0% found this document useful (0 votes)
14 views14 pages

Bank Meters U&d

This document describes a project to install a three-phase meter bank of 380-220V for the users of the Unión and Dignidad Market in Puno, Peru. The project aims to improve electrical service and safety in the market. Technical details such as voltage, frequency, power factor, and overhead distribution system are described. It also includes calculations of installed power, demand, and voltage drop, as well as specifications for the accessories.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views14 pages

Bank Meters U&d

This document describes a project to install a three-phase meter bank of 380-220V for the users of the Unión and Dignidad Market in Puno, Peru. The project aims to improve electrical service and safety in the market. Technical details such as voltage, frequency, power factor, and overhead distribution system are described. It also includes calculations of installed power, demand, and voltage drop, as well as specifications for the accessories.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

UNION AND DIGNITY MARKET

METER BANK INSTALLATION PROJECT

INSTALLATION PROJECT OF:

THREE-PHASE METERING BOARD IN 380–220 V


FOR USERS OF THE UNION AND DIGNITY MARKET
A LOT–A LOT–A LOT

MEASURING BANK

OWNERS : USERS - UNION MARKET AND


DIGNITY
ADDRESS UNION AND DIGNITY MARKET
DISTRICT ADDITION
PROVINCE THE GATHERING
REGION Puno
UNION AND DIGNITY MARKET
INSTALLATION PROJECT OF METER BANK

INSTALLATION PROJECT OF:

THREE-PHASE METERING BANK AT 380–220


FOR USERS OF THE UNION MARKET AND
DIGNITY PUNO–PUNO–PUNO

INDEX:
I. DESCRIPTIVE MEMORY Page 03

II. PLANS AND DETAILS Page 10

III. PHOTOGRAPHIC PANEL Page 19

IV. ANNEXES Page 22


UNION AND DIGNITY MARKET
PROJECT FOR INSTALLATION OF METER BANK

INSTALLATION PROJECT OF: “BANK


THREE-PHASE METERS IN 380–220 V
FOR USERS OF THE UNION MARKET AND
DIGNITY–PUNO–PUNO–PUNO
I. DESCRIPTIVE MEMORY

1.1. INTRODUCTION

This technical file profile encompasses the work Installation of:


THREE-PHASE METERING BANK AT 380–220 V FOR USERS OF
UNION AND DIGNITY MARKET - PUNO - PUNO - PUNO, which are users of
the sales stalls of the Union and Dignity Market, the same that has been
developed taking into account the criteria and Distribution Standards of
Low voltage aerial system.

ZONE Typical Sector II.


SYSTEM Aerial.
TYPE Urban.

1.2. OBJECTIVE

Access to electricity service in a comprehensive manner with a three-phase feeder


for the Meter Bank of the 'Union and Dignity Market', with meters
single-phase their respective Thermal Magnetic.

When evaluating the area under study, it has been determined that to achieve social development
it is necessary to provide an electricity service in a comprehensive manner
reliable to the meter bank.

Improvement in the quality of electric service, improvement of productive performance in the


Union and Dignity Market and improve the safety of electrical risks.

The main objective of this technical file profile is to provide the


electric service to the sales positions and have the meter bank installed
in safe conditions.

1.3. GENERALITIES

The purpose of this file is the design and calculation of the measuring bank.
that will be located on the premises of the multifamily housing, such facilities will
they are carried out for the measurement of electrical energy in the different departments.
UNION AND DIGNITY MARKET
PROJECT FOR INSTALLATION OF METERING BANK

1.4. PROJECT DESCRIPTION

SECONDARY NETWORK

Nominal Tension 380–220 V.


Frequency 60 Hz.
Power Factor 0.9
System Three-phase (3ф).
Distribution System Aerial.
Structures Meter Bank.

1.5. ELECTRICAL DESIGN CRITERIA

1.5.1.GENERAL CONCEPTS

ELECTRICAL MEASUREMENT UNITS

VOLTAGE: It is the energy required to put electrons in motion.

Symbol V.
Unit Volt (V).
Measuring instrument Voltmeter.

INTENSITY: It is the amount of electrons that flow per second in a


electrical circuit.

Symbol I.
Unit Ampere (A).
Measuring instrument Ammeter.

ACTIVE POWER: Work done by electrons in an electrical circuit.


Symbol P.
Unity Watt (W).
Measuring instrument Wattmeter
Formula P = V * I * cos(φ).

ENERGY It is the ability to perform a task.

Symbol kW-h.
Unit kilowatt-hour (kW-h).
Measuring instrument Meter or Counter.
Formula E=P*T

1.5.2. CALCULATION OF INSTALLED POWER

The Power or Installed Load is the total power obtained by adding the powers.
of each of the receivers.

1.5.3. CALCULATION OF DEMAND

It is the average power at the receiving terminals over a period of time.


By definition, the demand factor is equal to:
UNION AND DIGNITY MARKET
MEASUREMENT BANK INSTALLATION PROJECT

fd = Demand
Installed Capacity
So the Demand is:

Demand = fd * Installed Load

1.5.4.VOLTAGE DROP

The maximum voltage drop between the distribution substation and the endpoint.
the farthest terminal from the network should not exceed 5% of the nominal voltage, it is
to say

Networks 380 / 220 V 19 V.

1.5.5.POWER FACTOR (cosφ)

For private service loads 1.00

1.5.6.GROUND RESISTANCE

The value of the grounding resistance of the neutral conductor at the highest points
unfavorable, while the entire PAT system is connected, it should not exceed the
following values:

Single-phase system 380 / 220 V. 10 ohm.

The grounding should basically consist of a buried copper electrode.


(PAT-1), according to the details shown in the typical assemblies and in the design plans.

1.6. CHARACTERISTICS OF THE EQUIPMENT

1.6.1. SUPPLY OF ACCESSORIES FOR CONNECTIONS AND SERVICE LINES

CONDUCTOR FOR DOMESTIC CONNECTIONS

It will be of electrolytic Cu, soft temper, concentric SET type, 4x6 mm2
(Urban) from section, for three-phase household connections; with
isolation of Polyvinyl Chloride PVC, weather-resistant and to
aging, for voltages of 0.6/1.0 kV, each of the phases and
protected with a common exterior insulation of resistant black polyethylene
to the elements and aging. The manufacturing standards to be considered in
The account will be ASTM-B3 and the 1PCEA for its insulation.

Test protocol

The manufacturer must provide the buyer and supervisor with the protocol of
Tests of the cable based on the manufacturing test in which I certify
the minimum required conditions of the product. They will be developed with
sample of cable of two lengths and of 3% of the length of cable purchased.

ARMELLA TIRAFÓN

It will be made of hot-dip galvanized iron according to ASTM A 153-82 standard.


which will be 0.63 cm in diameter x 10.16 cm in length The load
The minimum work will be 2 kN.
UNION AND DIGNITY MARKET
METER BANK INSTALLATION PROJECT

TEMPLAR

It will be made of SAE-1020 steel, hot-dip galvanized according to standards.


ASTM A 153-82. The minimum working load will be 2 kN. It will be 1.6 mm of
hot-dip galvanized thickness with a thickness of 80 micrometers in such a way
that allows for the proper securing of the concentric conductor.

Service Pipe

They will be F°G° of 25.4 mm in diameter x 1.50 m in length with a elbow.


of 90°.

CONNECT BIMETALLIC AL/CU, AL 35MM2/CU 4-10 MM2

They will be made of corrosion-resistant aluminum alloy, of the aerial carrier type.
encapsulated fuse. Pre-assembled and high anti-fraud connection
inviolability.

Upper and lower body made of thermosetting plastic material, constructed in


polyamide with fiberglass and flame retardant, highly resistant to weather conditions
especially ultraviolet radiation. The fitted and airtight
coupling keeps the Neozed type fuse isolated from the elements
climatic, guaranteeing that its main characteristics remain unchanged (Curve of
fusion, breaking capacity, etc.

It must have a stainless steel spring, which ensures the pressure.


contact necessary during the lifespan of the fuse holder.
It has a soldered copper bottom contact; for the use of fuses.
from 10 to 60 A.

DERIVED CONDUCTOR
CONFIGURATION
SECTION DIAMETER WITH COVER
MATERIAL
mm² mm
2.5 to 3.5
Al - Cu 1.5 - 6 Copper
(1.4 to 2.8)

It will have the following terms of use:

Service voltage of the network 380/220 V.


Nominal Intensity 63 Amp.
Frequency 60 Hz.
Degree of mechanical protection IP 33.

BANK OF METAL BOX METERS

They will be of type 'L' measuring 1.35 x 0.90 x 0.17m for embedding, which will be
expected of a sliding grid facilitating the visualization of the meter
when required, bolts made of SAE-1020 steel, galvanized
hot according to ASTM A 153-82; with a diameter of 0.95 cm and a length of 1.9 cm
to the outside, which will feature a transverse hole of 3.2mm in diameter
for the installation of fastening keys and/or security seals; for
fix the meter, secured with 0.8 mm iron plate.
UNION AND DIGNITY MARKET
INSTALLATION PROJECT OF METER BANK

They will be made of cold-rolled iron sheet of 0.8 mm.


thickness, the body; and 1.6 mm thick the lid and frame, surface
properly prepared free of impurities by any process that
guarantee its cleanliness such as sandblasting, stripping, sulfating and
phosphated.

Protection with 2 layers of anticorrosive paint and finished with paint


gray enamel, externally and internally in its entirety, with oven drying.

Energy Meter

They will be single-phase for domestic household connections.


The single-phase meters will have the following characteristics:

Type Electronic.
Precision class 1.
Overload Factor 4 (to 8)
Frequency 60 Hz.
Nominal Voltage 220 V.
Nominal Current 10 A.
Units of Measure kW-h.
Number of threads 2.
The Meter Box must have on the Plate:
Serial number in low relief
Precision Class.
Year of Manufacture
Brand
Maximum Precision Intensity 5(60) A.

For built-in installation, it will be of the best quality and first use.

WALL ANCHOR

They will be made of hot-dip galvanized steel designed to be attached to the


pared

1.6.2. TECHNICAL SPECIFICATIONS FOR GROUNDING

It is made up of the following materials:

16mm diameter copper rod, 2400mm in length

Which will be 16 mm in diameter and 2400 mm in length.

The grounding pit will typically be standardized, composed of black earth.


free of stones and compacted.

TYPE AB CONNECTOR FOR COPPER GROUNDING ROD

It will be for a 16 mm diameter electrode and a 25 mm2 copper conductor and will serve.
to connect the copper grounding rod with the Cu conductor.

25 mm2 copper conductor, for grounding

Which will be wired (insulated and/or bare) of 25 mm2 will have a


minimum conductivity of 99.66% I.A.C.S. at 20 °C, the same that
corresponds to ASTM B 399. The conductor will pass the tests
UNION AND DIGNITY MARKET
PROJECT FOR THE INSTALLATION OF METER BANK

mechanical and electrical of the ASTM B 56 Standard.


TABLE OF TECHNICAL DATA
THICKNESS DIAMETER RESISTANCE CAPACITY OF
CALIBER NUMBER OF DIAMETER WEIGHT
OUTER COVER Traction ELECTRIC CURRENT
mm² THREADSmm kg/km
mm mm kN ohm/km A
25 7 2.14 1.20 8.8 261 9.95 0.741 196

BIMETALLIC CONNECTOR, AL 25 MM2/ CU 25 MM2, INSULATED NEUTRAL, TYPE


DRILLING AND COVERING

It will be Al 25 mm2 / Cu 25 mm2 for insulated neutral, type perforation more


cover, insulator. The connector is a corrosion-proof bimetallic Al/Cu
for the connection of the grounding conductor to the neutral (messenger).

Its tensile strength must be greater than 31 kg/mm2 (300 N/mm2).


Connection teeth: Strut profile made of aluminum alloy 6061-T6 and must
to use special galvanized steel bolts (bulones) by immersion in
hot, with a tensile strength of 8 kg/mm2.

CONCRETE BOX WITH COVER FOR EARTHING ELECTRODE


EARTH

It will be 450 x 450 x 250 mm in depth dimension.

Bentonite

Bentonite will be used in the preparation of a grounded well lined with a


cover and must comply with the Peruvian Technical Standard 334.009

The sampling conditions will be those specified by the Technical Standard.


Peruvian 334,007.

BLACK EARTH

The black earth will be cultivated for your ground well preparation, free of
sneaky and compacted.

SYNTHETIC ENAMEL PAINT FOR SIGNAGE PAINTING

The paints will be synthetic enamel in white, black, and yellow.


Caterpillar.

1.7. INSPECTION AND TESTING OF PINIONS.

ELECTRO PUNO S.A.A. through the representatives in charge of verifying the work at the bank of
meters in coordination with the contractor conducts the Inspection and Tests
Final steps leading to its operation.

1.8. PLANS AND DETAILS

The plans corresponding to the design of the Private Service Networks and
derivation of the household connections are:
UNION AND DIGNITY MARKET
METER BANK INSTALLATION PROJECT

DESCRIPTION PLAN
THREE-PHASE METER BANK AT 380–220 V FOR USERS OF
UNION AND DIGNITY MARKET - PUNO - PUNO - PUNO BM - 01
It includes location plans, legends, and diagrams, as well as the list of
The detail sheets are as follows:

SUMMARY OF ASSEMBLIES

ITEM DETAIL SHEET


1PROJECT LOCATION PLAN L-01
DETAIL OF THREE-PHASE COMMITMENT L-02
3 DETAIL OF EXTERIOR FRONT VIEW OF THE L-03
METER BANK
4DETAIL OF FRONT VIEW INSIDE THE METER L-04
BANK
5 DETAIL OF METER BANK L-05
6 SINGLE LINE DIAGRAM L-06
7GROUNDING DETAIL L-07
UNION AND DIGNITY MARKET
METER BANK INSTALLATION PROJECT

PLANS AND DETAILS


UNION AND DIGNITY MARKET
PROJECT FOR THE INSTALLATION OF A METER BANK
UNION AND DIGNITY MARKET
INSTALLATION PROJECT OF METER BANK

PHOTOGRAPHIC PANEL
UNION AND DIGNITY MARKET
METER BANK INSTALLATION PROJECT

ANNEXES
UNION AND DIGNITY MARKET
INSTALLATION PROJECT OF METER BANK

MEASUREMENT FOR THE INSTALLATIONS


ELECTRICS

You might also like