0% found this document useful (0 votes)
8 views1 page

Fault On LVbus16.SQ2S - Sequence of Operation

The document is a Sequence-of-Operation Event Summary Report detailing a symmetrical 3-phase fault at Bus16. It includes specific data on current, time, and conditions for circuit breakers and relays involved in the fault. Key events are recorded at various time intervals, indicating the operational response of the system components.

Uploaded by

IGHORODJE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views1 page

Fault On LVbus16.SQ2S - Sequence of Operation

The document is a Sequence-of-Operation Event Summary Report detailing a symmetrical 3-phase fault at Bus16. It includes specific data on current, time, and conditions for circuit breakers and relays involved in the fault. Key events are recorded at various time intervals, indicating the operational response of the system components.

Uploaded by

IGHORODJE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Project: ETAP Page: 1

Location: 19.0.1C Date: 25-04-2025

Contract: SN:

Engineer: Revision: Base


Study Case: SM
Filename: UGHELLI EAST FIELD POWER NTWK Config.: Normal

Sequence-of-Operation Event Summary Report

Symmetrical 3-Phase Fault at Bus16.

Time (ms) ID If (kA) T1 (ms) T2 (ms) Condition


140 CB08 7.642 80.0 140 Phase

200 CB03 7.642 140 200 Phase

1543 Relay2 0.095 1543 Phase - OC1 - 51

1563 CB02 20.0 Tripped by Relay2 Phase - OC1 - 51