0% found this document useful (0 votes)
10 views112 pages

2021 11 Service Manual For R32 Multi

The Super Inverter Series Service Manual provides essential safety precautions and servicing information for both indoor and outdoor units, including installation guidelines, features, and troubleshooting procedures. It emphasizes the importance of following safety protocols to prevent fire, electric shock, and other hazards during installation and maintenance. The manual also outlines proper handling of refrigerants and necessary checks to ensure safe operation of the air conditioning systems.

Uploaded by

Sandro Pepe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
0% found this document useful (0 votes)
10 views112 pages

2021 11 Service Manual For R32 Multi

The Super Inverter Series Service Manual provides essential safety precautions and servicing information for both indoor and outdoor units, including installation guidelines, features, and troubleshooting procedures. It emphasizes the importance of following safety protocols to prevent fire, electric shock, and other hazards during installation and maintenance. The manual also outlines proper handling of refrigerants and necessary checks to ensure safe operation of the air conditioning systems.

Uploaded by

Sandro Pepe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
You are on page 1/ 112

SUPER INVERTER SERIES

MULTI TYPE
Service Manual
CONTENTS
1. Precaution ....................................................................................................................................................... 1

2 Information servicing...................................................................................................................................... 3

3. General information of Indoor Units............................................................................................................. 7

4. Features .......................................................................................................................................................... 8

5. Dimensions....................................................................................................................................................19

6. Service Space (unit: mm)..............................................................................................................................25

7. Wiring diagram ..............................................................................................................................................28

8. Indoor units combination .............................................................................................................................39

9. Operation temperature range.......................................................................................................................42

10. Electronic function......................................................................................................................................43

11. General information of Outdoor Units .......................................................................................................59

12. Features .......................................................................................................................................................60

13. Dimensions..................................................................................................................................................61

14. Refrigeration Cycle Diagram ......................................................................................................................62

15. Sound Levels ...............................................................................................................................................64

16. Installation Details.......................................................................................................................................65

17. Electronic control function.........................................................................................................................73

18. Troubleshooting ..........................................................................................................................................78

Caution: Risk of fire/flammable materials

※The specifications, designs, and information in this book are subject to change without notice for
product improvement.
1. Precaution fall with it, causing property damage, product
failure, and personal injury.
1.1 Safety Precaution  Do not let the air conditioner run for a
 To prevent injury to the user or other long time when the humidity is very high and
people and property damage, the following a door or a window is left open.
instructions must be followed.  Take care to ensure that power cable
 Incorrect operation due to ignoring could not be pulled out or damaged during
instruction will cause harm or damage. operation.
 Before service the unit, be sure to read There is risk of fire or electric shock.
this service manual at first.  Do not place anything on the power
1.2 Warning cable.
 Appliance shall be stored in a room without There is risk of fire or electric shock.
continuously operating open flames (for  Do not plug or unplug the power supply
example an operating gas appliance) and plug during operation.
ignition sources (for example an operating There is risk of fire or electric shock.
electric heater).  Do not touch (operation) the product
 Installation with wet hands.
 Do not install the unit at place where  Do not place a heater or other
leakage of flammable gas may occur. In case appliance near the power cable.
gas leaks and accumulates at surrounding of There is risk of fire and electric shock.
the unit, it may cause fire.  Do not allow water to run into electrical
 Do not use a defective or underrated parts.
circuit breaker. Use this appliance on a It may cause fire, failure of the product, or
dedicated circuit. electric shock.
There is risk of fire or electric shock.  Do not store or use flammable gas or
 For electrical work, contact the dealer, combustible near the product.
seller, a qualified electrician, or an authorized There is risk of fire or failure of product.
service center.  Do not use the product in a tightly
Do not disassemble or repair the product, there closed space for a long time.
is risk of fire or electric shock. Oxygen deficiency could occur.
 Always ground the product.  When flammable gas leaks, all naked
There is risk of fire or electric shock. flames shall be removed or extinguished.
 Install the panel and the cover of  If strange sounds or smoke comes
control box securely. from product, turn the breaker off or
There is risk of fire of electric shock. disconnect the power supply cable.
 Always install a dedicated circuit and There is risk of electric shock or fire.
breaker.  Stop operation and close the window in
Improper wiring or installation may cause fore storm or hurricane. If possible, remove the
or electric shock. product from the window before the hurricane
 Use the correctly rated breaker of fuse. arrives.
There is risk of fire or electric shock. There is risk of property damage, failure of
 Do not modify or extend the power product, or electric shock.
cable.  Do not open the inlet grill of the
There is risk of fire or electric shock. product during operation. (Do not touch the
 Do not install, remove, or reinstall the electrostatic filter, if the unit is so equipped.)
unit by yourself (customer). There is risk of physical injury, electric shock, or
There is risk of fire, electric shock, explosion, or product failure.
injury.  When the product is soaked, contact an
 Be caution when unpacking and authorized service center.
installing the product. There is risk of fire or electric shock.
Sharp edges could cause injury, be especially  Be caution that water could not enter
careful of the case edges and the fins on the the product.
condenser and evaporator. There is risk of fire, electric shock, or product
 For installation, always contact the damage.
dealer or an authorized service center.  Ventilate the product from time to time
 Do not install the product on a when operating it together with a stove etc.
defective installation stand. There is risk of fire or electric shock.
 Be sure the installation area does not  Turn the main power off when cleaning
deteriorate with age. or maintaining the product.
If the base collapses, the air conditioner could There is risk of electric shock.

1
 When the product is not be used for a through air inlet or outlet while the product is
long time, disconnect the power supply plug operated.
or turn off the breaker.  Do not drink the water drained from the
There is risk of product damage or failure, or product.
unintended operation.  Use a firm stool or ladder when
 Take care to ensure that nobody could cleaning or maintaining the product.
step on or fall onto the outdoor unit. Be careful and avoid personal injury.
This could result in personal injury and product  Replace the all batteries in the remote
damage. control with new ones of the same type. Do
not mix old and new batteries or different
 CAUTION types of batteries.
 Always check for gas (refrigerant) There is risk of fire or explosion.
leakage after installation or repair of product.  Do not recharge or disassemble the
Low refrigerant levels may cause failure of batteries. Do not dispose of batteries in a fire.
product. They may burn of explode.
 Install the drain hose to ensure that  If the liquid from the batteries gets onto
water is drained away properly. your skin or clothes, wash it well with clean
A bad connection may cause water leakage. water. Do not use the remote of the batteries
 Keep level even when installing the have leaked.
product.
It can avoid vibration of water leakage.
 Do not install the product where the
noise or hot air from the outdoor unit could
damage the neighborhoods.
It may cause a problem for your neighbors.
 Use two or more people to lift and
transport the product.
 Do not install the product where it will
be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product.
Corrosion, particularly on the condenser and
evaporator fins, could cause product
malfunction or inefficient operation.

 Operational
 Do not expose the skin directly to cool
air for long time. (Do not sit in the draft).
 Do not use the product for special
purposes, such as preserving foods, works of
art etc. It is a consumer air conditioner, not a
precision refrigerant system.
There is risk of damage or loss of property.
 Do not block the inlet or outlet of air
flow.
 Use a soft cloth to clean. Do not use
harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage
to the plastic parts of the product.
 Do not touch the metal parts of the
product when removing the air filter. They are
very sharp.
 Do not step on or put anything on the
product. (outdoor units)
 Always insert the filter securely. Clean
the filter every two weeks or more often if
necessary.
A dirty filter reduces the efficiency of the air
conditioner and could cause product
malfunction or damage.
 Do not insert hands or other objects
2
7. Ventilated area
2 Information servicing
Ensure that the area is in the open or that it is
1.Checks to the area adequately ventilated before breaking into the
Prior to beginning work on systems containing system or conducting any hot work. A degree of
flammable refrigerants, safety checks are ventilation shall continue during the period
necessary to ensure that the risk of ignition is that the work is carried out. The ventilation should
minimised. For repair to the refrigerating safely disperse any released refrigerant
system, the following precautions shall be complied and preferably expel it externally into the
with prior to conducting work on the atmosphere.
system. 8. Checks to the refrigeration equipment
2. Work procedure Where electrical components are being changed,
Work shall be undertaken under a controlled they shall be fit for the purpose and to the correct
procedure so as to minimise the risk of a specification. At all times the manufacturer's
flammable gas or vapour being present while the maintenance and service guidelines shall be
work is being performed. followed. If in doubt consult the manufacturer's
3. General work area technical department for assistance. The following
checks shall be applied to installations using
All maintenance staff and others working in the flammable refrigerants:
local area shall be instructed on the nature
the charge size is in accordance with the room
of work being carried out. Work in confined spaces size within which the refrigerant containing parts
shall be avoided. The area around the are installed;
work space shall be sectioned off. Ensure that the the ventilation machinery and outlets are
conditions within the area have been operating adequately and are not obstructed;
made safe by control of flammable material. if an indirect refrigerating circuit is being used,
4. Checking for presence of refrigerant the secondary circuit shall be checked
The area shall be checked with an appropriate for the presence of refrigerant; marking to the
refrigerant detector prior to and during work, equipment continues to be visible and legible.
to ensure the technician is aware of potentially markings and signs that are illegible shall be
flammable atmospheres. Ensure that the corrected;
leak detection equipment being used is suitable for refrigeration pipe or components are installed
use with flammable refrigerants, i.e. no in a position where they are unlikely to be exposed
sparking, adequately sealed or intrinsically safe. to any substance which may corrode refrigerant
5. Presence of fire extinguisher containing components, unless the components are
constructed of materials which are inherently
If any hot work is to be conducted on the resistant to being
refrigeration equipment or any associated parts,
appropriate fire extinguishing equipment shall be corroded or are suitably protected against being so
available to hand. Have a dry powder or corroded.
CO2 fire extinguisher adjacent to the charging area. 9. Checks to electrical devices
6. No ignition sources Repair and maintenance to electrical components
shall include initial safety checks and component
No person carrying out work in relation to a inspection procedures. If a fault exists that could
refrigeration system which involves exposing compromise safety, then no
any pipe work that contains or has contained electrical supply shall be connected to the circuit
flammable refrigerant shall use any sources of until it is satisfactorily dealt with. If the fault cannot
ignition in such a manner that it may lead to the risk be corrected immediately but it is necessary to
of fire or explosion. All possible ignition continue operation, an adequate
sources, including cigarette smoking, should be temporary solution shall be used. This shall be
kept sufficiently far away from the site of reported to the owner of the equipment so all
installation, repairing, removing and disposal, parties are advised. Initial safety checks shall
during which flammable refrigerant can include:
possibly be released to the surrounding space. that capacitors are discharged: this shall be
Prior to work taking place, the area around done in a safe manner to avoid possibility of
the equipment is to be surveyed to make sure that sparking;
there are no flammable hazards or ignition
risks.NO SMOKING signs shall be displayed.
3
that there no live electrical components and refrigerant leaks. A halide torch (or any other
wiring are exposed while charging, recovering or detector using a naked flame)
purging the system; shall not be used.
that there is continuity of earth bonding. 14. Leak detection methods
10. Repairs to sealed components The following leak detection methods are deemed
10.1 During repairs to sealed components, all acceptable for systems containing
electrical supplies shall be disconnected from the flammable refrigerants. Electronic leak detectors
equipment being worked upon prior to any removal shall be used to detect flammable
of sealed covers, etc. If it is absolutely necessary to
refrigerants, but the sensitivity may not be adequate,
have an electrical supply to equipment during
or may need re-calibration. (Detection equipment
servicing, then a permanently operating form of
shall be calibrated in a refrigerant-free area.)
leak detection shall be located at the most critical
Ensure that the detector is not a potential source of
point to warn of a potentially hazardous situation.
ignition and is suitable for the refrigerant used. Leak
10.2 Particular attention shall be paid to the detection equipment shall be set at a percentage of
following to ensure that by working on electrical the LFL of the refrigerant and shall be calibrated to
components, the casing is not altered in such a way the refrigerant employed and the appropriate
that the level of protection is affected. This shall percentage of gas (25 % maximum) is confirmed.
include damage to cables, excessive number of Leak detection fluids are suitable for use with most
connections, terminals not made to original refrigerants but the use of detergents containing
specification, damage to seals, incorrect fitting of chlorine shall be avoided as the chlorine may react
glands, etc. with the refrigerant and corrode the copper
Ensure that apparatus is mounted securely. pipe-work.
Ensure that seals or sealing materials have not If a leak is suspected, all naked flames shall be
degraded such that they no longer serve the removed or extinguished.
purpose of preventing the ingress of flammable If a leakage of refrigerant is found which requires
atmospheres. Replacement parts shall be in brazing, all of the refrigerant shall be
accordance with the manufacturer's specifications. recovered from the system, or isolated (by means
NOTE: The use of silicon sealant may inhibit the of shut off valves) in a part of the system
effectiveness of some types of leak detection remote from the leak. Oxygen free nitrogen (OFN)
equipment. Intrinsically safe components do not shall then be purged through the system both
have to be isolated prior to before and during the brazing process.
working on them. 15. Removal and evacuation
11. Repair to intrinsically safe components When breaking into the refrigerant circuit to make
Do not apply any permanent inductive or repairs or for any other purpose
capacitance loads to the circuit without ensuring conventional procedures shall be used. However, it
that this will not exceed the permissible voltage and is important that best practice is
current permitted for the equipment in use.
followed since flammability is a consideration. The
Intrinsically safe components are the only types that
following procedure shall be adhered to:
can be worked on while live in the presence of a
flammable atmosphere. The test apparatus shall be remove refrigerant;
at the correct rating. purge the circuit with inert gas;
Replace components only with parts specified by evacuate;
the manufacturer. Other parts may result purge again with inert gas;
in the ignition of refrigerant in the atmosphere from open the circuit by cutting or brazing.
a leak.
The refrigerant charge shall be recovered into the
12. Cabling correct recovery cylinders. The system
Check that cabling will not be subject to wear, shall be flushed with OFN to render the unit
corrosion, excessive pressure, vibration, sharp safe. This process may need to be repeated several
edges or any other adverse environmental effects. times. Compressed air or oxygen shall not be used
The check shall also take into account the effects of for this task. Flushing shall be achieved by breaking
aging or continual vibration from sources such as the vacuum in the system with OFN and continuing
compressors or fans. to fill until the working pressure is achieved, then
13. Detection of flammable refrigerants venting to atmosphere, and finally pulling down to a
Under no circumstances shall potential sources of vacuum. This process shall be repeated until no
ignition be used in the searching for or detection of refrigerant is within the system. When the final OFN
charge is used, the system shall be vented down to

4
atmospheric pressure to enable work to take place. f) Make sure that cylinder is situated on the scales
This operation is absolutely vital if brazing before recovery takes place.
operations on the pipe-work are to take place. g) Start the recovery machine and operate in
Ensure that the outlet for the vacuum pump is not accordance with manufacturer's instructions.
close to any ignition sources and there is h) Do not overfill cylinders. (No more than 80 %
ventilation available. volume liquid charge).
16. Charging procedures i) Do not exceed the maximum working pressure of
In addition to conventional charging procedures, the cylinder, even temporarily.
the following requirements shall be followed: j) When the cylinders have been filled correctly and
Ensure that contamination of different the process completed, make sure that the
refrigerants does not occur when using charging cylinders and the equipment are removed from site
equipment. Hoses or lines shall be as short as promptly and all isolation valves on the equipment
possible to minimize the amount of refrigerant are closed off.
contained in them. k) Recovered refrigerant shall not be charged into
Cylinders shall be kept upright. another refrigeration system unless it has
Ensure that the refrigeration system is earthed been cleaned and checked.
prior to charging the system with refrigerant. 18. Labelling
Label the system when charging is complete (if Equipment shall be labelled stating that it has been
not already). de-commissioned and emptied of
Extreme care shall be taken not to overfill the refrigerant. The label shall be dated and signed.
refrigeration system. Ensure that there are labels on the equipment
Prior to recharging the system it shall be stating the equipment contains flammable
pressure tested with OFN. The system shall be refrigerant.
leak tested on completion of charging but prior to 19. Recovery
commissioning. A follow up leak test shall be When removing refrigerant from a system,
carried out prior to leaving the site. either for servicing or decommissioning, it is
17. Decommissioning recommended good practice that all refrigerants
Before carrying out this procedure, it is essential are removed safely.
that the technician is completely familiar with the When transferring refrigerant into cylinders,
equipment and all its detail. It is recommended ensure that only appropriate refrigerant
good practice that all refrigerants are recovered recovery cylinders are employed. Ensure that the
safely. Prior to the task being carried out, an oil and correct numbers of cylinders for holding the total
refrigerant sample shall be taken. system charge are available. All cylinders to be
In case analysis is required prior to re-use of used are designated for the recovered refrigerant
reclaimed refrigerant. It is essential that and labelled for that refrigerant (i.e. special
electrical power is available before the task is cylinders for the recovery of refrigerant). Cylinders
commenced. shall be complete with pressure relief valve and
associated shut-off valves in good working order.
a) Become familiar with the equipment and its
operation. Empty recovery cylinders are evacuated and, if
possible, cooled before recovery occurs.
b) Isolate system electrically.
The recovery equipment shall be in good
c) Before attempting the procedure ensure that:
working order with a set of instructions concerning
mechanical handling equipment is available, if the equipment that is at hand and shall be suitable
required, for handling refrigerant cylinders; for the recovery of flammable refrigerants. In
all personal protective equipment is available addition, a set of calibrated weighing scales shall
and being used correctly; be available and in good working order.
the recovery process is supervised at all times Hoses shall be complete with leak-free
by a competent person; disconnect couplings and in good condition. Before
recovery equipment and cylinders conform to using the recovery machine, check that it is in
the appropriate standards. satisfactory working order, has been properly
maintained and that any associated electrical
d) Pump down refrigerant system, if possible.
components are sealed to prevent
e) If a vacuum is not possible, make a manifold so
ignition in the event of a refrigerant release. Consult
that refrigerant can be removed from various parts
manufacturer if in doubt.
of the system.

5
The recovered refrigerant shall be returned to
the refrigerant supplier in the correct
recovery cylinder, and the relevant Waste Transfer
Note arranged. Do not mix refrigerants
in recovery units and especially not in cylinders.
If compressors or compressor oils are to be
removed, ensure that they have been
evacuated to an acceptable level to make certain
that flammable refrigerant does not
remain within the lubricant. The evacuation process
shall be carried out prior to returning
the compressor to the suppliers. Only electric
heating to the compressor body shall be
employed to accelerate this process. When oil is
drained from a system, it shall be carried out safely.

6
3. General information of Indoor Units
Four-way cassette (compact) Four-way cassette (Super Slim )

A6 Ducted
Cool Easy

Under Ceiling
18 C

ODU

14/18/21/27K 28/36/42K

7
Capacity
Power supply Carrier Model
(Btu/h)

14K-HP-T2 1 Φ, 220-240V~,50Hz 38QUS014D8S2-1


18K-HP-T2 1 Φ, 220-240V~,50Hz 38QUS018D8S2-2
21K-HP-T3 1 Φ, 220-240V~,50Hz 38QUS021D8S3-1
R32 New Multi
CDU 27K-HP-T3 1 Φ, 220-240V~,50Hz 38QUS027D8S3-2
28K-HP-T4 1 Φ, 220-240V~,50Hz 38QUS028D8S4-1
36K-HP-T4 1 Φ, 220-240V~,50Hz 38QUS036D8S4-1
42K-HP-T5 1 Φ, 220-240V~,50Hz 38QUS042D8S5-1
7K-HP Accord to ODU 42QHE07D8SH
R32 9K-HP Accord to ODU 42QHE09D8SH
Cool Easy 12K-HP Accord to ODU 42QHE12D8SH
Hiwall IDU 18K-HP Accord to ODU 42QHE18D8SH
24K-HP Accord to ODU 42QHE24D8SH
7K-HP Accord to ODU 42QHG007D8S
R32 9K-HP Accord to ODU 42QHG009D8S
18C/AG Hiwall 12K-HP Accord to ODU 42QHG012D8S
IDU 18K-HP Accord to ODU 42QHG018D8S
24K-HP Accord to ODU 42QHG024D8S
7K-HP Accord to ODU 42QTD007D8S
9K-HP Accord to ODU 42QTD009D8S
R32 IDU New
12K-HP Accord to ODU 42QTD012D8S-1
Cassette
18K-HP Accord to ODU 42QTD018D8S-2
24K-HP Accord to ODU 42QTD024D8S
7K-HP Accord to ODU 42QSS007D8S

R32 IDU New 9K-HP Accord to ODU 42QSS009D8S


Ducted 12K-HP Accord to ODU 42QSS012D8S-1
18K-HP Accord to ODU 42QSS018D8S-1
24K-HP Accord to ODU 42QSS024D8S
R32 IDU 18K-HP Accord to ODU 42QZL018D8S-2
Under Ceiling 24K-HP Accord to ODU 42QZL024D8S-1

7-1
4. Features
4.1 Four-way cassette type(compact)
4.1.1 New panel
 360°surrounding air outlet design, affords comfortable feeling

4.1.2 Compact design


 The body size is 570×260×570mm, it’s just smaller than the ceiling board, so it’s very easy for
installation and will not damage the decoration. The panel size is 647×50×647mm.
 The hooks are designed in the four corners of the body, which can save installation space.

4.1.3 Electric control box built-in design


 The E-box is simply and safely built inside the indoor unit. It’s convenient for installation and
maintenance. Can check the control part easily, you only need to open the air return grille.

4.1.4 Fresh air intake function:


 Fresh air fulfills air quality more healthy and comfortable.

8
Fresh
Air

Dimension:Φ75mm

4.1.5 Air passage function


 Reserves the space for air outlet from the side of indoor unit; It’s availed to connect air duct
from the two sides to the nearby small rooms.

9
4.2 Four-way cassette type(super slim)
4.2.1 360° Air Flow
 360°directional wind can deliver air evenly throughout every corner in any space, reducing hot and cold
spots in the room.

4.2.2 Easy Installation


 The Cassette is much slimmer due to the redesigned heat exchanger and overall structures. It now
requires less space for installation.

4.2.3 Reserved Air Outlet for Duct


 The cassette unit is equipped with reserved connection for air outlet at the side of the indoor unit. It can
connect to an air duct to cool a small room nearby.

4.2.4 Reserved remote on-off and alarm ports(Optional for fixed-speed units, standard for inverter
units)
 Remote on-off: With the reserved ports. a remote switch can be easily connected to realize remote
control.
 Alarm: The built-in PCB can output alarm signal, which achieve setting up an external alarm light or
vibration gauge possible.

10
4.2.5 Fresh Air
 Fresh air intake function brings you fresh and comfortable air feeling.

4.2.6 Wired Controller(Optional)


 Compared with infrared remote controller, wired controller can be fixed on the wall and avoid mislaying.
It's mainly used for commercial zone and makes air conditioner control more convenient.

11
4.3 Ducted
4.3.1 Higher Static Pressure
 As a ducted air conditioner with medium static pressure, it has the widest static pressure range.
 The maximum static pressure reaches 160 Pa

4.3.2 Slim Design


 The industry Lowest height is designed to be fitted into tight roof spaces.

4.3.3 Constant air volume control


 For ordinary duct, when the static pressure exceeds the expected range, it is fairly difficult even for an
experienced installer to calculate and adjust the air volume precisely.
 With constant air volume control technology, the duct will automatically adjusts to perfect static pressure
and keep constant air volume.

4.3.4 Installation accessories: (Optional)


 Canvas Air Passage, Filter, for easy installation

12
Filter

4.3.5 Flexible Air Intake Way (Bottom side or Rear side)


 The frame size of air inlet in rear and bottom is the same. It’s very easy to switch to match different
application.

Air intake from rear (Standard) Air intake from bottom (Optional)

4.3.6 Communication wire connection


 A6 duct uses two wires without polarity connection way, which almost has no mistake during the
installation.

13
4.3.7 Easy Clean
 Clean the filter (Optional, standard product without filter)
 It is easy to draw out the filter from the indoor unit for cleaning, even the filter is installed in rear side or
bottom side.

 With a larger window design, once the motor and the blower wheels have been detached, heat
exchanger and water receiver tray in behind can be seen very clearly. Dusted can be easily removed
from the inside by vacuum

4.3.8 Easy maintenance


 A6 ducted allows operators maintenance the motor from the bottom more easily compare with that on
the top.

14
 A6 ducted has big space for maintenance at the side

4.3.9 Fresh air intake function(Optional)


 Install one duct from the reserved fresh-air intake to outdoor.
Continually inhale the fresh air to improve the quality of the indoor air, fulfills air quality more healthy and
comfortable.
 A ventilation motor (provided by the installer) can be installed inside the fresh air duct to improve the
fresh air volume. There are reserved ports for this motor on main PCB (Standard for 3D inverter units,
and only optional for DC inverter 53~160 units).

4.3.10 Built-in drain pump (Optional)


 Built-in drain pump can lift the water to 750mm upmost, which widens the drainage piping range.
Max 750mm

15
4.4 Console (NO Model)
4.4.1 Consumes up to 30% less energy than non-inverter units
——DC inverter compressor
——indoor fan motor adopts DC motor

4.4.2 Achieves set temperature more quickly


——air supplying from top and bottom or from top only
——air inlet from four directions

4.4.3 Compact unit body, space saving


——this unit body is very thin and harmonious with room. It is beautiful, elegant and space saving.
——light weight and compact.

4.4.4 Flexible installation.


——can be used for floor standing or lower wall applications
——as a floor standing floor model, it can be semi or fully recessed without loss of capacity.

4.4.5 High efficiency filter


——built in Formaldehyde nemesis filter
——active-carbon and biological anti-virus filter is optional.

16
4.4.6 Comfort
——flexible air blow: vertical auto swing and wide angle louvers ensure that warm air reaches the furthest
corners of the room and increase the air flow coverage
——Low noise operation, lowest to 23Db
——Low starting power and precise room temperature adjustment

4.4.7 Powerful mode can be selected for rapid cooling or heating.

4.4.8 Easy cleaning grille and maintenance

4.4.9 Indoor unit adopts DC motor, it has five level fan speed meet different requirements.

4.5 Under Ceiling


4.5.1 New design, more modern and elegant appearance.

4.5.2 Convenient installation


--The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow
--It is especially useful when installation of an air conditioner in the center of the ceiling is impossible
due to a structure such as one lighting.

4.5.3 Two direction auto swing (vertical & horizontal) and wide angle air flow,
--Air flow directional control minimizes the air resistance and produces wilder air flow to vertical
direction.
--The range of horizontal air discharge is widened which secures wider air flow distribution to provide
more comfortable air circulation no matter where the unit is set up

4.5.4 Three level fan speed, more humanism design, meets different air-supply requirement.

4.5.5 New foam drain pan with plastic-spraying inner surface

17
4.5.6 Easy operation.

4.5.7 Remote control and optional wired control method.

18
5. Dimensions
5.1 Four-way cassette type (compact):

Drain hole
Gas side ( for Service )
Liquid side Body
4-install hanger

2- 150 Distribution duct

2- 170

523

570
E-parts box

4-Screw hole
(for install panel)

545

570 260

32 Drain pipe
65 Fresh air intake

75
156
125
44

Wiring connection port 40


68

Panel
647

647 50

19
5.2 Four-way cassette type (super slim):

Model(KBtu/h) Unit A B C D
mm 165 80 204 50
24
inch 6.5 3.15 8.03 1.97

20
5.3 A6 Ducted

Model
unit A B C D E F G H I J K L M H1 H2 W1 W2
(KBtu/h)

mm 700 200 506 450 137 537 30 152 599 186 50 741 360 84 140 84 84
7/9/12
inch 27.56 7.87 19.92 17.72 5.39 21.14 1.18 5.98 23.58 7.32 1.97 29.17 14.17 3.31 5.51 3.31 3.31

mm 880 210 674 600 140 706 50 136 782 190 40 920 508 78 148 88 112
18
inch 34.65 8.27 26.54 23.62 5.51 27.8 1.97 5.35 30.79 7.48 1.57 36.22 20 3.07 5.83 3.46 4.41

mm 1100 249 774 700 140 926 50 175 1001 228 5 1140 598 80 150 130 155
24
inch 43.31 9.80 30.47 27.56 5.51 36.46 1.97 6.89 39.41 8.98 0.2 44.88 23.54 3.15 5.91 5.12 6.10

21
5.4 Console (N/A)

600
700 210

Hanging arm
195

16 Drain pipe

22
5.5 Under Ceiling
2- 33 Wiring connection port

2- 40 Drain discharge port

204
140
94
120 Fresh air intake
Refrigerant pipe hole
120

B
C

D
Hanging arm
220
222

Capacity (KBtu/h) A B C D
18 1068 675 235 983
24 1068 675 235 983

23
5.6 Hi-wall

5.6.1 AG Indoor unit

Model (KBtu/h) W D H
7K/9K 726 210 291
12K 835 208 295
18K 969 241 320
24K 1083 244 336

24
5.6 Hi-wall

5.6.2 Cool Easy Indoor unit

Capacity
Capacity Body
Body Code
Code W(mm/inch)
W(mm/inch) D(mm/inch)
D(mm/inch) H(mm/inch)
H(mm/inch)
9k~12k B 795/31.3 225/8.86 295/11.61
18k C 965/38 239/9.41 319/12.56
24k D 1140/44.88 275/10.83 370/14.57

24
6. Service Space (unit: mm)
6.1 Four-way cassette (compact)

6.2 Four-way cassette (super slim)

25
6.3 Ducted
Ensure enough space required for installation and maintenance.

All the indoor units reserve the hole to joint the fresh air pipe. The hole size as following:

6.4 Console

26
6.5 Under Ceiling

6.6 Hi-wall

18C/AG

Cool Easy

27
7. Electrical Wiring Diagrams

7.1 Indoor unit


A6 Duct type
7K/9K
Specifications
12K/18K/24K
Specifications
Compact Cassette type:
7K/9K

Specifications

 Page 67 
12K
Specifications

 Page 68 
18K

Specifications

 Page 69 
24K

Specifications

 Page 69 
Wall mounted type
18C 7K/9K/12K/18K
Specifications

 Page 70 
18C 24K

Specifications

 Page 71 
Cool easy 7K/9K/12K/18/24K

INDOOR WIRING DIAGRAM CAP


M
16022000034214
INDOOR M
FAN M
M M

2
3 5(3 or 2) 5(10) 5(10) 5
2 2 PLASMA OR ION(12V)
Transformer or CN11 CN13 CN12 CN27 CN19 CN21 CN22 CN26 OR UVC
Power board 2 CN10
CN15
Pipe Temperature Sensor
MAIN BOARD CN29 2 CN701 Switch board
Y/G P_1 L-OUT
CN14
WHITE Room Temperature Sensor
ON
RED S1
Y/G N-IN L-IN 4
BLUE(BLACK) 12 Wi-Fi Controller
CN31 CN32 CN18
YELLOW
5 Wire Controller
W 1(L) 2(N) S JX1
Indoor unit MULTI-FUNCTION CONTROL BOARD 2 4(8) CN3
CN43 5(3 or 4)
CN42 CN41 CN40 CN1 Infrared Sensor
Outdoor unit CN44 CN45 CN2
X Y E 12V/5V HA HB CN46 3
CN5 5 Humidity Sensor
CN21
To outdoor unit To CCM Comm.Bus To Randomly To Remote To Remote CN4
or Connected Alarm Switch Room Temperature Sensor
485 Wire-controller Wire-controller

FOR SETTING NETADDRESS (CCM Comm.Bus)


S1_1 S1_2 TYPE OPTIONAL
ENC3+F1 0 ON 0 ON 0 ON 0 ON
OFF OFF 9K
ON OFF 12K (MULTI-FUNCTION
NOTE: The dotted bordered
OFF ON 18K CONTROL BOARD) 12 12 8 12 12
8 8 8 rectangle represents the
ON ON 24K CODE 0~F 0~F 0~F 0~F component is optional, the
NETADDRESS 0~15 16~31 32~47 48~63 actual shape shall prevail.
FACTORY SETTING
7.2 Outdoor Unit
14K/18K

16022300002793
Specifications

Y/G
Y/G
Y/G

Y/G
CRANKCASE
4 -WAY

HE ATER
HEATER

PAN

AC-FAN
N

L
S

CA PACI T OR
BROWN
Y/G

AMBIENT TEMP. SENSOR

CONDENSER TEMP. SENSOR


BLACK

OPTIONAL:
BLUE

DC-FAN
V

RED
U

 Page 80 
21K/27K

16022000035910

Specifications

 Page 81 
28K

RJ45 Notes:
4 DR BOARD This symbol indicates the element is optional,

CN2
16022300000803

HIGH PRESSURE PROTECT


the actual shape shall be prevail.

LOW PRESSURE PROTECT


FOR USER CN1 CN5
This symbol indicates field wiring.
TO CONNECT
A B C D
RED(BROWN) OPTIONAL
INDOOR PIPE
OUT TEMP

Specifications
YELLOW
BLUE(BLACK)

RED
4
OUTDOOR AMBIENT
T4 TEMPERATURE SENSOR

CN7 CN17
CN29 CN12 CN14 CN15 CONDENSER
BLUE

CompTop T2B T3 TEMPERATURE SENSOR


RED

CN32 LOW/HIGH
CN33 DISCHARGE SENSOR
L-OUT
CN4 CN5 4
CN26
IPM BOARD ON(4) CN37 ELECTRONIC
~ ~
COM(3) 6

CN24
VALVE-D EXPANSIVE
RY2 VALVE
ELECTRONIC

CN22
6
5 VALVE-C EXPANSIVE

CN21
CN1 VALVE
CN2 CN3 ELECTRONIC

CN19
6
VALVE-B EXPANSIVE
U V W
MAIN BOARD VALVE
ELECTRONIC

CN18
6
BLUE BLUE P-1 VALVE-A EXPANSIVE
CN14 P1
RED VALVE
BLACK S-B S-C S-D P2
BLUE RED L-IN N-IN S-A OPTIONAL1
WHITE

Y/G CN3 CN4 P-2


CN16
CN20
CN25

CN23

3
4-WAY HEAT1 HEAT2
OPTIONAL CN1 CN2 CN6 CN5 CN9 CN8 Y/G
3

W(C)
REACTOR V(S) DC FAN
BROWN

BROWN

BROWN

BROWN
BLACK

BLACK

BLACK
BLACK

BLACK
BLUE
Y/G

BLUE
BLUE
BLUE
RED

U(R)
L
COMPRESSOR N L(A) N(A) S(A) L(B) N(B) S(B) L(C) N(C) S(C) L(D) N(D) S(D)
HEATER2
HEATER1
4-WAY

Use the magnetic ring. ١:NOTE


( optional part, not supplied )
MAGNETIC MAGNETIC MAGNETIC
RING
MAGNETIC
RING
MAGNETIC
RING
to hitch the connective cable
RING RING
OPTIONAL OPTIONAL of indoor and outdoor units
OPTIONAL
Y/G one magnetic. after installation
POWER TO A TO B TO C TO D . ring is used for one cable
SUPPLY REACT0R2 R05094A OPTIONAL2
Y/G Y/G Y/G Y/G or١ Choosing OPTIONAL .٢
. or decision-is either٢ OPTIONAL

 Page 81 
36k
Specifications

 Page 78 
42k

Specifications

 Page 79 
8. Indoor units combination
8.1 Indoor unit combination for 14K ODU
One unit Two unit
7 7+7 9+9
9 7+9 9+12
12 7+12
18
8.2 Indoor unit combination for 18K ODU
One unit Two unit
7 7+7 9+9
9 7+9 9+12
12 7+12 12+12
18

8.3 Indoor unit combination for 21K ODU


One unit Two unit Three unit
7 7+7 9+9 7+7+7 7+9+9
9 7+9 9+12 7+7+9 9+9+9
12 7+12 9+18 7+7+12
18 7+18 12+12

8.4 Indoor unit combination for 27K ODU


One unit Two unit Three unit
7 7+7 7+18 9+18 7+7+7 7+9+12 9+12+12
9 7+9 9+9 12+12 7+7+9 7+12+12 12+12+12
12 7+12 9+12 12+18 7+7+12 9+9+9
18 7+9+9 9+9+12

8.5 Indoor unit combination for 28 K ODU

One unit Two unit Three unit Four unit


7 7+7 9+9 12+18 7+7+7 7+9+12 9+9+18 7+7+7+7 7+7+9+12
9 7+9 9+12 12+24 7+7+9 7+9+18 9+12+12 7+7+7+9 7+9+9+9
12 7+12 9+18 18+18 7+7+12 7+12+12 12+12+12 7+7+7+12 9+9+9+9
18 7+18 9+24 7+7+18 9+9+9 7+7+9+9
24 7+24 12+12 7+9+9 9+9+12

14
8.6 Indoor unit combination for 36K ODU

One unit Two unit Three unit Four unit


7 7+7 9+18 7+7+7 7+9+12 7+18+18 9+12+18 7+7+7+7 7+7+9+12 7+9+9+12 9+9+9+12
9 7+9 9+24 7+7+9 7+9+18 9+9+9 9+12+24 7+7+7+9 7+7+9+18 7+9+9+18 9+9+9+18
12 7+12 12+12 7+7+12 7+9+24 9+9+12 9+18+18 7+7+7+12 7+7+12+12 7+9+12+12 9+9+12+12
18 7+18 12+18 7+7+18 7+12+12 9+9+18 12+12+12 7+7+7+18 7+7+12+18 7+12+12+12 9+12+12+12
24 7+24 12+24 7+7+24 7+12+18 9+9+24 12+12+18 7+7+9+9 7+9+9+9 9+9+9+9 12+12+12+12
9+9 18+18 7+9+9 7+12+24 9+12+12
9+12

If one of indoor units is ATW,


One unit Two unit Three unit Four unit
7 7+ATW 7+7+ATW 9+12+ATW 7+7+7+ATW 7+9+12+ATW 9+12+12+ATW
9 9+ATW 7+9+ATW 9+18+ATW 7+7+9+ATW 7+9+18+ATW 9+12+18+ATW
12 12+ATW 7+12+ATW 12+12+ATW 7+7+12+ATW 9+9+9+ATW 12+12+12+ATW
18 18+ATW 7+18+ATW 12+18+ATW 7+7+18+ATW 9+9+12+ATW 12+12+18+ATW
ATW 9+9+ATW 18+18+ATW 7+9+9+ATW 9+9+18+ATW
Note: ATW can only be connected with an A system.

15
8.7 Indoor unit combination for 42K ODU
One Unit Two Unit Three Unit
7 7+7 9+18 7+7+7 7+9+18 9+9+12 12+12+12
9 7+9 9+24 7+7+9 7+9+24 9+9+18 12+12+18
12 7+12 12+12 7+7+12 7+12+12 9+9+24 12+12+24
18 7+18 12+18 7+7+18 7+12+18 9+12+12 12+18+18
24 7+24 12+24 7+7+24 7+12+24 9+12+18
9+9 18+18 7+9+9 7+18+18 9+12+24
9+12 7+9+12 9+9+9 9+18+18
Four Unit
7+7+7+7 7+7+9+18 7+9+9+12 7+12+12+12 9+9+12+18
7+7+7+9 7+7+9+24 7+9+9+18 7+12+12+18 9+9+12+24
7+7+7+12 7+7+12+12 7+9+9+24 9+9+9+9 9+12+12+12
7+7+7+18 7+7+12+18 7+9+12+12 9+9+9+12 9+12+12+18
7+7+7+24 7+7+12+24 7+9+12+18 9+9+9+18 12+12+12+12
7+7+9+9 7+7+18+18 7+9+12+24 9+9+9+24 12+12+12+18
7+7+9+12 7+9+9+9 7+9+18+18 9+9+12+12
Five Unit
7+7+7+7+7 7+7+7+9+18 7+7+9+12+12 7+9+9+9+18 9+9+9+12+12
7+7+7+7+9 7+7+7+12+12 7+7+9+12+18 7+9+9+12+12 9+9+12+12+12
7+7+7+7+12 7+7+7+12+18 7+7+12+12+12 7+9+12+12+12
7+7+7+7+18 7+7+9+9+9 7+7+12+12+18 9+9+9+9+9
7+7+7+9+9 7+7+9+9+12 7+9+9+9+9 9+9+9+9+12
7+7+7+9+12 7+7+9+9+18 7+9+9+9+12 9+9+9+9+18

16
9. Operation temperature range
Temperature
Cooling operation Heating operation Drying operation
Mode

Room temperature 17℃~32℃ 0℃~27℃ 17℃~32℃

Outdoor temperature -10℃~50℃ -15℃~24℃ -10℃~50℃

CAUTION:

1. If the air conditioner is used beyond the above conditions, certain safety protection features may
come into operation and cause the unit to operate abnormally.

2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this figure,
the surface of the air conditioner may attract condensation. Please set the vertical air flow louver to its
maximum angle (vertically to the floor), and set HIGH fan mode.

3. The optimum performance will be achieved during this operating temperature zone.

42
10 Electronic function
Note: Below function only for light commercial, for Hi-wall units, please refer to 1 drive 1 service manuals.
10.1 Abbreviation
For AG/ Cool easy :
T1: Indoor room temperature

T2: Coil temperature of evaporator

T3: Coil temperature of condenser

T4: Outdoor ambient temperature

Tp: Compressor discharge temperature

Tsc: Ajusted setting temperature

For other models:

T1: Indoor room temperature

T2: Indoor evaporator temperature

T2B : Coil temperature of indoor heat exchanger outlet (This sensor is located in outdoor unit)

T3: Coil temperature of outdoor heat exchanger

T4: Outdoor ambient temperature

T5: Compressor discharge temperature

Ts: Setting temperature

10.2 Icon explanation on indoor display board


10.2.1 Four-way cassette (compact)

10.2.2 Four-way cassette (super slim)

43
10.2.3 A6 Ducted
PRE-DEF indicator(cooling and heating type)
or fan only indicator(cooling only type)
Timer indicator Alarm indicator
Operation lamp Infrared signal receiver
Temporary button Display digital tube

MANUAL OPERATION TIMER DEF./FAN ALARM

10.2.4 Console

10.2.5 Under Ceiling

10.2.6 15C&AB&AG& Cool easy

44
10.3 Mode co nfl ict
The indoor units can not work cooling mode and heating at same time.
Heating m ode has a priority.

1. Definition

Cooling m ode Heating M ode Fan O ff


Cooling mode No Yes No No
Heating Mode Yes No Yes No
Fan No Yes No No
Off No No No No
No: No mode conflict;
Yes: Mode conflic t

2. Unit action

 In case of one Indoor unit working in cooling mode or fan mode, and another indoor unit is set to heating
mode, the indoor unit working in cooling mode or fan mode will change to off. The outdoor unit will
change to heating mode after compressor stop 3 minutes. .
 In case of one Indoor unit working in heating mode, and another indoor unit is set to cooling mode or fan
mode, the indoor unit setting to cooling mode or fan mode will change to stand by. The outdoor unit will
continue working in heating mode.

If heating mode stops (not including the indoor unit in heating mode reaching the set temperature), 3
minutes after the outdoor uni t resta rts and works in cooling mode or fan-only mode.

58
11 General information of Outdoor Units
Model name Dimension (mm) Compressor
14K 805x330x554 KSN140D21UFZ
18K 805x330x554 KSN140D21UFZ
21K 890x342x673 KSN140D21UFZ
27K 890x342x673 KTM240D57UMT
28K 946x410x810 KTM240D57UMT
36K 946x410x810 KTF310D43UMT
42K 946x410x810 KTF310D43UMT

59
12 Features

Outdoor unit

Power relay control

Low noise air flow system

Hydrophilic aluminum fin

The hydrophilic fin can improve the heating efficiency at operation mode.

4 way valve control

It is only operated in the heating operation mode except defrosting operation.

Anti-rust cabinet

Valve protection cover

It protects the valves and prevents water from dripping.

Discharge pipe temperature protection

60
13 Dimensions
14K/18K
Specifications
21K/27K

Specifications
28K/36K/42K
Specifications
14. Refrigerant Cycle Diagrams

Specifications
Pipe Size Piping length (m)
Elevation (m)
(Diameter:ø) Max Additional
Model
Rated IDU and Between Refrigerant
Gas Liquid Single Total
ODU IDUs
14K
2x9.52 2x6.35 15 25 40 15 10 12g/m
18K
Specifications

Pipe Size Piping length (m)


Elevation (m)
(Diameter:ø) Max Additional
Model
Rated IDU and Between Refrigerant
Gas Liquid Single Total
ODU IDUs

21K

3x9.52 3x6.35 22.5 30 60 15 10 12g/m

27K
Specifications
Piping length (m)
Pipe Size (Diameter:ø) Elevation (m)
Max Additional
Model
Rated IDU and Between Refrigerant
Gas Liquid Single Total
ODU IDUs

28K 3x9.52+1x12.7 4x6.35 30 35 80 15 10 12g/m

36K 3x9.52+1x12.7 4x6.35 30 35 80 15 10 12g/m


Specifications

Piping length (m)


Pipe Size (Diameter:ø) Elevation (m)
Max Additional
Model
Rated IDU and Between Refrigerant
Gas Liquid Single Total
ODU IDUs

42K 4x9.52+1x12.7 5x6.35 37.5 35 80 15 10 12g/m


15 Sound Levels
Outdoor Unit

Microphone

1.0m
Note: H= 0.5 × height of outdoor unit

Model Noise Power dB(A) Noise level dB(A)


14K 64 56

18K 63 54
21K 66 58

27K 67 60

28K 70 63
36K 72 64

42K 72 63

64
16Installation Details
16.1 Wrench torque sheet for installation
Outside diameter Torque Additional tightening torque
mm N.cm N.cm
Ф6.35 1500(153kgf.cm) 1600(163kgf.cm)
Ф9.52 2500(255kgf.cm) 2600(265kgf.cm)
Ф12.7 3500(357kgf.cm) 3600(367kgf.cm)

16.2 Connecting the cables


The power cord of connect should be selected according to the following specifications sheet.

Rated current of appliance Nominal cross-sectional area (mm²)


>3 and ≤6 0.75
>6 and ≤10 1
>10 and ≤16 1.5
>16 and ≤25 2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the
nameplate which located on the side panel of the unit. Please refer to the nameplate before selecting the
cable, fuse and switch.

16.3 Pipe length and the elevation


Maximum piping length and height difference

1 drive 2 1 drive 3 1 drive 4 1 drive 5

Model(Btu/h) 14K 18K 21K 27K 28K 36K 42K

Max. length for all rooms (m) 40 40 60 60 80 80 80

Max. length for one IU (m) 25 25 25 30 30 35 35

Max. height difference between IU and OU (m) 15 15 15 15 15 15 15

Max. height difference between IUs (m) 10 10 10 10 10 10 10

Additional refrigerant charge

1 drive 2 1 drive 3 1 drive 4 1 drive 5

Chargeless pipe
15 22.5 30 37.5
length (m)

Additional
12 x (length for all 12 x (length for all 12 x (length for all 12 x (length for all
refrigerant charge
rooms - 15) rooms – 22.5) rooms - 30) rooms – 37.5)
(g)

65
Caution:

● Refrigerant pipe diameter is different according to indoor unit to be connected. When using the
extension pipe, refer to the tables below.

● When refrigerant pipe diameter is different from that of outdoor unit union (for 18K&24K indoor unit),
additional transfer connector needs to be used on outdoor unit union.

Indoor unit Extension pipe diameter (mm/inch)

Model Pipe diameter (mm/inch)

Liquid 6.35(1/4) Liquid 6.35(1/4)


7K9K12K
Gas 9.52(3/8) Gas 9.52(3/8)

Liquid 6.35(1/4) Liquid 6.35(1/4)


18K
Gas 12.7(1/2) Gas 12.7(1/2)

24K Liquid 9.52(3/8) Liquid 9.52(3/8)

Gas 15.9(5/8) Gas 15.9(5/8)

Outdoor unit union diameter (mm/inch)

Liquid 6.35(1/4) *2
1 drive 2 Gas 9.52(3/8) *2

Liquid 6.35(1/4) *3
1 drive 3 Gas 9.52(3/8) *3

Liquid 6.35(1/4) *4
9.52(3/8) *3
1 drive 4 Gas
12.7(1/2) *1

Liquid 6.35(1/4) *5
1 drive 5 9.52(3/8) *4
Gas
12.7(1/2) *1

16.4 Installation for the first time


Air and moisture in the refrigerant system have undesirable effects as below:
● Pressure in the system rises.
● Operating current rises.
● Cooling or heating efficiency drops.
● Moisture in the refrigerant circuit may freeze and block capillary tubing.
● Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and
evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):

66
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out,
the pipes have leakage.
1. Air purging with vacuum pump

(Indoor unit) (Liquid side) (Outdoor unit)

Two-way valve

Close

(Gas side)

Three-way valve

Manifold valve Close


Compound meter
Pressure
gauge
-0.1MPa
Lo Hi

Handle Lo Handle Hi
Charge hose Charge hose

Vacuum
pump

Vacuum
pump

1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and 3-way
valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If the
pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm
that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas
coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a
little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.

67
2. Adding the refrigerant if the pipe length >5m

Electronic scale

Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve.

Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the
cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure the liquid charge.

2). Purge the air from the charge hose.

Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).

3) Put the charging cylinder onto the electronic scale and record the weight.

4) Operate the air conditioner at the cooling mode.

5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose from
the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port

Use torque wrench to tighten the service port cap to a torque of 18N.m.

Be sure to check for gas leakage.

68
16.5 Adding the refrigerant after running the system for many years

Electronic scale

Procedure:

1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve.

Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the
cylinder bottom up to ensure liquid charge.

2). Purge the air from the charge hose.

Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).

3) Put the charging cylinder onto the electronic scale and record the weight.

4) Operate the air conditioner at the cooling mode.

5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low side),
disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air conditioner
before disconnecting the hose.
7). Mount the valve stem caps and the service port

Use torque wrench to tighten the service port cap to a torque of 18N.m.

Be sure to check for gas leakage.

69
16.6 Re-installation while the indoor unit need to be repaired
1. Collecting the refrigerant into the outdoor unit

Procedure

1). Confirm that both the 2-way and 3-way valves are set to the opened position
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose.
Open the handle Lo valve of the manifold valve slightly to purge air from the charge hose for 5 seconds and
then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
6). Set the 3-way valve to the closed position immediately
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
Disconnect the charge set, and tighten the 2-way and 3-way valve’s stem nuts.
Use a torque wrench to tighten the 3-way valves service port cap to a torque of 1.8 kgf.m.
Be sure to check for gas leakage.

70
16.7 Re-installation while the outdoor unit need to be repaired
1. Evacuation for the whole system

Procedure:

1). Confirm that both the 2-way and 3-way valves are set to the opened position.

2). Connect the vacuum pump to 3-way valve’s service port.


3). Evacuation for approximately one hour. Confirm that the compound meter indicates -0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.

71
2. Refrigerant charging

Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the
cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.

2). Purge the air from the charge hose

Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).

3) Put the charging cylinder onto the electronic scale and record the weight.

4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant
If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at a
time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one time is
not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way valve’s
service port immediately

If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.

6). Mounted the valve stem caps and the service port

Use torque wrench to tighten the service port cap to a torque of 18N.m.

Be sure to check for gas leakage

72
17 Electronic control function
17.1 Abbreviation
For AG:
T1: Indoor room temperature

T2: Coil temperature of evaporator

T3: Coil temperature of condenser

T4: Outdoor ambient temperature

Tp: Compressor discharge temperature

Tsc: Ajusted setting temperature

For other models:

T1: Indoor ambient temperature

T2: Coil temperature of indoor heat exchanger middle.

T2B: Coil temperature of indoor heat exchanger outlet(This sensor is located in outdoor unit)

T3: Coil temperature of outdoor heat exchanger

T4: Outdoor ambient temperature

T5: Compressor discharge temperature

Ts: Setting temperature

17.2 Electric control working environment.


1. Input voltage: 198V~264V.

2. Input power frequency:50Hz.

3. Indoor fan normal working amp. is less than 1A.

4. Outdoor fan. normal working amp. is less than 1.5A.

5. Four-way valve normal working amp. is less than 1A.

17.3 Outdoor unit’s digital display tube


There is a digital display tube in outdoor PCB.

Digital display tube display function

 In standby , the LED displays “- -”


 In compressor operation, the LED display the running frequency,
 In defrosting mode, The LED displays “dF” or alternative displays between running frequency and

“dF”(each displays 0.5s)


 In compressor pre-heating, The LED displays “PH” or alternative displays between running frequency

and “PH”(each displays 0.5s)


 During the oil return process, The LED displays “RO” or alternative displays between running

frequency and “RO”(each displays 0.5s)


 In low ambient cooling mode, the LED displays “LC” or alternative displays between running

73
frequency and “LC”(each displays 0.5s)
 In forced cooling mode, the LED displays “FC” or alternative displays between running frequency and

“FC”(each displays 0.5s)


 When PFC module protection occurs three times within 15 minutes, the LED displays “E6” or

alternative displays between running frequency and “E6”(each displays 0.5s)


 In protection or malfunction, the LED displays error code or protection code.
17.4 Outdoor unit point check function
A check switch is included on the outdoor PCB.

Push SW1 to check the unit's status while running. The digital display shows the following codes each time
the SW1 is pushed.

Display Remark
Number
of
Presses
0 Normal display Displays running frequency, running state, or malfunction code
1 Quantity of indoor units with working connection Actual data
Display Number of indoor unit
1 1

2 2

3 3

4 4

2 Outdoor unit running mode code Off: 0,Fan only: 1, Cooling: 2, Heating: 3, Forced cooling: 4. Forced
defrosting :A
3 Indoor unit A capacity
4 Indoor unit B capacity
The capacity unit is horse power. If the indoor unit is not connected, the
5 Indoor unit C capacity digital display shows the following: “――”
(9K:1HP,12K:1.2HP,18K:1.5HP)
6 Indoor unit D capacity
7 Indoor unit E capacity
8 Indoor unit A capacity demand code
9 Indoor unit B capacity demand code
10 Indoor unit C capacity demand code Norm code*HP
(9K: 1HP,12K: 1.2HP,18K: 1.5HP)
11 Indoor unit D capacity demand code
12 Indoor unit E capacity demand code
13 Outdoor unit amendatory capacity demand code
14 The frequency corresponding to the total indoor
units' amendatory capacity demand
15 The frequency after the frequency limit
16 The frequency sending to compressor control
chip
17 Indoor unit A evaporator outlet temperature (T2BA)
18 Indoor unit B evaporator outlet temperature (T2BB)
19 Indoor unit C evaporator outlet temperature If the temperature is lower than -9 ℃, the digital display shows “-9.” If the
(T2BC) temperature is higher than 70 ℃, the digital display shows “70.” If the
20 Indoor unit D evaporator outlet temperature indoor unit is not connected, the digital display shows: “――”
(T2BD)
21 Indoor unit E evaporator outlet temperature (T2BE)
22 Indoor unit A room temperature (T1A) If the temperature is lower than 0 ℃, the digital display shows “0.” If the

74
23 Indoor unit B room temperature (T1B) temperature is higher than 50 ℃, the digital display shows “50.” If the
indoor unit is not connected, the digital display shows: “――”
24 Indoor unit C room temperature (T1C)
25 Indoor unit D room temperature (T1D)
26 Indoor unit E room temperature (T1E)
27 Indoor unit A evaporator temperature (T2A)
28 Indoor unit B evaporator temperature (T2B)
29 Indoor unit C evaporator temperature (T2C)
If the temperature is lower than -9 ℃, the digital display shows “-9.” If the
30 Indoor unit D evaporator temperature (T2D) temperature is higher than 70 ℃, the digital display shows “70.” If the
indoor unit is not connected, the digital display shows: “――”
31 Indoor unit E evaporator temperature (T2E)
32 Condenser pipe temperature (T3)
33 Outdoor ambient temperature (T4)
34 Compressor discharge temperature (TP) The display value is between 30–129 ℃. If the temperature is lower than
30 ℃, the digital display shows “30.” If the temperature is higher than
99 ℃, the digital display shows single and double digits. For example, if
the digital display shows “0.5", the compressor discharge temperature is
105 ℃.
35 AD value of current The display value is a hex number.
For example, the digital display tube shows “Cd”, it means AD value is
36 AD value of voltage 205.
37 EXV open angle for A indoor unit
38 EXV open angle for B indoor unit Actual data/4.
If the value is higher than 99, the digital display shows single and double
39 EXV open angle for C indoor unit digits.
For example, if the digital display shows “2.0", the EXV open angle is
40 EXV open angle for D indoor unit 120×4=480p.
41 EXV open angle for E indoor unit
Frequency limit caused by IGBT The display
Bit7
radiator value is a
Bit6 hexidecimal
Frequency limit caused by PFC number. For
Bit5 Frequency limit caused by T4. example, the
digital display
Bit4 Frequency limit caused by T2. show 2A, then
42 Frequency limit symbol
Bit5=1, Bit3=1,
Bit3 Frequency limit caused by T3. and Bit1=1.
Bit2 Frequency limit caused by T5. This means that
a frequency limit
Bit1 Frequency limit caused by current may be caused
by T4, T3, or the
Bit0 Frequency limit caused by voltage current.
43 Average value of T2 (Sum T2 value of all indoor units)/(number of indoor units in good
connection)
44 Outdoor unit fan motor state Off: 0, High speed:1, Med speed: 2, Low speed: 3, Breeze:4, Super
breeze: 5
45 The last error or protection code 00 means no malfunction and protection
46 F indoor unit capacity
47 F indoor unit capacity demand code
48 F indoor unit evaporator outlet temperature (T2BF) If the temperature is lower than -9 ℃, the digital display shows “-9.” If the
temperature is higher than 70 ℃, the digital display shows “70.” If the
49 F indoor unit room temperature (T1F)
indoor unit is not connected, the digital display shows: “――”
50 F indoor unit evaporator temperature (T2F)
51 EXV open angle for F indoor unit

75
17.5 Protection
17.5.1 Three minutes delay at restart for compressor.
17.5.2 Temperature protection of compressor discharge.
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:

T5

C o m p re s s o r o ff

F re q u e n c y lim it

F re q u e n c y h o ld in g

N o rm a l

17.5.3 Low voltage protection


VO LTAGE

N o lim it

V O L T _ LT M _ F R E Q 1_ A D D

V O L T _ LT M _ F R E Q 2_ A D D

Note: if the low voltage protection occurs and not resumes within 3min, it will keep the protection always
after restart the machine.
17.5.4 Compressor current limit protection
Temperature interval.of current limit is same as range of T4 limited frequency.
Cooling mode:
T4

CoolZone5

CoolZone4

CoolZone3

CoolZone2
CoolZone1

Heating mode:

76
T4

HeatZone4

HeatZone3

HeatZone2

HeatZone1
17.5.5 Indoor / outdoor units communication protection
If the indoor units cannot receive the feedback signal from the outdoor units for 2 minutes, the AC will stop
and display the failure.

17.5.6 High condenser coil temp. protection.


T3

Off

Decrease

Hold

Resume

17.5.7 Outdoor unit anti-freezing protection


When T2<4℃ for 250 seconds or T2<0℃, the indoor unit capacity demand will be zero and resume to
normal when T2>8℃ and the time of protection is no less than 3 minutes.

17.5.8 Oil return


Running rules:
1. If the compressor frequency keeps lower than setting frequency for setting time, the AC will rise the
frequency to setting frequency for setting time and then resume to former frequency.
2. The EXV will keep 300p while the indoor units will keep the current running mode.
If the outdoor ambient is higher than setting frequency during the oil return, the AC quit oil return.

17.5.9 Low outdoor ambient temperature protection


When compressor is off, T4 is be lower than -35℃.for 10s, the AC will stop and display “LP”.
When compressor is on, T4 is be lower than -40℃.for 10s, the AC will stop and display “LP”.
When T4 is no lower than -32℃.for 10s, the unit will exit protection.

77
18. Troubleshooting
18.1 Indoor unit error code explanation:
For Four-way cassette type (compact), A6 Duct(7K/9K)
:
Operation Lamp
Malfunction Error Code Timer Lamp (flashes)

Indoor EEPROM malfunction E0 X 1


Communication malfunction between indoor and outdoor units E1 X 2
Indoor fan speed has been out of control E3 X 4
Open or short circuit of T1 temperature sensor E4 X 5
Open or short circuit of T2 temperature sensor E5 X 6
Refrigerant leakage detection EC X 7
Water level alarm EE X 8
Overcurrent protection (For some units) F0 O 1
Open or short circuit of T4 temperature sensor F1 O 2
Open or short circuit of T3 temperature sensor F2 O 3
Open or short circuit of T5 temperature sensor F3 O 4
Outdoor EEPROM malfunction (For some units) F4 O 5
Outdoor fan speed is out of control F5 O 6
Open or short circuit of T2B temperature sensor F6 O 7
Communication malfunction between indoor two chips(For A6 Duct) FA O 11
IPM module malfunction P0 ☆ 1

Over voltage or over low voltage protection P1 ☆ 2

Too low ambient temperature protection P3 ☆ 4

Inverter compressor drive protection P4 ☆ 5

Indoor units mode conflict -- ☆ 6

Low pressure protection of compressor P6 ☆ 7


O (on) X(off) ☆(flash at 2Hz)

78
For Mission2 type and Ultimate Comfort type:

Malfunction Error Code

Indoor unit EEPROM parameter error E0/EA


Indoor / outdoor units communication error E1
Indoor fan speed is operating outside of the normal range E3
Indoor room temperature sensor T1 open circuit or short circuit E4
Evaporator coil temperature sensor T2 open circuit or short circuit E5
Communication error between the indoor PCB and display board Eb/EH 0b

Refrigerant leakage detection EC


Overload current protection F0
Outdoor ambient temperature sensor T4 open circuit or short circuit F1
Condenser coil temperature sensor T3 open circuit or short circuit F2
Compressor discharge temperature sensor T5 open circuit or short circuit F3
Outdoor unit EEPROM parameter error F4
Outdoor fan speed is operating outside of the normal range F5
IPM malfunction or IGBT over-strong current protection P0
Over or low voltage protection P1
High temperature protection of IPM module P2
Inverter compressor drive error P4
Indoor units mode conflict --

For AG andCool easy type:


Running
Timer Lamp Display Error Information
Lamp
EH 00/EH
1 time OFF Indoor unit EEPROM parameter error
0A
2 times OFF EL 01 Indoor/outdoor unit communication error
3 times OFF EH 02 Zero-crossing signal detection error
The indoor fan speed is operating outside of the
4 times OFF EH 03
normal range
5 times OFF EC 51 Outdoor unit EEPROM parameter error
Condenser coil temperature sensor T3 is in open
5 times OFF EC 52
circuit or has short circuited
Outdoor room temperature sensor T4 is in open
5 times OFF EC 53
circuit or has short circuited
Compressor discharge temperature sensor TP is in
5 times OFF EC 54
open circuit or has short circuited
Evaporator coil outlet temperature sensor T2B is in
5 times OFF EC 56 open circuit or has short circuited(for free-match
indoor units)
Indoor room temperature sensor T1 is in open circuit
6 times OFF EH 60
or has short circuited

79
Evaporator coil middle temperature sensor T2 is in
6 times OFF EH 61
open circuit or has short circuited
The outdoor fan speed is operating outside of the
12 times OFF EC 07
normal range
9 times OFF EH 0b Indoor PCB/Display board communication error
8 times OFF EL 0C Refrigerant leakage detection

IPM malfunction or IGBT over-strong current


7 times FLASH PC 00
protection
2 times FLASH PC 01 Over voltage or over low voltage protection
Top temperature protection of compressor or High
3 times FLASH PC 02 temperature protection of IPM module or High
pressure protection

5 times FLASH PC 04 Inverter compressor drive error

1 time FLASH PC 08 Current overload protection


7 times FLASH PC 03 Low pressure protection
1 times ON -- Indoor units mode conflict

Notes:all IDU error code could refer to Hiwall and LC IDU.

80
18.2 Outdoor unit error code explanation:
For other models,

Display LED STATUS

E0 Outdoor EEPROM malfunction

E2 Indoor / outdoor units communication error

E3 Communication malfunction between IPM board and outdoor main board

E4 Open or short circuit of outdoor unit temperature sensor(T3,T4.T5)

E5 Voltage protection

E6 PFC module protection

E8 Outdoor fan speed has been out of control or compressor speed has been out of control

F1 No A Indoor unit coil outlet temperature sensor or connector of sensor is defective

F2 No B Indoor unit coil outlet temperature sensor or connector of sensor is defective

F3 No C Indoor unit coil outlet temperature sensor or connector of sensor is defective

F4 No D Indoor unit coil outlet temperature sensor or connector of sensor is defective

F5 No E Indoor unit coil outlet temperature sensor or connector of sensor is defective

P0 Top temperature protection of compressor

P1 High pressure protection (For M4OB-36HFN8-Q, M5OD-42HFN8-Q)

P2 Low pressure protection (For M4OB-36HFN8-Q, M5OD-42HFN8-Q)

P3 Current protection of compressor

P4 Temperature protection of compressor discharge

P5 High temperature protection of condenser

P6 IPM module protection

E9 24k indoor unit wiring error

LP Low ambient temperature protection

Note: Once these error codes display, they will disappear in at least 30 seconds if the unit come back to
normal.(Except E2&E3)

81
For 21/27/42K Model

Display LED STATUS

EC 51 Outdoor EEPROM malfunction

EL 01 Indoor / outdoor units communication error

PC 40 Communication malfunction between IPM board and outdoor main board

PC 08 Outdoor overcurrent protection

PC 10 Outdoor unit low AC voltage protection

PC 11 Outdoor unit main control board DC bus high voltage protection

PC 12 Outdoor unit main control board DC bus high voltage protection /341 MCE error

PC 00 IPM module protection

PC 0F PFC module protection

EC 71 Over current failure of outdoor DC fan motor

EC 72 Lack phase failure of outdoor DC fan motor

EC 07 Outdoor fan speed has been out of control

PC 43 Outdoor compressor lack phase protection

PC 44 Outdoor unit zero speed protection

PC 45 Outdoor unit IR chip drive failure

PC 46 Compressor speed has been out of control

PC 49 Compressor overcurrent failure

PC 30 High pressure protection (For M5OE-42HFN8-Q)

PC 31 Low pressure protection (For M5OE-42HFN8-Q)

PC 0A High temperature protection of condenser

PC 06 Temperature protection of compressor discharge

PC 0L Low ambient temperature protection

PC 02 Top temperature protection of compressor

EC 52 Condenser coil temperature sensor T3 is in open circuit or has short circuited

EC 53 Outdoor room temperature sensor T4 is in open circuit or has short circuited

EC 54 Compressor discharge temperature sensor T5 is in open circuit or has short circuited

EC 56 Evaporator coil outlet temperature sensor T2B is in open circuit or has short circuited

82
EC 50 Open or short circuit of outdoor unit temperature sensor(T3,T4.T5)

83
18.3 Trouble shooting
18.3.1 For the indoor unit
18.3.1.1 Indoor EEPROM malfunction (IDU E0/EA/EH 00/EH 0A)

Power off, then restart the


unit 2 minutes later

Yes

Replace the indoor main PCB

EEPROM: An electrically erasable programmable read-only memory whose contents can be erased and
reprogrammed using a pulsed voltage.

84
18.3.1.2 Indoor / outdoor units communication error(E1(IDU)/ E2(ODU)/ EL 01(IDU/ODU))
Indoor / outdoor units communication error

Start: Power off , then Power on the


A/C by the Breaker. (reconnect the
power wire). Is it still displaying the
error code?

Yes

Check wiring on the outdoor and indoor


terminal follow the wiring diagram. Is all No Reconnect the wiring
connecting correctly?
No
No
Reconnect the wiring

Yes

Measure Vs, is it moving


Turn on all indoor unit by remote alternately between positive value A: Is all the wiring between
controller. Is all indoor unit display No and negative value? (Vs is the No terminal and Indoor PCB
error code? voltage between S and N). Refer connect ok?
PIC 1

Yes Yes
Yes
Yes
Replace the Indoor PCB

Turn off the all indoor units. Is IPM Replace IPM board or
power LED or operating LED lamp No the outdoor main PCB
On? Refer PIC2

Power on by remote
controller, IIs it still
Yes displaying the error code
after 3 minutes?

Is main board Is the reactor connecting


No No Reconnect the wiring
lamp on? Refer PIC 3. well?

No

Yes Yes

Replace the outdoor main PCB

Is indoor units number correct? Check


on the outdoor check point . (2 for dual
Trouble is solved
zone, 3 for tri zone, 4 for qua zone,5 for
qui zone). Refer PIC 4.

No first time No second time A

Replacee outdoor unit PCB assembly(include


wiring) totally

85
Pic 1: check the voltage of N to S
(Vs), is it moving alternately
between positive value and negative
value?

Pic 2:IPM or outdoor main PCB

Operating

Self-Check

Pic 2: IPM or outdoor main PCB

Power,

Self-Check

Operating

86
PIC3 :Main board LED when power on and unit
standby.

. PIC 4: check point button,


Press 1 time for check how many indoor units are
connected

87
18.3.1.3 Indoor fan speed has been out of control (IDU E3/ EH 03)

Power
Power off,
off, then
then restart
restart the the
unit minutes later.
unit 22 minutes later. IsIs itit still
still No The
The unit
unit operates
operates normally.
normally.
displaying
displaying the
the error
error code?
code?

Yes
Find
Find out
out the
the cause
cause and
and
Shut
Shut offoff the
the power
power supply,
supply, have
have it solved. For
it solved. For
rotate
rotate the fan by
the fan by hand.
hand. Does
Does No example,
example, whether
whether the
the fan
fan
itit rotate isis blocked
blocked oror the
the screws
screws
rotate properly?
properly?
which
which fix
fix the
the fan
fan are
are
tighten.
tighten.
Yes

Check
Check the
the wiring
wiring ofof fan
fan
motor. Are all the
motor. Are all the No Correct
Correct the
the connections.
connections.
connections
connections good?
good?

Yes

Check
Check whether
whether the
the main
main PCB
PCB No Replace
Replace the
the main
main PCB
PCB
isis normal
normal through
through index
index 1?
1?

Yes

Replace
Replace the
the fan
fan motor
motor No

Index 1:
1: Indoor AC fan motor
Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds, measure
the voltage of pin1 and pin2. If the value of the voltage is less than 100V(208~240V power supply)or
50V(115V power supply), the PCB must have problems and need to be replaced.

2. Indoor DC fan motor(control chip is inside fan motor)


Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must have
problems and need to be replaced.

88
DC motor voltage input and output
For split type:
NO. Color Signal Voltage
1 Red Vs/Vm 280V~380V
2 --- --- ---
3 Black GND 0V
4 White Vcc 14-17.5V
5 Yellow Vsp 0~5.6V
6 Blue FG 14-17.5V

For other types:


NO. Color Signal Voltage
1 Red Vs/Vm 192V~380V
2 --- --- ---
3 Black GND 0V
4 White Vcc 13.5-16.5V
5 Yellow Vsp 0~6.5V
6 Blue FG 13.5-16.5V

89
18.3.1.4 Open or short circuit of temperature sensor(IDU E4/E5/EH 60/EH 61)

Check
Check the
the connections
connections
between
between temperature
temperature No Correct
Correct the
the connections.
connections.
sensor
sensor and
and PCB.
PCB. Are
Are the
the
connections
connections good?
good?

Yes

Measure
Measure the
the resistance
resistance value
value
of
of the
the sensor
sensor via
via Appendix
Appendix 11

IsIs itit normal?


normal? No Replace
Replace the
the sensor.
sensor.

Yes

Replace
Replace the
the indoor
indoor PCB
PCB

10.3.1.5 Water-level alarm malfunction(IDU EE)


Power
Power off,
off, then
then restart
restart the
the unit
unit 22 minutes
minutes
later.
later. Is it still displaying the error
Is it still displaying the error code?
code?

Yes

IfIf the
the water-level
water-level switch
switch No Insert
Insert the
the water-level
water-level switch
switch well
well
is
is inserted
inserted well?
well?

Yes

IfIf the
the water-level
water-level switch
switch Yes Replace
Replace the
the water-level
water-level switch
switch
is
is broken?
broken?

No

Replace
Replace the
the water
water pump,
pump, IfIf
malfunction
malfunction is still not
is still not
solved
solved

Yes

Replace
Replace the
the indoor
indoor main
main PCB
PCB

90
18.3.1.7 Communication error between the indoor PCB and display board(IDU Eb/EH 0b)

Power off, then restart the unit


2 minutes later

Yes

Check the wirings Correct the connection


No
and connection or replace the wirings

Yes

Replace the indoor main PCB

Yes

Replace the Display board

10.3.1.8 Inverter compressor drive malfunction(IDU P4/ PC04)

The trouble shooting is same with IPM module protection.


10.3.1.9 Communication malfunction between indoor two chips (IDU FA)

Shut off the power supply and


turn it on 2 minutes later.

Is it still displaying
NO The unit is operating normally.
the error code?

YES

Replace the indoor main


PCB.

10.3.1.10 Refrigerant Leakage Detection(IDU EC/ EL 0C)

91
Power off, then restart the unit 2 minutes later.

Does a problem remain?

YES

Put your hands in front of the


indoor air outlet.

Is there cool
air blowing out from YES Check the T2 sensor.
indoor air outlet?

NO Is it securely Replace the


YES
attached? indoor PCB
Check system for leakages.

NO

Are any leakages Repair the leakage and


YES
present? recharge the refrigerant.

NO

Check System for blockages and


clear blockages if present.

92
18.3.3 For the outdoor unit
18.3.3.1 Outdoor EEPROM malfunction(ODU E0/EC 51)

Power
Power off,
off, then
then restart
restart the
the
unit
unit 22 minutes
minutes later
later

Yes

Replace
Replace the
the outdoor
outdoor main
main PCB
PCB

EEPROM: An electrically erasable programmable read-only memory whose contents can be erased and
reprogrammed using a pulsed voltage.

10.3.3.2 Condenser coil temperature sensor T3 is in open circuit or has short circuited(EC 52)

Outdoor room temperature sensor T4 is in open circuit or has short circuited(EC 53)
Compressor discharge temperature sensor T5 is in open circuit or has short circuited(EC 54)

Evaporator coil outlet temperature sensor T2B is in open circuit or has short circuited(EC 56)

Open or short circuit of outdoor unit temperature sensor(T3,T4.T5)(E4/ EC 50)

Check the connection


between temperature
No Ensure proper connection
sensor and PCB. Is it
properly wired?

Yes

Measure the resistance


value of the sensor. Is it
within acceptable No Replace the sensor
parameters?

Yes

Replace outdoor main PCB

93
18.3.3.3 Communication malfunction between IPM board and outdoor main board(ODU E3/PC 40)

E3 display

Communication malfunction between


IPM board and outdoor main board

Is there at least one LED in


the IPM board light?

No

Check the signal wire between


the IPM board and the main Yes
board, is it connected good?

No

Yes
Reconnect and retry. Is
error still display?

No

No
Replace IPM board, and
then check whether the Yes
system can run normally

No

Replace outdoor main


board, and then check
Yes
whether the system can run
normally

No

Replace the electric control


Trouble is solved
box

94
18.3.3.4 Voltage protection(ODU E5)

Outdoor unit low AC voltage protection(PC10)

Outdoor unit main control board DC bus high voltage protection(PC11)

Outdoor unit main control board DC bus high voltage protection /341 MCE error(PC12)

Voltage protection

Check the voltage of


outdoor unit power supply,
whether the voltage No Check the power supply
between L(L1) and N (L2) is
about 220~240VAC

Yes

Check whether the voltage


of IPM board P and N is
normal? DC277-356V for
18-27KBtu/h; DC277-410V
for 36-42KBtu/h

No

Replace bridge rectifiers,


and then check whether the
system can run normally Yes
Yes

No

Replace IPM board, and


then check whether the Yes
system can run normally

No

Replace outdoor main board Trouble is solved

95
18.3.3.5 PFC module protection (ODU E6/PC 0F)

PFC module protection

Check whether the


connecting line between
Connect it tightly, check
main board and the PFC No
normal or not
module(IPM module) is
connected tightly

Yes
No

Check whether the voltage


range of P-N on IPM module
is normal? DC277-356V for Yes Replace the outdoor main board Yes
18-27KBtu/h; DC277-410V
for 36-42KBtu/h

No

Check whether the


inductance of PFC module
is good? If the inductance is No Replace the inductance
good, the resistance of the
two ports is 0

Yes

Replace the PFC module(IPM


Trouble is solved
module)

96
18.3.3.6 Outdoor fan speed has been out of control or compressor speed has been out of control
(ODU E8/EC 07)
Over current failure of outdoor DC fan motor (ODU EC71)
Power off, then restart the unit after 2
minutes.

Does a problem remain? NO The unit is operating normally

YES

Shut off the power supply,


Rotate the fan by hand.

Does it turn easily? NO Find the cause of the problem and resolve it

YES

Check the wiring of fan motor.

Is it improperly wired? Ensure proper connections

YES

Measure the voltage for


the fan motor from the PCB.

Replace the outdoor main


Is it within normal parameters? NO
PCB

YES
Replace the DC fan IPM board (if
has)

Replace the fan motor

YES
Does a problem remain?

YES

Check the compressor


resistance values.

Are they within


acceptable parameters?

YES

Replace the compressor.

97
Index 1:
1. Outdoor DC fan motor(control chip is inside fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must have
problems and need to be replaced.

DC motor voltage input and output


NO. Color Signal Voltage
1 Red Vs/Vm 140V~380V
2 --- --- ---
3 Black GND 0V
4 White Vcc 13.5-16.5V
5 Yellow Vsp 0~6.5V
6 Blue FG 15V

2. Indoor or outdoor DC Fan Motor (control chip is in PCB)


Release the UVW connector. Measure the resistance of U-V, U-W, and V-W. If the resistances are not equal
to each other, the fan motor may be experiencing problems and need to be replaced. Otherwise, the PCB
must has problems and need to be replaced.

98
18.3.3.7 High pressure protection (ODU P1/PC 30)(For M4OB-36HFN8-Q, M5OD-42HFN8-Q)

High
High pressure
pressure protection
protection

Whether
Whether the the wiring
wiring
between
between thethe high
high pressure
pressure
switch
switch and
and main
main control
control No Connect
Connect itit well
well
board
board is
is connected
connected well
well or
or
correctly
correctly

Yes

Whether
Whether the
the high
high
pressure
pressure protector
protector
is
is broken
broken

Method:
Method: Disconnect
Disconnect the
the plug.
plug.
Measure
Measure the
the resistance of the
resistance of the
high
high pressure
pressure protector,
protector, ifif No Replace
Replace high
high pressure
pressure protector
protector
the
the protector
protector is
is normal
normal thethe
value
value is
is o,
o,

Yes

Check
Check whether
whether the
the outdoor
outdoor
ambient
ambient temperature
temperature isis Yes Stop
Stop the
the unit
unit
higher
higher than
than 50℃
50℃

No

Check
Check ifif the
the outdoor
outdoor unit
unit
ventilation
NO Make
Make the
the outdoor
outdoor unit
unit ventilate
ventilate well
well
ventilation isis good
good

Yes
please
please refer
refer to
to the
the solution
solution of
of fan
fan
Check
Check ifif the
the outdoor
outdoor fan
fan runs
runs speed
speed has
has been
been outout of
of control
control
No malfunction
malfunction .. Find
Find out
out the
the cause
cause and
and
properly
properly
have
have itit solved.
solved.

Yes

Check
Check whether
whether the
the heat
heat
exchanger
Yes Clean
Clean the
the heat
heat exchanger
exchanger
exchanger is
is dirty
dirty

No
Replace
Replace outdoor
outdoor main
main
board
board

No

Check
Check whether
whether the
the refrigerant
refrigerant
system
system isis ok
ok

99
18.3.3.8 Low pressure protection (ODU P2/PC 31) (For M4OB-36HFN8-Q, M5OD-42HFN8-Q)

Low
Low pressure
pressure protection
protection

Whether
Whether the the wiring
wiring
between
between thethe low
low pressure
pressure
protector
protector and
and main
main control
control No Connect
Connect itit well
well
board
board is
is connected
connected well
well or
or
correctly
correctly

Yes

Whether
Whether thethe low
low
pressure
pressure protector
protector
is
is broken
broken

Method:
Method: Disconnect
Disconnect the
the plug.
plug.
Measure
Measure the
the resistance
resistance of
of the
the
low
low pressure
pressure protector.
protector. If
If the
the No Replace
Replace low
low pressure
pressure protector
protector
protector
protector is
is normal
normal the
the value
value isis
oo

Yes

Check
Check whether
whether the
the outdoor
outdoor
ambient
ambient temperature
temperature is
is too
too Yes Stop
Stop the
the unit
unit
low
low

No

Check
Check whether
whether valve
valve core
core
Open
Open fully
fully valve
valve core
core of
of
of
of high
high pressure
pressure valve
valve is
is No
high pressure valve
high pressure valve
opened
opened

Yes
please
please refer
refer to
to the
the solution
solution of
of fan
fan
Check
Check ifif the
the indoor
indoor fan
fan runs
runs speed
speed has
has been
been out
out of
of control
control
No malfunction.
malfunction. Find
Find out
out the
the cause
cause and
and
properly
properly in in cooling
cooling mode
mode
have
have itit solved.
solved.

Yes

Replace
Replace outdoor
outdoor main
main board
board

No
Refrigerant
Refrigerant isis not
not enough
enough add
add the
the
refrigerant
refrigerant

No

Check
Check whether
whether the
the refrigerant
refrigerant
system is ok
system is ok

100
18.3.3.9 Current protection of compressor (ODU P3/PC 08)
Outdoor unit zero speed protection(ODU PC44)
Compressor speed has been out of control(ODU PC46)
Compressor overcurrent failure(ODU PC49)

Current protection of compressor

Judge 1: Check whether the


input current of the power
supply wire is higher than max
protection current value

Yes

Check whether
the refrigerant
system is ok

Judge 2: Check whether the


outdoor ambient
Yes Stop the unit
temperature is higher than
50℃

No

Judge 3: Check whether the


Yes Make the outdoor unit ventilate well
outdoor unit is bad ventilation

No

Judge 4: Check whether the


Yes Clean the heat exchanger
heat exchanger is dirty

No

Let the refrigerant out, then use the high


Judge 5: The refrigerant
Yes pressure nitrogen or refrigerant to blow pipe,
pipe is blocked
vacuumize and charge the refrigerant again

No

Replace outdoor main


board,and check whether Yes
the system can run normally

No

Replace the electric control box Yes Trouble is solved

101
18.3.3.10 Temperature protection of compressor discharge (ODU P4/ PC 06)

Temperature
Temperature protection
protection of
of
compressor
compressor discharge
discharge

Check
Check whether
whether the
the
compressor Check
Check whether
whether the the
compressor discharge
discharge temp.
temp. isis Yes Yes Stop
Stop leaking
leaking and
and add
add refrigerant
refrigerant
refrigerant
refrigerant isis leak
leak
more
more than
than 115°C
115°C ??

No
No

Check
Check whether
whether the
the
connection
connection isis right
right between
between
compressor
compressor discharge
discharge temp.
temp. No Correct
Correct the
the wiring
wiring connection
connection
sensor
sensor and
and PCB
PCB according
according
to
to wiring
wiring diagrams?
diagrams?

Yes

Measure
Measure thethe resistance
resistance value
value
of compressor
of compressor discharge
discharge
temp.
temp. sensor.
sensor. IfIf the
the value
value is
is No Replace
Replace the
the compressor
compressor discharge
discharge temp.
temp. sensor
sensor
not normal is
not normal is normal
normal refer
refer to
to
the
the Appendix
Appendix 2?
2?

Yes

Replace
Replace outdoor
outdoor main
main PCB
PCB

No

Replace
Replace high
high pressure
pressure valve
valve assy
assy

102
18.3.3.11 High temperature protection of condenser (ODU P5/ PC 0A)
When outdoor pipe temperature is more than 65°C, the unit will stop, and unit runs again when outdoor pipe
temperature less than 52°C.

Check
Check the
the connection
connection
between
between temperature
temperature No Correct
Correct the
the connection
connection
High
High temperature
temperature protection
protection of
of No sensor
sensor and
and PCB.
PCB.
condenser
condenser

Yes

Check
Check whether
whether the
the
condenser
condenser temperature
temperature is
is Check
Check whether
whether the
the
Higher
Higher than
than 65°
65°C
C resistance
resistance of of condenser
condenser
temp.
temp. sensor
sensor is
is normal
normal
No Replace
Replace the
the temperature
temperature sensor
sensor
refer
refer to
to the
the Appendix
Appendix 11
Yes

Check
Check whether
whether the
the outdoor
outdoor
ambient
ambient temperature
temperature isis Yes Stop
Stop the
the unit
unit
higher
higher than
than 50℃
50℃

No

Check
Check ifif the
the outdoor
outdoor unit
unit
ventilation
No Make
Make the
the outdoor
outdoor unit
unit ventilate
ventilate well
well
ventilation isis good
good

Yes
please
please refer
refer to
to the
the solution
solution of
of fan
fan
Check
Check ifif the
the outdoor
outdoor fan
fan runs
runs speed
speed has
has been
been outout of
of control
control
No malfunction
malfunction .. Find
Find out
out the
the cause
cause and
and
properly
properly
have
have itit solved.
solved.

Yes

Check
Check whether
whether the
the heat
heat
exchanger
Yes Clean
Clean the
the heat
heat exchanger
exchanger Yes
exchanger is
is dirty
dirty

No
Replace
Replace outdoor
outdoor main
main
board
board

No
Refrigerant
Refrigerant isis not
not enough
enough add
add the
the
refrigerant
refrigerant

No

Check
Check whether
whether the
the refrigerant
refrigerant
system
system isis ok
ok

103
18.3.3.12 IPM module protection (ODU P6/PC 00)
IPM module protection

Check whether the voltage range


Check whether the input Regulate it to correct, then
of P-N on IPM module is normal?
No power supply is correct? No check whether the system
DC277-356V for 18-28KBtu/h;
208-230V, 1N, 60Hz can work normally?
DC277-410V for 36-42KBtu/h

Yes

Yes No

Check whether the connecting


line between main board and Connect it tightly,
No
the IPM module is connected check ok or not? Check whether the
Connect it correctly
tightly power supply line is
No and tightly, check ok
connected correctly and
or not?
tightly

Yes
No
Yes No

Check whether the connecting


Connect it well, check
line of the compressor is No
ok or not?
connected correctly or tightly Check whether the lines
Connect it tightly,
in E-part box are No
check ok or not?
connected tightly

Yes
No

Yes No
Replace the IPM module,
check whether the system can
work normally? Check whether the bridge rectifiers are
normal? Use the multimeter to measure
the resistance between each two
terminals, check whether there is the
No condition that value of resistance is 0
No
Check whether the resistance of
the fan motor is normal. If not, Yes
Check if the outdoor fan replace the fan motor. For other Yes
runs properly or the outdoor Yes models, refer to the solution of Replace the bridge rectifiers
unit ventilation is good. fan speed has been out of
control malfunction . F i n d o u t
Check whether the connecting line of
the cause and have it solved. every reactor is normal? If the line is
broken, the resistance of the two ports is
No ∞(models except for M4OA-36HFN1-
Q,M4OD-28HFN1-Q, M5OC-36HFN1-
Q);Check whether the PFC module
broken (for M4OA-36HFN1-Q,M4OD-
No
Replace the main board; check 28HFN1-Q, M5OC-36HFN1-Q,M50D-
whether the system can work Yes 42HFN1-Q)
normally?
Replace the connecting line or
reactor or replace the PFC
module(for M4OC-36HRFN1-
No M,M50D-42HFN1-Q)

Replace the compressor, check


Yes whether the system can work Yes
normally?

Trouble is solved

104
18.3.3.13 Top temperature protection of compressor (ODU P0/ PC 02 )

Check if the air flow system


Clear up the air inlet and outlet or the heat
of indoor and outdoor units Yes
exchanger of indoor and outdoor units.
are obstructed?

No

Turn off the power supply and turn


it on 10 minutes later.

Yes

Check if the temperature of Check if all the connection, especially


compressor Top No the connection of OLP (Over Load No Correct the connection.
Is more than 90℃? Protector) sensor is good.

Yes
Yes
Measure the resistance
Check if the refrigerant between the two ports of No Replace the OLP.
system the OLP. Is it zero?
is normal?
No
Yes Yes Replace the outdoor control PCB.

Repair the refrigerant


Replace the outdoor control PCB.
system .

105
18.3.3.14 Lack phase failure of outdoor DC fan motor(EC72)

Power off,then restart the unit


The unit operates
2 minutes later.Is it still No
normally
displaying the error code

Yes

Check the wiring of fan


motor.Are all the connections No Correct the connections
good?

Yes

Check whether the three-


phase resistance of the fan is No Replace the fan motor
symmetrical

Yes

Check the fan three-phase


output for obvious open No Replace the main PCB
circuit

Yes

Trobule is solved

106
18.3.3.15 Outdoor compressor lack phase protection(PC43)

Power off,then restart the unit


The unit operates
2 minutes later.Is it still No
normally
displaying the error code

Yes

Check both ends of


compressor connecting
No Correct the connections
line .Are all the connections
good?
Yes

Check whether the three-


phase resistance of the No Replace the compressor
compressor is symmetrical

Yes

Check the compressor three-


phase output for obvious No Replace the main PCB
open circuit

Yes

Trobule is solved

10.3.3.16 Outdoor unit IR chip drive failure(PC45)

Power off,then restart the unit


2 minutes later.

Yes

Replace the inverter module


PCB.

18.3.3.17 The cooling operation or heating operation does not operate.


Potential causes ● Faulty 4-way valve
Check of 4-way, please refer to part 4 in 10.4 Trouble Criterion Of Main Parts.

18.3.3.18 When cooling, heat exchanger of non-operating indoor unit frosts.


When heating, non-operating indoor unit get warm.
Potential causes ● Faulty EXV
● Wire and piping connected in reverse.
Check of EXV, please refer to part 5 in 10.4 Trouble Criterion Of Main Parts.

107
18.3.3.19 Automatic correction of wiring/piping error:
Press the "check switch" on the outdoor unit PCB board 5 seconds until LED display "CE", which
mean this function is working, Approximately 5-10 minutes after the switch is pressed, the "CE"
disappear the wiring/piping error will be corrected, and wiring/piping is properly connected.

Check switch

LED display

108
18.4 Main parts check
1. Temperature sensor checking
Disconnect the temperature sensor from PCB, measure the resistance value with a tester.

Temperature Sensors.
Room temperature(T1) sensor,
Indoor coil temperature(T2) sensor,
Outdoor coil temperature(T3) sensor,
Outdoor ambient temperature(T4) sensor,
Compressor discharge temperature(T5) sensor.
Measure the resistance value of each winding by using the multi-meter.

109
Appendix 1 Temperature Sensor Resistance Value Table for T1,T2,T3,T4,T2B (℃--K)
℃ K Ohm ℃ K Ohm ℃ K Ohm ℃ K Ohm
-20 115.266 20 12.6431 60 2.35774 100 0.62973
-19 108.146 21 12.0561 61 2.27249 101 0.61148
-18 101.517 22 11.5000 62 2.19073 102 0.59386
-17 96.3423 23 10.9731 63 2.11241 103 0.57683
-16 89.5865 24 10.4736 64 2.03732 104 0.56038
-15 84.2190 25 10.000 65 1.96532 105 0.54448
-14 79.3110 26 9.55074 66 1.89627 106 0.52912
-13 74.5360 27 9.12445 67 1.83003 107 0.51426
-12 70.1698 28 8.71983 68 1.76647 108 0.49989
-11 66.0898 29 8.33566 69 1.70547 109 0.48600
-10 62.2756 30 7.97078 70 1.64691 110 0.47256
-9 58.7079 31 7.62411 71 1.59068 111 0.45957
-8 56.3694 32 7.29464 72 1.53668 112 0.44699
-7 52.2438 33 6.98142 73 1.48481 113 0.43482
-6 49.3161 34 6.68355 74 1.43498 114 0.42304
-5 46.5725 35 6.40021 75 1.38703 115 0.41164
-4 44.0000 36 6.13059 76 1.34105 116 0.40060
-3 41.5878 37 5.87359 77 1.29078 117 0.38991
-2 39.8239 38 5.62961 78 1.25423 118 0.37956
-1 37.1988 39 5.39689 79 1.21330 119 0.36954
0 35.2024 40 5.17519 80 1.17393 120 0.35982
1 33.3269 41 4.96392 81 1.13604 121 0.35042
2 31.5635 42 4.76253 82 1.09958 122 0.3413
3 29.9058 43 4.57050 83 1.06448 123 0.33246
4 28.3459 44 4.38736 84 1.03069 124 0.32390
5 26.8778 45 4.21263 85 0.99815 125 0.31559
6 25.4954 46 4.04589 86 0.96681 126 0.30754
7 24.1932 47 3.88673 87 0.93662 127 0.29974
8 22.5662 48 3.73476 88 0.90753 128 0.29216
9 21.8094 49 3.58962 89 0.87950 129 0.28482
10 20.7184 50 3.45097 90 0.85248 130 0.27770
11 19.6891 51 3.31847 91 0.82643 131 0.27078
12 18.7177 52 3.19183 92 0.80132 132 0.26408
13 17.8005 53 3.07075 93 0.77709 133 0.25757
14 16.9341 54 2.95896 94 0.75373 134 0.25125
15 16.1156 55 2.84421 95 0.73119 135 0.24512
16 15.3418 56 2.73823 96 0.70944 136 0.23916
17 14.6181 57 2.63682 97 0.68844 137 0.23338
18 13.9180 58 2.53973 98 0.66818 138 0.22776
19 13.2631 59 2.44677 99 0.64862 139 0.22231

110
Appendix 2 Temperature Sensor Resistance Value Table for T5 (℃--K) (TP for AG)
℃ K Ohm ℃ K Ohm ℃ K Ohm ℃ K Ohm

-20 542.7 20 68.66 60 13.59 100 3.702


-19 511.9 21 65.62 61 13.11 101 3.595
-18 483 22 62.73 62 12.65 102 3.492
-17 455.9 23 59.98 63 12.21 103 3.392
-16 430.5 24 57.37 64 11.79 104 3.296
-15 406.7 25 54.89 65 11.38 105 3.203
-14 384.3 26 52.53 66 10.99 106 3.113
-13 363.3 27 50.28 67 10.61 107 3.025
-12 343.6 28 48.14 68 10.25 108 2.941
-11 325.1 29 46.11 69 9.902 109 2.86
-10 307.7 30 44.17 70 9.569 110 2.781
-9 291.3 31 42.33 71 9.248 111 2.704
-8 275.9 32 40.57 72 8.94 112 2.63
-7 261.4 33 38.89 73 8.643 113 2.559
-6 247.8 34 37.3 74 8.358 114 2.489
-5 234.9 35 35.78 75 8.084 115 2.422
-4 222.8 36 34.32 76 7.82 116 2.357
-3 211.4 37 32.94 77 7.566 117 2.294
-2 200.7 38 31.62 78 7.321 118 2.233
-1 190.5 39 30.36 79 7.086 119 2.174
0 180.9 40 29.15 80 6.859 120 2.117
1 171.9 41 28 81 6.641 121 2.061
2 163.3 42 26.9 82 6.43 122 2.007
3 155.2 43 25.86 83 6.228 123 1.955
4 147.6 44 24.85 84 6.033 124 1.905
5 140.4 45 23.89 85 5.844 125 1.856
6 133.5 46 22.89 86 5.663 126 1.808
7 127.1 47 22.1 87 5.488 127 1.762
8 121 48 21.26 88 5.32 128 1.717
9 115.2 49 20.46 89 5.157 129 1.674
10 109.8 50 19.69 90 5 130 1.632
11 104.6 51 18.96 91 4.849
12 99.69 52 18.26 92 4.703
13 95.05 53 17.58 93 4.562
14 90.66 54 16.94 94 4.426
15 86.49 55 16.32 95 4.294 B(25/50)=3950K
16 82.54 56 15.73 96 4.167
17 78.79 57 15.16 97 4.045 R(90℃)=5KΩ±3%
18 75.24 58 14.62 98 3.927
19 71.86 59 14.09 99 3.812

111
2.Compressor checking
1. Measure the resistance value of each winding by using a multi-meter.
2. Check the resistance value of each winding in the following table.

112
3. IPM continuity check
Electricity remains in capacitors even when the power supply is off. Ensure the capacitors are fully discharged before
troubleshooting.
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital
tester to measure the resistance between P and UVWN; UVW and N.

Digital tester Normal resistance value Digital tester Normal resistance value

(+)Red (-)Black (+)Red (-)Black

N U
∞ ∞
U V
P (Several MΩ) N (Several MΩ)
V W

W (+)Red

113

You might also like