Created On:11-Sep-2025 12:45 PM Page 1 of 2

Cable Size
Report
Project name: EHV
Calculation name: Cable Size

Cable: Single core / Thermosetting (XLPE or EPR) (90 °C) / Aluminium

Installation: D2 Sheathed cables direct in the ground

✓ Complies with IEC 60364-5-52

Load: 650 A Power factor: 0.9

Supply: 3 phase 1000 V Fault level: 25 kA

Length of run: 10000 m

Cable Size Results Current-carrying Capacity: PASS


Active cable: 65 x 300 mm², 1C Current rating of circuit-derated: 16952 A
Neutral cable: 65 x 300 mm², 1C Spare current-carrying capacity of circuit: 16302 A
Earth cable (copper): 1 x 630 mm², 1C Overall derating factor: 0.8
Dictating factor for active size: Voltage drop Conductor operating temperature: 20.1 °C

Fault Loop Impedance: PASS Voltage Drop:PASS


Total loop, Zs: 1.1187 Ω Voltage drop: 24.75 V
Source, Zext: 0.2237 Ω Voltage drop: 2.47 %
Cables, Zint: 0.8949 Ω Permissible voltage drop: 2.5 %
Maximum allowed, Zdevice: - Maximum length of run: 10101.27 m
Touch voltage: 452.16 V

Short-circuit Performance: PASS Conduit Size: N/A


Three-phase short-circuit current: 13939.9 A Space occupied by cables/recommended: -
Min. active size to withstand short-circuit: 36.75 mm² Cable diameter: -
Software Licensed to ELEK

Phase-to-earth short-circuit current: 516.1 A Cables per conduit: -


Min. earth size to withstand short-circuit: 0.9 mm²

Protective Device: Unknown


Rating: - Duration of Short-circuit: 0.1 s
Thermal setting: - Earth fault time: -
Trip current: - RCD: -

Cable Pro Web © 2025 ELEK Software


Version 9.5.2.0 www.elek.com
Created On:11-Sep-2025 12:45 PM Page 2 of 2

References - Cable sizing


Standards: IEC Standard 60364-5-52

Tabulated current rating of cable: 326 A


Table name: B.52.5
Column No. 8

Conductor impedances used in voltage drop calculations

W
Resistance Reactance
Phase conductor: 0.12 Ω/km Phase conductor: 0.08 Ω/km

IE
EV

N
O
TI
IP
SE

R
PR

C
U

BS
L

SU
IA
C

R
ER

U
EE

YO
M
M

E
AD
O
C
FR

R
PG
R
FO

U
R
T

O
O

E
N

AS
Software Licensed to ELEK

H
C
R
PU
SE
EA
PL

Cable Pro Web © 2025 ELEK Software


Version 9.5.2.0 www.elek.com

You might also like