function and programmable scheme logic settings), for the particular installation, have
been correctly applied to the protection.
This test verifies that the accuracy of current measurement is within the acceptable tolerances.
Checking its magnitude using a multimeter. The corresponding reading can then be checked
either in the protection’s submenu “DSP METERING” column or a portable computer connected to
the front communication port with software RCSPC.
The measurement accuracy of the protection is ± 5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.
This test verifies that the accuracy of voltage measurement is within the acceptable tolerances.
Checking its magnitude using a multimeter. The corresponding reading either in the protection’s
submenu “DSP METERING” or a portable computer connected to the front communication port
with software RCSPC.
The measurement accuracy of the protection is ±5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.
Note!
The trip circuit should remain isolated during these checks to prevent accidental operation
of the associated circuit breaker.
Note!
The applied current and/or voltage should be big enough to ensure that both general fault
detector and protective fault detector can operate.
2. Simulate a normal condition with normal bus voltage and line voltage applied to the relay and
wait for 10s until the LED “VT ALARM” is turned off. Wait for the reclaim time of the
auto-reclosing element (15s) until LED “AR READY” lightens.
3. Simulate a internal single-phase or multi-phase fault by applying current and voltage that is
within the range of 0~Un.
Where:
ZSet= [Z_DPFC]
When m=0.9, DPFC distance protection should not operate reliably. When m=1.1, DPFC distance
protection should operate reliably. When m=1.2, the operation time of DPFC distance protection
within the range of 0~10ms.
Note!
2. Short-circuit the terminal RX and terminal TX in the CPU module through the fibre, set
[ID_Local] = [ID_Remote] and [En_InnClock]=1 (The LED “CH ALARM” is turned off)
3. Simulate a normal condition with normal bus voltage and line voltage applied to the relay and
wait for 10s until the LED “VT ALARM” is turned off. Wait for the reclaim time of the
auto-reclosing element (15s) until LED “AR READY” lightens.
When m=1.05, Steady-state current differential protection operates. The time delay is 10~25ms.
When m=0.95, current differential protection should not operate reliably.
When m=1.05, Steady-state current differential protection operates. The time delay is 40~60ms.
When m=0.95, current differential protection should not operate reliably.
6. Increase the setting [I_H_Diff], [I_L_Diff], 2In recommended, and [I_ROC_FD] that is equal to
0.1Un.
7. Setting [XC1L] that make UN/XC1 is greater than 0.1In, 0.4In recommended, [XC0L] should
be a little greater than [XC1L]
8. Simulate a normal condition with three-phase positive sequence voltage and current. Current
leads the voltage 90°and is equal to UN/2XC1, which make capacitance current compensation
condition met.
9. Increase any phase current and keep the other two phases current fixedness, which make
3I0 is greater than 0.3In.
10. Zero sequence current differential protection operates. The time delay is about 120ms.
Note!
The duration of AC input to simulate a fault should last longer than the time setting of
related protection element under testing.
2. Simulate a normal condition with normal bus voltage and line voltage applied to the relay and
wait for 10s until the LED “VT ALARM” is turned off. Wait for the reclaim time of the
auto-reclosing element (15s) until LED “AR READY” lightens.
3. Simulate a forward three-phase fault by applying current I=5A and voltage U=0.95×I×ZSet
(ZSet is the setting of Zone 1 of phase-to-phase distance element [Z_PP1]).
4. The zone 1 of distance element should operate. LED “TRIP” on the front plate should lighten
and a trip report appears on the LCD screen.
5. Simulate a forward single phase-earth fault by applying current I=5A and voltage U=0.95×
(1+K)×I×ZSet (ZSet is the setting of Zone 1 of phase-to-ground distance element [Z_PG1], K=
[K0] setting) to phase A.
7. Check zone 2, 3 of phase-to-ground and phase-to-phase distance elements using the above
method.
8. Simulate reverse single phase-to-ground fault and three-phase by applying 4In current and
0V voltage to the corresponding phase(s). The distance elements should not operate.
Note!
When reverse three phases fault happens with voltage is 0V, zone 3 distance relay will
pick up after memorized polarization quantity disappears, and then trip with time delay
[t_PP3] or [t_PG3].
2. Simulate a normal condition with normal bus voltage and line voltage applied to the relay.
Wait for the reclaim time of the auto-reclosing element (15s) until LED “AR READY” lightens
3. Simulate a forward single phase-to-ground fault by applying 30V voltage and current I=1.05
×ISet (ISet is the setting of stage 2 of directional zero-sequence overcurrent protection
[I_ROC2]) to phase A. Phase angle of injected current lags 78 degrees to voltage.
5. Apply 30V voltage and current I=0.95×ISet (ISet is the setting of stage 2 of directional
zero-sequence overcurrent element [I_ROC2]) to phase A. Phase angle of injected current
lags 78 degrees to voltage. The stage 2 of directional zero-sequence overcurrent protection
should not operate.
6. Apply 30V voltage and current I=1.2×ISet (ISet is the setting of stage 2 of directional
zero-sequence overcurrent protection [I_ROC2]) to phase A. Phase angle of injected current
leads 102 degrees to voltage. The zero sequence overcurrent element should not operate.
2. Simulate a fault by applying current I=m×[I_OC_VTS] when VTS. When m=1.05, phase
overcurrent protection with VTS operates. When m=0.95, phase overcurrent protection with
VTS does not operate. When m=1.2, check the time delay.
4. Simulate a fault by applying current 3I0=m×[I_ROC_VTS] when VTS. When m=1.05, phase
overcurrent protection with VTS operates. When m=0.95, phase overcurrent protection with
VTS does not operate. When m=1.2, check the time delay.
2. When CT circuit failure, the normally open contacts (901-903) and (906-908) are closed.
3. Open the circuit of tripping output and enable current differential protection, distance
protection and zero sequence overcurrent protection. When simulate a three-phase fault by
applying 0V voltage and 10A current, the normally open contacts (903-907), (908-912),
(924-925), (926-927) and (919-921), (923-925), (927-929) are closed.
4. Open the circuit of tripping output, enable current differential protection, distance protection,
zero sequence overcurrent protection and auto-reclosing and set [En_NoChk_AR]=1. After
the LED “VT ALARM” is turned off and LED “AR READY” is lightened, simulating a
three-phase fault by applying 0V voltage and 10A current, the normally open contacts
(901-905), (A01-A11) and (A29-A30) are closed.
6. Shorten contact (614-627) and energize the binary input [BI_Send_TS1], the normally open
contact (910-914) and (916-918) are closed. Shorten contact (614-628) and energize the
binary input [BI_Send_TS2], the normally open contact (909-913) and (915-917) are closed.
7. Broken “TX” of optic fibre interface in CPU module with “RX” of optic fibre in CPU module, the
LED “CH ALARM” will be lightened and the normally open contacts (910-912) and
(909-911)are closed.
The LED “CH ALARM” is turned off on the front panel of equipment without the alarm
[Alm_CH] and these normally open contacts TDGJ are not closed.
Press key “▲” to enter the main menu at first. Move cursor to the item “VALUES→COMM
CH” and press key “ENT” to display following interface and then press key “ESC” to exit. The
number of [N_LossSyn], [N_CrcFail], [N_FrameErr] and [N_FrameDly] are not changed. (add
10 per day mostly)
Comm Ch
Remote ID : 000500
Ch Delay : 00000us
Comm Ch
N_LossSyn : 00000
N_CrcFail : 00000
Comm Ch
N_CrcFail : 00000
N_FrameErr : 00000
N_FrameDly : 00000
Where:
N_FrameDly : the number of the time delay of message extending fixed interval.
Note!
Please keep the fibre optic splice clear, when connect the fibre optic splice to the fibre
optic interface, ensure the bulge of fibre optic splice align with the gap of enamel and then
screw up the FC splice.
If the equipment of channel interface is used in the channel, which should be kept earthing
reliably, the tie line between interface equipment and communication equipment should
conformity with the requirement of NARI and the two terminal of tie line should be earthing
reliably. The earthing net of protection cubicle and communication cubicle should be
divided in physical.
3. Self-check and the transition of binary input in the process of devices start
If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the protection is put into service.
Ensure that all event records, fault records, disturbance records and alarms have been cleared
and LED’s has been reset before leaving the protection.
Chapter 11 Maintenance
NR numerical relay RCS-900 series line relay is designed to require no special maintenance. All
measurement and signal processing circuit are fully solid state. All input modules are also fully
solid state. The output relays are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals
are not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
2. It is only allowed to plug or withdraw relay board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the
primary system is live when withdrawing an AC module. Never try to insert or withdraw the
relay board when it is unnecessary.
3. Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “ALM REPORT” screen on the LCD.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (AI, PWR, CPU, SIG, BI, BO
etc.) and hardware type-form as the removed module. Furthermore, the CPU module replaced
should have the same software version. And the AI and PWR module replaced should have the
same ratings.
The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “VERSION”.
Caution!
When handling a module, take anti-static measures such as wearing an earthed wrist
band and placing modules on an earthed conductive mat. Otherwise, many of the
electronic components could suffer damage. After replacing the CPU module, check the
settings.
1. Replacing a module
Short circuit all AC current inputs and disconnect all AC voltage inputs
Warning!
Hazardous voltage can be present in the DC circuit just after switching off the DC power
supply. It takes approximately 30 seconds for the voltage to discharge.
Unplug the ribbon cable on the front panel by pushing the catch outside.
After replacing the CPU module, input the application-specific setting values again.
Warning!
Units and modules may only be replaced while the supply is switched off and only by
appropriately trained and qualified personnel. Strictly observe the basic precautions to
guard against electrostatic discharge.
Warning!
When handling a module, take anti-static measures such as wearing an earthed wrist
band and placing modules on an earthed conductive mat. Otherwise, many of the
electronic components could suffer damage. After replacing the CPU module, check the
settings.
Danger!
After replacing modules, be sure to check that the same configuration is set as before the
replacement. If this is not the case, there is a danger of the unintended operation of
switchgear taking place or of protections not functioning correctly. Persons may also be
put in danger.
11.5 Cleaning
Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning.
Front panel cleaning: use a smooth cloth. Do not use abrasive material or detergent chemicals.
11.6 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC standard
60255-6 the storage temperature should be from -40oC to 70oC, but the temperature of from -10oC
to 40oC is recommended for long-term storage.
12.1 Decommissioning
1. Switching off
To switch off the protective device, switch off the external miniature circuit breaker of the power
supply.
2. Disconnecting Cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
Danger!
Before disconnecting the power supply cables that connected with the DC module of the
protective device, make sure that the external miniature circuit breaker of the power
supply is switched off.
Danger!
Before disconnecting the cables that are used to connect analog input module with the
primary CTs and VTs, make sure that the circuit breaker for the primary CTs and VTs is
switched off.
3. Dismantling
The protective device rack may now be removed from the system cubicle, after which the cubicles
may also be removed.
Danger!
When the station is in operation, make sure that there is an adequate safety distance to
live parts, especially as dismantling is often performed by unskilled personnel.
12.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
Note!
Strictly observe all local and national regulations when disposing of the device.