                                                  p/n: P-164000387
                                                        Revision 09
                               IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
                This manual contains important instructions that you should follow during installation and maintenance
                of the UPS and batteries. Please read all instructions before operating the equipment and save this
                manual for future reference.
                                                                    !      IMPORTANT
                To ensure you have the most up-to-date content and information for this product, please review the
                latest manual revision on our website, www.eaton.com/93PM.
Eaton reserves the right to change specifications without prior notice. Modbus is a registered trademark of Schneider Automation, Inc.
MOXA is a registered trademark and MGate is a trademark of MOXA, Inc. Spiralock is a registered trademark of Spiralock Corporation.
KIRK is a registered trademark of Kirk Key Interlock company, LLC, a subsidiary of Halma plc. National Electrical Code and NEC are
registered trademarks of National Fire Protection Association, Inc. ERIFLEX and FLEXIBAR are registered trademark of Erico International
Corporation. All other trademarks are property of their respective companies.
©Copyright 2013-2020 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the
express written approval of Eaton.
Table of Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
    1.1 Features ................................................................................................................................................... 1
    1.2 Installation Features .................................................................................................................................... 1
    1.3 Model Configurations .................................................................................................................................. 1
    1.4 Using This Manual ...................................................................................................................................... 4
    1.5 Conventions Used in This Manual .................................................................................................................. 4
    1.6 Symbols, Controls, and Indicators .................................................................................................................. 5
    1.7 For More Information .................................................................................................................................. 5
    1.8 Getting Help .............................................................................................................................................. 6
    1.9 Equipment Registration ............................................................................................................................... 6
2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
    4.1 Preliminary Installation Information............................................................................................................... 35
    4.2 Unloading the Field Installed SIAC-B from the Pallet......................................................................................... 35
    4.3 Mechanically Joining the UPS Cabinet and SIAC-B........................................................................................... 38
    4.4 Electrically Connecting the UPS Cabinet and SIAC-B ........................................................................................ 39
          4.4.1 Installing SIAC-B Internal Power Wiring ................................................................................................... 39
          4.4.2 Installing SIAC-B Interface Connections................................................................................................... 44
    4.5 Removing and Reinstalling the Factory Installed SIAC-B.................................................................................... 51
          4.5.1 Electrically Disconnecting the UPS Cabinet and SIAC-B............................................................................... 51
          4.5.2 Mechanically Disconnecting the UPS Cabinet and SIAC-B ........................................................................... 51
          4.5.3 Mechanically Rejoining the UPS Cabinet and SIAC-B .................................................................................. 52
          4.5.4 Electrically Reconnecting the UPS Cabinet and SIAC-B ............................................................................... 52
    4.6 Unloading the Factory Installed SIAC-B from the Pallet and Mechanical Installation................................................. 53
    4.7 Two-Hole Barrel Lug Terminations to Bus Bar Installation.................................................................................. 53
    4.8 Installing SIAC-B External Power Wiring ........................................................................................................ 54
    4.9 Initial Startup ........................................................................................................................................... 62
    4.10 Completing the Installation Checklist........................................................................................................... 62
    4.11 Installation Checklist................................................................................................................................ 62
                     Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                                                                                                                                                     iii
Table of Contents
7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
     7.1 Important Safety Instructions ...................................................................................................................... 87
     7.2 Performing Preventive Maintenance ............................................................................................................. 87
          7.2.1 DAILY Maintenance ............................................................................................................................ 87
          7.2.2 PERIODIC Maintenance ....................................................................................................................... 87
          7.2.3 ANNUAL Maintenance......................................................................................................................... 87
     7.3 Maintenance Training ................................................................................................................................ 88
8 Product Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
     8.1 Model Numbers ....................................................................................................................................... 89
     8.2 Specifications .......................................................................................................................................... 89
          8.2.1 Input ................................................................................................................................................ 89
          8.2.2 Output.............................................................................................................................................. 89
          8.2.3 Environmental and Safety Specifications.................................................................................................. 90
9 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
iv                                                    Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
List of Figures
            Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                  v
List of Figures
vi                     Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
List of Tables
           Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09          vii
List of Tables
viii             Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
Chapter 1 Introduction
                 The Eaton® 93PM 150 kW and 200 kW Three-Wire Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) is
                 designed for use with the 93PM 150 kW and 200 kW Three-Wire UPS systems. The 93PM 150 kW and 200
                 kW Four-Wire SIAC-B is designed for used with the 93PM 150 kW and 200 kW Four-Wire UPS systems. The
                 SIAC-B provides maintenance bypass functions with configurable features, enabling adaptation and expansion
                 without costly electrical rework.
                              NOTE             Startup and operational checks must be performed by an authorized Eaton Customer
                                               Service Engineer, or the warranty terms specified on the product's resources page
                                               become void. See Chapter 9 Warranty for details. This service is offered as part of the
                                               sales contract for the UPS. Contact an Eaton service representative in advance (a
                                               minimum two-week notice is required) to reserve a preferred startup date.
1.1   Features
                 The following descriptions provide a brief overview of the SIAC-B functions:
                 •     Two breaker configuration: The bypass sidecar contains only a Maintenance Bypass (MBP) and
                       Maintenance Isolation (MIS) breaker. This allows Maintenance bypass for system repair or maintenance.
                       The critical load is NOT protected in the Maintenance bypass mode.
                 •     Three breaker configuration (used with single-feed systems): Maintenance Bypass (MBP) and
                       Maintenance Isolation (MIS) breakers, and a Bypass Input Breaker (BIB) enable power to completely
                       bypass the UPS. The UPS can then be safely serviced or replaced without interrupting power to critical
                       systems.
                 •     Four breaker configuration (used with dual-feed systems): Maintenance Bypass (MBP) and Maintenance
                       Isolation (MIS) breakers, and a Bypass Input Breaker (BIB) enable power to completely bypass the UPS. A
                       Rectifier Input Breaker (RIB) provides a convenient method for removing power from the UPS when using
                       the maintenance bypass to supply the load. The UPS can then be safely serviced or replaced without
                       interrupting power to critical systems.
                 Figure 1 shows the SIAC-B. Figure 2 and Figure 3 show the SIAC-B mounted to the UPS cabinet.
                       –      Right-mounted two breaker configuration containing a MBP with auxiliary contacts and MIS
                       –      Right-mounted three breaker configuration containing a MBP with auxiliary contacts, a MIS, and a BIB
                       –      Right-mounted four breaker configuration containing a MBP with auxiliary contacts, a MIS, a BIB,
                              and a RIB
                       –      Left-mounted two breaker configuration containing a MBP with auxiliary contacts and MIS
       Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09   1
Introduction
                   –      Left-mounted three breaker configuration containing a MBP with auxiliary contacts, a MIS, and a BIB
                   –      Left-mounted four breaker configuration containing a MBP with auxiliary contacts, a MIS, a BIB,
                          and a RIB
2                      Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                         Introduction
Figure 2. Eaton 93PM 150 UPS with SIAC-B (Three or Four Wire)
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09              3
Introduction
Figure 3. Eaton 93PM 200 kW UPS with SIAC-B (Three or Four Wire)
               •   Bold type highlights important concepts in discussions, key terms in procedures, and menu options, or
                   represents a command or option that you type or enter at a prompt.
               •   Italic type highlights notes and new terms where they are defined.
               •   Screen type represents information that appears on the screen or LCD.
Icon Description
[Keys] Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].
4                    Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                                 Introduction
                       In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS
                       system refers to the entire power protection system – the UPS cabinet, an external battery system, and
                       options or accessories installed.
                       The term line-up-and-match refers to accessory cabinets that are physically located adjacent to the UPS.
                       The term standalone refers to accessory cabinets that are located separate from the UPS.
                SpecialSymbols
               Special
               Special  Symbols
               Special Symbols
                       Symbols
1.6   S y m b oThe
                lThe
                 s , Cfollowing
               The      o n t r o l s ,are
                        following
                       following        aare
                                       aren dexamples
                                               I n d i c a t oof
                                              examples
                                             examples          r ssymbols
                                                               of
                                                              of   symbolsused
                                                                  symbols  usedon
                                                                          used  onthe
                                                                               on   theUPS
                                                                                   the  UPSor
                                                                                       UPS  oraccessories
                                                                                           or  accessoriesto
                                                                                              accessories   toalert
                                                                                                           to  alertyou
                                                                                                              alert  youto
                                                                                                                    you   toimportant
                                                                                                                         to   important
                                                                                                                             important
                The  following are examples of symbols used on the UPS or accessories to alert you to important
                 information:
                information:
               information:
                 The following are examples of symbols used on the UPS or accessories to alert you to important information:
                information:
                                       RISKOF
                                      RISK  OF   RISK OF ELECTRIC
                                             OFELECTRIC
                                                ELECTRIC   SHOCK- -SHOCK
                                                          SHOCK          - Observe
                                                                    Observe
                                                                   Observe         the warning
                                                                             thewarning
                                                                            the   warning      associated with
                                                                                             associated
                                                                                            associated    with
                                                                                                          withthe riskrisk
                                                                                                                 the
                                                                                                                the     of electric
                                                                                                                       risk  of shock symbol.
                                                                                                                            of
                                      RISK
                                      RISK  OF ELECTRIC
                                               ELECTRIC  SHOCK
                                                          SHOCK -- Observe
                                                                   Observe the
                                                                            the warning
                                                                                 warning associated
                                                                                            associated with
                                                                                                          with the
                                                                                                                the risk
                                                                                                                     risk ofof
                                       electric
                                      electric
                                      electric  shock
                                               shock    symbol.
                                                       symbol.
                                      electric shock
                                               shock symbol.
                                                       symbol.
                                        CAUTION:CAUTION:
                                       CAUTION:
                                      CAUTION:      REFERTO
                                                   REFER
                                                  REFER    TO
                                                          TO   OPERATOR'S
                                                              OPERATOR'S
                                                             REFER           MANUAL
                                                                            MANUAL
                                                                   TO OPERATOR'S
                                                              OPERATOR'S    MANUAL      --- -Refer
                                                                                     MANUAL   Refer
                                                                                             Refer    toyour
                                                                                                     to
                                                                                                   -to   your
                                                                                                     Refer      operator's
                                                                                                               operator's
                                                                                                           to your            manual
                                                                                                                             manual
                                                                                                                   operator'smanual
                                                                                                                             manual     for
                                                                                                                                    forfor
                                                                                                                                         additional
                                       CAUTION:
                                        additional REFER  TOsuch
                                                              OPERATOR'S
                                                    information,
                                                 information,     such
                                                                 as     as  MANUAL
                                                                            important
                                                                    important operating   andRefer   to your
                                                                                             operating  your
                                                                                               maintenanceand
                                                                                                               operator's
                                                                                                               operator's
                                                                                                               maintenance
                                                                                                             instructions.   manual for
                                                                                                                                      for
                                       additional
                                      additional   information,
                                                  information,   such  as  important      operating      and  maintenance
                                       additional  information, such
                                        instructions.            such as
                                                                       as important
                                                                           important operating
                                                                                          operating and  and maintenance
                                                                                                              maintenance
                                       instructions.
                                      instructions.
                                       instructions.
                                                    This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This
                                         Thissymbol
                                       This
                                      This     symbol
                                              symbol     indicates
                                                        indicates
                                                   product            thatyou
                                                                    that
                                                           containsthat
                                                       indicates    sealed, you
                                                                           you     should
                                                                                 should
                                                                              lead-acid      notdiscard
                                                                                            not
                                                                                         batteriesdiscard   the
                                                                                                           the
                                                                                                    and must     UPSor
                                                                                                                UPS
                                                                                                             be UPS
                                                                                                                disposedorofthe
                                                                                                                             the   UPSbatteries
                                                                                                                                  UPS
                                                                                                                               properly.  batteries
                                                                                                                                         batteries
                                                                                                                                         For more information,
                                       This
                                         in   symbol
                                            the  trash. indicates
                                                         This
                                                   contact
                                                                    that
                                                              product
                                                           your local
                                                                           you should
                                                                                 should
                                                                           contains
                                                                       recycling/reuse
                                                                                           not
                                                                                            not discard
                                                                                       sealed,
                                                                                        or
                                                                                                 discard  the
                                                                                                           the
                                                                                                   lead‐acid
                                                                                           hazardous   waste
                                                                                                                UPS or or the
                                                                                                               batteries
                                                                                                             center.
                                                                                                                           the
                                                                                                                             and
                                                                                                                                 UPS
                                                                                                                                  UPS
                                                                                                                                   must  batteries
                                                                                                                                           be
                                       in the
                                      in   the trash.
                                                trash. This
                                                        This product
                                                             product contains
                                                                          contains sealed,
                                                                                      sealed, lead‐acid
                                                                                                 lead‐acid batteries
                                                                                                              batteries and
                                                                                                                          and mustmust be be
                                       indisposed
                                           the trash.   This product
                                                     ofproperly.
                                                         properly.        contains
                                                                    Formore           sealed, lead‐acid
                                                                           moreinformation,
                                                                                   information,               batteries
                                                                                                      contactyour
                                                                                                               yourlocal  and
                                                                                                                      local       must be
                                                                                                                               recycling/reuse      or
                                       disposed of
                                      disposed      of properly.   For
                                                                   For    more    information,       contact
                                                                                                    contact   your   local    recycling/reuse
                                                                                                                             recycling/reuse       or
                                                                                                                                                  or
                                       disposed
                                         hazardous  of properly.
                                                      waste        For
                                                               center.    more    information,       contact  your   local    recycling/reuse      or
                                       hazardous
                                      hazardous      waste    center.
                                       hazardous waste
                                                     waste center.
                                                              center.
                                                    This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in
                                       This      the trash.
                                        Thissymbol
                                             symbol
                                            symbol          For proper
                                                       indicates
                                                      indicates      thatdisposal,
                                                                      that you     contactnot
                                                                            youshould
                                                                                 should
                                                                                should     your local
                                                                                           notdiscard recycling/reuse
                                                                                                discard
                                                                                               discard                or hazardous
                                                                                                           wasteelectrical
                                                                                                          waste     electrical
                                                                                                                   electrical      waste center.
                                                                                                                                orelectronic
                                                                                                                               or  electronic
                                                                                                                                  electronic
                                      This
                                       This symbol   indicates
                                                      indicates     that
                                                                     that you
                                                                           you  should   not
                                                                                          not  discard   waste
                                                                                                          waste    electrical or
                                                                                                                               or electronic
                                        equipment(WEEE)
                                       equipment
                                      equipment      (WEEE)in
                                                    (WEEE)      ininthe
                                                                      thetrash.
                                                                     the   trash.For
                                                                                   Forproper
                                                                                  For   properdisposal,
                                                                                                  disposal,contact
                                                                                                 disposal,     contactyour
                                                                                                                         yourlocal
                                                                                                                               local
                                       equipment    (WEEE)
                                        recycling/reuse     or  in the trash.
                                                               hazardous  trash.  For proper
                                                                               waste   proper
                                                                                        center.  disposal, contact
                                                                                                              contact your
                                                                                                                        your local
                                                                                                                              local
                                       recycling/reuse
                                      recycling/reuse     or  hazardous       waste    center.
                                       recycling/reuse or or hazardous
                                                              hazardous waste waste center.
                                                                                       center.
                 •     Installation instructions, including site preparation, planning for installation, wiring and safety information,
                       and detailed illustrations of cabinets with dimensional and connection point drawings
       Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                    5
Introduction
                •       Operation, including breakers, standard features and optional accessories, procedures for using the tie and
                        bypass functions, and information about maintenance
                Visit www.eaton.com/powerquality or contact an Eaton service representative for information on how to obtain
                copies of these manuals.
                Please use the following e-mail address for manual comments, suggestions, or to report an error in this
                manual:
Model Number:
Serial Number:
6                         Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
Chapter 2 Safety Warnings
                                                                                         DANGER
               This UPS system contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED
               SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
WARNING
               •     The UPS system is powered by its own energy source (batteries). The output terminals may carry live
                     voltage even when the UPS is disconnected from an AC source.
               •     To reduce the risk of fire or electric shock, install this UPS system in a temperature and humidity
                     controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed
                     40°C (104°F). Do not operate near water or excessive humidity (95% maximum). The system is not
                     intended for outdoor use.
               •     As a result of the connected loads high leakage current is possible. Connection to earth ground is required
                     for safety and proper product operation. Do not check UPS system operation by any action that includes
                     removal of the earth (ground) connection with loads attached.
               •     Ensure all power is disconnected before performing installation or service.
               •     ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS system or battery wiring or connectors.
                     Attempting to alter wiring can cause injury.
CAUTION
               •     Installation or servicing should be performed by qualified service personnel knowledgeable of UPS and
                     battery systems, and required precautions. Keep unauthorized personnel away from equipment. Consider
                     all warnings, cautions, and notes before installing or servicing equipment.
               •     Keep the Accessory cabinet doors closed and front panels installed to ensure proper cooling airflow and to
                     protect personnel from dangerous voltages inside the unit.
               •     Do not install or operate the UPS system close to gas or electric heat sources.
               •     The operating environment should be maintained within the parameters stated in this manual.
               •     Keep surroundings uncluttered, clean, and free from excess moisture.
               •     Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the
                     equipment.
     Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09   7
Safety Warnings
8                 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
Chapter 3 Installation Plan and Unpacking
                 This chapter includes planning for the Eaton 93PM 150 kW and 200 kW Sidecar Integrated Accessory Cabinet-
                 Bypass (SIAC-B).
                              NOTE             The SIAC-B is typically attached to and directly integrated with the UPS cabinet at the
                                               factory but it can be ordered and shipped separately from the UPS and installed onsite.
                                               This section must be used along with the applicable Eaton 93PM UPS Installation and
                                               Operation manual, listed in paragraph 1.7 For More Information, during installation
                                               planning and unpacking.
3.1   Use the following basic sequence of steps to install the SIAC-B:
                 1.    Create an installation plan for the SIAC-B.
                 2.    Prepare your site for the SIAC-B.
                 3.    Inspect and unpack the SIAC-B.
                 4.    Unload and install the SIAC-B.
                 5.    Externally wire the SIAC-B.
                 6.    Complete the Installation Checklist.
                 7.    Have authorized service personnel perform preliminary operational checks and start up the system.
                              NOTE             Startup and operational checks must be performed by an authorized Eaton Customer
                                               Service Engineer, or the warranty terms specified on the product's resources page
                                               become void. See Chapter 9 Warranty for details. This service is offered as part of the
                                               sales contract for the UPS. Contact an Eaton service representative in advance (a
                                               minimum two-week notice is required) to reserve a preferred startup date.
       Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09   9
Installation Plan and Unpacking
              The SIAC-B operating environment must meet the weight requirements shown in Table 1. The SIAC-B size
              requirements are shown in Figure 4 through Figure 6 or Figure 7 through Figure 9. Dimensions are in
              millimeters (inches).
                  Eaton 93PM                   200-4          Three-Wire SIAC-B (2-Breaker)                  815 (1795)            784 (1728)           8 at 98 (216)
                  Three-Wire UPS               200-1          Three-Wire SIAC-B (4-Breaker)                  637 (1404)            606 (1337)           8 at 76 (167)
200-4 Three-Wire SIAC-B (4-Breaker) 828 (1825) 797 (1758) 8 at 100 (220)
10                     Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
            Eaton 93PM                      200-4          Four-Wire SIAC-B (2-Breaker)                   849 (1875)            818 (1808)    8 at 102 (288)
            Four-Wire UPS                   200-1          Four-Wire SIAC-B (4-Breaker)                   871 (1479)            640 (1412)     8 at 80 (226)
200-4 Four-Wire SIAC-B (4-Breaker) 862 (1900) 831 (1833) 8 at 104 (229)
The clearances required around the SIAC-B are the same as the attached UPS.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                         11
Installation Plan and Unpacking
Figure 4. Eaton 93PM 150 kW UPS with SIAC-B (Three or Four Wire) Dimensions (Front View)
12                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
          Figure 5. Eaton 93PM 150 kW UPS with SIAC-B (Three or Four Wire) Dimensions (Top and Bottom
          Views)
Front Front
                                                                           Bottom                 Bottom
                                                                           View                   View
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                       13
Installation Plan and Unpacking
Figure 6. Eaton 93PM 150 kW UPS with Left-Mounted SIAC-B (Three or Four Wire) – Center of Gravity
                                                                                                                                   B
                                  C
                        NOTE              The 93PM 150 kW UPS is shown with a left-mounted SIAC-B. A UPS with a right-
                                          mounted SIAC-B is the mirror image.
Weight and Center of Gravity with Left-Mounted 150 kW Three-Wire SIAC-B (letters A, B, and C map to Figure 6)
                                                                                           A                  B                    C              Installed Weight
                                                                                         mm (in)            mm (in)              mm (in)                kg (lb)
Eaton 93PM-150-1 Capacity UPS with 2-Breaker SIAC-B 862 (33.9) 508 (20.0) 501 (19.7) 541 (1192)
Eaton 93PM-150-2 Capacity UPS with 2-Breaker SIAC-B 913 (35.9) 510 (20.1) 518 (20.4) 604 (1332)
Eaton 93PM-150-3 Capacity UPS with 2-Breaker SIAC-B 985 (38.8) 512 (20.2) 531 (20.9) 668 (1473)
Eaton 93PM-150-1 Capacity UPS with 4-Breaker SIAC-B 870 (34.3) 507 (20.0) 494 (19.4) 554 (1222)
Eaton 93PM-150-2 Capacity UPS with 4-Breaker SIAC-B 819 (36.2) 509 (20.0) 510 (20.1) 618 (1363)
Eaton 93PM-150-3 Capacity UPS with 4-Breaker SIAC-B 989 (38.9) 511 (20.1) 524 (20.6) 682 (1503)
14                   Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
Weight and Center of Gravity with Right-Mounted 150 kW Three-Wire SIAC-B (letters A, B, and C map to Figure 6)
                                                                                        A                    B                   C         Installed Weight
                                                                                      mm (in)              mm (in)             mm (in)           kg (lb)
Eaton 93PM-150-1 Capacity UPS with 2-Breaker SIAC-B 862 (33.9) 508 (20.0) 437 (17.2) 541 (1192)
Eaton 93PM-150-2 Capacity UPS with 2-Breaker SIAC-B 913 (35.9) 510 (20.1) 420 (16.5) 604 (1332)
Eaton 93PM-150-3 Capacity UPS with 2-Breaker SIAC-B 985 (38.8) 512 (20.2) 407 (16.0) 668 (1473)
Eaton 93PM-150-1 Capacity UPS with 4-Breaker SIAC-B 870 (34.3) 507 (20.0) 445 (17.5) 554 (1222)
Eaton 93PM-150-2 Capacity UPS with 4-Breaker SIAC-B 819 (36.2) 509 (20.0) 428 (16.9) 618 (1363)
Eaton 93PM-150-3 Capacity UPS with 4-Breaker SIAC-B 989 (38.9) 511 (20.1) 414 (16.3) 682 (1503)
Weight and Center of Gravity with Left-Mounted 150 kW Four-Wire SIAC-B (letters A, B, and C map to Figure 6)
                                                                                        A                   B                    C         Installed Weight
                                                                                      mm (in)             mm (in)              mm (in)           kg (lb)
Eaton 93PM-200-1 UPS with 2-Breaker SIAC-B 853 (33.6) 552 (21.7) 501 (19.7) 569 (1255)
            Eaton 93PM-200-2 UPS with 2-Breaker SIAC-B                               903 (35.5)          550 (21.7)           517 (20.3)      633 (1395)
            Eaton 93PM-200-3 UPS with 2-Breaker SIAC-B                               973 (38.3)          548 (21.6)           529 (20.8)      696 (1536)
            Eaton 93PM-200-1 UPS with 4-breaker SIAC-B                               861 (33.9)          553 (21.8)           494 (19.4)      583 (1285)
            Eaton 93PM-200-2 UPS with 4-breaker SIAC-B                               909 (35.8)          551 (21.7)           510 (20.1)      646 (1425)
            Eaton 93PM-200-3 UPS with 4-breaker SIAC-B                               977 (38.5)          549 (21.6)           523 (20.6)      710 (1566)
Weight and Center of Gravity with Right-Mounted 150 kW Four-Wire SIAC-B (letters A, B, and C map to Figure 6)
                                                                                        A                   B                    C         Installed Weight
                                                                                      mm (in)             mm (in)              mm (in)           kg (lb)
Eaton 93PM-200-1 UPS with 2-Breaker SIAC-B 853 (33.6) 552 (21.7) 421 (16.6) 569 (1255)
            Eaton 93PM-200-2 UPS with 2-Breaker SIAC-B                              903 (35.5)           550 (21.7)          407 (16.0)      633 (1395)
            Eaton 93PM-200-3 UPS with 2-Breaker SIAC-B                              973 (38.3)           548 (21.6)          395 (15.5)      696 (1536)
            Eaton 93PM-200-1 UPS with 4-breaker SIAC-B                              861 (33.9)           553 (21.8)          429 (16.9)      583 (1285)
            Eaton 93PM-200-2 UPS with 4-breaker SIAC-B                              909 (35.8)           551 (21.7)          414 (16.3)      646 (1425)
            Eaton 93PM-200-3 UPS with 4-breaker SIAC-B                              977 (38.5)           549 (21.6)          402 (15.8)      710 (1566)
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                        15
Installation Plan and Unpacking
Figure 7. Eaton 93PM 200 kW UPS with SIAC-B (Three or Four Wire) Dimensions (Front View)
16                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
          Figure 8. Eaton 93PM 200 kW UPS with SIAC-B (Three or Four Wire) Dimensions (Top and Bottom
          Views)
Front Front
                                                                   Bottom                  Bottom
                                                                   View                    View
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                          17
Installation Plan and Unpacking
Figure 9. Eaton 93PM 200 kW UPS with Left-Mounted SIAC-B (Three or Four Wire) – Center of Gravity
                                                                                                                                                    B
                                        C
                                                                                                                        Dimensions are in millimeters [inches]
18                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
Figure 10. Eaton 93PM 200 kW UPS with Right-Mounted SIAC-B (Three or Four Wire) – Center of Gravity
                   B
                                                                                                                         C
Weight and Center of Gravity with Left-Mounted 200 kW Three-Wire SIAC-B (letters A, B, and C map to Figure 9)
                                                                                         A                   B                   C            Installed Weight
                                                                                       mm (in)             mm (in)             mm (in)              kg (lb)
            Eaton 93PM-200-1 UPS with 2-Breaker SIAC-B                               855 (33.7)          564 (22.2)           580 (22.8)            593 (1307)
            Eaton 93PM-200-2 UPS with 2-Breaker SIAC-B                               866 (34.1)          561 (22.1)           587 (23.1)            656 (1447)
            Eaton 93PM-200-3 UPS with 2-Breaker SIAC-B                               908 (35.7)          559 (22.0)           593 (23.3)            720 (1588)
            Eaton 93PM-200-4 UPS with 2-Breaker SIAC-B                               968 (38.1)          557 (21.9)           598 (23.5)            784 (1728)
            Eaton 93PM-200-1 UPS with 4-Breaker SIAC-B                               864 (34.0)          575 (22.6)           574 (22.6)            606 (1337)
            Eaton 93PM-200-2 UPS with 4-Breaker SIAC-B                               873 (34.4)          571 (22.5)           582 (22.9)            670 (1477)
            Eaton 93PM-200-3 UPS with 4-Breaker SIAC-B                               914 (36.0)          568 (22.4)           588 (23.1)            734 (1618)
            Eaton 93PM-200-4 UPS with 4-Breaker SIAC-B                               973 (38.3)          566 (22.3)           594 (23.4)            797 (1758)
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                           19
Installation Plan and Unpacking
Weight and Center of Gravity with Right-Mounted 200 kW Three-Wire SIAC-B (letters A, B, and C map to Figure 10)
                                                                                          A                   B                   C               Installed Weight
                                                                                        mm (in)             mm (in)             mm (in)                 kg (lb)
               Eaton 93PM-200-1 UPS with 2-Breaker SIAC-B                             857 (33.7)           566 (22.3)          593 (23.3)             593 (1307)
               Eaton 93PM-200-2 UPS with 2-Breaker SIAC-B                             868 (34.2)           563 (22.2)          563 (22.2)             656 (1447)
               Eaton 93PM-200-3 UPS with 2-Breaker SIAC-B                             909 (35.8)           561 (22.1)          538 (21.2)             720 (1588)
               Eaton 93PM-200-4 UPS with 2-Breaker SIAC-B                             970 (38.2)           559 (22.0)          517 (20.4)             784 (1728)
               Eaton 93PM-200-1 UPS with 4-Breaker SIAC-B                             864 (34.0)           575 (22.6)          599 (23.6)             606 (1337)
               Eaton 93PM-200-2 UPS with 4-Breaker SIAC-B                             874 (34.4)           571 (22.5)          568 (22.4)             670 (1477)
               Eaton 93PM-200-3 UPS with 4-Breaker SIAC-B                             914 (36.0)           568 (22.4)          543 (21.4)             734 (1618)
               Eaton 93PM-200-4 UPS with 4-Breaker SIAC-B                             974 (38.3)           566 (22.3)          522 (20.6)             797 (1758)
Weight and Center of Gravity with Left-Mounted 200 kW Four-Wire SIAC-B (letters A, B, and C map to Figure 9)
                                                                                         A                    B                   C               Installed Weight
                                                                                       mm (in)              mm (in)             mm (in)                 kg (lb)
               Eaton 93PM-200-1 UPS with 2-Breaker SIAC-B                             844 (33.2)          562 (22.2)           590 (23.2)             627 (1382)
               Eaton 93PM-200-2 UPS with 2-Breaker SIAC-B                             855 (33.7)          560 (22.0)           595 (23.4)             690 (1522)
               Eaton 93PM-200-3 UPS with 2-Breaker SIAC-B                             896 (35.3)          558 (22.0)           600 (23.6)             754 (1663)
               Eaton 93PM-200-4 UPS with 2-Breaker SIAC-B                             955 (37.6)          556 (21.9)           604 (19.8)             818 (1808)
               Eaton 93PM-200-1 UPS with 4-Breaker SIAC-B                             852 (33.6)          573 (22.6)           582 (22.9)             640 (1412)
               Eaton 93PM-200-2 UPS with 4-Breaker SIAC-B                             863 (34.0)          570 (22.4)           588 (23.1)             704 (1552)
               Eaton 93PM-200-3 UPS with 4-Breaker SIAC-B                             902 (35.5)          567 (22.3)           593 (23.4)             768 (1693)
               Eaton 93PM-200-4 UPS with 4-Breaker SIAC-B                             960 (37.8)          565 (22.2)           598 (23.5)             831 (1833)
Weight and Center of Gravity with Right-Mounted 200 kW Four-Wire SIAC-B (letters A, B, and C map to Figure 10)
                                                                                          A                   B                   C               Installed Weight
                                                                                        mm (in)             mm (in)             mm (in)                 kg (lb)
               Eaton 93PM-200-1 UPS with 2-Breaker SIAC-B                             846 (33.3)          564 (22.2)           575 (22.6)             627 (1382)
               Eaton 93PM-200-2 UPS with 2-Breaker SIAC-B                             857 (33.7)          562 (22.1)           548 (21.6)             690 (1522)
               Eaton 93PM-200-3 UPS with 2-Breaker SIAC-B                             897 (35.3)          560 (22.0)           525 (20.7)             754 (1663)
               Eaton 93PM-200-4 UPS with 2-Breaker SIAC-B                             957 (37.7)          558 (22.0)           506 (19.9)             818 (1808)
               Eaton 93PM-200-1 UPS with 4-Breaker SIAC-B                             853 (33.6)          573 (22.6)           584 (23.0)             640 (1412)
               Eaton 93PM-200-2 UPS with 4-Breaker SIAC-B                             863 (34.0)          570 (22.4)           556 (21.9)             704 (1552)
               Eaton 93PM-200-3 UPS with 4-Breaker SIAC-B                             902 (35.5)          567 (22.3)           533 (21.0)             768 (1693)
               Eaton 93PM-200-4 UPS with 4-Breaker SIAC-B                             960 (37.8)          565 (22.2)           514 (20.2)             831 (1833)
20                   Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
          Figure 11. Eaton 93PM 150 kW UPS Cabinet with SIAC-B Floor Mounting Bracket Dimensions — Rear
          View
                       NOTE             The 93PM 150 kW UPS is shown with a left-mounted SIAC-B. A UPS with a right-
                                        mounted SIAC-B is the mirror image.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             21
Installation Plan and Unpacking
              Figure 12. Eaton 93PM 150 kW UPS Cabinet with SIAC-B Floor Mounting Bracket Dimensions — Top
              View
Rear
Front
                       NOTE              The 93PM 150 kW UPS is shown with a left-mounted SIAC-B. A UPS with a right-
                                         mounted SIAC-B is the mirror image.
22                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
          Figure 13. Eaton 93PM 200 kW UPS Cabinet with SIAC-B Floor Mounting Bracket Dimensions — Rear
          View
                       NOTE             The 93PM 200 kW UPS is shown with a left-mounted SIAC-B. A UPS with a right-
                                        mounted SIAC-B is the mirror image.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             23
Installation Plan and Unpacking
              Figure 14. Eaton 93PM 200 kW Capacity UPS Cabinet with SIAC-B Floor Mounting Bracket Dimensions
              — Top View
Rear
Front
                         NOTE              The 93PM 200 kW UPS is shown with a left-mounted SIAC-B. A UPS with a right-
                                           mounted SIAC-B is the mirror image.
                                                                                       WARNING
              As a result of the connected loads high leakage current is possible. Connection to earth ground is required for
              safety and proper product operation. Do not check SIAC-B operation by any action that includes removal of the
              earth (ground) connection with loads attached.
• Refer to national and local electrical codes for acceptable external wiring practices.
24                    Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
          •      For external wiring, use 75°C copper wire only. Wire sizes listed in Table 2 and Table 3 are for copper
                 wiring only. If wire is run in an ambient temperature greater than 40°C, higher temperature wire and/or
                 larger size wire may be necessary. Wire sizes are based on using the specified breakers.
          •      Recommended wire sizes are based on NFPA National Electrical Code® (NEC®)70 Table 310.15(B)(16) 75°
                 C ampacity with 40°C ambient correction factors.
          •      Three-wire SIAC-B models do not use a neutral. Four-wire SIAC-B models use a neutral for bypass input
                 and load output, but not for rectifier input.
          •      The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-
                 linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be
                 sized in accordance with NFPA NEC 70 Article 310.15(B)(5).
          •      Refer to NEC Article 250 and local codes for proper grounding practices.
          •      Phase rotation must be clockwise starting with phase A (rotation A, B, C).
          •      Per NEC Article 300-20(a), all three-phase conductors must be run in the same conduit. A ground wire
                 must be run in the same conduit as the phase conductors.
          •      Conduit is to be sized to accommodate three phase conductors, one neutral conductor (four-wire models
                 only), and one ground conductor. If an oversized neutral conductor (four-wire models only) is to be
                 installed, a larger conduit size is needed to accommodate the oversized neutral.
          •      Refer to the appropriate Eaton 93PM UPS Installation and Operation manual, listed in paragraph
                 1.7 For More Information, for UPS cabinet conduit and terminal specifications and locations.
          •      Material and labor for external wiring recommendations are to be provided by the customer.
          •      If installing an external maintenance bypass, all feeds to the UPS including the Rectifier Input Breaker (RIB)
                 (if installed) must have a service disconnect independent of the maintenance bypass power path. Most
                 maintenance bypass solutions provide UPS input feeds derived from but isolated from the maintenance
                 bypass power path. If the maintenance bypass solution being installed does not provide such functionality,
                 DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass.
          •      The term line-up-and-match refers to accessory cabinets that are physically located adjacent to the UPS.
                 The term standalone refers to accessory cabinets that are located separate from the UPS.
          For three-wire SIAC-B external power wiring recommendations, including the minimum AWG size of external
          wiring, see Table 2 or Table 3. Wire sizes listed are for copper wiring only.
          Table 2. External Power Wiring Recommendations: Eaton 93PM 150 kW and 200 kW Three-Wire SIAC-B – Two and
          Three Breaker Maintenance Bypass
                                                                                               Units                                Rating 60 Hz
              Basic Unit Rating                                                                  kW                         150                     200
              Input/Output Voltage                                                              Volts                    480/480                   480/480
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                       25
Installation Plan and Unpacking
              Table 2. External Power Wiring Recommendations: Eaton 93PM 150 kW and 200 kW Three-Wire SIAC-B – Two and
              Three Breaker Maintenance Bypass (Continued)
NOTE Callout letters A and C map to Figure 39, Figure 40, Figure 42, and Figure 43.
              Table 3. External Power Wiring Recommendations: Eaton 93PM 150 kW and 200 kW Three-Wire SIAC-B – Four Breaker
              Maintenance Bypass
                                                                                                 Units                               Rating 60 Hz
               Basic Unit Rating                                                                  kW                          150                        200
               Input/Output Voltage                                                              Volts                     480/480                    480/480
26                   Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
          For four-wire SIAC-B external power wiring recommendations, including the minimum AWG size of external
          wiring, see Table 4 or Table 5. Wire sizes listed are for copper wiring only.
                       NOTE             The UL 924 Emergency Lighting UPS utilizes the SIAC-B for maintenance purposes only.
                                        The SIAC-B is not used for protection of conductors and is utilized as a switching
                                        component only. Use the tables provided in the applicable Eaton 93PM UPS Installation
                                        and Operation manual, listed in paragraph 1.7 For More Information, for the appropriate
                                        conductor and upstream breaker size.
          Table 4. External Power Wiring Recommendations: Eaton 93PM 150 kW and 200 kW Four-Wire SIAC-B – Two and Three
          Breaker Maintenance Bypass
                                                                                               Units                                Rating 60 Hz
            Basic Unit Rating                                                                    kW                         150                     200
            Input/Output Voltage                                                                Volts                    480/480                   480/480
            Minimum Conductor Size (Phase A, B, and C and                       A          AWG or kcmil                     2/0                      4/0
            Neutral)                                                                         (each)                         (2)                      (2)
            Number per Phase
            NOTE Callout letters A and C map to Figure 39, Figure 40, Figure 45, and Figure 46.
                      The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to
                      the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA
                      NEC 70 Article 310.15(B)(5).
                       NOTE             The UL 924 Emergency Lighting UPS utilizes the SIAC-B for maintenance purposes only.
                                        The SIAC-B is not used for protection of conductors and is utilized as a switching
                                        component only. Use the tables provided in the applicable Eaton 93PM UPS Installation
                                        and Operation manual, listed in paragraph 1.7 For More Information, for the appropriate
                                        conductor and upstream breaker size.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                       27
Installation Plan and Unpacking
              Table 5. External Power Wiring Recommendations: Eaton 93PM 150 kW and 200 kW Four-Wire SIAC-B – Four Breaker
              Maintenance Bypass
                                                                                                 Units                               Rating 60 Hz
               Basic Unit Rating                                                                  kW                          150                        200
               Input/Output Voltage                                                              Volts                     480/480                    480/480
               Minimum Conductor Size (Phase A, B, and C and                      A         AWG or kcmil                      2/0                        4/0
               Neutral)                                                                       (each)                          (2)                        (2)
               Number per Phase
              The power wiring terminals for the 93PM 150 kW Three-Wire SIAC-B are pressure terminations. The power
              wiring connections for this equipment are UL and CSA rated. See Table 6 for external power cable
              terminations.
              Figure 34 or Figure 35 show the location of the SIAC-B power cable terminals.
28                   Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
Table 6. External Input Power Cable Terminations for the Eaton 93PM 150 kW Three-Wire SIAC-B
          The power wiring terminals for the 93PM 150 kW Four-Wire SIAC-B are pressure terminations. The power
          wiring connections for this equipment are UL and CSA rated. See Table 7 for external power cable
          terminations.
          Figure 34 or Figure 35 show the location of the SIAC-B power cable terminals.
Table 7. External Input Power Cable Terminations for the Eaton 93PM 150 kW Four-Wire SIAC-B
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                29
Installation Plan and Unpacking
Table 7. External Input Power Cable Terminations for the Eaton 93PM 150 kW Four-Wire SIAC-B (Continued)
              The power wiring terminals E1 through E3 for the 93PM 200 kW Three-Wire SIAC-B are pressure terminations.
              Power wiring terminals E6 through E11 for the 93PM 200 kW Three-Wire SIAC-B are 2-hole bus bar mountings
              for standard NEMA 2-hole barrel lugs. The power wiring connections for this equipment are UL and CSA rated.
              See Table 8 for external power cable terminations, for supplied external wiring terminal hardware, and for
              recommended installation parts and tools not supplied by Eaton.
              Figure 36 or Figure 37 show the location of the SIAC-B power cable terminals.
Table 8. External Input Power Cable Terminations for the Eaton 93PM 200 kW Three-Wire SIAC-B
AC Output to Critical Load E9 Phase A 2 – 2 bolt mounting 35 (26) M12 Hex Bolt
               Building, Inter-Cabinet, and               TBG               Ground               4 – #14–1/0              5.1 Nm (45 lb in)             Slotted
               Load Ground
              The power wiring terminals E1 through E3 for the 93PM 200 kW Four-Wire SIAC-B are pressure terminations.
              Power wiring terminals E6 through E11 for the 93PM 200 kW Four-Wire SIAC-B are 2-hole bus bar mountings
              for standard NEMA 2-hole barrel lugs. The power wiring connections for this equipment are UL and CSA rated.
              See Table 9 for external power cable terminations, for supplied external wiring terminal hardware, and for
              recommended installation parts and tools not supplied by Eaton.
30                   Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
Figure 36 or Figure 37 show the location of the SIAC-B power cable terminals.
Table 9. External Input Power Cable Terminations for the Eaton 93PM 200 kW Four-Wire SIAC-B
AC Output to Critical Load E9 Phase A 2 – 2 bolt mounting 35 (26) M12 Hex Bolt
              Building, Inter-Cabinet, and              TBG               Ground                4 – #14–1/0             5.1 Nm (45 lb in)     Slotted
              Load Ground
                                                                                    WARNING
          Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
          required.
          Read and understand the following notes while planning and performing the installation:
          •       Use Class 1 wiring methods (as defined by the NEC) for interface wiring from 30V to 600V. The wire
                  should be rated for 600V, 1A minimum. 12 AWG maximum wire size.
          •       Use Class 2 wiring methods (as defined by the NEC) for interface wiring up to 30V. The wire should be
                  rated for 24V, 1A minimum.
          •       Use twisted-pair wires for each input and return or common.
          •       All interface wiring and conduit is to be supplied by the customer.
          •       Interface wiring can be installed using the inter-cabinet wiring access pass-through or by routing wiring
                  through conduit between cabinets.
          •       Install the interface wiring in separate conduit from the power wiring.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                     31
Installation Plan and Unpacking
Figure 15. Eaton 93PM 150 kW UPS with SIAC-B (Three or Four Wire) as Shipped on Pallet
32                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                      Installation Plan and Unpacking
Figure 16. Eaton 93PM 200 kW UPS with SIAC-B (Three or Four Wire) as Shipped on Pallet
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             33
Installation Plan and Unpacking
34                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
Chapter 4 Installation
                 This chapter includes installation instructions for the Eaton 93PM 150 kW AND 200 kW Sidecar Integrated
                 Accessory Cabinet-Bypass (SIAC-B).
                              NOTE             The SIAC-B is typically attached to and directly integrated with the UPS cabinet at the
                                               factory but it can be ordered and shipped separately from the UPS and installed onsite.
                                               This section must be used along with the applicable Eaton 93PM UPS Installation and
                                               Operation manual, listed in paragraph 1.7 For More Information, during installation.
                 •     See Chapter 3 Installation Plan and Unpacking for cabinet dimensions, equipment weight, wiring and
                       terminal data, and installation notes.
                 •     Do not tilt the cabinets more than ±10° during installation.
                 Use the applicable procedure from the following list for the type of installation being performed:
                 •     For field installation of a separately shipped SIAC-B, proceed to paragraph
                       4.2 Unloading the Field Installed SIAC-B from the Pallet.
                 •     For site removal and reinstallation of the SIAC-B, proceed to paragraph
                       4.5 Removing and Reinstalling the Factory Installed SIAC-B.
                 •     For a factory installed SIAC-B, proceed to paragraph
                       4.6 Unloading the Factory Installed SIAC-B from the Pallet and Mechanical Installation.
                                                                                           WARNING
                 The SIAC-B is heavy (approximately 220 kgs/486 lbs). If unpacking and unloading instructions are not closely
                 followed, the cabinet may tip and cause serious injury.
CAUTION
                              NOTE             For the following steps, verify that the forklift or pallet jack is rated to handle the weight
                                               of the cabinet (approximately 220 kgs/486 lbs).
       Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09   35
Installation
                  1.     If not already accomplished, use a forklift or pallet jack to move the SIAC-B to the installation area, or as
                         close as possible, before unloading from the pallet. Insert the forklift or pallet jack forks between the
                         supports on the bottom of the pallet.
                  2.     Remove the screw securing the bottom of the SIAC-B front panel. Lift the panel straight up to remove it
                         from the panel hanger bracket at the top of the cabinet. Retain screw for later use.
                  3.     Locate the four 1/2" jacking bolts from the parts kit and install them in the threaded holes in the front and
                         rear supports as shown in Figure 18. Place a floor protector from the parts kit underneath each jacking bolt,
                         and screw the bolts down against them.
                         The floor protectors protect the floor from being marred by the jacking bolts.
Figure 18. Removing the Pallet Skids and Supports – Eaton 93PM Field Installed SIAC-B
                                                                                                                                               Shipping Brace
                                                                                                                                               Mounting Screws
                                                                                                                                               (2 places front)
                                                                                                                                               (2 places rear)
                                                                                                                                               Shipping Brace
                                                                                                                                               (2 places front)
                       Rear Cabinet                                                                                                            (2 places rear)
                       Support
                                                                                                                                                   Right Side
               Cabinet                                                                                                                             Cabinet Support
               Support Bolts
               (2 places at
                                                                                                                                                   Shipping Brace
               each corner)
                                                                                                                                                   Mounting Bolts
                                                                                                                                                   (2 places front)
           Cabinet Side Wheels                                                                                                                     (2 places rear)
           (2 places left side)
           (2 places right side)                                                                                                                   Cabinet
                                                                                                                                                   Mounting Bolts
                                                                                                                                                   (2 places front)
                                                                                                                                                   (2 places rear)
                                                                                                                                                   Front Cabinet
                                                                                                                                                   Support
                                                                                                                                               Floor Protectors
                                                                                                                                               (2 places front)
                                                                                                                                               (2 places rear)
                                                                                                WARNING
                  Do not remove or loosen the cabinet mounting or cabinet support bolts until instructed.
                  4.     Loosen, but do not remove, the skid mounting bolts holding the pallet skids to the front and rear supports,
                         and to the left and right side supports (see Figure 18).
36                             Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                         Installation
                                                                                    WARNING
          RISK OF INSTABILITY. Turning the jacking bolts unevenly may cause the cabinet to become unbalanced. To
          prevent tipping the cabinet, raise and lower the jacking bolts evenly.
                                                                                    CAUTION
          CABINET MAY TIP. Raise the SIAC-B no more than 3 mm (1/8") above the floor (just enough to allow the
          removal of the pallet skids).
          5.    Turn each jacking bolt consecutively, two full turns, until the pallet skids clear the floor by approximately
                3 mm (1/8").
          6.    Remove the hardware loosened in Step 4.
          7.    Pull the pallet skids out from under the metal angle supports without disturbing the jacking bolts. Recycle
                the pallet skids and hardware in a responsible manner.
                                                                                    CAUTION
          CABINET MAY FALL. Do not loosen the hardware attaching the front supports to the cabinet base. The cabinet
          must be lowered by the jacking bolts before the supports can be removed.
          8.    Carefully and evenly lower the cabinet by turning each jacking bolt consecutively two full turns
                (maximum) until the cabinet side wheels contact the floor and the cabinet is no longer supported by the
                jacking bolts.
          9.    After the SIAC-B is resting on the floor, remove the jacking bolts and floor protectors. Recycle them in a
                responsible manner.
          10. Remove the shipping brace screws securing the front left and right shipping braces to the cabinet (see
              Figure 18). Do not reinstall screws. Recycle the screws in a responsible manner.
          11. Remove the bolts securing the front left and right shipping braces to the front cabinet support (see
              Figure 18). Remove the braces.
          12. Remove the screws securing the back left and right shipping braces to the cabinet (see Figure 18).
              Reinstall the screws (without the nylon washers) to secure the rear panel to the frame.
          13. Remove the bolts securing the back left and right shipping braces to the rear cabinet support (see
              Figure 18). Remove the braces.
          14. Remove the cabinet support bolts fastening the front, rear, and side cabinet supports together and remove
              the side supports (see Figure 18).
          15. Remove the cabinet mounting bolts holding the front and rear supports to the cabinet base (see Figure 18).
          16. Recycle the bolts along with the shipping braces and support brackets in a responsible manner.
          17. Reinstall the SIAC-B front panel and secure with retained screw.
          18. If the leveling feet are not retracted, turn all four leveling feet until they are retracted as far into the cabinet
              as possible.
                       NOTE             In line-up-and-match installations, the SIAC-B and UPS cabinets should be located as
                                        shown in Figure 2 or Figure 3.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             37
Installation
                                                                                       CAUTION
               To prevent tipping when rolling the cabinet and damage to the front door, push the cabinet from the rear
               whenever possible. Do not push the cabinet from the sides.
               1.   Lower all four leveling feet until nearly in contact with the floor.
               2.   Remove the two SIAC-B side wheels facing the UPS cabinet by removing the single bolt securing the
                    wheel to the cabinet.
               3.   Move the SIAC-B into position against the UPS cabinet and remove the remaining two SIAC-B side
                    wheels.
               4.   Use the leveling feet to align and level the SIAC-B vertically with the UPS cabinet.
               5.   Locate the top tie strap shipped attached to the SIAC-B (see Figure 19) and remove the screws securing
                    the strap to the SIAC-B. Retain the hardware for later use.
               6.   Remove the screws securing the adjacent cabinet top panel. Retain the hardware for later use.
               7.   Install the top tie strap between the cabinets and secure the tie strap with the retained hardware.
                         NOTE              A rear tie strap is attached to the back of the cabinet and is used only for seismic
                                           installations.
               8.   Remove the screws securing the internal safety shield panel and remove the panel to gain access to the
                    pass-through tie strap. Retain the hardware for later use.
               9.   Locate the pass-through tie strap at the bottom right or left side of the SIAC-B (see Figure 19) and remove
                    the screws securing the strap to the SIAC-B.
               10. Remove the corresponding screws at the bottom of the UPS cabinet pass-through. Retain the hardware
                   for later use.
               11. Install the pass-through tie strap between the cabinets and secure the tie strap with the retained
                   hardware.
               12. If necessary after the installing the attaching straps, secure the SIAC-B in position by adjusting the leveling
                   feet until the cabinet is level and locked in place.
               13. Proceed to paragraph 4.4 Electrically Connecting the UPS Cabinet and SIAC-B.
38                    Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                                           Installation
                              NOTE 1           In the following steps, only two phase harnesses are shipped if an RIB is not installed.
                              NOTE 2           Neutral harnesses are only provided with four-wire models.
                 1.    Locate and remove the three internal power wiring phase harnesses, two neutral harnesses, and MBP
                       interface harness packed inside the SIAC-B. Retain for later use.
                              NOTE 1           When routing cable harnesses, ensure the cables ends marked UPS are routed to the
                                               UPS terminals.
                              NOTE 2           150 kW SIAC-B phase harnesses have ferrules attached to the each end of the cables.
                                               200 kW phase harnesses have ferrules attached to the SIAC-B cable ends and two-hole
                                               barrel lugs attached to the UPS cable ends.
                 2.    Route the phase harness ends marked for the UPS Output, UPS Bypass, and UPS Input (if installed) from
                       the SIAC-B through the bottom of the SIAC-B and UPS inter-cabinet wiring access pass-through to the
                       UPS cabinet terminals. See Figure 20 or Figure 21 for SIAC-B terminal locations. Refer to the applicable
                       Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7 For More Information, for the
                       UPS pass-through and terminal locations.
                 3.    In the UPS cabinet, locate the harness cable ends marked UPS Output. Connect marked phase A, B, and C
                       cable ends to the corresponding output terminals of the UPS.
       Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                        39
Installation
               4.   In the UPS cabinet, locate the harness cable ends marked UPS Bypass. Connect marked phase A, B, and C
                    cable ends to the corresponding bypass input terminals of the UPS.
               5.   In the UPS cabinet if an RIB is installed, locate the harness cable ends marked UPS Input. Connect marked
                    phase A, B, and C cable ends to the corresponding rectifier input terminals of the UPS.
               6.   In the SIAC-B, locate the harness cable ends marked MIS. Connect marked phase A, B, and C terminal
                    number cable ends to the corresponding terminal number of the MIS breaker.
                    For a detailed view of the MIS breaker terminals, see Figure 22. Tighten terminals to 31Nm (275 lb in)
                    torque.
               7.   In the SIAC-B, locate the harness cable ends marked MIS. Connect marked phase A, B, and C terminal
                    number cable ends to the corresponding terminal number of the MIS breaker.
                    For a detailed view of the BIB breaker terminals, see Figure 23. Tighten terminals to 31Nm (275 lb in)
                    torque.
               8.   In the SIAC-B if and RIB is installed, locate the harness cable ends marked RIB. Connect marked phase
                    A, B, and C terminal number cable ends to the corresponding terminal number of the RIB breaker.
                    For a detailed view of the RIB breaker terminals, see Figure 24. Tighten terminals to 31Nm (275 lb in)
                    torque.
               9.   If installing a four-wire SIAC-B, proceed to Step 10; otherwise, proceed to Step 15.
                         NOTE              When routing neutral cable harnesses, ensure the cable ends with the Gray and Red
                                           Anderson connectors are routed to the SIAC-B neutral connectors.
               10. Route the output and bypass neutral harnesses from the SIAC-B through the bottom of the SIAC-B and
                   UPS inter-cabinet wiring access pass-through to the UPS cabinet terminals. See Figure 20 or Figure 21 for
                   SIAC-B terminal locations. Refer to the applicable Eaton 93PM UPS Installation and Operation manual,
                   listed in paragraph 1.7 For More Information, for the UPS pass-through and terminal locations.
               11. In the UPS cabinet, locate the harness cable ends marked UPS E12 Output. Connect marked cable ends to
                   the corresponding neutral terminals of the UPS.
               12. In the UPS cabinet, locate the harness cable ends marked UPS E12 Bypass. Connect marked cable ends to
                   the corresponding neutral terminals of the UPS.
               13. In the SIAC-B, locate the cable with the Gray Anderson connector and connect to the Gray Anderson
                   connector mounted to the cabinet sidewall (see Figure 20 or Figure 21).
               14. In the SIAC-B, locate the cable with the Red Anderson connector and connect to the Red Anderson
                   connector mounted to the cabinet sidewall (see Figure 20 or Figure 21).
               15. Proceed to paragraph 4.4.2 Installing SIAC-B Interface Connections
40                    Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                              Installation
Figure 20. Left-Mounted SIAC-B – RIB, BIB, and MIS Breaker Terminal Locations
            AC Output to                                                                       AC Output to
            UPS Rectifier                                                                      UPS Bypass
                 A, B, C                                                                       A, B, C
     Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             41
Installation
Figure 21. Right-Mounted SIAC-B – RIB, BIB, and MIS Breaker Terminal Locations
                      AC Output to
                      UPS Rectifier                                                                      AC Output to
                           A, B, C                                                                       UPS Bypass
                                                                                                         A, B, C
42                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                         Installation
MIS
                                                  Phase A (MIS-2)
                             AC Input from
                                                  Phase B (MIS-4)
                             UPS Output
                                                  Phase C (MIS-6)
BIB
                                                  Phase A (BIB-2)
                              AC Output to
                                                  Phase B (BIB-4)
                              UPS Bypass
                                                  Phase C (BIB-6)
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             43
Installation
RIB
                                                     Phase A (RIB-2)
                                 AC Output to
                                                     Phase B (RIB-4)
                                 UPS Rectifier
                                                     Phase C (RIB-6)
                          NOTE 1            The SIAC-B is typically attached to and directly integrated with the UPS cabinet at the
                                            factory but it can be ordered and shipped separately from the UPS and installed onsite.
                                            This section must be used along with the applicable Eaton 93PM UPS Installation and
                                            Operation manual, listed in paragraph 1.7 For More Information, during installation.
                          NOTE 2            The SIAC-B MBP auxiliary contact control interface wiring is prewired between the
                                            attached factory installed SIAC-B and UPS. Table 10 and Table 11, and Figure 25 through
                                            Figure 30 are for reference only for the factory installed SIAC-B.
                          NOTE 3            Keep interface wiring separate from power wiring.
               1.   Locate the MBP interface harness removed from inside the SIAC-B in paragraph
                    4.4.1 Installing SIAC-B Internal Power Wiring.
                          NOTE              When routing the MBP interface cable harness, ensure the green ten position terminal
                                            header end is routed to the SIAC-B terminal block.
               2.   Route the SIAC-B MBP auxiliary contact control interface wiring harnesses from the SIAC-B through the
                    bottom of the SIAC-B and UPS inter-cabinet wiring access pass-through to the UPS cabinet terminals. See
                    Figure 25 or Figure 26 for SIAC-B terminal locations, and Figure 28 or Figure 29 for UPS terminal locations.
                    Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph
                    1.7 For More Information, for the UPS pass-through location.
               3.   Connect the MBP interface harness green ten position header to the SIAC-B green terminal block.
44                     Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                         Installation
          4.    Connect the MBP interface harness white two position connector to the UPS MBP interface terminal block
                connector (see Figure 30).
          5.    Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph
                1.7 For More Information, to complete the mechanical installation of the UPS and SIAC-B. After completing
                the mechanical installation return to paragraph
                4.7 Two-Hole Barrel Lug Terminations to Bus Bar Installation.
Figure 25. 93PM 150 kW Three-Wire and Four-Wire SIAC-B Interface Terminal Location
   Interface
   Terminal
   Block
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             45
Installation
Figure 26. 93PM 200 kW Three-Wire and Four-Wire SIAC-B Interface Terminal Location
                    Interface
                    Terminal
                    Block
46                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                                    Installation
Not Used
Not Used
Not Used
                       NOTE 1           The removable terminal block header faces in for a left-mount SIAC-B and out for a right-
                                        mount SIAC-B.
                       NOTE 2           UPS building alarm signals are customer programmable. Customer interface wiring for
                                        the SIAC-B MBP assumes that the UPS Building Alarm is programmed to monitor
                                        Normally Open (NO) contacts.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                           47
Installation
                NOTE UPS building alarm signals are customer programmable. Customer interface wiring for the SIAC-B MBP assumes that the
                     UPS Building Alarm is programmed to monitor Normally Open (NO) contacts.
                       “Return“ indicates connection to electronics circuit ground. “Common” indicates connection to common side of isolated
                       relay contact
48                   Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                          Installation
Figure 28. 93PM 150 kW Three-Wire and Four-Wire SIAC-B UPS MBP Interface Terminal Location
                                                                                                                         MBP Interface
                                                                                                                         Terminal Block
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09              49
Installation
Figure 29. 93PM 200 kW Three-Wire and Four-Wire SIAC-B UPS MBP Interface Terminal Location
                                                                                                                                    MBP Interface
                                                                                                                                    Terminal Block
50                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                                Installation
                                   MBP Interface
                                   Terminal Block
       Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             51
Installation
               2.   Remove the screws securing the internal safety shield panel and remove the panel. Retain the hardware
                    for later use.
               3.   Lower the leveling feet until in contact with the floor.
               4.   Carefully pull all disconnected cables through the pass-through into the bottom of the SIAC-B.
               5.   Remove the screws securing the top tie strap and remove the strap (see Figure 19). Retain the strap and
                    hardware for later use.
               6.   Remove the screws securing the pass-through tie strap and remove the strap (see Figure 19). Retain the
                    strap and hardware for later use.
                          NOTE              The rear shipping bracket attached to the back of the cabinet is used only for shipping
                                            and seismic installations. Recycle the bracket in a responsible manner unless needed for
                                            seismic installation.
               7.   Remove the screws securing the rear shipping bracket and remove the bracket (refer to the applicable
                    Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7 For More Information, for strap
                    location). Reinstall the screws.
                                                                                        CAUTION
               Brace the SIAC-B after removing from the UPS cabinet to prevent the SIAC-B from falling,
                          NOTE              A rear tie strap is attached to the back of the cabinet and is used only for seismic
                                            installations.
               4.   Reinstall the pass-through tie strap (see Figure 19) between the cabinets and secure the tie strap with the
                    retained hardware.
               5.   If necessary after the installing the attaching straps, secure the SIAC-B in position by adjusting the leveling
                    feet until the cabinet is level and locked in place.
               6.   Proceed to paragraph 4.5.4 Electrically Reconnecting the UPS Cabinet and SIAC-B.
               1.   Carefully route all disconnected cables through the pass-through into the bottom of the UPS cabinet.
               2.   Reconnect the UPS output, the UPS bypass input, and if an RIB is installed the UPS rectifier input tagged
                    wiring to the respective UPS terminals. Refer to the applicable Eaton 93PM UPS Installation and Operation
                    manual, listed in paragraph 1.7 For More Information, for terminal locations and requirements.
52                     Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                                Installation
                 3.    If installing a four-wire SIAC-B, reconnect the tagged neutral wiring to the respective UPS terminals.
                 4.    Reconnect the UPS MBP interface harness connector to the UPS MBP interface terminal block connector
                       (see Figure 28 or Figure 29, and Figure 30).
                 5.    Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph
                       1.7 For More Information, to complete the mechanical installation of the UPS and SIAC-B. After completing
                       the mechanical installation return to paragraph
                       4.7 Two-Hole Barrel Lug Terminations to Bus Bar Installation.
4.6   Unloading the Factory Installed SIAC-B from the Pallet and Mechanical Installation
                 The SIAC-B is attached to and directly integrated with the UPS cabinet at the factory. Refer to the applicable
                 Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7 For More Information, for unloading
                 and mechanical installation instructions.
                 After completing the unloading and installation of the UPS with the attached SIAC-B, return to paragraph
                 4.7 Two-Hole Barrel Lug Terminations to Bus Bar Installation.
                              NOTE             Conical washers are special purpose washers that look similar to flat washers, except
                                               for a slight conical shape. When installing conical washers, the top of the dome should
                                               be next to the bolt head and the base of the washer should be against a flat surface such
                                               as a bus bar, flat washer, or large terminal.
       Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             53
Installation
Figure 31. Typical Bus Bar Barrel Lug Mounting – Hardware Assembly Sequence
                                                                                                                                 Bolt Head
                                                                                                                                 Conical Washer
                       Lug                                                                                                       Flat Washer
                                                                                                                                Bus Bar
                                                                                                                                Threaded Clinch Nut
                                                                                                                                 Bolt Head
                                                                                                                                 Conical Washer
                       Lug                                                                                                       Flat Washer
                       Lug
                                                                                                                                 Bus Bar
                                                                                                                                 Threaded Clinch Nut
                         NOTE 2            External power wiring can be routed either through the top or bottom of the SIAC-B.
                         NOTE 3            Remove the SIAC-B top or bottom conduit landing plate to drill or punch conduit holes
                                           (see Figure 32 or Figure 33).
               To install wiring:
               1.   Remove the screw securing the bottom of the SIAC-B front panel. Lift the panel straight up to remove it
                    from the panel hanger bracket at the top of the cabinet. Retain screw for later use.
               2.   Remove the screws securing the internal safety shield panel and remove the panel to gain access to the
                    maintenance bypass input, critical load output, and rectifier input (if installed) terminals. Retain the
                    hardware for later use.
               3.   If wiring the SIAC-B using top entry wiring access, proceed to Step 4; otherwise, proceed to Step 7.
               4.   Top Entry Wiring. Remove the top conduit landing plate (see Figure 32 or Figure 33) from the top of the
                    SIAC-B. Identify all conduit requirements and mark their location. Drill and punch all conduit holes in the top
                    cover prior to mounting on the SIAC-B. Install the top conduit plate and install all conduit runs into the top
                    cover.
               5.   Route the maintenance bypass input, critical load output, and rectifier input (if installed) cables (phase A, B,
                    and C, Ground, and if required Neutral) through the conduit on the top of the SIAC-B to the SIAC-B
54                    Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                         Installation
                terminals. See Figure 32 or Figure 33 for SIAC-B wiring access information, and Figure 34, Figure 35,
                Figure 36, or Figure 37 for terminal locations.
          6.    Proceed to Step 9.
          7.    Bottom Entry Wiring. Remove the bottom conduit landing plate (see Figure 32 or Figure 33) from the
                bottom of the SIAC-B. Identify all conduit requirements and mark their location. Drill and punch all conduit
                holes in the bottom conduit plate prior to mounting on the SIAC-B. Install the conduit plate and install all
                conduit runs into the plate.
          8.    Route the maintenance bypass input, critical load output, and rectifier input (if installed) cables (phase A, B,
                and C, Ground, and if required Neutral) through the conduit on the bottom of the SIAC-B to the SIAC-B
                terminals. See Figure 32 or Figure 33 for SIAC-B wiring access information, and Figure 34, Figure 35,
                Figure 36, or Figure 37 for terminal locations.
          9.    If wiring a 93PM 200 kW Three-Wire SIAC-B or 93PM 200 kW Four-Wire SIAC-B, proceed to Step 10; if
                wiring a 93PM 150 kW Three-Wire SIAC-B or 93PM 150 kW Four-Wire SIAC-B, proceed to Step 15.
          10. Locate the external wiring terminal hardware kit packed at the bottom of the SIAC-B.
          11. Using hardware from the external wiring terminal hardware kit, connect phase A, B, and C, and Ground
              bypass input power wiring from the utility source to the SIAC-B maintenance bypass input terminals. See
              paragraph 3.3.3 SIAC-B Power Wiring Preparation, Table 2 or Table 3 and Table 6 through Table 9 for SIAC-
              B wiring and termination requirements.
                For SIAC-B terminal phase wiring assignments, see Figure 36 or Figure 37.
          12. Using hardware from the external wiring terminal hardware kit, connect phase A, B, and C, and Ground
              output power wiring from the SIAC-B output terminals to the critical load.
                For SIAC-B terminal phase wiring assignments, see Figure 36 or Figure 37.
          13. If an RIB is installed, use hardware from the external wiring terminal hardware kit to connect phase A, B,
              and C, and Ground rectifier input power wiring from the utility source to the SIAC-B rectifier input
              terminals.
                For a detailed view of the SIAC-B RIB terminals, see Figure 38.
          14. Proceed to Step 18.
          15. Connect phase A, B, and C, Ground, and if required Neutral bypass input power wiring from the utility
              source to the SIAC-B maintenance bypass input terminals.
                For SIAC-B terminal phase wiring assignments, see Figure 34 or Figure 35.
          16. Connect phase A, B, and C, Ground, and if required Neutral output power wiring from the SIAC-B output
              terminals to the critical load or Integrated Accessory Cabinet-Distribution (IAC-D). Refer to the Eaton 93PM
              Integrated Accessory Cabinet-Distribution (50 kW, 100 kW, 150 kW, and 200 kW IAC-D) Installation and
              Operation Manual, listed in paragraph 1.7 For More Information, for conduit and terminal locations and
              termination requirements.
                For SIAC-B terminal phase wiring assignments, see Figure 34 or Figure 35.
          17. If an RIB is installed, connect phase A, B, and C, and Ground rectifier input power wiring from the utility
              source to the SIAC-B rectifier input terminals.
                For a detailed view of the SIAC-B RIB terminals, see Figure 38.
          18. Reinstall the internal safety shield panel and secure with retained screws.
          19. Reinstall the SIAC-B front panel and secure with retained screw.
          20. After the SIAC-B is wired, return to the applicable Eaton 93PM UPS installation and operation manual,
              listed in paragraph 1.7 For More Information, to complete the UPS wiring.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             55
Installation
Figure 32. 93PM 150 kW Three-Wire and Four-Wire SIAC-B Conduit Landing Wire Entry Locations
                                                                                    Top
                                                                                    View
                                   Front                                                                                    Front
                                                                           Top Entry Conduit Landing
                                                                            (Remove plate to drill or
                      UPS with Left-Mounted SIAC-B                            punch conduit holes.)            UPS with Right-Mounted SIAC-B
Front Front
                                                                                  Bottom
                                                                                   View
56                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                         Installation
Figure 33. 93PM 200 kW Three-Wire and Four-Wire SIAC-B Conduit Landing Wire Entry Locations
                                                                                 Top
                                                                                 View
                               Front                                                                              Front
                                                                         Top Entry Conduit Landing
                                                                          (Remove plate to drill or
                                                                            punch conduit holes.)
                   UPS with Left-Mounted SIAC-B                                                       UPS with Right-Mounted SIAC-B
Front Front
                                                                               Bottom
                                                                                View
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             57
Installation
Figure 34. 93PM 150 kW Three-Wire and Four-Wire SIAC-B Left-Mounted Bypass — Terminal Locations
                           AC Input to
                           UPS Rectifier
                           (Source 1)
                           A, B, C
                                                                                                                     Phase A (E9)
                                                                                                                                           AC Output
                                                                                                                     Phase B (E10)         to Critical Load
Phase C (E11)
Front
58                   Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                                  Installation
Figure 35. 93PM 150 kW Three-Wire and Four-Wire SIAC-B Right-Mounted Bypass — Terminal Locations
                                AC Input to
                                UPS Rectifier
                                (Source 1)
                                A, B, C
                                     Phase A (E9)
               AC Output
                                     Phase B (E10)
               to Critical Load
                                     Phase C (E11)
Front
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                      59
Installation
Figure 36. 93PM 200 kW Three-Wire and Four-Wire SIAC-B Left-Mounted Bypass — Terminal Locations
                           AC Input to
                           UPS Rectifier
                           (Source 1)
                           A, B, C
Phase A (E9)
Ground Terminals
Front
60                   Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                                  Installation
Figure 37. 93PM 200 kW Three-Wire and Four-Wire SIAC-B Right-Mounted Bypass — Terminal Locations
                                AC Input to
                                UPS Rectifier
                                (Source 1)
                                A, B, C
                                       Phase A (E9)
             AC Output
             to Critical Load          Phase B (E10)
Phase C (E11)
Ground Terminals
Front
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                       61
Installation
                                                                                                Phase A
                                                                                                              AC Input to
                                                                                                Phase B       UPS Rectifier
                                                                                                              (Source 1)
                                                                                                Phase C
RIB
               After the installation is complete, an Eaton Customer Service Engineer must verify the operation of the UPS
               system and commission it to support the critical load. The service representative cannot perform any
               installation tasks other than verifying software and operating setup parameters. Service personnel may request
               a copy of the completed Installation Checklist to verify all applicable equipment installations have been
               completed.
                         NOTE             The Installation Checklist MUST be completed prior to starting the UPS system for the
                                          first time.
62                   Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                         Installation
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09             63
Installation
Notes
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
64                     Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
Chapter 5 Onelines and Schematics
5.1   Onelines
                Figure 39, Figure 40, and Figure 41 show the simplified internal structure of the Sidecar Integrated Accessory
                Cabinet-Bypass (SIAC-B) for the following configurations:
                •     Two-breaker Maintenance Bypass with a Maintenance Isolation Breaker (MIS) and a Maintenance Bypass
                      Breaker (MBP)
                •     Three-breaker Maintenance Bypass with a MIS, a MBP, and a Bypass Input Breaker (BIB)
                •     Four-breaker Maintenance Bypass with a MIS, a MBP, a BIB, and a Rectifier Input Breaker (RIB)
                           480V 3-Phase
                           Input from
                           UPS Inverter
                           Output
                                                                                      MBP
                                             A                                                                                                 C
                           480V 3-Phase                                                                                                            480V 3-Phase
                           Input to                           Input                                                         Output                 SIAC-B Output
                           Maintenance                      Terminals                                                      Terminals               to Critical Load
                           Bypass
      Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                          65
Onelines and Schematics
                    480V 3-Phase
                    Input from
                    UPS Inverter
                    Output
                                                                               MBP
                                       A                                                                                                   C
                    480V 3-Phase                                                                                                                 480V 3-Phase
                    Input to                           Input                                                        Output                       SIAC-B Output
                    Maintenance                      Terminals                                                     Terminals                     to Critical Load
                    Bypass                                                     BIB
                                                                                                                                                 480V 3-Phase
                                                                                                                                                 Output to UPS
                                                                                                                                                 Bypass Input
66                Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                      Onelines and Schematics
                           480V 3-Phase
                           Input from
                           UPS Inverter
                           Output
                                                                                      MBP
                                             A
                           480V 3-Phase                                                                                                            480V 3-Phase
                           Input to                           Input                                                       Output                   SIAC-B Output
                           Maintenance                      Terminals                                                    Terminals                 to Critical Load
                           Bypass                                                     BIB                                                      C
                                                                                                                                                   480V 3-Phase
                                                                                                                                                   Output to UPS
                                                                                                                                                   Bypass Input
                                             B           RIB
Voltage
                        See Figure 42               93PM-150 3-                480                   480            Single reverse transfer three-wire UPS with
                                                       Wire                                                         external battery and two-breaker three-wire
                                                    93PM-200 3-                                                     SIAC-B
                                                       Wire
                        See Figure 43               93PM-150 3-                480                   480            Single reverse transfer three-wire UPS with
                                                       Wire                                                         external battery and three-breaker three-wire
                                                    93PM-200 3-                                                     SIAC-B
                                                       Wire
                        See Figure 44               93PM-150 3-                480                   480            Single reverse transfer three-wire UPS with
                                                       Wire                                                         external battery and four-breaker three-wire
                                                    93PM-200 3-                                                     SIAC-B
                                                       Wire
      Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                          67
Onelines and Schematics
Voltage
                  See Figure 45             93PM-150 4-                 480                   480           Single reverse transfer four-wire UPS with
                                               Wire                                                         external battery and two-breaker four-wire
                                            93PM-200 4-                                                     SIAC-B
                                               Wire
                  See Figure 46             93PM-150 4-                 480                   480           Single reverse transfer four-wire UPS with
                                               Wire                                                         external battery and three-breaker four-wire
                                            93PM-200 4-                                                     SIAC-B
                                               Wire
                  See Figure 47             93PM-150 4-                 480                   480           Single reverse transfer four-wire UPS with
                                               Wire                                                         external battery and four-breaker four-wire
                                            93PM-200 4-                                                     SIAC-B
                                               Wire
68                Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                Onelines and Schematics
Figure 42. Eaton 93PM 150 kW or 200 kW UPS with Two-Breaker SIAC-B (Three-Wire) — System Online
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09               69
Onelines and Schematics
             Figure 43. Eaton 93PM 150 kW or 200 kW UPS with Three-Breaker SIAC-B (Three-Wire) — System
             Online
70                Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                Onelines and Schematics
Figure 44. Eaton 93PM 150 kW or 200 kW UPS with Four-Breaker SIAC–B (Three-Wire) — System Online
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09               71
Onelines and Schematics
Figure 45. Eaton 93PM 150 kW or 200 kW UPS with Two-Breaker SIAC-B (Four-Wire) — System Online
72                Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                Onelines and Schematics
Figure 46. Eaton 93PM 150 kW or 200 kW UPS with Three-Breaker SIAC-B (Four-Wire) — System Online
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09               73
Onelines and Schematics
Figure 47. Eaton 93PM 150 kW or 200 kW UPS with Four-Breaker SIAC-B (Four-Wire) — System Online
74                 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                Onelines and Schematics
Figure 48. Eaton 93PM 150 kW or 200 kW Three-Wire SIAC-B — Two-Breaker Schematic
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09               75
Onelines and Schematics
Figure 49. Eaton 93PM 150 kW or 200 kW Three-Wire SIAC-B — Three-Breaker Schematic
76                Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                      Onelines and Schematics
Figure 50. Eaton 93PM 150 kW or 200 kW Three-Wire SIAC-B — Four-Breaker Schematic
      Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09               77
Onelines and Schematics
Figure 51. Eaton 93PM 150 kW or 200 kW Four-Wire SIAC-B — Two-Breaker Schematic
78                Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                                Onelines and Schematics
Figure 52. Eaton 93PM 150 kW or 200 kW Four-Wire SIAC-B — Three-Breaker Schematic
                                                                                                                                         Output
                      Output
         NEUTRAL INPUTS                                                                                                                             TO UPS NEUTRAL
                          Bypass                                                                                                         Bypass
              TO UPS GROUND
                                                                                                                                                  BLDG ALARM 1
             TO LOAD GROUND                                                                                                                       OF UPS1
      FROM BUILDING GROUND
                   LEGEND
                                    Factory Wiring                 Customer Wiring
                                    (105˚C Insulation)             (75˚C Insulation)
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                               79
Onelines and Schematics
Figure 53. Eaton 93PM 150 kW or 200 kW Four-Wire SIAC-B — Four-Breaker Schematic
80                Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
Chapter 6 SIAC-B Operating Instructions
This section describes how to operate the Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B).
                             NOTE 1           Before using the SIAC-B, ensure all installation tasks are complete and a preliminary
                                              startup has been performed by authorized service personnel. The preliminary startup
                                              verifies all electrical interconnections to ensure the installation was successful and the
                                              system operates properly.
                             NOTE 2           Read this section of the manual and have thorough knowledge of UPS and SIAC-B
                                              operation before attempting to operate any of the controls.
                •     Maintenance Bypass Breaker – The Maintenance Bypass Breaker (MBP) transfers the load from the UPS
                      output to the bypass input feeder.
                •     Maintenance Isolation Breaker – The Maintenance Isolation Breaker (MIS) isolates the UPS from the
                      bypass feed and the load.
                •     Bypass Input Breaker – (Optional – only three and four breaker configurations) The Bypass Input Breaker
                      (BIB) provides a single point of input power control to the UPS on single-feed systems or bypass input
                      power control to the UPS on dual-feed systems. Using the BIB easily removes power from the UPS for
                      servicing.
                •     Rectifier Input Breaker – (Optional – only four breaker configurations) The optional Rectifier Input Breaker
                      (RIB) (four-breaker version only) provides a single point of rectifier input power control to the UPS on dual-
                      feed systems and easily removes power from the UPS for servicing.
                        MBP                                                                                                            OPEN
                        MIS                                                                                                           CLOSED
                        BIB (if installed)                                                                                            CLOSED
                        RIB (if installed)                                                                                            CLOSED
                6.    Start the UPS. Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in
                      paragraph 1.7 For More Information, for UPS operating procedures.
      Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09   81
SIAC-B Operating Instructions
7. Reinstall the SIAC-B front panel and secure with retained screw.
Figure 54. Eaton 93PM 150 kW or 200 kW SIAC-B (Three or Four Wire) Breakers – Left-Mounted SIAC-B
RIB (optional)
BIB (optional)
               Bypass Interlock
               Plate
MBP
MIS
SIAC-B UPS
82                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                         SIAC-B Operating Instructions
Figure 55. Eaton 93PM 150 kW or 200 kW SIAC-B (Three or Four Wire) Breakers – Right-Mounted SIAC-B
BIB (optional)
RIB (optional)
                                                                                                                                    Bypass Interlock
                                                                                                                                    Plate
MIS
MBP
UPS SIAC-B
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09                 83
SIAC-B Operating Instructions
                                                                                       CAUTION
              Only trained personnel familiar with the operation of this equipment should transfer loads. Failure to follow this
              transfer sequence may cause loss of power to loads.
                                                                                       CAUTION
              In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
                                                                                       CAUTION
              Failure to close the MBP before opening the MIS will result in the loss of power to the critical load.
                                                                                       WARNING
              The BIB and RIB (if installed) or the bypass feeder breaker must be opened to electrically isolate the UPS.
                                                                                       CAUTION
              Only trained personnel familiar with the operation of this equipment should transfer loads. Failure to follow this
              transfer sequence may cause loss of power to loads.
              1.   Remove the screw securing the bottom of the SIAC-B front panel. Lift the panel straight up to remove it
                   from the panel hanger bracket at the top of the cabinet. Retain screw for later use.
              2.   If installed, close the BIB.
              3.   If installed, close the RIB.
84                    Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
                                                                                                                         SIAC-B Operating Instructions
          4.    Start the UPS in bypass mode. Refer to the applicable Eaton 93PM UPS Installation and Operation manual,
                listed in paragraph 1.7 For More Information, for UPS operating procedures.
                                                                                    CAUTION
          Failure to close the MIS before opening the MBP will result in the loss of power to the critical load.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09              85
SIAC-B Operating Instructions
86                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
Chapter 7 Maintenance
                 The components inside the Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) is secured to a sturdy metal
                 frame. All repairable parts and assemblies are located for easy removal, with very little disassembly. This
                 design allows authorized service personnel to perform routine maintenance and servicing quickly.
                 You must schedule periodic performance checks of the UPS system to keep it running properly. Regular
                 routine checks of operation and system parameters enable your system to function efficiently for many trouble-
                 free years.
WARNING
                 1.    Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the
                       unit.
                 2.    Ensure the air intakes on the Accessory cabinets are not blocked.
                 3.    Ensure the operating environment is within the parameters specified in paragraph
                       3.3.1 Environmental and Installation Considerations and Chapter 8 Product Specifications.
       Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09   87
Maintenance
88                  Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
Chapter 8 Product Specifications
                 •      Model numbers
                 •      Input specifications
                 •      Output specifications
                 •      Environmental and safety specifications
Eaton 93PM 150 kW Three-Wire SIAC-B SIAC-B for the Eaton 93PM 150 kW Capacity Three-Wire UPS
                     Eaton 93PM 200 kW Three-Wire SIAC-B                                       SIAC-B for the Eaton 93PM 200 kW Three-Wire UPS
                     Eaton 93PM 200 kW Four-Wire SIAC-B                                         SIAC-B for the Eaton 93PM 200 kW Four-Wire UPS
8.2   Specifications
                 The following sections detail the input, output, and environmental and safety specifications for the SIAC-B.
8.2.1 Input
8.2.2 Output
       Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09       89
Product Specifications
               Ventilation                                          Convection
               Relative Humidity (operating and                     5% to 95% maximum noncondensing
               storage)
90                    Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09
Chapter 9 Warranty
For warranty information, please refer to the Resources link on our website, www.eaton.com/93PM.
               EQUIPMENT REGISTRATION
               Please visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory.
Model Number:
Serial Number:
     Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 09   91
P-16400038709
    P-164000387 09