Bank Meters U&d
Bank Meters U&d
MEASURING BANK
INDEX:
I. DESCRIPTIVE MEMORY Page 03
1.1. INTRODUCTION
1.2. OBJECTIVE
When evaluating the area under study, it has been determined that to achieve social development
it is necessary to provide an electricity service in a comprehensive manner
reliable to the meter bank.
1.3. GENERALITIES
The purpose of this file is the design and calculation of the measuring bank.
that will be located on the premises of the multifamily housing, such facilities will
they are carried out for the measurement of electrical energy in the different departments.
UNION AND DIGNITY MARKET
PROJECT FOR INSTALLATION OF METERING BANK
SECONDARY NETWORK
1.5.1.GENERAL CONCEPTS
Symbol V.
Unit Volt (V).
Measuring instrument Voltmeter.
Symbol I.
Unit Ampere (A).
Measuring instrument Ammeter.
Symbol kW-h.
Unit kilowatt-hour (kW-h).
Measuring instrument Meter or Counter.
Formula E=P*T
The Power or Installed Load is the total power obtained by adding the powers.
of each of the receivers.
fd = Demand
Installed Capacity
So the Demand is:
1.5.4.VOLTAGE DROP
The maximum voltage drop between the distribution substation and the endpoint.
the farthest terminal from the network should not exceed 5% of the nominal voltage, it is
to say
1.5.6.GROUND RESISTANCE
The value of the grounding resistance of the neutral conductor at the highest points
unfavorable, while the entire PAT system is connected, it should not exceed the
following values:
It will be of electrolytic Cu, soft temper, concentric SET type, 4x6 mm2
(Urban) from section, for three-phase household connections; with
isolation of Polyvinyl Chloride PVC, weather-resistant and to
aging, for voltages of 0.6/1.0 kV, each of the phases and
protected with a common exterior insulation of resistant black polyethylene
to the elements and aging. The manufacturing standards to be considered in
The account will be ASTM-B3 and the 1PCEA for its insulation.
Test protocol
The manufacturer must provide the buyer and supervisor with the protocol of
Tests of the cable based on the manufacturing test in which I certify
the minimum required conditions of the product. They will be developed with
sample of cable of two lengths and of 3% of the length of cable purchased.
ARMELLA TIRAFÓN
TEMPLAR
Service Pipe
They will be made of corrosion-resistant aluminum alloy, of the aerial carrier type.
encapsulated fuse. Pre-assembled and high anti-fraud connection
inviolability.
DERIVED CONDUCTOR
CONFIGURATION
SECTION DIAMETER WITH COVER
MATERIAL
mm² mm
2.5 to 3.5
Al - Cu 1.5 - 6 Copper
(1.4 to 2.8)
They will be of type 'L' measuring 1.35 x 0.90 x 0.17m for embedding, which will be
expected of a sliding grid facilitating the visualization of the meter
when required, bolts made of SAE-1020 steel, galvanized
hot according to ASTM A 153-82; with a diameter of 0.95 cm and a length of 1.9 cm
to the outside, which will feature a transverse hole of 3.2mm in diameter
for the installation of fastening keys and/or security seals; for
fix the meter, secured with 0.8 mm iron plate.
UNION AND DIGNITY MARKET
INSTALLATION PROJECT OF METER BANK
Energy Meter
Type Electronic.
Precision class 1.
Overload Factor 4 (to 8)
Frequency 60 Hz.
Nominal Voltage 220 V.
Nominal Current 10 A.
Units of Measure kW-h.
Number of threads 2.
The Meter Box must have on the Plate:
Serial number in low relief
Precision Class.
Year of Manufacture
Brand
Maximum Precision Intensity 5(60) A.
For built-in installation, it will be of the best quality and first use.
WALL ANCHOR
It will be for a 16 mm diameter electrode and a 25 mm2 copper conductor and will serve.
to connect the copper grounding rod with the Cu conductor.
Bentonite
BLACK EARTH
The black earth will be cultivated for your ground well preparation, free of
sneaky and compacted.
ELECTRO PUNO S.A.A. through the representatives in charge of verifying the work at the bank of
meters in coordination with the contractor conducts the Inspection and Tests
Final steps leading to its operation.
The plans corresponding to the design of the Private Service Networks and
derivation of the household connections are:
UNION AND DIGNITY MARKET
METER BANK INSTALLATION PROJECT
DESCRIPTION PLAN
THREE-PHASE METER BANK AT 380–220 V FOR USERS OF
UNION AND DIGNITY MARKET - PUNO - PUNO - PUNO BM - 01
It includes location plans, legends, and diagrams, as well as the list of
The detail sheets are as follows:
SUMMARY OF ASSEMBLIES
PHOTOGRAPHIC PANEL
UNION AND DIGNITY MARKET
METER BANK INSTALLATION PROJECT
ANNEXES
UNION AND DIGNITY MARKET
INSTALLATION PROJECT OF METER BANK