Axpert KS RS232 communication Protocol
1
Axpert KS RS232 Communication Protocol
2
Axpert KS RS232 Communication Protocol
4 Appendix ............................................................................................................................................... 19
4.1 CRC calibration method ........................................................................................................................... 19
3
Axpert KS RS232 Communication Protocol
1 Communication format
Baud rate Start bit Data bit Parity bit Stop bit
2400 1 8 N 1
2 Inquiry Command
1
Axpert KS RS232 Communication Protocol
2
Axpert KS RS232 Communication Protocol
0: AGM
O O Battery type 1: Flooded
2: User
Current max AC charging P is an Integer ranging from 0 to 9
P PP
current The units is A.
Q is an Integer ranging from 0 to 9.
Q QQ0 Current max charging current
The units is A.
0: Appliance
O O Input voltage range
1: UPS
0: Utility first
P P Output source priority 1: Solar first
2: SBU first
For KS Series:
0: Utility first
1: Solar first
2: Solar + Utility
3: Only solar charging permitted
Q Q Charger source priority
For MKS Series 1K~3K:
0: Utility first
1: Solar first
2: Solar + Utility
3: Only solar charging permitted
R R Parallel max num R is an Integer ranging from 0 to 9.
00: Grid tie;
S SS Machine type 01: Off Grid;
10: Hybrid.
0 transformerless
T T Topology
1 transformer
00: single machine output
01: parallel output
U U Output mode 02: Phase 1 of 3 Phase output
03: Phase 2 of 3 Phase output
04: Phase 3 of 3 Phase output
V is an Integer ranging from 0 to 9.
V VV.V Battery re-discharge voltage
The units is V.
0: As long as one unit of inverters
has connect PV, parallel system will
consider PV OK;
W W PV OK condition for parallel
1: Only All of inverters have connect
PV, parallel system will consider PV
OK
X X PV power balance 0: PV input max current will be the
3
Axpert KS RS232 Communication Protocol
4
Axpert KS RS232 Communication Protocol
5
Axpert KS RS232 Communication Protocol
Example:
Computer: QMOD<CRC><cr>
DEVICE: (L<CRC><cr>
Means: the current DEVICE mode is Grid mode.
6
Axpert KS RS232 Communication Protocol
otherwise warning
Compile with a1, if a1=1,fault,
a10 Fan locked
otherwise warning
Compile with a1, if a1=1,fault,
a11 Battery voltage high
otherwise warning
a12 Battery low alarm Warning
a13 Reserved
a14 Battery under shutdown Warning
a15 Reserved Warning
Compile with a1, if a1=1,fault,
a16 Over load
otherwise warning
a17 Eeprom fault Warning
a18 Inverter Over Current Fault
a19 Inverter Soft Fail Fault
a20 Self Test Fail Fault
a21 OP DC Voltage Over Fault
a22 Bat Open Fault
a23 Current Sensor Fail Fault
a24 Battery Short Fault
a25 Power limit Warning
a26 PV voltage high Warning
a27 MPPT overload fault Warning
a28 MPPT overload warning Warning
a29 Battery too low to charge Warning
a30 Reserved
a31 Reserved
7
Axpert KS RS232 Communication Protocol
KS-1000
20A
MKS-1000-24
KS-2000
KS-3000
KS-4000
KS-5000
D is an Integer 30A
Max AC charging MKS-2000-24
D 00DD ranging from 0 to 9.
current MKS-3000-24
The unit is A.
MKS-2000-24 Plus
MKS-3000-24 Plus
MKS-1000-48
MKS-2000-48
MKS-3000-48 15A
MKS-2000-48 Plus
MKS-3000-48 Plus
E is an Integer
E EE.E Battery Under voltage ranging from 0 to 9.
The unit is V.
F is an Integer
Charging float
F FF.F ranging from 0 to 9.
voltage
The unit is V.
G is an Integer
G GG.G Charging bulk voltage ranging from 0 to 9.
The unit is V.
H is an Integer
Battery default
H HH.H ranging from 0 to 9. 11.5/23/46 for 12/24/48V unit.
re-charge voltage
The units is V.
KS Series 50A
MKS-1000-24
MKS-2000-24
25A
MKS-3000-24
(not
I is an Integer ranging MKS-1000-48
show)
I II Max charging current from 0 to 9. The units MKS-2000-48
is A. MKS-3000-48
MKS-4000
MKS-5000
MKS-2000-48 60A
MKS-3000-48
MKS-2000-48 Plus
8
Axpert KS RS232 Communication Protocol
MKS-3000-48 Plus
AC input voltage J is an Integer ranging
J J Default 0 for appliance range
range from 0 to 1. No unit
K is an Integer
K K Output source priority ranging from 0 to 1. No Default 0 for utility first
unit
L is an Integer
Charger source
L L ranging from 0 to 1. No Default 0 for Utility first
priority
unit
M is an Integer
M M Battery type ranging from 0 to 1. No Default 0 for AGM
unit
N is an Integer
Enable/disable silence
N N ranging from 0 to 1. No Default 0 for enable buzzer
buzzer or open buzzer
unit
O is an Integer Default 0 for disable power
Enable/Disable power
O O ranging from 0 to 1. No saving
saving
unit
P is an Integer Default 0 for disable overload
Enable/Disable
P P ranging from 0 to 1. No restart
overload restart
unit
Enable/Disable over Q is an Integer Default 0 for disable over
Q Q temperature restart ranging from 0 to 1. No temperature restart
unit
Enable/Disable LCD R is an Integer Default 1 for enable LCD
R R backlight on ranging from 0 to 1. No backlight on
unit
Enable/Disable alarm S is an Integer Default 1 for enable alarm on
S S on when primary ranging from 0 to 1. No when primary source interrupt
source interrupt unit
Enable/Disable fault T is an Integer
Default 0 for disable fault code
T T code record ranging from 0 to 1. No
record
unit
U is an Integer
Default 0 for disable overload
U U Overload bypass ranging from 0 to 1. No
bypass function
unit
Enable/Disable LCD
V is an Integer
display escape to Default 1 for LCD display
V V ranging from 0 to 1. No
default page after 1min escape to default page
unit
timeout
Output mode W is an Integer
W W Default 0 for single output
ranging from 0 to 4. No
9
Axpert KS RS232 Communication Protocol
unit
2.12 QMUCHGCR<cr>: Enquiry selectable value about max utility charging current
Computer: QMUCHGCR<CRC><cr>
Device: (AAA BBB CCC DDD……<CRC><cr>
More value can be added, make sure there is a space character between every value.
Parallel Command
10
Axpert KS RS232 Communication Protocol
11
Axpert KS RS232 Communication Protocol
0: single machine
1: parallel output
V T Output mode 2: Phase 1 of 3 phase output
3: Phase 2 of 3 phase output
4: Phase 3 of 3 phase output
0: Utility first
1: Solar first
W U Charger source priority
2: Solar + Utility
3: Solar only
V is an Integer ranging from 0 to
X VVV Max charger current
9. The units is A.
W is an Integer ranging from 0 to
Y WWW Max charger range
9. The units is A.
Z is an Integer ranging from 0 to
Z ZZ Max AC charger current
9. The units is A.
PV input current for X is an Integer ranging from 0 to
a XX
battery 9. The units is A.
Y is an Integer ranging from 0 to
b YYY Battery discharge current
9. The units is A.
12
Axpert KS RS232 Communication Protocol
54 Self-test failed
13
Axpert KS RS232 Communication Protocol
14
Axpert KS RS232 Communication Protocol
MKS-3000-48 Plus
KS-1000
20A
MKS-1000-24
KS-2000
KS-3000
KS-4000
KS-5000
30A
MKS-2000-24
Max utility charging current
MKS-3000-24
MKS-2000-24 Plus
MKS-3000-24 Plus
MKS-1000-48
MKS-2000-48
MKS-3000-48 15A
MKS-2000-48 Plus
MKS-3000-48 Plus
4 AC input voltage range 0: Appliance range
5 Output source priority 0: Utility first
Battery re-charge voltage 11.5/23/46 for 12/24/48V unit.
6 Charger source priority 0: Utility first
7 Battery type 0: AGM
8 Enable/disable buzzer alarm 1: Enable buzzer alarm
9 Enable/Disable power saving 0: Disable power saving
10 Enable/Disable overload restart 0: Disable overload restart
11 Enable/Disable over temperature restart 0: Disable over temperature restart
12 Enable/Disable LCD backlight on 1: Enable LCD backlight on
13 Enable/Disable alarm on when primary 1: Enable beep on when primary source
source interrupt interrupt
Enable/Disable overload bypass when 0: Disable overload bypass
overload happened in battery mode
Enable/Disable LCD display escape to 1: Enable LCD display escape to default
default page after 1min timeout page
Output mode 0: single output(for 4K/5K)
float charging voltage 13.5/27/54 for 12/24/48V unit.
Bulk charging voltage 14.1/28.2/56.4 for 12/24/48V unit.
Battery cut-off voltage 10.5/21/42 for 12/24/48V unit.
Battery re-discharge voltage 13.5/27/54 for 12/24/48V unit.
Note: The correct default value can be gain by QDI command.
15
Axpert KS RS232 Communication Protocol
Computer: PBDV<nn.n><CRC><cr>
Device: (ACK<CRC><cr> if device accepts this command, otherwise, responds (NAK<CRC><cr>
12V unit: 00.0V12V/12.3V/12.5V/12.8V/13V/13.3V/13.5V/13.8V/14V/14.3V/14.5
24V unit: 00.0V/24V/24.5V/25V/25.5V/26V/26.5V/27V/27.5V/28V/28.5V/29V
48V unit: 00.0V48V/49V/50V/51V/52V/53V/54V/55V/56V/57V/58V
16
Axpert KS RS232 Communication Protocol
Parallel Command
3.19 MNCHGC<mnnn><cr>: Setting max charging current (More than 100A) (For 4000/5000)
Computer: MNCHGC<mnnn><CRC><cr>
Device: (ACK<CRC><cr> if device accepts this command, otherwise, responds (NAK<CRC><cr>
18
Axpert KS RS232 Communication Protocol
4 Appendix
CRC.c