0% found this document useful (0 votes)
35 views2 pages

SLD & Panel Scheduiles 00000 CGG Nc1 XXX DWG El Xx0001

The document outlines electrical equipment specifications and configurations for a construction project, including tentative sizes and load categories. It details the naming conventions for electrical equipment, panel schedules, and cable sizes, emphasizing flexibility for load adjustments. Additionally, it includes notes on installation requirements and references to specific drawings and standards.

Uploaded by

mahmoud.gomaa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views2 pages

SLD & Panel Scheduiles 00000 CGG Nc1 XXX DWG El Xx0001

The document outlines electrical equipment specifications and configurations for a construction project, including tentative sizes and load categories. It details the naming conventions for electrical equipment, panel schedules, and cable sizes, emphasizing flexibility for load adjustments. Additionally, it includes notes on installation requirements and references to specific drawings and standards.

Uploaded by

mahmoud.gomaa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

1 2 3 4 5 6

REFERENCE DRAWINGS DWG NO.

NOTES:

1- ALL ELECTRICAL EQUIPMENT SIZES ARE TENTATIVE


ONLY AND SUBJECT TO CHANGE AS PER FINAL LOAD
SCHEDULE CALCULATED BY THE CONSTRUCTION
CONTRACTOR DURING EXECUTION.

2- THE CABLE SIZE IS BIGGER FORV FEATURE FLEXIBILITY


AND MAXIMUM LOAD

THE SPACE ACCOMMODATION IS ONLY


REQUIRED FOR SPARE SEC KWH
METERS AND CIRCUIT BREAKERS

ELECTRICAL EQUIPMENT NAMING CONVENTION:


POWER METER CENTER (AS PER SEC STANDARD)
D D
METER FRAME (40 CM X96.5 CM) NC1 - PP BGF - EL 1
BY INFRASTRUCTURE BY CONTRACTOR (TYPICAL)
PANEL NUMBER: (1,2,3...10)
CONTRACTOR
SPACE SPACE SPACE SPACE CIRCUIT BREAKER LOAD CATEGORY:
C.B C.B C.B C.B NL - NORMAL LOAD
EL - EMERGENCY LOAD
UL - UNINTERRUPTIBLE POWER SUPPLY LOAD
EQ - EMERGENCY EQUIPMENT LOAD
POWER METER ELECTRICAL EQUIPMENT LOCATION & LEVEL:
M M M M SPACE SPACE SPACE SPACE BASE
SPARE (TYPICAL) B01 - BUILDING BASEMENT FOOR
KWH-M KWH-M KWH-M KWH-M KWH-M KWH-M KWH-M KWH-M BGF - BUILDING GROUND FLOOR
30 A 30 A 30 A 30 A BRF - BUILDING ROOF FLOOR
POWER KILO-WATT
HOUR LOAD SERVED:
METER (TYPICAL)
PP - POWER PANELBOARD
LP - LIGHTING PANELBOARD
TAPPING POINT BY INFR .CONTRACTOR BY CONTRACTOR
PL - COMBINATION OF LIGHTING & POWER
2 (4 X 300mm2) (AL / XLPE / PVC) PANELBOARD
MDP - MAIN DISTRIBUTION PANEL
DP - DISTRIBUTION PANEL
ATS - AUTOMATIC TRANSFER SWITCH
RMU - RING MAIN UNIT
TR - TRANSFORMER
UPS - UNINTERRUPTIBLE POWER SUPPLY
SPACE SPACE SPACE EMDP - EMERGENCY MAIN DISTRIBUTION PANEL
M M M M M M BUILDING/AREA SERVED:
INCOMING
KWH-M KWH-M KWH-M KWH-M KWH-M KWH-M KWH-M KWH-M KWH-M
30 A 30 A 30 A 30 A 150 A 100 A NC1 - NEIGHBORHOOD COMMUNITY
SERVICE

SPACE SPACE SPACE CIRCUIT BREAKER


KEY PLAN
C.B C.B C.B

C C
B

M.R A.Y M.S H.O M.H M.H ISSUED FOR DETAILED DESIGN APR. 2024 00-DD
30AT 30AT 30AT 30AT 30AT 30AT 30AT 30AT 150AT SPACE SPACE SPACE SPACE SPACE SPACE SPACE
100AT D.D T.D APP. CHK. DRW. DES. ISSUNING DATE REV
30AF 30AF 30AF 30AF 30AF 30AF 30AF 30AF 250AF 100AF BY BY BY BY

PROJECT TITLE :

THIS DRAWING IS COPYRIGHT AND MUST NOT BE REPRODUCED WITHOUT THE WRITTEN CONSENT OF THE CONSULTANT.
PROTOTYPE DESIGNS FOR PUBLIC
AMENITY BUILDINGS

(4x50mm 2) CU/XLPE/PVC
BUILDING NAME :
(4x25mm 2) CU/XLPE/PVC

(4x25mm 2) CU/XLPE/PVC

(4x25mm 2) CU/XLPE/PVC

(4x25mm 2) CU/XLPE/PVC

(4x25mm 2) CU/XLPE/PVC

(4x25mm 2) CU/XLPE/PVC

(4x25mm 2) CU/XLPE/PVC

(4x25mm 2) CU/XLPE/PVC

(4x70mm 2) CU/XLPE/PVC

CU/PVC
CU/PVC

CU/PVC

CU/PVC

CU/PVC

CU/PVC

CU/PVC

CU/PVC

CU/PVC

CU/PVC
NEIGHBORHOOD COMMUNITY CENTER
(NC1)

2
+E25 mm
2

2
+E16 mm

+E16 mm

+E16 mm

+E16 mm

+E16 mm

+E16 mm

+E16 mm

+E16 mm

+E35mm
CLIENT :

RT-01 RT-02 RT-03 RT-04 RT-05 RT-06 RT-07 RT-08 RT - 09


TCL=22 KVA TCL=22 KVA TCL=22 KVA TCL=22 KVA TCL=22 KVA TCL=22 KVA TCL=22 KVA TCL=22 KVA TCL=75 KVA
TDL=13.2KVA TDL=13.2KVA TDL=13.2KVA TDL=13.2KVA TDL=13.2KVA TDL=13.2KVA TDL=13.2KVA TDL=13.2KVA TDL=45KVA

NC1-DPBGF-NL-1
SPACE ONLY
BY INFRASTRUCTURE BY CONTRACTOR TCL= 87.8 KVA ROSHN REAL ESTATE COMPANY (RRE)
CONTRACTOR TDL= 78.5 KVA 150 AT
250 AF

MAIN CONSULTANT : B
B 30AT 50AT 30AT 50AT 50AT 30AT 30AT 50AT
100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF
3P 3P 3P 3P 3P 3P 3P 3P 3P 3P
(4x10mm 2) CU/XLPE/PVC
(4x16mm 2) CU/XLPE/PVC

) CU/XLPE/PVC

50 mm UPVC PIPE FOR EV

50 mm UPVC PIPE FOR EV


(4x6mm 2) CU/XLPE/PVC
C:\Users\mohamed.elbashir.CGCairo\Documents\00000-CGG-NC1-ZZZ-PIM-EL-000000_mfikryEB95J.rvt

CU/PVC
CU/PVC

CU/PVC
CU/PVC

SPARE

SPARE

SPACE
CHARGER CABLE

CHARGER CABLE
2

2
2
2

+E6 mm 2
+E16 mm
+E6 mm

+E6 mm
(4x6mm

DISCIPLINE

E.O TCL=23.2 KVA


E.O TCL=23.2 KVA
E.O TCL=10.00 KVA ELECTRICAL
TDL=23.2 KVA TDL=23.2 KVA TDL=10.00 KVA
NC1-PPB01-NQ-1 NC1-PLBGF-NL-1 NC1-PLBGF-NL-2
TCL=6.7 KVA TCL=21.1 KVA TCL=3.6 KVA SHEET TYPE
TDL=5.2 KVA TDL=13.4 KVA TDL=3.5 KVA FOR FOOD TRUCK @LANDSCAPE
(FOR PUMP ROOM ) (FOR (FOR LANDSCAPE )
LIGHTNG & FOR 1 EV CHARGER @LANDSCAPE SCHEMATIC DIAGRAMS
POWER ) PARKING AREA
FOR 1 EV CHARGER @LANDSCAPE
PARKING AREA SHEET TITLE :

POWER SINGLE LINE DIAGRAM

DRAWING NUMBER
SCALE SIZE REVISION
PROJECT NO. BLDG CODE SHEET NO.

00000 NC1 080001 N.T.S A1 00-DD

POWER SINGLE LINE DIAGRAM DRAWING NO :

A
A1 N.T.S
00000-CGG-NC1- XXX-DWG- EP- 080001
A
1 2 3 4 5 6 SHEET SIZE - ISO A1 841*594 MM
1 2 3 4 5 6

REFERENCE DRAWINGS DWG NO.

PANEL SCHEDULE (EU) 00000-CGG-NC1-XXX-DWG-EU-080001

PANEL BOARD SCHEDULE PANEL BOARD SCHEDULE


according to IEC & Master Specs according to IEC & Master Specs

Panel NO : NC1-PPB01-NQ-1 LOCATION PUMP ROOM BA 01 Panel NO : NC1-PLBGF-NL-1 LOCATION ELEC. ROOM GR 14
Mains Rating Distribution System Enclosure Mains Rating Distribution System Enclosure
Fed From: NC1-DPBGF-NL-1 Main C.B 30A MCCB 230/400 Wye V Flush Fed From: NC1-DPBGF-NL-1 Main C.B 50 A MCCB 230/400 Wye V Flush NOTES:
10 KA 10 KA
Cable Size: 1 // (4x6)+6 CU/XLPE/PVC Cable Size: 1 // (4x16)+16 CU/XLPE/PVC 1- FOR LANDSCAPE PANEL SCHEDULE (NC1-PLBGF-NL-2)
REFER TO SHEET NO: (00000-CGG-NC1-INF-DWG-EU-010004)
Wire/ Wire/
Conduit Conduit Conduit Conduit
Circuit Circuit Cable Circuit Circuit Cable
Size LOAD DESCRIPTION Cable Size Rating R Y B R Y B Rating Cable Size LOAD DESCRIPTION Size Size LOAD DESCRIPTION Rating A B C A B C Rating LOAD DESCRIPTION Size
Number Number Size(mm Number Number Size(mm
(mm) (mm) (mm) (mm)
2) 2)
20 Lighting 3*2.5 16 A 1 64 540 2 20 A 2X4+2.5 Sockets * 25 25 EF-02 2X4+2.5 20 A 1 141 180 2 20 A 2X4+2.5 Sockets * 25
25 EF-04 (HVAC) 2X4+2.5 20 A 3 611 622 4 32 SPU-02 (STAND-BY) 2X6+4 30 A 3 0 107 4 16 A 3X2.5 EXIT SIGN 20
(4*4)+ 4
25 FAF-02 (HVAC) 20 A 5 611 622 6 20 A FOR IRR .PUMP SET 25 25 EF-03 2X4+2.5 20 A 5 141 231 6 16 A 3X2.5 Lighting 20
CU/XLPE/PVC
7 500 622 8
(4*4)+ 4 25 EF-01 2X4+2.5 20 A 7 294 311 8 16 A 3X2.5 Lighting*** 20
25 FOR SUMP PIT SET 20 A 9 500 0 10 20 A -- Spare --
CU/XLPE/PVC 20 Lighting** 3X2.5 16 A 9 127 231 10 16 A 3X2.5 Lighting 20
11 500 0 12 20 A -- Spare --
13 500 -- 14 -- -- Space -- 20 Lighting 3X2.5 16 A 11 286 1500 12 20 A 2X4+2.5 EWH * 25
(4*4)+ 4 20 Lighting*** 3X2.5 16 A 13 311 720 14 20 A 2X4+2.5 Sockets * 25
25 FOR BOOSTER.PUMP SET 20 A 15 500 -- 16 -- -- Space --
CU/XLPE/PVC
17 500 -- 18 -- -- Space -- 25 Sockets 2X4+2.5 20 A 15 1080 4118 16 30 A 2X6+4 SPU-02 32
2226 VA 2233 VA 2233 VA 25 Sockets 2X4+2.5 20 A 17 900 1000 18 20 A 2X4+2.5 FACP 25
25 HAND DRYER* 2X4+2.5 20 A 19 1500 1500 20 20 A 2X4+2.5 E.W.H * 25
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals 25 HAND DRYER * 2X4+2.5 20 A 21 1500 0 22 20 A -- Spare --
Mechanical Equipment 3365 VA 80.00% 2692 VA Connected Load 6692 VA 25 Sockets 2X4+2.5 20 A 23 1080 1875 24 30 A 2X6+4 SPU-01 32
HVAC 2722 VA 80.00% 2178 VA Demand Factor 77.77%
D 32 IT RACK 2X6+4 30 A 25 2000 0 26 20 A -- Spare -- D
Lighting 64 VA 100.00% 64 VA Demand Load 5204 VA
-- Spare -- 20 A 27 0 0 28 20 A -- Spare --
Sockets 540 VA 50.00% 270 VA
-- Space -- -- 29 -- -- 30 -- -- Space --
6958 VA 7163 VA 7013 VA

Notes: Remarks: Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(*) Means C.B will be protected with RCCB devices of trip rating 30mA HVAC 6569 VA 80.00% 5255 VA Connected Load 21133 VA
Lighting 1604 VA 100.00% 1604 VA Demand Factor 63.59%
Sockets 7960 VA 50.00% 3980 VA Demand Load 13439 VA
IT 2000 VA 100.00% 2000 VA
E.W.H 3000 VA 20.00% 600 VA

Notes: Remarks:
(*) Means C.B will be protected with RCCB devices of trip rating 30mA
(**) Means circuit will be controlled with motion sensor check details 05000
(***) Means circuit will be controlled by Photocell (At Roof) and by Contactor,Timer and Push Button
(Inside Electrical Panel Board)

NC ( NEIGHBORHOOD COMMUNITY CENTER )


VOLTAGE DROP & SHORT CIRCUIT CALCULATION KEY PLAN

C TRIP C
B
FRAME
CONNECTE DEMAND RATING It (A) %VD IS.C (short
Feeder POWER DEMAND RATING In(A) CABLE Length No.of Cable XLPE/ CCC mV/A/m Or %VD (Not Z cable Z total M.R A.Y M.S H.O M.H M.H ISSUED FOR DETAILED DESIGN APR. 2024 00-DD
From To Voltage D Phase 3/1 CURRENT Ib*1.25 Ir (A) I2 (A) Installation Iz(A) Iz ≥ Ir I2 ≤ 1.45 Iz (Accumulati circuit current) D.D T.D APP. CHK. DRW. DES. ISSUNING DATE REV
No. FACTOR Load (KW) TYPE (m) //Cables Size,mm2/A PVC (A) (mΩ/m) Accumulative) (mΩ) (mΩ) BY BY BY BY
Load (KW) Ib (A) ve) kA
In In It PROJECT TITLE :

THIS DRAWING IS COPYRIGHT AND MUST NOT BE REPRODUCED WITHOUT THE WRITTEN CONSENT OF THE CONSULTANT.
PROTOTYPE DESIGNS FOR PUBLIC
ELECTRICAL METER AMENITY BUILDINGS
ELECTRICAL 19.05 SUCCEE BUILDING NAME :
F1 RT-01 400 0.85 18.7 11.22 3 19.05 23.82 30 30 43.5 MC 45 1 25 XLPE GROUND 143 143 SUCCEED 1.39 0.422 0.58 40.53 49.40 4.656
METER 256 D NEIGHBORHOOD COMMUNITY CENTER
(NC1)
ELECTRICAL 19.05 SUCCEE
F2 RT-02 400 0.85 18.7 11.22 3 19.05 23.82 30 30 43.5 MC 53 1 25 XLPE GROUND 143 143 SUCCEED 1.39 0.497 0.65 47.74 56.60 4.063
METER 256 D CLIENT :

ELECTRICAL 19.05 SUCCEE


F3 RT-03 400 0.85 18.7 11.22 3 19.05 23.82 30 30 43.5 MC 61 1 25 XLPE GROUND 143 143 SUCCEED 1.39 0.572 0.73 54.94 63.81 3.605
METER 256 D

ELECTRICAL 19.05 SUCCEE


F4 RT-04 400 0.85 18.7 11.22 3 19.05 23.82 30 30 43.5 MC 65 1 25 XLPE GROUND 143 143 SUCCEED 1.39 0.610 0.76 58.55 67.41 3.412
METER 256 D

ELECTRICAL 19.05 SUCCEE


F5 RT-05 400 0.85 18.7 11.22 3 19.05 23.82 30 30 43.5 MC 48 1 25 XLPE GROUND 143 143 SUCCEED 1.39 0.450 0.60 43.23 52.10 4.415
METER 256 D

ELECTRICAL 19.05 SUCCEE ROSHN REAL ESTATE COMPANY (RRE)


F6 RT-06 400 0.85 18.7 11.22 3 19.05 23.82 30 30 43.5 MC 46 1 25 XLPE GROUND 143 143 SUCCEED 1.39 0.431 0.59 41.43 50.30 4.573
METER 256 D
MAIN CONSULTANT : B
B ELECTRICAL 19.05 SUCCEE
F7 RT-07 400 0.85 18.7 11.22 3 19.05 23.82 30 30 43.5 MC 38 1 25 XLPE GROUND 143 143 SUCCEED 1.39 0.356 0.51 34.23 43.09 5.337
METER 256 D

ELECTRICAL 19.05 SUCCEE


F8 RT-08 400 0.85 18.7 11.22 3 19.05 23.82 30 30 43.5 MC 30 1 25 XLPE GROUND 143 143 SUCCEED 1.39 0.281 0.44 27.02 35.89 6.409
METER 256 D
C:\Users\mohamed.elbashir.CGCairo\Documents\00000-CGG-NC1-ZZZ-PIM-EL-000000_mfikryEB95J.rvt

ELECTRICAL 64.95 SUCCEE


F9 RT-09 400 0.85 63.75 38.25 3 64.95 81.19 100 100 145 MC 36 1 50 XLPE GROUND 205 205 SUCCEED 0.79 0.651 0.80 16.25 25.12 9.157
METER 191 D

ELECTRICAL 113.3 SUCCEE


F10 NC1-DPBGF-NL-1 400 0.85 74.63 66.725 3 113.30 141.63 250 150 217.5 MC 15 1 70 XLPE GROUND 252 252 SUCCEED 0.57 0.232 0.39 4.85 13.72 16.768 DISCIPLINE
METER 05 D

NC1-DPBGF-N NC1-PPB01-NQ 7.505 SUCCEE


ELECTRICAL
F11 400 0.85 5.695 4.42 3 7.51 9.38 100 30 43.5 MC 55 1 6 XLPE GROUND 64 64 SUCCEED 5.57 0.630 0.78 206.26 215.12 1.069
L-1 -1 554 D
SHEET TYPE
NC1-DPBGF-N NC1-PLBGF-NL 19.34 SUCCEE
F12 400 0.85 17.935 11.39 3 19.34 24.18 100 50 72.5 MC 15 1 16 XLPE GROUND 111 111 SUCCEED 2.14 0.208 0.36 21.10 29.97 7.675 GENERAL SHEETS
L-1... -1 123 D

NC1-DPBGF-N NC1-PLBGF-NL 5.051 SUCCEE SHEET TITLE :


F13 400 0.85 3.06 2.975 3 5.05 6.31 100 30 43.5 MC 15 1 6 XLPE GROUND 64 64 SUCCEED 5.57 0.092 0.25 56.25 65.12 3.532
L-1... -2 815 D
PANEL SCHEDULES

DRAWING NUMBER
SCALE SIZE REVISION
PROJECT NO. BLDG CODE SHEET NO.

00000 NC1 080002 N.T.S A1 00-DD

PANEL SCHEDUILES DRAWING NO :

A
A1 N.T.S
00000-CGG-NC1- XXX-DWG- EP- 080002
A
1 2 3 4 5 6 SHEET SIZE - ISO A1 841*594 MM