SG4400UD-MV-US

MV Grid-connected PV Inverter for 1500Vdc System

HIGH YIELD EASY O&M


Advanced three-level technology Integrated current, voltage and MV parameters monitoring
Full power operation at 40 ℃ (104 ℉) function for online analysis and trouble shooting
Effective cooling, wide operation temperature Modular design, easy for maintenance

SAVED INVESTMENT GRID SUPPORT


Low transportation and installation cost due Compliance with standards:UL 1741,UL 1741 SA/SB, IEEE
to 20-foot container size design 1547, Rule 21 and NEC code
DC 1500V system, low system cost Low / High voltage ride through (L/HVRT),L/HFRT,soft
Q at night start / stop
Active & reactive power control and power ramp rate
control

CIRCUIT DIAGRAM EFFICIENCY CURVE

100%
98%
96%
94% Vdc=875V

92% Vdc=1100V
90% Vdc=1300V
88%
0% 20% 40% 60% 80% 100%
Type designation SG4400UD-MV-US
Input (DC)
Max. PV input voltage 1500 V
Min. PV input voltage / Start-up input voltage 915 V / 955 V
Available DC fuse sizes 250 A – 630 A
MPP voltage range 915 V – 1500 V
Full power MPP voltage range @ 40 ℃ 1)
915 V – 1337 V
No. of independent MPP inputs 4
28 inputs negative grounding
No. of DC inputs
( optional: 24 inputs floating )
Max. PV input current 4 * 1226 A
Max. DC short-circuit current 4 * 3528 A
PV array configuration Negative grounding or floating
Output (AC)
AC output power 4400 kVA @ 40 ℃ ( 104 ℉ ) (Optional: 4400 kVA @ 45 ℃( 113 ℉ ) )
Max. AC output current 73 A
Nominal grid frequency / Grid f requency range 60 Hz / 57 Hz – 63 Hz
THD < 3 % ( at nominal power )
Power factor at nominal power / Ajustable power factor > 0.99 / 0.8 leading – 0.8 lagging
Nominal AC voltage 34.5 kV
Efficiency
Max. inverter unit efficiency 98.9 %
CEC inverter unit efficiency 98.5 %
Max. efficiency ( including transformer ) 98.2 %
CEC efficiency ( including transformer ) 97.5 %
Protection
DC protection DC load switch + fuse
AC protection MV load switch + fuse
Surge protection DC Type II / AC Type II
Grid monitoring / Ground fault monitoring Yes / Yes
Insulation monitoring Yes
Overheat protection Yes
General data
6058 mm * 2896 mm * 2438 mm
Dimensions ( W * H * D )
238.5'' * 114.0'' * 96.0''
Weight ≤ 36376 lbs
Transformer vector Dy1 ( Optional: Dy11, Yny0, YNd1)
Degree of protection NEMA 4X ( Electronic enclosure ) / NEMA 3R ( Others )
Auxiliary power supply 5 kVA, 120 Vac ; Optional : 35 kVA 480 Vac + 5 kVA 120 Vac
-35 ℃ – 60 ℃ / optional: -40 ℃ – 60 ℃
Operating ambient temperature range 2)

-31 ℉ – 140 ℉ / optional: -40 ℉ – 140 ℉


Allowable relative humidity range 0 % - 100 %
Cooling method Forced air cooling + KNAN ( Optional: ONAN )
1000 m ( Standard ) / > 1000 m ( Customized )
Max. Operating altitude
( 3280.8 ft ( Standard ) / > 3280.8 ft ( Customized ) )
Display LED Indicators , Ethernet + WebHMI
Night reactive power function Yes
DC-Coupled storage interface Optional
Charging power f rom the grid Optional
Communication Standard: RS485, Ethernet
UL1741, UL62109-1, CSA C22.2 No.107.1-16, IEEE1547-2018, IEEE1547.1-2020, UL1741
Compliance
SA/SB, California Rule21, HECO SRD V2.0, NEC 2023,PRC-024
1) Full power MPP range is temperature dependent, check the characteristic curve of the inverter for more information.
2) The ambient temperature is determined as the average temperature obtained f rom at least four evenly distributed temperature
monitoring points located at a distance of 1 meter from the equipment, at a height halfway up the machine. The temperature sensors must
be shielded from airflow, thermal radiation, and rapid temperature fluctuations to prevent display inaccuracies.

V.28 NA