Specifications

Eaton 118702
Eaton ESR5 Safety relay emergency
stop/protective door, 24VDC/AC, 3 enabling
paths

General specifications
PRODUCT NAME Eaton ESR5 Safety relay

CATALOG NUMBER 118702

MODEL CODE ESR5-NO-31-24VAC-DC

EAN 4015081168422

PRODUCT
114.5 mm
LENGTH/DEPTH

PRODUCT HEIGHT 99 mm

PRODUCT WIDTH 22.5 mm

PRODUCT WEIGHT 0.164 kg

2014/30/EU
UL File No.: E29184
EN ISO 13849-1
UL report applies to both
US and Canada
CE
UL Category Control No.:
NKCR; NKCR7
UL 508
IEC 62061
CERTIFICATIONS
UL
EN 50178
Certified by UL for use in
Canada
IEC/EN 60204
IEC 61508, Parts 1-7
CSA-C22.2 No. 14-95
CSA Class No.: 3211-83;
3211-03
Machines 2006/42/EG

Replacement: ESR5-NO-
CATALOG NOTES
31-24VDC (EP-401062)

GLOBAL CATALOG 118702


Product specifications Resources
eaton-esr5-safety-relay-
• Emergency stop BROCHURES brochure-br049005en-en-
category 0; us.pdf
emergency
TYPE eaton-product-overview-
switching off
• Feedback circuit CATALOGS for-machinery-catalogue-
• Protective door ca08103003zen-en-us.pdf

eaton-safety-relays-esr5-
Rail mounting possible CHARACTERISTIC CURVE safety-relay-characteristic-
Top-hat rail fixing curve.eps
MOUNTING METHOD
(according to IEC/EN
eaton-safety-relay-
60715, 35 mm) DECLARATIONS OF
declaration-of-conformity-
CONFORMITY
OPERATING eu250613en.pdf
55 °C
TEMPERATURE - MAX
eaton-safety-relays-relay-
OPERATING esr5-safety-relay-
-20 °C
TEMPERATURE - MIN dimensions-002.eps

6 kV between input circuit eaton-general-esr5-safety-


and enable current paths relay-symbol-002.eps
Safe insulation DRAWINGS
Reinforced insulation eaton-safety-relays-relay-
FEATURES
3 Non-delayed enable esr5-safety-relay-3d-
current paths drawing.eps
Automatic reset
Basic insulation eaton-general-esr5-safety-
relay-symbol.eps
The panel builder is
responsible for the DA-CE-ETN.ESR5-NO-31-
ECAD MODEL
temperature rise 24VAC-DC
10.10 TEMPERATURE RISE
calculation. Eaton will INSTALLATION
IL05013029Z
provide heat dissipation INSTRUCTIONS
data for the devices.
MANUALS AND USER
MN049008_EN
Is the panel builder's GUIDES
responsibility. The
10.11 SHORT-CIRCUIT eaton-safety-relays-
specifications for the
RATING drawings-esr5-no-xx-
switchgear must be
24vdc.dwg
observed.
MCAD MODEL
Is the panel builder's eaton-safety-relays-3d-
responsibility. The models-esr5-no-xx-
10.12 ELECTROMAGNETIC 24vdc.stp
specifications for the
COMPATIBILITY
switchgear must be eaton-safety-relays-esr5-
observed. safety-relay-wiring-
The device meets the diagram-009.eps
requirements, provided
10.13 MECHANICAL eaton-safety-relays-esr5-
the information in the
FUNCTION WIRING DIAGRAMS safety-relay-wiring-
instruction leaflet (IL) is
diagram-008.eps
observed.

10.2.2 CORROSION Meets the product eaton-safety-relays-esr5-


RESISTANCE standard's requirements. safety-relay-wiring-
diagram-007.eps
10.2.3.1 VERIFICATION OF
Meets the product
THERMAL STABILITY OF
standard's requirements.
ENCLOSURES

10.2.3.2 VERIFICATION OF Meets the product


RESISTANCE OF standard's requirements.
INSULATING MATERIALS
TO NORMAL HEAT

10.2.3.3 RESIST. OF
INSUL. MAT. TO
Meets the product
ABNORMAL HEAT/FIRE
standard's requirements.
BY INTERNAL ELECT.
EFFECTS

10.2.4 RESISTANCE TO
Meets the product
ULTRA-VIOLET (UV)
standard's requirements.
RADIATION

Does not apply, since the


10.2.5 LIFTING entire switchgear needs to
be evaluated.

Does not apply, since the


10.2.6 MECHANICAL
entire switchgear needs to
IMPACT
be evaluated.

Meets the product


10.2.7 INSCRIPTIONS
standard's requirements.

10.3 DEGREE OF Does not apply, since the


PROTECTION OF entire switchgear needs to
ASSEMBLIES be evaluated.

10.4 CLEARANCES AND Meets the product


CREEPAGE DISTANCES standard's requirements.

10.5 PROTECTION Does not apply, since the


AGAINST ELECTRIC entire switchgear needs to
SHOCK be evaluated.

10.6 INCORPORATION OF Does not apply, since the


SWITCHING DEVICES AND entire switchgear needs to
COMPONENTS be evaluated.

10.7 INTERNAL
Is the panel builder's
ELECTRICAL CIRCUITS
responsibility.
AND CONNECTIONS

10.8 CONNECTIONS FOR Is the panel builder's


EXTERNAL CONDUCTORS responsibility.

10.9.2 POWER-
Is the panel builder's
FREQUENCY ELECTRIC
responsibility.
STRENGTH

10.9.3 IMPULSE Is the panel builder's


WITHSTAND VOLTAGE responsibility.

10.9.4 TESTING OF
Is the panel builder's
ENCLOSURES MADE OF
responsibility.
INSULATING MATERIAL

ELECTRIC CONNECTION
Screw connection
TYPE

Approval for TÜV


Feedback circuit
FITTED WITH: Approval according to UL
Start input
Detachable clamps
POLLUTION DEGREE 2

Dry heat to IEC 60068-2-2


Cold to EN 60068-2-1
CLIMATIC PROOFING
Damp heat, constant, to
IEC 60068-2-3

RATED IMPULSE
WITHSTAND VOLTAGE 4000 V AC
(UIMP)

AIR PRESSURE 795 - 1080 hPa (operation)

ALTITUDE Max. 2000 m

CATEGORY (EN 954-1) 4

IP20
Terminals: IP20
DEGREE OF PROTECTION Installation location: ≥ IP54

Enclosure: IP20

Clearance in air and


creepage distances
ENVIRONMENTAL according to EN 50178, UL
CONDITIONS 508, CSA C22.2, No. 14-95
Condensation: Non-
condensing

NUMBER OF INPUTS One- and two-channel

2-channel
FUNCTIONS
1-channel

SAFETY PERFORMANCE
Level e
LEVEL (EN ISO 13849-1)

AMBIENT OPERATING
55 °C
TEMPERATURE - MAX

AMBIENT OPERATING
-20 °C
TEMPERATURE - MIN

AMBIENT STORAGE
70 °C
TEMPERATURE - MAX

AMBIENT STORAGE
-40 °C
TEMPERATURE - MIN

EQUIPMENT HEAT
DISSIPATION, CURRENT- 0W
DEPENDENT PVID

HEAT DISSIPATION
0W
CAPACITY PDISS

HEAT DISSIPATION PER


POLE, CURRENT- 0W
DEPENDENT PVID

LIFETIME 240 month

NOMINAL CURRENT 30 A

NUMBER OF OUTPUTS
(SAFETY RELATED, 0
DELAYED) WITH
CONTACT

NUMBER OF OUTPUTS
(SAFETY RELATED,
0
DELAYED,
SEMICONDUCTORS)

NUMBER OF OUTPUTS
(SAFETY RELATED,
3
UNDELAYED) WITH
CONTACT

NUMBER OF OUTPUTS
(SAFETY RELATED,
0
UNDELAYED,
SEMICONDUCTORS)

NUMBER OF OUTPUTS
(SIGNALING FUNCTION,
0
DELAYED) WITH
CONTACT

NUMBER OF OUTPUTS
(SIGNALING FUNCTION,
0
DELAYED,
SEMICONDUCTORS)

NUMBER OF OUTPUTS
(SIGNALING FUNCTION,
1
UNDELAYED) WITH
CONTACT

NUMBER OF OUTPUTS
(SIGNALING FUNCTION,
0
UNDELAYED,
SEMICONDUCTORS)

RATED CONTROL SUPPLY


VOLTAGE (US) AT AC, 50 26.4 V
HZ - MAX

RATED CONTROL SUPPLY


VOLTAGE (US) AT AC, 50 0V
HZ - MIN

RATED CONTROL SUPPLY


VOLTAGE (US) AT AC, 60 24 V
HZ - MAX

0.6 x 3.5 mm, Terminal


screws
SCREWDRIVER SIZE
2, Terminal screw, Pozidriv
screwdriver

VOLTAGE TYPE AC/DC

CONNECTION TYPE M3 screw terminals

MOUNTING POSITION As required

35 W max., inductive load


(τ = 40 ms), at 110 V DC
BREAKING POWER 40 W max., inductive load
(τ = 40 ms), at 48 V DC
48 W max., inductive load
(τ = 40 ms), at 24 V DC
1500 VA, max., resistive
load (τ = 0 ms), at 250 V AC

288 W max., resistive load


(τ = 0 ms), at 48 V DC
77 W max., resistive load (τ
= 0 ms), at 110 V DC
144 W max., resistive load
(τ = 0 ms), at 24 V DC
88 W max., resistive load (τ
= 0 ms), at 220 V DC
33 W max., inductive load
(τ = 40 ms), at 220 V DC

OVERVOLTAGE
III
CATEGORY

10A gL/gG, NEOZED (N/O),


Output fuse, External,
SHORT-CIRCUIT Output data
PROTECTION RATING 6A gL/gG, NEOZED (N/C),
Output fuse, External,
Output data

DUTY FACTOR 100 %

EMITTED INTERFERENCE According to EN 61000-6-4

CURRENT 140 mA, AC


CONSUMPTION 65 mA, DC

Contacts: silver tin oxide,


gold plated (AgSnO2, 0.2
MATERIAL µ m Au)
Enclosure: Polyamide (PA),
not reinforced

INTERFERENCE According to EN 662061_x


IMMUNITY According to EN-61000-6-2

TIGHTENING TORQUE 0.6 Nm, Screw terminals

MOUNTING WIDTH 22.5 mm

Module used to safely


interrupt electrical circuits
Monitoring of position
switches
SUITABLE FOR Monitoring of emergency-
stop circuits
Safety relay for monitoring
emergency stop and
protective door switch

RELATIVE HUMIDITY < 75 %

Status indication of
LED INDICATOR SmartWire-DT network:
Green LED

100 ms typ. (K1, K2 - for


PICK-UP TIME UN automatic mode)
100 ms typ. (at Uₑ in
automatic mode)

LIFESPAN, MECHANICAL 10,000,000 Operations

∞ ms, Simultaneity for


INPUT
inputs 1/2

RECOVERY TIME 1000 ms

RESISTANCE 50 Ω (impedance)

INRUSH CURRENT 0.025 - 6 A

MODEL Basic device

SAFETY TYPE (IEC 61496-


None
1)

SHORT-CIRCUIT CURRENT 2.3 A, Input data

10 - 150 Hz, Amplitude:


VIBRATION RESISTANCE 0.15 mm, Acceleration: 2 g,
(IEC/EN 60068-2-6)

300,000 switching cycles,


SAFETY PARAMETER (EN B10d
ISO 13849-1) Cat. 4, Category
PL e, Performance level

2 x (0.25 – 1) mm², flexible


with ferrule
24 - 12 AWG, solid or
stranded
TERMINAL CAPACITY
1 x (0.2 – 2.5) mm², solid
2 x (0.2 – 1) mm², solid
1 x (0.25 – 2.5) mm²,
flexible with ferrule

RATED CONTROL SUPPLY


VOLTAGE (US) AT AC, 60 20.4 V
HZ - MIN

RATED CONTROL SUPPLY


VOLTAGE (US) AT DC - 24 V
MAX

RATED CONTROL SUPPLY


VOLTAGE (US) AT DC - 0V
MIN

RATED INSULATION
250 V
VOLTAGE (UI)

RATED OPERATIONAL
CURRENT FOR SPECIFIED 0A
HEAT DISSIPATION (IN)

RELEASE-DELAY - MAX 0s

RELEASE-DELAY - MIN 0s

STATIC HEAT
DISSIPATION, NON-
5.16 W
CURRENT-DEPENDENT
PVS

STRIPPING LENGTH
7 mm
(MAIN CABLE)
SWITCHING VOLTAGE 250 V

PRODUCT CATEGORY Electronic safety relays

Finger and back-of-hand


proof, Protection against
PROTECTION direct contact when
actuated from front (EN
50274)

SIL (IEC 61508) 3

PERMISSIBLE TOTAL Approx. 50 Ω (input and


CABLE RESISTANCE starting circuits for UN)

POWER LOSS Normally 5.16 W

1.6 W (DC operated)


POWER SUPPLY CIRCUIT 3.4 W (AC operated 50/60
Hz)

66 Months (Low Demand)


PROOFTEST 240 Months (High
Demand)

QUADRATIC
72 A² (ITH² = I1² + I2² + I3²)
SUMMATION CURRENT

230 V AC
24 V AC/DC (power supply)
RATED OPERATIONAL
VOLTAGE Approx. 24 V DC at input,
starting and feedback
circuit

Normally 10 ms (dual-
RESET TIME channel)
45 ms (single-channel)

SIL 3, Safety integrity level


SIL 3, Safety integrity level,
In accordance with IEC
61508
SAFETY PARAMETER (IEC Cat. 4, Category
62061) SILCL 3, Safety integrity
level claim limit
5.05 x 10-10, PFHd,
Probability of failure per
hour

6 A N/C, Limiting
UNINTERRUPTED continuous current
CURRENT 6 A N/O, Limiting
continuous current

Short-circuit proof, 24 V,
Fuse for control circuit
SHORT-CIRCUIT
supply, Control circuit
PROTECTION
Fuse 6 A gL/gG, For output
circuits, External

STOP CATEGORY (IEC


0
60204)

SWITCHING CAPACITY 4 A at 360 O/h, DC-13 at 24


V, Outputs
In accordance with IEC
60947-5-1, Outputs
3 A at 3600 O/h, AC-15 at
230 V, Outputs
2.5 A at 3600 O/h, DC-13 at
24 V, Outputs
0.4 W
4 A at 360 O/h, AC-15 at
230 V, Outputs

SWITCHING FREQUENCY Max. 0.5 Hz, Input data

POWER CONSUMPTION 5.16 W

CONTROL VOLTAGE 1 -
24 V
MIN

CONTROL VOLTAGE 1 -
24 V
MAX

CONTROL VOLTAGE 2 -
24 V
MIN

CONTROL VOLTAGE 2 -
24 V
MAX

CONTROL VOLTAGE 1
AC/DC
TYPE

CONTROL VOLTAGE 2
AC/DC
TYPE

VOLTAGE TYPE OF
AC/DC
SUPPLY VOLTAGE

VOLTAGE TYPE OF
AC/DC
OPERATING VOLTAGE

RATED SWITCH CURRENT 6A

SUPPLY VOLTAGE AT AC,


24 V
50 HZ - MIN

SUPPLY VOLTAGE AT AC,


24 V
50 HZ - MAX

SUPPLY VOLTAGE AT AC,


24 V
60 HZ - MIN

SUPPLY VOLTAGE AT AC,


24 V
60 HZ - MAX

SUPPLY VOLTAGE AT DC -
24 V
MIN

SUPPLY VOLTAGE AT DC -
24 V
MAX

OPERATING VOLTAGE AT
24 V
AC, 50 HZ - MIN

OPERATING VOLTAGE AT
24 V
AC, 50 HZ - MAX

OPERATING VOLTAGE AT
24 V
AC, 60 HZ - MIN

OPERATING VOLTAGE AT 24 V
AC, 60 HZ - MAX

OPERATING VOLTAGE AT
24 V
DC - MIN

OPERATING VOLTAGE AT
24 V
DC - MAX

PROJECT NAME:

PROJECT NUMBER:

PREPARED BY:

DATE:

Eaton Corporation plc Follow us on social media to get the


Eaton House latest product and support
30 Pembroke Road information.
Dublin 4, Ireland
Eaton.com

© 2025 Eaton. All Rights Reserved.

You might also like