Mvaxenbr Sa
Mvaxenbr Sa
T&D
Energy Automation & Information
Type MVAX 12, 21, 31, 91
Trip Circuit Supervision Relays
Features
• Low burden
• Trip circuit can be supervised with
breaker open or closed
• Mis-tripping of breaker by
accidental short-circuits avoided
• No false alarms given due to
protection operation
Application
The Type MVAX relay supervises the
trip circuit of a circuit breaker,
initiating audible alarm and visual
indication if the trip circuit fails or Figure 1: MVAX
the mechanism does not operate.
Four types are available giving
supervision as follows:
Description Under healthy conditions with the
Relay type Faults detected circuit breaker closed, both units
The relays are basically attracted
are energised. If the trip circuit
MVAX 12 Failure of trip armature units of simple and robust
becomes open or the supply fails,
supply only construction having a positive
unit RL2 drops off and opens
MVAX 21, action without chatter.
contact RL2–1 to de-energise unit
MVAX 31 and Type MVAX12 is a single unit which RL1. When the circuit breaker is
MVAX 91 Failure of trip supply is simply connected across the trip open, the auxiliary switch shunts
Open circuit trip coil circuit supply as shown in Figure contact RL2–1 to hold in unit RL1.
or trip circuit wiring 2(a). The unit is normally energised
Failure of circuit The units are delayed (by means of
and drops off if the trip voltage is
breaker tripping copper slugs) on drop-off for a total
lost or falls below approximately
mechanism of 400ms, to prevent a false alarm
40% of nominal. The unit picks up
Type MVAX 31 gives supervision due to voltage dips caused by faults
below 80% of rated voltage.To
with the circuit breaker in either in other circuits or during a normal
avoid operation due to voltage dips
state, and type MVAX 21 with tripping operation, when unit RL2 is
caused by faults in other circuits a
circuit breaker closed only. momentarily short circuited by the
resistance-capacitance time delay
If required, the alarm units of types self reset trip relay contact. If the
circuit is incorporated to give
MVAX 21 and MVAX 31 can be trip relay fails to reset due possibly
100ms delayed drop off.
operated via pilot wires. to failure of the circuit breaker
Type MVAX 91, three separate Type MVAX 21 consists of two units tripping mechanism, the alarm is
MVAX 31’s in a size 8 case. connected as shown in Figure 2(b). initiated.
2
Type MVAX 31 consists of three
units connected as shown in Figure Case earth
Vx
2(c). Under healthy conditions with 1 2 Viewed from front _
+
the circuit breaker closed, units RL2 3 4
2 1
5 6
and RL1 are energised and the 4 3
operation is the same as type R ext 13 R1 14
RL1
MVAX 21. 13 14
2
C1 R2
When the circuit breaker is open,
unit RL3 is also energised via the
normally closed auxiliary switch 21 22
and unit RL1 is held in by contact Note 1 (a) CT shorting links make
before (b) & (c) disconnect
RL3–1. Unit RL3 will detect trip
circuit abnormalities with the circuit 27 28
b) Short terminals break before (c)
breaker open, in a similar manner (c) Long terminals
to unit RL2 with the circuit breaker Module terminal
block viewed from rear
closed.
The units are delayed a total of
Figure 2 (a): MVAX 12 Trip supply supervision
400ms on drop off, as in type
MVAX 21.
Type MVAX 91 consists of three + CB Aux Alarm supply (Vx (1)) _
switch
separate MVAX 31’s connected as 52-b 21 28 Rext (1)
shown in Figure 2(d). RL1
3
27 RL2-1
2 RL1-2 4
Alarm
contacts
5 RL1-3 7
Note: Contact arrangement shown is typical only.
+ _
Trip supply (Vx (2))
Trip relay 52-a
52
T
CB Aux
switches
Rext (2) 13 14 Rext (3) 21 22
RL2 RL3
52-b
Alarm supply (Vx (1)) _
+
27 RL3-1 28 Rext (1)
RL1
3
RL2-1
1 RL1-1 3
2 RL1-2 4 Alarm
contacts
5 RL1-3 7
Note: Contact arrangement shown is typical only.
3
Phase A
+ _
Trip supply (Vx (2))
Trip relay 52-a 29 RL1-1 31
52
T
CB Aux
30 RL1-2 32 Alarm
Rext (2) 47 48 Rext (3) 45 46 contacts
RL2 RL3
52-b 33 RL1-3 35
Alarm supply (Vx (1))
+ _
49 RL3-1 50 Rext (1)
RL1
3
RL2-1
Phase B
+ _
Trip supply (Vx (2))
Trip relay 52-a 37 RL1-1 39
52
T
CB Aux
38 RL1-2 40 Alarm
Rext (2) 53 54 Rext (3) 51 52 contacts
RL2 RL3
52-b 41 RL1-3 43
Alarm supply (Vx (1))
+ _
55 RL3-1 56 Rext (1)
RL1
3
RL2-1
Phase C
+ _
Trip supply (Vx (2))
Trip relay 52-a 1 RL1-1 3
52
T
CB Aux
2 RL1-2 4 Alarm
Rext (2) 25 26 Rext (3) 23 24 contacts
RL2 RL3
52-b 5 RL1-3 7
Alarm supply (Vx (1))
+ _
27 RL3-1 28 Rext (1)
RL1
3
RL2-1
4
Case earth
1 2 Front mounted facing front
Rear mounted facing rear Rear mounted facing rear viewed from front
5 6 viewed from front viewed from front 1
7 8 3
2 5
A A 4 7
11 12
13 14
RL3 RL2 RL1
3
22 14 28
27 28 V V V
21 R1 13 R2 27 RL2-A
Module terminal block V +
Vx V +
Vx V +
Vx
viewed from rear
RL3-A
Note 1
(a) CT shorting links make
Combinations of Output contacts to
before (b) & (c) disconnect output contacts module terminals
(b) Short terminals break before (c)
1 3 5 7 2 4
(c) Long terminals 3M – M M M
2M 1B B M M
1M 2B B M B
5
Front mounted facing front
Rear mounted facing rear Rear mounted facing rear viewed from front
viewed from front viewed from front 29
31
30 33
A A 32 35
V V V
45 R1 47 R2 49 RL2-A
Vx + Vx + Vx +
RL3-A
V V V
51 R1 53 R2 55 RL2-A
Vx + Vx + Vx +
RL3-A
V V V
23 R1 25 R2 27 RL2-A
Vx + Vx + Vx +
RL3-A
Figure 2(f): MVAX 91 Trip circuit supervision relay with preclosing supervision (ac)
6
Technical Data Operating/resetting times
Note: For ac supervision relays, • Typical operating times
the technical information is the MVAX 12 < 20ms
same as for dc versions MVAX 21, 31, 91 < 70ms
• Typical resetting times
Voltage ratings (Vx) MVAX 12 >100 ms
Relays are available for use on any MVAX 21, 31, 91 > 400 ms
combination of the following standard
auxiliary supplies for trip and alarm. Note: Times measured at the lower
Rating Operative range rated voltage. 91 – (3 x MVAX 31)
(V dc) (V dc)
Operation indicator
24/27 19 – 30
30/34 24 – 37.5 A hand or self reset mechanical
48/54 37.5 – 60 operation indicator can be
110/125 87.5 – 137.5 supplied.
220/250 175 – 275
All relays will withstand the maximum Contacts
voltage in the operative range • MVAX 12
continuously. 2 pairs of electrically separate
Note: MVAX 91 not available in contacts in any combination of
220/250V range. normally open or closed
7
High voltage withstand Mechanical environment Cases
• Dielectric withstand • Vibration Type MVAX 12 is available in a
IEC 60255-5:1977 IEC 60255-21-1:1988 size 2 case, see Figure 3. Types
2kV rms for 1 minute between all Response class 1 MVAX 21 and MVAX 31 are
terminals and case earth available in size 3 cases see Figure
2kV rms for 1 minute between 4. Type MVAX 91 is available in a
terminals of independent circuits size 8 case, see Figure 5.
including contact circuits, with
terminals on each independent
circuit connected together. 13
4 holes 4.4ø 24
1kV rms for 1 minute across open 45
contacts of output relays.
• High voltage impulse
IEC 60255-5:1977 168 159
EMC Compliance
89/336/EEC
Compliance with the European
177 157 max.
Commission Directive on EMC is
claimed via the Technical
Reset
Construction File route.
EN 50081-2:1994 51 Flush mounting
EN 50082-2:1995 All dimensions in mm
Generic Standards were
used to establish conformity. Figure 3:
Case outline size 2
Product safety
73/23/EEC 26
4 holes 4.4ø 23.5
Compliance with the European 71
Commission Low Voltage Directive.
EN 61010-1: 1993/A2 : 1995 EN
60950 : 1992/A11: 1997 168 159
Compliance is demonstrated by
reference to generic safety
standards. Push button 73
projection 10 max
Panel cut-out:
Atmospheric environment Flush mounting fixing details
• Temperature
32 212 25 min.
IEC 60255-6:1988
Storage and transit -25°C to +70°C
Operating -25°C to +55°C
IEC 60068-2-1:1990 Cold 177 157 max.
IEC 60068-2-2:1974 Dry heat
• Humidity Reset
IEC 60068-2-3:1969
77 Flush mounting
56 days at 93% RH and 40°C
All dimensions in mm
• Enclosure protection
IEC 60529:1989
Figure 4:
IP50 (dust protected) Case outline size 3
8
155.4
4 holes 4.4ø 24
200
168 159
32 212 25 min.
Reset
Figure 5:
Case outline size 8
Information Required
with Order
Relay type
Alarm and trip supply voltages
Contact combination
Operation indicator required
9
© 2003 ALSTOM - 020300 - Electronic File
Publication: MVAX/EN BR/Sa
Transmission & Distribution Energy Automation & Information, Le Sextant, 3 avenue André Malraux, 92300 Levallois-Perret. France
Tel: +33 (0) 1 41 49 20 00 Fax: +33 (0) 1 41 49 24 85 [email protected] www.tde.alstom.com
Contact Centre on line 24 hours a day : +44 (0) 1785 25 00 70
ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product
referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.