The document provides a short-circuit summary report detailing fault currents for Bus16, including 3-phase, line-to-ground, line-to-line, and line-to-line-to-ground fault currents. It also includes a sequence impedance summary report with positive, negative, and zero sequence impedances for the same bus. Additionally, a sequence-of-operation event summary report outlines the timing and conditions of a symmetrical 3-phase fault at Bus16.

Uploaded by

IGHORODJE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2 views3 pages

Fault On LVbus16.SQ2S - Summary

The document provides a short-circuit summary report detailing fault currents for Bus16, including 3-phase, line-to-ground, line-to-line, and line-to-line-to-ground fault currents. It also includes a sequence impedance summary report with positive, negative, and zero sequence impedances for the same bus. Additionally, a sequence-of-operation event summary report outlines the timing and conditions of a symmetrical 3-phase fault at Bus16.

Uploaded by

IGHORODJE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Project: ETAP Page: 1

Location: 19.0.1C Date: 25-04-2025

Contract: SN:

Engineer: Revision: Base


Study Case: SM
Filename: UGHELLI EAST FIELD POWER NTWK Config.: Normal

Short-Circuit Summary Report

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib Ik I"k ip Ib Ik

Bus16 0.400 7.660 11.075 7.642 6.505 9.405 6.505 6.505 6.633 9.591 6.633 6.633 7.268 10.509 7.268 7.268

All fault currents are in rms kA. Current ip is calculated using Method C.

* LLG fault current is the larger of the two faulted line currents.
Project: ETAP Page: 2

Location: 19.0.1C Date: 25-04-2025

Contract: SN:

Engineer: Revision: Base


Study Case: SM
Filename: UGHELLI EAST FIELD POWER NTWK Config.: Normal

Sequence Impedance Summary Report

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)

ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus16 0.400 0.02945 0.01163 0.03166 0.02945 0.01163 0.03166 0.04565 0.01648 0.04853 0.00000 0.00000 0.00000
Project: ETAP Page: 3

Location: 19.0.1C Date: 25-04-2025

Contract: SN:

Engineer: Revision: Base


Study Case: SM
Filename: UGHELLI EAST FIELD POWER NTWK Config.: Normal

Sequence-of-Operation Event Summary Report

Symmetrical 3-Phase Fault at Bus16.

Time (ms) ID If (kA) T1 (ms) T2 (ms) Condition


140 CB08 7.642 80.0 140 Phase

200 CB03 7.642 140 200 Phase

1543 Relay2 0.095 1543 Phase - OC1 - 51

1563 CB02 20.0 Tripped by Relay2 Phase - OC1 - 51