Manual UPS NT 15 100kVA UL en Us
Manual UPS NT 15 100kVA UL en Us
User Manual
www.deltapowersolutions.com
SAVE THIS MANUAL
This manual contains important instructions and warnings that you should
follow during the installation, operation, storage and maintenance of this
product. Failure to heed these instructions and warnings will void the warranty.
Copyright © 2018 by Delta Electronics Inc. All Rights Reserved. All rights of this
User Manual (“Manual”), including but not limited to the contents, information,
and figures are solely owned and reserved by Delta Electronics Inc. (“Delta”).
The Manual can only be applied to the operation or the use of this product. Any
disposition, duplication, dissemination, reproduction, modification, translation,
extraction, or usage of this Manual in whole or in part is prohibited without the prior
written permission of Delta. Given that Delta will continuously improve and develop
the product, changes may be made to the information in this Manual at any time
without obligation to notify any person of such revision or changes. Delta will make
all possible efforts to secure the accuracy and the integrity of this Manual. Delta
disclaims any kinds or forms of warranty, guarantee, or undertaking, either expressly
or implicitly, including but not limited to the completeness, faultlessness, accuracy,
QRQLQIULQJHPHQWPHUFKDQWDELOLW\RU¿WQHVVIRUDSDUWLFXODUSXUSRVHRIWKH0DQXDO
Ultron NT Series II
Table of Contents
Table of Contents
Chapter 1 : Important Safety Instructions ------------------------------- 1
III
4.6 UPS Installation Checklist ---------------------------------------26
4.7 Floor Weight Loading Table -------------------------------------28
4.8 Cable Selection-----------------------------------------------------28
4.9 Electrical Connections --------------------------------------------31
4.9.1 15~30kVA Output 208/ 120Vac Terminal Wiring Diagram
(Only for Dual Input Application) ---------------------------------------31
4.9.2 60kVA Output 208/ 120Vac Terminal Wiring Diagram
(Only for Dual Input Application) ---------------------------------------32
4.9.3 100kVA Output 208/ 120Vac Terminal Wiring Diagram
(Only for Dual Input Application)----------------------------------------32
4.9.4 UPS Parallel Wiring Diagram (Dual Input) ---------------------------33
4.10 Communication Interfaces (NT-Q Board) --------------------34
4.11 Dry Contact Wiring Diagram (Default Value)----------------35
4.12 RS-485 Pin Assignment ------------------------------------------35
Ultron NT Series IV
Table of Contents
$SSHQGL[7HFKQLFDO6SHFL¿FDWLRQV ----------------------------------71
V
Chapter 1 : Important Safety Instructions
z This manual contains important instructions that should be followed during in-
stallation and maintenance of the UPS and batteries. Before wiring and opera-
tion, read all instructions thoroughly.
z RQRWXVHWKH836LQDFRPSXWHUURRPDVGH¿QHGLQWKH6WDQGDUGIRUWKH3UR-
'
tection of Electronic Computer/ Data Processing Equipment, ANSI/ NFPA 75.
z Install the UPS in a well-ventilated indoor area where is free of conductive con-
WDPLQDQWVDQGDZD\IURPÀDPPDEOHOLTXLGDQGJDV'RQRWOHWWKHXQLWFRPHLQ
contact with water. The UPS is only suitable for being installed on the concrete
and non-combustible surface. Do not place it outdoors. Please refer to Chapter
4.6 for more information
z The ambient operating temperature should be kept between 0°C ~ 40°C (32°F ~
104°F).
z For each operation mode’s block diagram, please refer to Chapter 3.
z For PERMANENTLY CONNECTED EQUIPMENT application, a readily acces-
sible disconnected device shall be incorporated in the building’s wiring system
for AC Input, AC Output and DC Input. Please refer to Chapter 4.8 for relevant
VSHFL¿FDWLRQV
z For the external terminals that need to connect to the UPS, please refer to
Chapter 4.8 for more information.
z The conduit size shall be 6 inches or other equivalent size. Wiring method shall
be in accordance with the National Electric Code, ANSI/ NFPA 70. When con-
necting to AC and DC wiring terminals, use adequate wire gauge, copper wires
with temperature resistance up to 90°C and lb-in torque force. For more informa-
tion, please refer to Chapter 4.8.
z The external slits and openings in the UPS are provided for ventilation. To en-
sure reliable operation of the UPS and to protect the UPS from overheating,
these slits and openings must not be blocked or covered. Do not insert any ob-
ject into the slits and openings that may hinder ventilation.
z Do not put beverages on the UPS, battery cabinet(s) or any other accessory as-
sociated with the UPS.
Ultron NT Series 1
Chapter 1 Important Safety Instructions
z The UPS is designed to power modern computer loads and associated periph-
HUDOGHYLFHVVXFKDVPRQLWRUVPRGHPVFDUWULGJHWDSHGULYHVH[WHUQDOÀRSS\
drives, etc. Do not connect (1) inductive loads, (2) capacitive loads or (3) life
support equipment to the UPS.
z OOPDLQWHQDQFHDQGLQVWDOODWLRQVKRXOGEHSHUIRUPHGE\TXDOL¿HGVHUYLFHSHU-
$
sonnel. The UPS contains high voltage which is potentially hazardous.
z The risk of dangerous high voltage is possible when batteries are still connected
to the UPS even though the UPS is disconnected from AC power sources. Be-
IRUHPDLQWHQDQFHSOHDVHWXUQRႇHYHU\H[WHUQDOEDWWHU\FDELQHW¶VFLUFXLWEUHDNHU
WRFXWRႇWKHEDWWHU\SRZHUIURPWKH836
z Isolate the UPS before working on the circuit. A readily accessible disconnected
device shall be installed.
z Before applying electrical power to the UPS, make sure the UPS is grounded to
avoid a possible risk of current leakage.
z The protective device shall be a four-pole device and shall disconnect all line
conductors and the neutral conductor.
z Battery installation and maintenance instructions shall be provided by the battery
manufacturer.
z Before battery installation and maintenance, ensure that the instructions written
in the battery manufacturer’s installation and maintenance manuals are thor-
oughly followed.
z For information about the maximum battery fault current, please refer to Chap-
ter 5.
z For information about the battery usage, connection, replacement, etc., please
refer to Chapter 5.
z 'RQRWGLVSRVHRIWKHEDWWHU\RUEDWWHULHVLQD¿UH7KHEDWWHULHVPD\H[SORGH
z Do not open or damage the battery or batteries. The released electrolyte is
harmful to the skin and eyes and may be toxic.
z A battery can present a risk of electric shock and high short-circuit current. The
following precautions should be observed before replacement of batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
2
3. Wear insulating gloves and boots.
4. Do not lay tools or metal parts on the top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the
battery terminals.
WARNING:
This is a class-A UPS. In a domestic environment, the product may
cause radio interference, in which case, the user may be required to
take additional measures.
z Standard Compliance:
- UL 1778
- FCC47 CFR Part 15, Subpart B, Class A
z Symbol Introduction
Ultron NT Series 3
Chapter 2 Introduction
Chapter 2 : Introduction
The NT series UPS is a dedicated design for large scales of power systems such
as data centers, communication systems, satellite systems, network rooms, medical
devices, monitoring, safety and emergency systems as well as factory facilities.
The UPS adopts high frequency SPWM (Sinusoidal Pulse-Width Modulation)
inverter technology. The inverter uses an advanced IGBT module capable to
reduce the MTTR (Mean Time to Repair) and easier to be maintained, came with
DGYDQWDJHVLQKLJKHႈFLHQF\ORZWKHUPDOORVVORZQRLVHVPDOOYROXPHDQGORQJ
product life expectation. The applied MCU simplifies complicated control circuits
and reduces number of components. To improve reliability, the NT series UPS is
designed with the following two functions:
Hot standby redundancy: dual input application.
Parallel redundancy: no need to add external parallel control cards and capable to
parallel up to 8 UPS units.
The LCD display with multi-language graphical interface makes the user easier to
operate. System block diagram and status are also available on the LCD providing
the user with clear operating modes and overall conditions. The user can also
implement long-distance monitoring via various communication ports, computers
and network systems. As a result, direct monitoring and control of the UPS is
available (all messages on the LCD are generated by MCU). With the installation of
the provided exclusive software, UPSentry 2012, a total of 31 UPS units’ status can
be monitored at the same time via only one PC, which greatly reduces manpower
and facilitates centralized control. The circuit boards of the NT Series UPS are
interchangeable which minimizes component inventory management, and the
friendly design of the NT series UPS provides optimal and durable quality power
and enhances the unit’s availability and reliability.
4
Chapter 3 : Operation Modes
There are four basic operation modes for the NT series UPS, either of which can
deliver loads with reliable and high quality power source in any conditions. The
operation modes are described as follows.
MANUAL BYPASS
BREAKER
RECTIFIER INPUT
BREAKER
MAINS RECTIFIER INVERTER STATIC SWITCH
BATTERY BANK
In normal mode, DC power, rectifying from AC input power, charges batteries and
powers the inverter that transforms DC power to stable and clean AC power to the
loads (see Figure 3-1).
MANUAL BYPASS
BREAKER
RECTIFIER INPUT
BREAKER
MAINS RECTIFIER INVERTER STATIC SWITCH
BATTERY BANK
Ultron NT Series 5
Chapter 3 Operation Modes
When the utility AC power fails or unstable voltage occurs, the batteries will instantly
provide DC power to keep continuous operation. Hence, the UPS output will not be
interrupted.
RECTIFIER INPUT
BREAKER
MAINS RECTIFIER INVERTER STATIC SWITCH
BATTERY BANK
Figure 3-3: Reserve AC Power Supply Mode Block Diagram_ Single Unit
When the inverter encounters abnormal situations such as over temperature, long-
time overload, output short circuit, abnormal output voltage and exhausted battery,
the inverter will automatically shut down itself for self-protection. Meanwhile, if the
reserve AC power is normal, the static switch will switch to the reserve AC power
to supply power to the loads without any interruption of power supply. After the
abnormal situations mentioned above are eliminated, the static switch will switch
back to the main AC source (see Figure 3-3).
RECTIFIER INPUT
BREAKER
MAINS RECTIFIER INVERTER STATIC SWITCH
BATTERY BANK
6
When maintenance is needed and the reserve AC power is normal, the UPS can
be switched from inverter mode to bypass mode manually with continuous power
delivering to the loads. Under such conditions, the internal power will be completely
FXWRႇH[FHSWWKDWWKHWHUPLQDOVDQGPDQXDOE\SDVVEUHDNHUVWLOOKDYHKLJKYROWDJH
As a result, risks will not exist in the UPS so service personnel can perform
maintenance safely (see Figure 3-4).
MANUAL BYPASS
UPS 1
BREAKER
BATTERY BANK
Power Flow
LOAD
MANUAL BYPASS
UPS 2
BREAKER
BATTERY BANK
Two or more UPS units operating in parallel mode have to satisfy requirements of
the same capacity, output voltage, frequency, and equal load share. If one of the
units fails and its loads are less than the sum of rated-load values of other units in
parallel, the rest of units can share the sum of loads; otherwise, all UPS units will
shut down inverters and switch to the reserve AC power to supply power to the
loads (see Figure 3-5).
Ultron NT Series 7
Chapter 3 Operation Modes
MANUAL BYPASS
UPS 1
BREAKER
BATTERY BANK
Power Flow
LOAD
MANUAL BYPASS
UPS 2
BREAKER
BATTERY BANK
When the utility AC power fails or other unstable voltage occurs, the batteries will
instantly provide the inverter with DC power to keep continuous operation. Hence,
the UPS output will not be interrupted (see Figure 3-6).
8
3.7 Reserve AC Supply Mode (Parallel)
BATTERY BANK
Power Flow
LOAD
BATTERY BANK
Figure 3-7: Reserve AC Power Supply Mode Block Diagram_ Parallel Units
Ultron NT Series 9
Chapter 3 Operation Modes
Power Flow
BATTERY BANK
Power Flow
LOAD
Power Flow
Power Flow
BATTERY BANK
When maintenance is needed and the reserve AC power is normal, the parallel UPS
units can be switched from inverter mode to bypass mode manually with continuous
power delivering to the loads. Under such conditions, the internal power will be
completely cut off except that each parallel UPS's terminals and manual bypass
breaker still have high voltage. As a result, risks will not exist in the parallel UPS
units so service personnel can perform maintenance safely (see Figure 3-8).
10
3.9 Hot Standby Redundancy
)RUKRWVWDQGE\UHGXQGDQF\FRQ¿JXUDWLRQV83623LVFRQQHFWHGWRWKHUHVHUYH
AC power of UPS2 (see Figure 3-9). Such configurations could reduce the
SUREDELOLW\RISRZHUFXWRႇDQGLPSURYHWKHTXDOLW\RISRZHUVXSSO\
MANUAL BYPASS
UPS 1
BREAKER
BATTERY BANK
RESERVE INPUT
Power Flow BREAKER Power Flow
Power Flow
Power Flow UPS 2 OUTPUT
LOAD
RECTIFIER INPUT OUTPUT
BREAKER BREAKER
MAINS RECTIFIER INVERTER STATIC SWITCH
BATTERY BANK
In normal condition, the UPS2 supplies the loads. If the UPS2 fails, the static switch
will switch to UPS1 (the reserve AC power of UPS2) without a break of the power
supply. In order to reduce costs, the O/P of UPS1 could simultaneously connect to
UPS2, UPS3, etc..
Ultron NT Series 11
Chapter 3 Operation Modes
MANUAL BYPASS
UPS1
BREAKER
RESERVE
RESERVE INPUT
BREAKER Power flow
Power flow Power flow
Power flow
OUTPUT
RECTIFIER INPUT
BREAKER
MAINS BREAKER RECTIFIER INVERTER STATIC SWITCH
Power flow
BATTERY BANK
LOAD
MANUAL BYPASS
UPS2
BREAKER
RESERVE
RESERVE INPUT
BREAKER Power flow
Power flow Power flow
Power flow
OUTPUT
RECTIFIER INPUT
BREAKER
MAINS BREAKER RECTIFIER INVERTER STATIC SWITCH
1. When many UPS units share one external battery cabinet, you can’t execute
‘Battery Test’ from the LCD control panel.
)RUFRPPRQEDWWHU\FRQ¿JXUDWLRQVWKHVHWWLQJVRI‘Battery Capacity AH’ and
‘Battery Charge Current’ shown on the LCD display shall be the actual AH and
the total charge current divided by the total number of the parallel UPS units.
For example:
When two UPS units are in parallel, the capacity of common battery is 100AH
and the charge current is 12A, the settings of ‘Battery Capacity AH’ and
‘Battery Charge Current’ for each UPS should be ‘50AH’ and ‘6A’ respectively.
12
3.11 Dry Contacts
OR
UPS
Figure 3-11
The NT series UPS provides 6 sets of programmable dry contacts that can be set as
Normally Open or Normally Closed. The default settings of the 6 sets of dry contacts
are described as follows.
1. Normal: The UPS runs in normal mode.
2. Reserve: When the inverter is abnormal, it is the reserve AC power to supply
power to the loads.
3. Back-up: When the main AC power is abnormal, it is the batteries to supply
power to the loads.
4. BAT_LOW: When the main AC power is abnormal, it is the batteries to supply
power to the loads and the battery discharging voltage exceeds the setting
values (lower than 330V).
5. RES Fail: When the UPS runs in normal mode and the reserve AC power is
abnormal, the output frequency will be based on the rated frequency.
6. BATT Test Fail: When the battery test is executed, the battery test result shows
abnormalities.
A total of 20 events can be selected to set up the 6 sets of dry contacts. Please refer
to Table 3-1.
Ultron NT Series 13
Chapter 3 Operation Modes
Parallel Communication
7 Battery Test Failure 17
Abnormal
14
Chapter 4 : Installation & Wiring
W
D
836XQLWSUR¿OHGLPHQVLRQVWDEOH
(Input: 480Vac; Reserve I/P: 208/
120Vac; Output: 208/ 120Vac)
H
Figure 4-1
Rating Width Depth Height
(kVA) (mm) (mm) (mm)
15 600 800 1400
30 600 800 1400
Figure 4-1
Bottom View
702 800
R8
15
376
67
600
(Front)
Figure 4-2
Ultron NT Series 15
Chapter 4 Installation & Wiring
W D
836XQLWSUR¿OHGLPHQVLRQVWDEOH
(Input: 480Vac; Reserve I/P: 208/
H
120Vac; Output: 208/ 120Vac)
Figure 4-3
Rating Width Depth Height
(kVA) (mm) (mm) (mm)
60 800 830 1700
Figure 4-3
52
Bottom View
690 830
R7
21
137 522
90
800
(Front)
Figure 4-4
16
D
W
836XQLWSUR¿OHGLPHQVLRQVWDEOH
(Input: 480Vac; Reserve I/P: 208/
120Vac; Output: 208/ 120Vac)
H
Figure 4-5
Rating Width Depth Height
(kVA) (mm) (mm) (mm)
100 1200 830 1700
Figure 4-5
55 R7.5-6
Bottom View
21
830 690
Figure 4-6
Ultron NT Series 17
Chapter 4 Installation & Wiring
W
D
Figure 4-7
18
4.3 External & Internal Views
Ultron NT Series 19
Chapter 4 Installation & Wiring
Figure 4-10 Front view with door open & front panel removal: one battery
start-up switch, four fuses, four breakers, one SMART slot, and
communication interfaces (NT-Q board).
Battery start-up
switch
Figure 4-10
20
4.3.2 60kVA (Input: 480Vac; Reserve I/P: 208/ 120Vac;
Output: 208/ 120Vac)
Figure 4-11 Front view: LCD control panel.
Figure 4-12 Lateral view: open the front door.
Ultron NT Series 21
Chapter 4 Installation & Wiring
Figure 4-13 Front view with door open & front panel removal: one battery
start-up switch, four fuses, four breakers, one SMART slot, and
communication interfaces (NT-Q board).
Battery start-up
switch
Fuses
(From left to right)
SMART slot
1. Transformer fan fuse
2. Heat sink fan fuse
3. PCB power fuse
4. Power fuse
Communication Breakers
interfaces (From left to right)
(NT-Q board) 1. Rectifier input
2. Reserve input
3. Manual bypass
4. UPS output
Figure 4-13
22
4.3.3 100kVA (Input: 480Vac; Reserve I/P: 208/ 120Vac;
Output: 208/ 120Vac)
Figure 4-14 Front view: LCD control Panel.
Figure 4-15 Lateral view: open the front doors.
Figure 4-14
1
2
Open the
front doors
Figure 4-15
Ultron NT Series 23
Chapter 4 Installation & Wiring
Figure 4-16 Front view with door open & front panel removal: one battery
start-up switch, four fuses, four breakers, one SMART slot, and
communication interfaces (NT-Q board).
Fuses
(From left to right)
SMART slot 1. Transformer fan fuse
2. Heat sink fan fuse
3. PCB power fuse
4. Power fuse
Communication
interfaces
(NT-Q board)
Breakers
(From left to right)
1. Rectifier input
2. Reserve input
3. Manual bypass
4. UPS output
Figure 4-16
24
4.4 Installation Environment and Safety Precaution
To ensure UPS normal operation, prolong UPS lifetime, and protect UPS from
disorder and malfunction, the user should select an optimal installation location and
environment according to the following safety instructions.
1. Install the UPS indoors. Do not place it outdoors.
7KHZHLJKWRIWKH836LVFRQFHQWUDWHGRQDUHODWLYHO\VPDOOÀRRUDUHDGXHWRWKH
FDELQHWGHVLJQ7KHLQVWDOODWLRQORFDWLRQPXVWWKHUHIRUHKDYHDVXႈFLHQWÀRRU
loading capacity to bear the weight of the UPS.
3. The UPS and battery cabinet should be located on enough space for
maintenance and good ventilation.
Rear panel should be kept away from wall at least 50 cm.
The front of the UPS should be kept at least 100cm.
The top of the UPS should be kept at least 50cm.
4. For optimum performance and reliability to prolong UPS lifetime, the temperature
should be kept below 25°C, and humidity must be maintained within a range of
0 to 95% (non-condensing).
5. Check if the length and diameter of wires conform to the safety standard or not.
:DOOVFHLOLQJVÀRRUVDVZHOODVHYHU\WKLQJVXUURXQGLQJRUQHDUWKH836VKRXOG
be preferably constructed by noncombustible materials. The room should be
HTXLSSHGZLWKSRUWDEOH¿UHH[WLQJXLVKHUV
7KHÀRRUDUHDVXUURXQGLQJWKH836VKRXOGEHNHSWFOHDQ$FFHVVWRWKH836
room should be limited to a minimum number of operation and maintenance
personnel only. The doors should be kept locked and the keys should be
controlled to authorized personnel only.
8. If the UPS is supplied by a power source whose neutral is grounded, the
backfeed protective device installed as UPS input protection must be a 3-pole
type. If the UPS is supplied by a power source whose neutral is not grounded,
the backfeed protective device installed as UPS input protection must be a
4-pole type. The recommended electrical rating of the backfeed protective
device is as follows.
Ultron NT Series 25
Chapter 4 Installation & Wiring
NOTE:
When the total number of the parallel UPS units is more than four,
please install a load sharing choke between each parallel UPS and its
connected bypass input power to ensure that each bypass input power’s
current is even. For more information, please contact your local dealer,
sales representative or Delta customer service.
6. The external battery cabinet must be grounded and connected to the UPS’s
‘Battery Cabinet Ground’ terminal. Do not connect the external battery cabinet
to any other grounding system.
26
3. Whether the UPS room has enough space for UPS ventilation and personnel
maintenance.
4. Whether the space between the top of the UPS and the ceiling is large enough
for heat ventilation.
5. Whether the air conditioning is capable of keeping ambient around 25°C.
6. Whether the humidity is in rated limit.
7. Whether the UPS room is periodically inspected, and all unrelated things are
kept away from the UPS.
8. Whether the noise insulation devices are set to reduce noise.
9. Whether wiring is correct, and diameter of each wire complies with the electrical
standard.
&RQ¿UPWKDWWKHLQSXWSRZHUVRXUFHKDVEHHQVZLWFKHGRႇEHIRUHZLULQJ
11. Make sure that each wire has clear labels for polarities and phases.
:KHWKHUWKHÀRRUVZDOOVDQGFHLOLQJVDUHPDGHRIÀDPHSURRIPDWHULDOV
:KHWKHUWKH¿UHH[WLQJXLVKHUVFRPSO\ZLWKWKHVDIHW\VWDQGDUG
14. Whether the UPS room equips with a sprinkler system (not essential).
:KHWKHUWKHXVHUNQRZVKRZWRRSHUDWHWKH¿UHH[WLQJXLVKHUV
16. Whether the UPS room has a security lock and UPS door key is in charge by
authorized personnel.
:KHWKHU DOO RSHUDWRUV DQG PDLQWHQDQFH SHUVRQQHO KDYH VXႈFLHQW WUDLQLQJ IRU
the following tasks:
---- Normal and emergency operation procedures.
(PHUJHQF\¿UVWDLG
8VDJHRI¿UHH[WLQJXLVKHUV
'XULQJLQVWDOODWLRQHQVXUHWKDWWKH836LQSXWQHXWUDOLV¿UPO\FRQQHFWHGWRWKH
utility power neutral.
19. The top cover of UPS model 260kVA~500kVA is designed with air flow
ventilation holes. Ensure that there is no dust or liquid dropping from the top of
the UPS.
Ultron NT Series 27
Chapter 4 Installation & Wiring
Battery Type 12V/ 26AH 12V/ 40AH 12V/ 26AH 12V/ 40AH 12V/ 100AH
(AH) x 29PCS x 29PCS x 58PCS x 58PCS x 29PCS
Weight
360 520 796 1118 1420
(Kg)
Weight
loading 750 1084 1066 1497 1764
(kg/m2)
O/P Voltage (V) 208/ 120V 208/ 120V 208/ 120V 208/ 120V
28
UPS Capacity (VA) 15K 30K 60K 100K
NOTE :
1. The cable rating mentioned above is based on 105°C PVC type of cable.
2. Please follow the local regulations to install suitable cables and circuit
breakers.
3. Wiring method shall be in accordance with the National Electric Code,
ANSI/ NFPA 70.
'RQRWXVHWKH836LQDFRPSXWHUURRPDVGH¿QHGLQWKH6WDQGDUGIRU
the Protection of Electronic Computer/ Data Processing Equipment, ANSI/
NFPA 75.
z Wiring Information:
Use adequate wire gauge(*1), copper wires with temperature resistance up to
90°C and lb-in torque force (*2) when connecting to AC and DC wiring terminals.
Model Wiring Location Wire Gauge (*1) Bolt Type Torque (Ib-in) (*2)
PE 10 AWG X 1 M8 53.1
PE 8 AWG X 1 M8 53.1
Ultron NT Series 29
Chapter 4 Installation & Wiring
Model Wiring Location Wire Gauge (*1) Bolt Type Torque (Ib-in) (*2)
30
4.9 Electrical Connections
WARNING:
1. AC power source connection: Three-phase (R/ S/ T) of AC power source
must be in positive phase sequence and the R/ S/ T/ N cables must be
FRQQHFWHGWRWKHWHUPLQDOVµ5¶µ6¶µ7¶µ1¶VKRZQLQWKHIROORZLQJ¿JXUHV
2. Battery source connection: The positive and negative poles of the battery
cabinet must be connected to the terminal poles ‘+’ and ‘-’ shown in the
IROORZLQJ¿JXUHV
3. The external battery cabinet must be grounded and connected to the
UPS’s ‘Battery Cabinet Ground’ terminal. Do not connect the external
battery cabinet to any other grounding system.
4. Wrong wiring will cause damage to the UPS and electric shock.
Ultron NT Series 31
Chapter 4 Installation & Wiring
Input
Battery
32
4.9.4 UPS Parallel Wiring Diagram (Dual Input)
When UPSs are paralleled, the length of each unit's input cables (reserve source)
plus output cables must be the same. This ensures that the parallel UPSs can
equally share the critical loads in reserve AC supply mode.
UPS 1
IP 1 O/P
I/P
Res 1 CNQ7
Reserve Parallel Cable
CNQ8
I/P OP 1
UPS 2
IP 2 O/Pġġġ
OP 2
I/P LOAD
Res 2
Reserve CNQ7
CNQ8 OP 8
Reserve
UPS 8
UPS 8
IP 8 I/P O/P
Res1+OP1=Res2+OP2=…………..=Res8+OP8
NOTE:
When the total number of the parallel UPS units is more than four, please
install a load sharing choke between each parallel UPS and its connected
bypass input power to ensure that each bypass input power’s current is even.
For more information, please contact your local dealer, sales representative
or Delta customer service.
Ultron NT Series 33
Chapter 4 Installation & Wiring
34
4.11 Dry Contact Wiring Diagram (Default Value)
+12VR
3
1
RLQ1
DRY1 RELAY-SPDT
4
+12VR
3 CNQ14
1
DRY1COM
RLQ2 1
RELAY-SPDT
DRY1NO DRY 1: NORMAL: P1-2 NO
DRY2 2
DRY2COM
3
DRY2NO DRY 2: RESERVE: P3-4 NO
2
4
+12VR
3
1
RLQ3
DRY3 RELAY-SPDT
CNQ15
DRY3COM
2
+12VR 1
DRY3NO DRY 3: BACKUP: P1-2 NO
2
DRY4COM
3
3
1
+12VR
3
CNQ16
1
RLQ5 DRY5COM
1
RELAY-SPDT DRY5NO DRY 5: RES FAIL: P1-2 NO
DRY5 2
DRY6COM
3
DRY6NO DRY 6: BATT TEST FAIL: P3-4 NO
2
4
+12VR
3
1
RLQ6
DRY6 RELAY-SPDT
2
Ultron NT Series 35
Chapter 5 External Battery Cabinet
The NT series UPS must be connected to at least one external battery cabinet to
ensure that the critical loads connected are protected when a power failure occurs.
WARNING:
You can connect the critical loads to the UPS only after the batteries are
IXOO\FKDUJHG7KLVJXDUDQWHHVWKDWWKH836FDQSURYLGHVXႈFLHQWEDFNXS
power to the critical loads connected when a power failure occurs.
z Battery
1. Charge Voltage:
1) Float charge voltage: 393Vdc (default)
2) Boost charge voltage: 405Vdc (default)
2. Charge Current:
36
z Battery number for each string: 12V × 29 PCS.
NOTE : You can also choose 12V × 28 PCS or 12V × 30 PCS batteries.
Please contact your local dealer or customer service for battery selection,
installation and replacement.
z Only use the same type of batteries from the same supplier. Never use old, new
DQGGLႇHUHQW$KEDWWHULHVDWWKHVDPHWLPH
z The number of batteries must meet UPS requirements.
z Do not connect the batteries in reverse.
z Use a voltage meter to measure whether the total voltage, after battery connec-
tion, is around 12.5 Vdc × the total number of batteries.
NOTE :
7XUQRႇWKH836DQGFXWRႇWKH$&SRZHUVRXUFHEHIRUHSHUIRUPLQJ
battery/ battery cabinet replacement.
2. A battery can present a risk of electric shock and high short-circuit
current. Servicing of batteries and battery cabinets must be performed
RUVXSHUYLVHGE\TXDOL¿HGSHUVRQQHONQRZOHGJHDEOHLQWKHEDWWHULHV
battery cabinets and required precautions. Keep unauthorized
personnel away from the batteries and battery cabinets.
3. The maximum battery fault current is 2.8kA.
4. The table below shows each model’s battery fault current.
WARNING:
A battery leak can short-circuit the batteries and lead to serious
accidents. For safety's sake, you must insulate the batteries from their
touched metal cabinets by installing insulated devices (e.g. insulated
trays or boxes) in between. For relevant information about the insulated
materials for such application, please contact Delta customer service.
Ultron NT Series 37
Chapter 6 UPS Display and Settings
4
3
2
1. EPO switch: When an emergency event occurs, press the EPO switch to turn
RႇWKHUHFWL¿HULQYHUWHUDQGRXWSXWRIWKH836
5HFWL¿HU/(' JUHHQ :KHQWKHUHFWL¿HUZRUNVQRUPDOO\
3. Reserve power LED (green): When the reserve source is normal.
4. Maintenance bypass power LED (red): When the manual bypass breaker is
turned on.
5. Battery LED (orange): When the mains source is abnormal and the loads are
supplied by battery power.
6. Inverter LED (green): When the inverter works normally.
7. Reserve power static switch LED (green): When the loads are supplied by the
reserve AC power.
8. AC output LED (green): When the UPS has normal output.
9. Inverter M.C. LED (green): When the loads are supplied by the inverter.
10. Inverter control buttons: Press “ON” and “ ” simultaneously for 3 seconds to
turn on the inverter and press “OFF” and “ ” simultaneously for 3 seconds to
WXUQRႇWKHLQYHUWHU
11. “ ”“ ”“ ” buttons: Control the LCD display and set up parameters.
12. LCD display.
38
6.2 LCD Display Screen
1. Button functions:
Normal Mode
BYPASS
MAINS
ID : 1
4. Press the “ ” or “ ” button to choose “Measure Page”, and then press the “ ”
button to enter the “Measure Page”.
Ultron NT Series 39
Chapter 6 UPS Display and Settings
After entering the “Measure Page”, press the “ ” or “ ” button to monitor the
present status and parameters of the UPS.
The display order is as follows:
To leave the “Measure Page”, press the “ ” and “ ” buttons simultaneously to return to
the “Main Menu”.
40
5. In “Main Menu”, press the “ ” or “ ” button to choose “Parameter Setting”
and press the “ ” button to enter the “Parameter Setting” menu. Before
entering the “Parameter Setting” menu, password needs to be keyed in.
Æ Inverter Password
Output Setting
Bypass UPS ID
Input Setting
Battery Display
Setting Setting
Time and Language
Date Setting
5-1. Press the “ ” or “ ” button to choose “Inverter Output” and press the “ ”
button to enter the “Inverter Output Voltage” setting page.
To leave the “Inverter Output Voltage” setting page, press the “ ” and “ ” buttons
simultaneously to go back to the “Parameter Setting” menu.
Ultron NT Series 41
Chapter 6 UPS Display and Settings
5-2. Press the “ ” or “ ” button to choose “Bypass Input” and press the “ ”
button to enter the “Bypass Input Voltage/ Frequency” setting page.
To leave the “Bypass Input” setting page, press the “ ” and “ ” buttons simultaneously
to go back to the “Parameter Setting” menu.
5-3. Press the “ ” or “ ” button to choose “Battery Setting” and press the “ ”
button to enter the “Battery setting” menu.
Æ Capacity Test
AH Voltage
Boost Test
Voltage Time
Floated Commune
Voltage Battery
Stop Install
Voltage Date
Charge Replace
Current Remind
5-3.1. Press the “ ” or “ ” button to choose “Capacity AH” and press the “ ”
button to enter the “Battery Capacity AH” setting page.
42
z Press the “ ” or “ ” button to set up ˾̨̛̗̪̪̯
the battery capacity AH and press the ˿̗̦̗̙̟̪̯! ˽̄Ǻ
“ ” EXWWRQWRFRQ¿UPWKHVHWWLQJ 2!1!1!B!I
ʅǺɠ
ʆǺɡ
To leave the “Battery Capacity AH” setting page, press the “ ” and “ ” buttons
simultaneously to go back to the “Battery Setting” menu.
5-3.2. Press the “ ” or “ ” button to choose “Boost Voltage” and press the “ ”
button to enter the “Battery Boost Voltage” setting page.
ʅǺɠ
ʆǺɡ
To leave the “Battery Boost Voltage” setting page, press the “ ” and “ ” buttons
simultaneously to go back to the “Battery Setting” menu.
5-3.3. Press the “ ” or “ ” button to choose “Floated Voltage” and press the “ ”
button to enter the “Battery Floated Voltage” setting page.
ʅǺɠ
ʆǺɡ
To leave the “Battery Floated Voltage” setting page, press the “ ” and “ ” buttons
simultaneously to go back to the “Battery Setting” menu.
Ultron NT Series 43
Chapter 6 UPS Display and Settings
5-3.4. Press the “ ” or “ ” button to choose “Stop Voltage” and press the “ ”
button to enter the “Battery Stop Voltage” setting page.
ʅǺɠ
ɧ烉炼
To leave the “Battery Stop Voltage” setting page, press the “ ” and “ ” buttons
simultaneously to go back to the “Battery Setting” menu.
5-3.5. Press the “ ” or “ ” button to choose “Charge Current” and press the “ ”
button to enter the “Battery Charge Current” setting page.
ɥ烉為
ɧ烉炼
To leave the “Battery Charge Current” setting page, press the “ ” and “ ” buttons
simultaneously to go back to the “Battery Setting” menu.
5-3.6. Press the “ ” or “ ” button to choose “Test Voltage” and press the “ ”
button to enter the “Battery Test Voltage” setting page.
“ ”EXWWRQWRFRQ¿UPWKHVHWWLQJ 3 3 5 V
ʅǺɠ
ʆǺ炼
44
To leave the “Battery Test Voltage” setting page, press the “ ” and “ ” buttons
simultaneously to go back to the “Battery Setting” menu.
5-3.7. Press the “ ” or “ ” button to choose “Test Time” and press the “ ”
button to enter the “Battery Test Time” setting page.
ɥ烉為
ɧ烉炼
To leave the “Battery Test Time” setting page, press the “ ” and “ ” buttons
simultaneously to go back to the “Battery Setting” menu.
5-3.8. Press the “ ” or “ ” button to choose “Common Battery” and press the
“ ” button to enter the “Common Battery” setting page.
NOTE : When several UPS units share the common battery, the battery
test cannot be executed.
To leave the “Common Battery” setting page, press the “ ” and “ ” buttons
simultaneously to go back to the “Battery Setting” menu.
Ultron NT Series 45
Chapter 6 UPS Display and Settings
5-3.9. Press the “ ” or “ ” button to choose “Install Date” and press the “ ”
button to enter the “Install Date” setting page.
To leave the “Install Date” setting page, press the “ ” and “ ” buttons simultaneously
to go back to the “Battery Setting” menu.
5-3.10. Press the “ ” or “ ” button to choose “Replace Remind” and press the
“ ” button to enter the “Battery Replace Remind Warning” setting page.
To leave the “Battery Replace Remind Warning” setting page, press the “ ” and “ ”
buttons simultaneously to go back to the “Battery Setting” menu.
To leave the “Battery Setting” menu, press the “ ” and “ ” buttons simultaneously to
go back to the “Parameter Setting” menu.
46
5-4. Press the “ ” or “ ” button to choose “Time and Date” and press the “ ”
button to enter the “Time and Date” setting page.
To leave the “Time and Date” setting page, press the “ ” and “ ” buttons simultan-
eously to go back to the “Parameter Setting” menu.
5-5. Press the “ ” or “ ” button to choose “Password Setting” and press the
“ ” button to enter the “Password Setting” page.
ɥ烉為
ɧ烉炼
To leave the “Password Setting” page, press the “ ” and “ ” buttons simultaneously to
go back to the “Parameter Setting” menu.
5-6. Press the “ ” or “ ” button to choose “UPS ID Setting” and press the “ ”
button to enter the “UPS ID Setting” page.
Ultron NT Series 47
Chapter 6 UPS Display and Settings
z The UPS ID shown on the Start Display (see Figure 6-2) is for application of
the RS-485 interface and monitoring software (UPSentry 2012). It can be set up
right from the LCD control panel.
To leave the “UPS ID Setting” page, press the “ ” and “ ” buttons simultaneously to go
back to the “Parameter Setting” menu.
5-7. Press the “ ” or “ ” button to choose “Display Setting” and press the “ ”
button to enter the “Display Setting” page.
To leave the “Display Setting” page, press the “ ” and “ ” buttons simultaneously to
go back to the “Parameter Setting” menu.
5-8. Press the “ ” or “ ” button to choose “Language Setting” and press the
“ ” button to enter the “Language Setting” page.
48
To leave the “Language Setting” page, press the “ ” and “ ” buttons simultaneously to
go back to the “Parameter Setting” menu.
To leave the “Parameter Setting” menu, press the “ ” and “ ” buttons simultaneously
to go back to the “Main Menu”.
6-1. Press the “ ” or “ ” button to choose “Inverter ON/ OFF” and press the “ ”
button to enter the “Inverter Output” setting page.
Ultron NT Series 49
Chapter 6 UPS Display and Settings
6-2. Press the “ ” or “ ” button to choose “Buzzer ON/ OFF” and press the “ ”
button to enter the “Buzzer Status” setting page.
6-3. Press the “ ” and “ ” button to choose “Battery Test” and press the “ ”
button to enter the “Battery Manual Test” setting page.
NOTE : When several UPS units share the common battery, the battery
test cannot be executed.
50
z Press the “ ” and “ ” buttons simul- Battery Test OK
taneously to go back to the “System
Control” menu.
Battery Test
FailǺ
Please check
battery aging and make sure
make sure battery
line is normal
ɥ烉為
ɧ烉炼
Ultron NT Series 51
Chapter 6 UPS Display and Settings
6-5. Press the “ ” or “ ” button to choose “UPS Output ON/ OFF” and press
the “ ” button to enter the “UPS Output” setting page.
z Choose ON: The UPS has normal out- UPS
put. OutputǺ
ON
z &KRRVH2))7KH836WXUQVRႇRXWSXW
z Press the “ ” and “ ” buttons simul- ɥ烉為
taneously to go back to the “System ɧ烉炼
Control” menu.
6-6. Press the “ ” or “ ” button to choose “UPS Work Mode” and press the “ ”
button to enter the “UPS Work Mode” setting page.
6-7. Press the “ ” or “ ” button to choose “Force Bypass” and press the “ ”
button to enter the “UPS Force Bypass” setting page.
52
z Press the “ ” and “ ” buttons simultaneously to go back to the “System Con-
trol” menu.
To leave the “System Control” menu, press the “ ” and “ ” buttons simultaneously
to go back to the “Main Menu”.
To leave the “Event Log” menu, press the “ ” and “ ” buttons simultaneously to go
back to the “Main Menu”.
Ultron NT Series 53
Chapter 6 UPS Display and Settings
54
5HFWL¿HU6WDWLF6ZLWFK)DLO(YHQWFRGH
Ultron NT Series 55
Chapter 6 UPS Display and Settings
To leave the “Other Information” menu, press the “ ” and “ ” buttons simultaneously
to go back to the “Main Menu”.
56
Code UPS Status
2 Load on reserve
10 5HFWL¿HU$&VRIWVWDUW
18 Do inverter test
20 Load on inverter
24 Low battery
Ultron NT Series 57
Chapter 7 UPS Operation
1. Turn on the Reserve Input breaker, and the LCD will display ‘Bypass Mode’.
2. Turn on the 5HFWL¿HU,QSXW breaker and wait about 30 seconds. After that, the
DC BUS voltage will be established to 393V.
3. Turn on each external battery cabinet’s Battery breaker.
4. Press the ‘ON’ and ‘ ’ buttons simultaneously for 3 seconds. After that, the
inverter will start up. Once the inverter voltage is established, the power will be
switched from bypass to inverter. At this moment, it will be the inverter to supply
power to the connected loads, and the LCD will display ‘Normal Mode’. After
30 seconds, the UPS will automatically execute a battery test to check if the
connected batteries are normal or not.
58
5. If the battery test is normal, use a voltage meter to measure the UPS’s output
voltage (per phase). If normal, turn on the UPS Output breaker.
The Manual Bypass breaker can only be turned ON for UPS maintenance, which
ensures that the power supplying to the connected loads won’t be interrupted during
maintenance process.
If the Manual Bypass breaker is turned ON in Normal Mode, the inverter will be
turned OFF, the connected critical loads will be power-supplied by the manual
bypass and the output won’t be protected. Please ensure that the reserve AC power
is normal.
Ultron NT Series 59
Chapter 7 UPS Operation
1. Press the ‘OFF’ and ‘ ’ buttons simultaneously for 3 seconds. After the reserve
AC power is normal (the voltage and frequency of the reserve AC power is within
the setup range), the inverter will be turned off immediately and it will be the
reserve AC power to supply power to the connected loads. At the same time, the
LCD will display ‘Bypass Mode’.
7XUQRႇHDFKH[WHUQDOEDWWHU\FDELQHW¶VBattery breaker.
7XUQRႇWKH5HFWL¿HU,QSXW breaker.
4. (1) Wait about 5 minutes for the DC CAP to discharge, and ensure that the LCD
shows the battery voltage lower than 5V.
Or, (2) Press the ‘ON’ and ‘OFF’ buttons simultaneously for 3 seconds to let the
DC CAP to discharge, and ensure that the LCD shows the battery voltage lower
WKDQ9$IWHUFRQ¿UPDWLRQSUHVVWKHµOFF’ and ‘ ’ buttons simultaneously for
VHFRQGVWR¿QLVKWKHGLVFKDUJHSURFHVV
5. Turn on the Manual Bypass breaker. The connected loads will be power-
supplied by the manual bypass and the LCD will display ‘Manual Bypass ON’.
7XUQRႇWKHUPS Output breaker and Reserve Input breaker.
7. Disconnect all fuses. After that, the LCD will be OFF.
8. When the UPS is running in Manual Bypass Mode, there is no high voltage
inside the UPS except the wiring terminals and Manual Bypass breaker. Do
not touch the UPS’s wiring terminals and Manual Bypass breaker during UPS
maintenance process to avoid electric shock.
60
7.2.3.2 From Manual Bypass Mode to Normal Mode (Single)
NOTE : Before executing the following start-up procedures, please refer to 7.1
3UH6WDUWXS 3UH7XUQR௺:DUQLQJV¿UVW
%HIRUHSDUDOOHOLQJ836VSOHDVHFRQ¿UPWKDWHDFKXQLW¶VFDSDFLW\YROWDJHDQG
frequency are the same.
2. Turn on each UPS’s Reserve Input breaker, and each LCD will display ‘Bypass
Mode’.
3. Use the provided parallel cables to connect the parallel UPSs (at maximum 8
XQLWV DQGPDNHVXUHWKDWHDFKSDUDOOHOFDEOHLV¿UPO\¿[HG
4. Use the RS-232 and UPS parameter setting software (please contact service
personnel) to set up each parallel UPS’s parallel ID No. The parallel ID No. is
GLႇHUHQWIURPWKH,'1RVKRZQRQWKH/&'3OHDVHUHIHUWRWKHWDEOHEHORZIRU
the parallel ID No.
Ultron NT Series 61
Chapter 7 UPS Operation
UPS
1st 2nd 3rd 4th 5th 6th 7th 8th
(At Max. 8 Units)
Parallel ID No. 12 23 34 45 56 67 78 81
5. Turn on each UPS’s 5HFWL¿HU,QSXW breaker and wait about 30 seconds. After
that, the DC BUS voltage will be established.
6. Turn on each external battery cabinet’s Battery breaker.
7. Press one of the parallel UPSs’ ‘ON’ and ‘ ’ buttons simultaneously for 3
seconds, and its inverter will start up. Once the inverter voltage is established,
the LCD will display ‘Bypass Mode’.
8. Repeat the above-mentioned Step 7 to the rest of the parallel UPSs. After the
last parallel UPS’s inverter voltage is established, each parallel UPS’s contactor
will activate and each LCD will display ‘Normal Mode’.
9. Use a voltage meter to measure each parallel UPS’s output voltage (per phase).
The output voltage difference must be lower than 5V. If normal, turn on each
unit’s UPS Output breaker.
10.Now, the total loads will be equally shared by the parallel UPSs.
%HIRUHSDUDOOHOLQJ836VSOHDVHFRQ¿UPWKDWHDFKXQLW¶VFDSDFLW\YROWDJHDQG
frequency are the same.
2. Turn on each external battery cabinet’s Battery breaker.
3. Press each parallel UPS’s battery start-up switch once.
4. Use the provided parallel cables to connect the parallel UPSs (at maximum 8
XQLWV DQGPDNHVXUHWKDWHDFKSDUDOOHOFDEOHLV¿UPO\¿[HG
62
5. Use the RS-232 and UPS parameter setting software (please contact service
personnel) to set up each parallel UPS’s parallel ID No. The parallel ID No. is
GLႇHUHQWIURPWKH,'1RVKRZQRQWKH/&'3OHDVHUHIHUWRWKHWDEOHEHORZIRU
the parallel ID No.
UPS
1st 2nd 3rd 4th 5th 6th 7th 8th
(At Max. 8 Units)
Parallel ID No. 12 23 34 45 56 67 78 81
6. After each UPS’s DC BUS voltage reaches around 330V, each UPS’s battery
contactor will start up.
7. Press one of the parallel UPSs’ ‘ON’ and ‘ ’ buttons simultaneously for
3 seconds. After that, its inverter will start up and its inverter voltage will be
established.
8. Repeat Step 7 to the rest of the parallel UPSs. After the last parallel UPS’s
inverter voltage is established, each parallel UPS’s contactor will activate.
9. Use a voltage meter to measure each parallel UPS’s output voltage (per phase).
The output voltage difference must be lower than 5V. If normal, turn on each
unit’s UPS Output breaker.
10.Now, the total loads will be equally shared by the parallel UPSs and each LCD
will display ‘Backup Mode’.
For parallel application, each parallel UPS’s Manual Bypass breaker can only be
turned ON for UPS maintenance, which ensures that the power supplying to the
connected loads won’t be interrupted during maintenance process.
If each parallel UPS’s Manual Bypass breaker is turned ON in Normal Mode,
each parallel UPS’s inverter will be turned OFF, the connected critical loads will be
power-supplied by the manual bypass and the output won’t be protected. Please
ensure that the reserve AC power is normal.
Ultron NT Series 63
Chapter 7 UPS Operation
1. Press one of the parallel UPSs’ ‘OFF’ and ‘ ’ buttons simultaneously for 3
seconds. If the total connected loads are less than the total capacity of the rest
RIWKHSDUDOOHO836VWKH836WKDW\RXMXVWWXUQHGRႇZLOOVKXWGRZQDQGLWV/&'
will display ‘Inhibit Output’. Now, the total loads will be equally shared by the
rest of the parallel UPSs.
If the total loads are greater than the total capacity of the rest of the parallel
836VHDFK836¶VLQYHUWHUZLOOEHWXUQHGRႇLPPHGLDWHO\DIWHUWKHUHVHUYH$&
power is normal (the voltage and frequency of the reserve AC power is within the
setup range). After that, it will be the reserve AC power to supply power to the
connected loads and each UPS’s LCD will display ‘Bypass Mode’.
2. Repeat the above-mentioned Step 1 to the rest of the parallel UPSs in order to
let all parallel UPSs run in ‘Bypass Mode’.
7XUQRႇHDFKH[WHUQDOEDWWHU\FDELQHW¶VBattery breaker.
7XUQRႇHDFKSDUDOOHO836¶V5HFWL¿HU,QSXW breaker.
5. (1) Wait about 5 minutes for each DC CAP to discharge, and ensure that each
LCD shows the battery voltage lower than 5V.
Or, (2) Press each UPS’s ‘ON’ and ‘OFF’ buttons simultaneously for 3 seconds
to let its DC CAP to discharge, and ensure that each LCD shows the battery
voltage lower than 5V. After confirmation, press each UPS’s ‘OFF’ and ‘ ’
EXWWRQVVLPXOWDQHRXVO\IRUVHFRQGVWR¿QLVKWKHGLVFKDUJHSURFHVV
6. Turn on each parallel UPS’s Manual Bypass breaker. The connected loads will
be power-supplied by the manual bypass and each LCD will display ‘Manual
Bypass ON’.
7XUQRႇHDFKSDUDOOHO836¶VUPS Output breaker and Reserve Input breaker.
8. Disconnect all fuses. After that, each LCD will be OFF.
64
9. When each UPS is running in Manual Bypass Mode, there is no high voltage
inside any UPS except the wiring terminals and Manual Bypass breaker. Do
not touch any UPS’s wiring terminals and Manual Bypass breaker during UPS
maintenance process to avoid electric shock.
UPS
1st 2nd 3rd 4th 5th 6th 7th 8th
(At Max. 8 Units)
Parallel ID No. 12 23 34 45 56 67 78 81
6. Turn on each UPS’s 5HFWL¿HU,QSXW breaker and wait about 30 seconds. After
that, each unit’s DC BUS voltage will be established.
7. Turn on each external battery cabinet’s Battery breaker.
8. Press one of the parallel UPSs’ ‘ON’ and ‘ ’ buttons simultaneously for 3
seconds, and its inverter will start up. Once the inverter voltage is established,
the LCD will display ‘Bypass Mode’.
9. Repeat the above-mentioned Step 8 to the rest of the parallel UPSs. After the
last parallel UPS’s inverter voltage is established, each parallel UPS’s contactor
will activate and each LCD will display ‘Normal Mode’.
10. Now, the total loads will be equally shared by the parallel UPSs.
Ultron NT Series 65
Chapter 7 UPS Operation
7XUQRႇ3URFHGXUHV
1. Press the ‘EPO’ button. After that, the LCD will display ‘Inhibit Output’.
7XUQRႇHDFKH[WHUQDOEDWWHU\FDELQHW¶VBattery breaker.
66
7XUQRႇWKHUPS Output breaker.
7XUQRႇWKH5HFWL¿HU,QSXW breaker and Reserve Input breaker.
WARNING:
In battery mode, even if you follow the above-mentioned turn-off
SURFHGXUHV WR WXUQ Rႇ WKH 836 WKHUH LV VWLOO YROWDJH H[LVWLQJ LQVLGH WKH
UPS. Do not touch the UPS to avoid eclectic shock.
In manual bypass mode, the LCD is in the OFF status. To completely shut down the
836WXUQRႇWKHManual Bypass breaker.
1. Press one of the parallel UPSs’ ‘OFF’ and ‘ ’ buttons simultaneously for 3
seconds. If the total connected loads are less than the total capacity of the rest
RIWKHSDUDOOHO836VWKH836WKDW\RXMXVWWXUQHGRႇZLOOVKXWGRZQDQGLWV/&'
will display ‘Inhibit Output’. Now, the total loads will be equally shared by the
rest of the parallel UPSs.
If the total loads are greater than the total capacity of the rest of the parallel
836VHDFK836¶VLQYHUWHUZLOOEHWXUQHGRႇLPPHGLDWHO\DIWHUWKHUHVHUYH$&
power is normal (the voltage and frequency of the reserve AC power is within the
setup range). After that, it will be the reserve AC power to supply power to the
connected loads and each UPS’s LCD will display ‘Bypass Mode’.
Ultron NT Series 67
Chapter 7 UPS Operation
2. Repeat the above-mentioned Step 1 to the rest of the parallel UPSs in order to
let all parallel UPSs run in ‘Bypass Mode’.
7XUQRႇHDFKH[WHUQDOEDWWHU\FDELQHW¶VBattery breaker.
7XUQRႇHDFKSDUDOOHO836¶V5HFWL¿HU,QSXW breaker.
5. (1) Wait about 5 minutes for each DC CAP to discharge, and ensure that each
LCD shows the battery voltage lower than 5V.
Or, (2) Press each UPS’s ‘ON’ and ‘OFF’ buttons simultaneously for 3 seconds
to let its DC CAP to discharge, and ensure that each LCD shows the battery
voltage lower than 5V. After confirmation, press each UPS’s ‘OFF’ and ‘ ’
EXWWRQVVLPXOWDQHRXVO\IRUVHFRQGVWR¿QLVKWKHGLVFKDUJHSURFHVV
7XUQRႇHDFKXQLW¶VUPS Output breaker and Reserve Input breaker.
1. Press each parallel UPS’s ‘EPO’ button. After that, each LCD will display ‘Inhibit
Output’.
7XUQRႇHDFKH[WHUQDOEDWWHU\FDELQHW¶VBattery breaker.
7XUQRႇHDFKXQLW¶VUPS Output breaker.
7XUQRႇHDFKXQLW¶V5HFWL¿HU,QSXW breaker and Reserve Input breaker.
WARNING:
In battery mode, even if you follow the above-mentioned turn-off
procedures to turn off each parallel UPS, there is still voltage existing
inside every UPS. Do not touch any UPS to avoid eclectic shock.
68
0DQXDO%\SDVV0RGH7XUQRႇ3URFHGXUHV 3DUDOOHO
WARNING:
If you perform the following turn-off procedures to each parallel UPS, all
power supplying to the UPS will be completely cut off. Please make sure
the critical loads connected to the UPS have already been safely shut down
EHIRUH\RXSHUIRUPWKHWXUQRႇSURFHGXUHV
In manual bypass mode, each parallel UPS’s LCD is in the OFF status. To
completely shut down every parallel UPS, turn off each unit’s Manual Bypass
breaker.
Ultron NT Series 69
Chapter 8 Optional Accessories
70
$SSHQGL[7HFKQLFDO6SHFL¿FDWLRQV
Voltage Regulation:
Static % ±1
Output Dynamic % ±5
Nominal Frequency Hz 60
Frequency Regulation:
Ultron NT Series 71
Appendix 1 7HFKQLFDO6SHFL¿FDWLRQV
Programmable Parameter
Yes
Setting
2YHUDOO(ႈFLHQF\
Normal Mode % 86 87 89 90
30 minutes % 120
30 milliseconds % 1000
Transfer Time ms 0
Audible Noise
dBA 60 65
(at a distance of 1.5m)
Dimensions:
NOTE :
1. Please refer to the rating label for the safety rating.
$OOVSHFL¿FDWLRQVDUHVXEMHFWWRFKDQJHZLWKRXWSULRUQRWLFH
72
Appendix 2 : Warranty
Seller warrants this product, if used in accordance with all applicable instructions,
to be free from original defects in material and workmanship within the warranty
period. If the product has any failure problem within the warranty period, Seller will
repair or replace the product at its sole discretion according to the failure situation.
This warranty does not apply to normal wear or to damage resulting from improper
installation, operation, usage, maintenance or irresistible force (i.e. war, fire,
natural disaster, etc.), and this warranty also expressly excludes all incidental and
consequential damages.
Maintenance service for a fee is provided for any damage out of the warranty
period. If any maintenance is required, please directly contact the supplier or Seller.
WARNING!
The individual user should take care to determine prior to use whether the
environment and the load characteristic are suitable, adequate or safe for
the installation and the usage of this product. The User Manual must be
carefully followed. Seller makes no representation or warranty as to the
VXLWDELOLW\RU¿WQHVVRIWKLVSURGXFWIRUDQ\VSHFL¿FDSSOLFDWLRQ
No. 501326650000
Version : V 0.0
Release Date : 2018_10_02
Ultron NT Series 73