0% found this document useful (0 votes)
8 views2 pages

ESA CordexHP12kW Rec

The Cordex HP 12kW is a high-performance, modular switched mode three-phase rectifier designed for telecommunications environments, offering a 480VAC input and 12,000W power output. It features advanced efficiency, reduced operational costs, and a compact design, making it suitable for applications like data centers and central offices. The rectifier supports local and remote control via TCP/IP technology, ensuring easy configuration and monitoring.

Uploaded by

ANDRES WAGNER
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views2 pages

ESA CordexHP12kW Rec

The Cordex HP 12kW is a high-performance, modular switched mode three-phase rectifier designed for telecommunications environments, offering a 480VAC input and 12,000W power output. It features advanced efficiency, reduced operational costs, and a compact design, making it suitable for applications like data centers and central offices. The rectifier supports local and remote control via TCP/IP technology, ensuring easy configuration and monitoring.

Uploaded by

ANDRES WAGNER
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Cordex HP 12kW ®

Modular Switched Mode Three-Phase Rectifier

• High performance -48V high capacity rectifier for CO,


MSC, Data Center and Cable Headend facilities
• High efficiency for decreased OPEX and reduced
carbon footprint
• True three-phase, three wire 480VAC input
• Legacy power system upgrade ready, with Cordex®
HP controller

Cordex® High-Performance rectifiers make Cordex® HP 12kW is a true three-phase, three wire, 480VAC
a proven, reliable platform even better, with input rectifier which meets the critical requirements of current high
significant advancements in efficiency and density telecommunications environments. It combines the latest
performance. DSP controlled power conversion technology, to provide a flexible,
efficient and highly reliable DC power source. Local and remote
In a compact, fan-cooled design, Alpha® HP rectifiers open the setup, adjustment and control is a simple single-step process with
possibility for immediate OPEX/CAPEX savings, reducing total cost of Cordex® CXC HP system controllers. By utilizing TCP/IP technology,
ownership and impact on the environment, and are useable under a complete configuration and monitoring of power equipment is
wider range of applications. possible through a network web browser.

The Cordex® HP 12kW is a perfect solution for various 48VDC high


capacity applications including Central Office, MTSO’s and
Data Centers.

1
Cordex HP 12kW Modular Switched Mode Three-Phase Rectifier
®

P/N: 0100020-001

Electrical Environmental
Nominal: 480VAC (3Ø – 3 Wire + PE) Nominal Operation: -10 to 65°C (14 to 149°F) full rated power
Input Voltage: Range: 430 to 530VAC Temperature: output from 0 to 40°C (32 to 104°F)
Storage:-40 to 70°C (-40 to 185°F)
Input Frequency: 47 to 63Hz
Humidity: 0 to 90% RH non-condensing
Current: 17A max
Altitude: -100 to 2000m (-330 to 6560ft)
Power: 12,000W
Heat Dissipation: <2800 BTU per hour @ 480VAC
Power Factor: >0.96% from 50 to 100% load
Performance / Features
THD: <5% from 70 to 100% load
•AC mains OK —green LED
Efficiency: 94.6% Peak Indicators: •DC output OK — green LED
•Module fail — red LED
Output Voltage: 42 to 58VDC
•CAN interface to CXC-HP
Output Current: 220A max
Controls: •Controller
Static: <±0.5%
Load Regulation: Dynamic: <±4% for 40% - 90% load step •Float voltage
•Equalize voltage
Line Regulation: Static <±0.1% •High voltage alarm
•Low voltage alarm
Voice band: <42dBrnC Adjustments (via CXC HP Controller): •High voltage shutdown
Noise: Wide band: < 20mV RMS (to 10MHz)
•Current limit
<150mV pk to pk (to 100MHz)
•Slope
Psophometric: <4mV RMS •Start delay timers

Acoustic: <65dBa @ 1m (3ft), 30°C (86°F) •Current limit/short circuit


•Start delay
Mechanical Protection: •Input/output fuses
•Output high voltage shutdown
mm: 160H x 261W x 326D •Power limiting
incl. front panel & handle: 175H x 261W x 364D
Dimensions: inches: 6.3H x 10.3W x 11.8D Agency Compliance
incl. front panel & handle: 7H x 10.3W x 14.4D
CSA C22.2 No 60950-1
Weight: 12.8kg (28lbs) UL 60950-1
Safety: CE marked
Shelves IEC/EN 60950-1
23" Shelf (2 Modules) P/N: 0300167-001 CE Marked

mm: 177H x 530W x 388D EMC: ETSI 300 386


Dimensions: inches: 7H x 21.8W x 15.3D CFR47 (FCC) Part 15 Class A
Emissions: EN 55022 (CISPR 22) Class A
Weight: 11.3kg (25lbs)
EN 61000-4-2, 4-3, 4-5, 4-6, 4-11
Mounting: Fits 23" racks only flush/center mount Immunity: ANSI / IEEE C62.41 CatB3
Input: B ox type terminal block, 3 to 16mm (14 to 6AWG)
2
GR-1089 CORE
Connections:
Output: Bus adapters with ³⁄8” studs on 1” centers NEBS Level 3: GR-63 CORE
Chassis ground: Compression lug, 6 to 16mm2 (10 to 6AWG)
CAN communication: RJ 12 offset

Alpha Technologies Services, Inc. USA: 3767 Alpha Way, Bellingham, WA 98226 Canada: 7700 Riverfront Gate, Burnaby, BC V5J 5M4
Toll Free North America: +1 800 322 5742 Outside US: +1 360 647 2360 Technical Support: +1 800 863 3364
For more information visit www.alpha.com
© 2020 Alpha Technologies Services, Inc. All Rights Reserved. Trademarks and logos are the property of Alpha Technologies Services, Inc. 09/2020 2
and its affiliates unless otherwise noted. Subject to revisions without prior notice. E. & O.E. #047-0259-00 REV B

You might also like