Keyence Serial Ethernet
Keyence Serial Ethernet
VT5/VT3 Series
PLC Connection Manual
Keyence Corporation Serial Connection
Ethernet Connection
Checking Operation before Connection
System Configuration
Wiring Diagrams for Connections
Unit Settings
Available Devices
Error Messages and Remedies
About the 2-port Adapter MT-T2/T3
Target PLC
KV-8000 Series (Ethernet)
KV-8000 Series (Serial)
KV-7000 Series (Ethernet)
KV-7000 Series (Serial)
KV-5500/5000/3000(Ethernet)
KV-5500/5000/3000/L2*V
KV-1000/700(Ethernet)
KV-1000/700, KV-L20*/L21V
KV Nano Series [KV-N*](Ethernet)
KV Nano Series [KV-N*]
KV-10/16/24/40, KV-P16
KZ-300/350, KZ-L2
KZ-10/16/24/40/80
KZ-A500
Refer to “PLC Connection Manual” for
KZ-L10
other chapters and the appendix.
A82GB-001 2111-1
1-1 Checking Operation before Connection
1 This section describes how to check the items required for connecting VT5/VT3/Soft-VT/DT and PLC via serial
interface or Ethernet.
For the connection of other interfaces (Multi-Link or VT2 Multi-Link), see each chapter.
"Chapter 19 MULTI-LINK"
CONNECTING TO THE KV & KZ SERIES
Serial connections
Series Connection
CPU Unit Setting Target PLC
Name Methods
KV-XL402
KV-XL202 KV-8000 Series (Serial)*5 *7
P.1-27
*6
KV-L21V KV-8000 Series (Serial) <XYM>*3 *5 *7
KV-8000/8000A KV-L20V
KV-LM21V KV-8000 Series (KV-LM2V)*4 *5 *7
P.1-30
KV-LM20V KV-8000 Series (KV-LM2V) <XYM>*3 *4 *5 *7
KV-XL402
KV-XL202 KV-7000 Series (Serial)*5 *7
P.1-27
*6
KV-L21V KV-7000 Series (Serial) <XYM>*3 *5 *7
KV-7500 KV-L20V
KV-LM21V KV-7000 Series (KV-LM2V)*4 *5 *7
P.1-30
KV-LM20V KV-7000 Series (KV-LM2V) <XYM>*3 *4 *5 *7
Built-in serial port
P.1-27
direct link
KV-XL402 KV-7000 Series (Serial)*5 *7
*6 KV-XL202 KV-7000 Series (Serial) <XYM>*3 *5 *7
KV-7300 P.1-27
KV-L21V
KV-L20V
KV-LM21V KV-7000 Series (KV-LM2V)*4 *5 *7
P.1-30
KV-LM20V KV-7000 Series (KV-LM2V) <XYM>*3 *4 *5 *7
KV-5500/5000/3000/L2V*2 *7
KV-L21V
P.1-29 KV-5500/5000/3000/
KV-L20V
L2V<XYM>*2 *3 *7
KV-5500/5000 KV-5500/5000/3000
KV-LM21V (KV-LM2V)*1 *4 *7
P.1-30
KV-LM20V KV-5500/5000/3000
(KV-LM2V)<XYM>*1 *3 *4 *7
KV PLC port direct link Not required KV-5500/5000/3000/L2V*2 *7
KV-L21V KV-5500/5000/3000/
P.1-29 L2V<XYM>*2 *3 *7
KV-L20V
KV-3000 KV-5500/5000/3000
KV-LM21V (KV-LM2V)*1 *4 *7
P.1-30
KV-LM20V KV-5500/5000/3000
(KV-LM2V)<XYM>*1 *3 *4 *7
PLC port direct link Not required
KV-1000/700, KV-L20/L21V *7
KV-L21V KV-1000, KV-L20/
KV-L20V P.1-29 L21V<XYM>*2 *3 *7
KV-1000
KV-L20R
KV-LM21V KV-1000/700(KV-LM20/21V)*1 *4 *7
P.1-30
KV-LM20V KV-1000(KV-LM20/21V)<XYM>*1 *3 *4 *7
PLC port direct link Not required
KV-L21V
KV-L20V KV-1000/700, KV-L20/L21V *7
P.1-29
KV-L20R
KV-L20
KV-700
KV-LM21V
KV-LM20V P.1-30 KV-1000/700(KV-LM20/21V)*1 *4 *7
KV-LM20
KV-L20
P.19-13 KV-L20 (VT Multi-link)*1 *4 *7
(VT Multi-link)
Built-in serial port
P.1-31
KV Nano Series direct link KV Nano Series[KV-N] *7
(KV-N14/24/40/60) KV-N10L P.1-31 KV Nano Series[KV-N]<XYM>*3 *7
KV-N11L P.1-32
Series
Name
CPU
Connection
Methods
Unit Setting Target PLC 1
Built-in serial port
P.1-31
Ethernet connections
Series
PLC Connection Methods Unit Setting Target PLC
Name
Internal Ethernet port direct link P.1-46
KV-LE21V/KV-LE20V KV-8000 Series (Ethernet)
KV-8000/8000A*3 KV-EP21V
P.1-50 KV-8000 Series (Ethernet) <XYM>*2
KV-XLE02
KV-XD02
Internal Ethernet port direct link P.1-46
KV-7500*3 KV-LE21V/KV-LE20V
KV-EP21V P.1-50
KV-7000 Series (Ethernet)
KV-XLE02
KV-7000 Series (Ethernet) <XYM>*2
KV-LE21V/KV-LE20V
KV-7300*3 KV-EP21V P.1-50
KV KV-XLE02
Internal Ethernet port direct link P.1-49
KV-5500/5000 KV-5500/5000/3000
KV-LE21V/KV-LE20V
P.1-50 (EtherNet)
KV-EP21V
KV-5500/5000/3000
KV-LE21V/KV-LE20V (EtherNet) <XYM>*2
KV-3000 P.1-50
KV-EP21V
KV-LE20/KV-LE20A KV-1000/700 (EtherNet)
KV-1000/700 P.1-51
KV-LE20V/KV-LE21V KV-1000 (EtherNet) <XYM>*2
KV Nano Series KV Nano Series [KV-N*]
(KV-N24/40/60)*1 (EtherNet),
KV-NC1EP P.1-52
KV Nano Series KV Nano Series [KV-N*]
(KV-NC32) (EtherNet) <XYM>*2
*1 A KV-N1 connection conversion unit is required when using KV-NC1EP to connect to the VT5/VT3 Series.
*2 Support the XYM display mode of KV STUDIO ladder support software.
*3 A bus connection unit is required when using a KV-5000/3000 Series expansion unit to connect to the VT5/VT3 Series.
KV-7300
USB
VT3(PORT3) : Wiring diagram 31
SD/RD
KV-8000/8000A/7500/7300+KV-XL202/XL402
*2
RS-232C VT5(COM1)/VT3-W4Wiring diagram W28
(PORT1/PORT2) VT3(PORT2)/VT-T1Wiring diagram 12
VT3(PORT3) Wiring diagram 35
VT3-V6H(G)/Q5H(G)Wiring diagram H27
KV-XL202 VT3-V7RWiring diagram R13
*1*2
VT5(COM2)/VT3-W4AWiring diagram W44
RS-422A
(PORT1/PORT2) VT3(PORT2)/VT-T1Wiring diagram 13 VT5/VT3
KV-8000/8000A/
7500/7300 VT3-V6H(G)/Q5H(G)Wiring diagram H44 Series
VT3-V7RWiring diagram R14
*1 Not supported by the VT5-W07M.
*2 Not supported by the VT5-WX.
KV-XL402
MEMORY CARD
VT3-V6H(G)/Q5H(G) : Wiring diagram H20 PLC
LINK
ACT
KL RD
KL SD
DT series
MEMORY CARD
PLC
PLC
RUN
STOP
ˇ VT3(PORT2)/VT-T1/DT : Wiring diagram 7
PORT2 RS-232C
RUN
STOP
RUN
MEMORY CARD
CARD RD SD USB
PLC
SERIAL
VT3(PORT3) : Wiring diagram 33 LINK
ACT
KL RD
KL SD
KV-8000/8000A/7500/7300/5500/5000/3000+KV-LM20V/KV-LM21V
KV-LM20V/KV-LM21V
: Dedicated cable
+ KPEV-SB(1P)
: Connecting cable for VT3
handy Series/VT-C5R1
MEMORY CARD
KPEV-SB (1P)
PLC
LINK
ACT
KL RD
KL SD
CARD
Up to 15 units
Point • For KV-8000/8000A/7500/7300, a bus connection unit is required when using a KV-5000/
3000 series expansion unit to connect to the VT5/VT3 Series.
• The VT5 Series is not supported.
• Not supported by VT2 series and VT1 series (including the VT-7SR).
• Not supported by DT-80/80A and DT-100.
• Cannot connect to VT3-W4T/W4M(T)/W4G(T) (RS-232C).
• Max. speed of communication is 115200bit/s when connecting VT3-W4TA/W4M(T)A/
W4G(T)A (RS-422A/485). Be sure that the communication speed of other connecting
devices complies with VT3-W4TA/W4M(T)A/W4G(T)A.
• For one MegaLink, only one DT-100A can be connected.
• DT-100A, when used as the terminator of DT-500, can also use the MegaLink connection.
• VT3 handy Series and VT3-V7R can only be connected to both ends of the wiring.
• For connection with VT3 handy Series using VT-T1, never remove VT-T1 and OP-87194/
87195/87196 in power on status.
KV-1000/700+KV-LM20(V)/LM21V
1
KV-LM20(V)/LM21V
MEMORY CARD
KPEV-SB (1P)
PLC
LINK
ACT
KL RD
KL SD
CARD
Total length
≤ 1000m Cable Adapter
(including VT-C5R1, KL-B1
connecting cable for VT3
DT-100A
handy Series, and link cable)
VT3 series VT2 series VT3 series (terminator ON)
VT3 handy Series
(terminator ON)
Up to 15 units
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
SERIAL
KPEV-SB(1P)
Communication cable
KPEV-SB (1P)
VT-C5R1
(5m)
Total cable length
≤ 500 m
(including VT-C5R1 and
VT1 series connecting cable for VT3 series VT2 series
VT3 handy Series)
VT3 handy Series (terminator ON)
(terminator ON) VT3-V7R
Up to 16 units
KV Nano Series
VT5(COM1)/VT3-W4: Wiring diagram W20 *3
1
MEMORY CARD
PLC
LINK
PLC
0 1 2 3 4 5
KV-16AR
5ch
500 501 502 504
24V-OUT-OV C3 C4 503 505 OUT
MEMORY CARD
VT3-W4 : Wiring diagram W20 PLC
LINK
ACT
NEXT RESET ENTER KL RD
KL SD
F1 F2 F3 F4 F5
KV-P Series
(KV-P16T/16R/ DT Series
16TL/16RL)
KEYENCE
KZ - 10R
KZ, series PLC port direct link cable VT3-V6H(G)/Q5H(G) : Wiring diagram H20
VT3-W4 : Wiring diagram W20
KZ-10/16/24 VT3 Series
VT3-V7R : Wiring diagram R1
KZ-40/80 MT-T2
KZ Series
ACCESS 1+2 1ONLY
MEMORY CARD
PORTA
(PLC)
direct link cables VT3(PORT2)/VT-T1/DT : Wiring diagram 1
PLC
+
LINK
PORT1 ACT
(MT) KL RD
KL SD
PORT2
(TOOL) CARD
24V 0V
VT3-V6H(G)/Q5H(G) : Wiring diagram H20
VT3-V7R : Wiring diagram R1
2-port adapter
KZ-300/350 MT-T2
DT Series
KZ-300/350+KZ-L2
1
VT3(PORT2)/VT-T1/DT : Wiring diagram 2
MEMORY CARD
VT3-W4 : Wiring diagram W22 LINK
PLC
ACT
KL RD
MEMORY CARD
PLC
PORTA
(PLC)
VT3(PORT2)/VT-T1/DT : Wiring diagram 1 ACT
KL RD
KL SD
CARD
PORT1
(MT)
PORT2
VT3-V7R : Wiring diagram R2
KZ-A500 24V 0V
(TOOL)
KZ-A500+KZ-L10
VT3(PORT2)/VT-T1/DT: Wiring diagram 5
PORT1 RS-232C VT3-V6H(G)/Q5H(G): Wiring diagram H23
VT3-W4: Wiring diagram W23
VT3-V7R: Wiring diagram R6
PLC
LINK
ACT
KZ-A500 KZ-L10
VT3(PORT2)/VT-T1/DT: Wiring diagram 4
PORT2 RS-422A VT3-V6H(G)/Q5H(G): Wiring diagram H40
VT3-W4A: Wiring diagram W40
VT3-V7R: Wiring diagram R5 DT Series
KZ-A500
READY/
SELECT
ERROR
VT No.
0-7 8-15
S.ERR
VT-L16Z
2/10 6/14
VT-L16Z
3/11 7/15
1
2
SELECT
3
4 1 1 1 1
5 2 2 2 2
115.2 57.6 38.4 19.2
6
[kbit/s]
ON OFF
: Dedicated cable
KZ-350/300 KPEV-SB(1P)
A B SG
A B
Communication cable
KPEV-SB (1P)
VT-C5R1
(5m)
Total cable length
≤ 500 m
(including VT-C5R1 and
VT1 series connecting cable for VT3 series VT2 series
VT3 handy Series)
(terminator ON)
VT3 handy Series VT3-V7R
(terminator ON)
Up to 16 units
*1
Max. 16 units
*1 Please note that with the increase in the number of VT5/VT3 Series and Soft-VT units connected, the communications
load also increases.
*2 VT3 handy Series has built-in Ethernet function, so VT2-E1/E2 and VT3-E3 are not required.
*3 The VT5 Series has a built-in Ethernet function and does not require the VT2-E1/E2 and VT3-E3.
*4 A bus connection unit is required when using a KV-5000/3000 Series expansion unit to connect to the VT5/VT3 Series
and Soft-VT.
*5 The KV-XD02 can only be connected to the KV-8000.
Point When the serial number of the VT3-E3 ends in A or later, the VT3 system program must be in
Ver. 4.51 or later to enable connection to the VT3 Series.
KV-5500/5000/3000/1000/700 (Ethernet)
*1
+
VT5*3 VT3
Soft-VT VT2-E1/E2, VT3-E3*2
STP/UTP cable
ˇ ˇ
Max. 16 units
Point • KV-LE20 that can be connected to VT3 via Ethernet connection aremarked with the letter
"A" preceding the lot No..
• When the serial number of the VT3-E3 ends in A or later, the VT3 system program must be
in Ver. 4.51 or later to enable connection to the VT3 Series.
*2
Ethernet STP/UTPcable
Max. 16 units
*1 The KV-N1 connection conversion unit is required when using a KV-N24/40/60 and KV-NC1EP to connect the VT5/VT3
Series and Soft-VT.
*2 Please note that with the increase in the number of VT5/VT3 Series and Soft-VT units connected, the communications
load also increases.
*3 VT3 handy Series has built-in Ethernet function, so VT2-E1/E2 and VT3-E3 are not required.
*4 The VT5 Series has a built-in Ethernet function and does not require the VT2-E1/E2 and VT3-E3.
Point When the serial number of the VT3-E3 ends in A or later, the VT3 system program must be in
Ver. 4.51 or later to enable connection to the VT3 Series.
(2) (4)
* indicates a terminal diagram for the VT5 Series. * indicates a terminal diagram for the VT5 Series. RDA RDB
KV-L20
Terminal block No.
VT3-W4 KZ
(terminal block) Modular 6-pin *
View from cable TXD SD
connector RXD N.C.
TXD 5 SD side
RTS N.C.
RXD 3 RD
CTS RD
RTS 1 RS
SG SG
CTS 6 CS
SG 4 SG DTR
(6) (5) (4) (3) (2) (1)
DTR 2 5V DSR
Modular connector of kz,kv
DSR N.C.
N.C. N.C.
N.C.
* indicates a terminal diagram for the VT5 Series.
* 1 SD
TXD 1 SD RD
RXD 2 RD RS
RTS 3 RS CS
ER
CTS 4 CS
DR
SG 7 SG
7 SG
DTR
KV-XL202
DSR Terminal block No.
N.C.
N.C.
(2) (4)
RDA RDB
KV-L20
Terminal block No.
SDA-
TXDA
Orange (dot: black 1)
1 SDA( ) 1 /SR-
Orange (dot: black 2) SDB+
TXDB 2 SDB( ) /SR-
Orange (dot: black 3) RDA-
ON RXDA 3 RDA( )
Orange (dot: black 4)
RXDB 4 RDB( ) RDB+
Orange (no dot)
SG 5 SG 5 SG
TERM. Orange (dot: red 1)
RTSA
Orange (dot: red 2) KV-XL402
RTSB
Orange (dot: red 3) Terminal block No
CTSA
Orange (dot: red 4)
CTSB
Red Black
TXD 2 1 SG GND 7 1 SG
(1) (3) (5) Red
Red/white SG SDA RDA TXDA 11 2 SDB
RXD 3 (SG) (SD) (RD) Red/white
Green TXDB 12 3 SDA
RTS 4 3 SD (2) (4) Green (1) (3) (5)
Green/white * RXDA 13 4 RDB SG SDA RDA
CTS 5 SDB RDB
Green/white (SG) (SD) (RD)
Black RXDB 14 5 RDA
GND 7 5 RD KZ-L2 (KZ-L10) (2) (4)
TMR1 19 SDB RDB
terminal block No.
TMR2 20
* Not wired for loopback test inside the connector. KZ-L2 (KZ-L10)
RTSA 15
Solder the signal lead. terminal block No.
RTSB 16
CTSA 17
CTSB 18
1 Wiring Diagram 5
(RS-232C: OP-24027)
Wiring Diagram 6
(RS-232C: OP-24027)
CONNECTING TO THE KV & KZ SERIES
Reference For the pin assignment number of the connectors on the VT3 series/DT series, please see
the Appendix at the end of this manual.
Wiring Diagram 7 Wiring Diagram 8
(RS-232C: OP-24027) (RS-422A: OP-24028)
VT3 PORT2 (20-pin) KV-L20(R)/L2ΩV PORT2 (terminal block) VT3 PORT2 (20-pin) KV-L20(R)/L2ΩV PORT2 (terminal block)
DT PLC port (20-pin) DT PLC port (20-pin)
Red TXD 2 1 SD RD
TXD 2 SD Red/white
RXD 3 2 RD RS
Red/white Green
RXD 3 N.C. RTS 4 3 RS CS
Green Green/white *
RTS 4 * N.C. CTS 5 4 CS ER
Green/white Black DR
CTS 5 RD GND 7 7 SG
Black 7 SG
GND 7 SG
* Not wired for loopback test inside the connector. KV-XL202
Solder the signal lead. Terminal block No.
* Not wired for loopback test inside the connector.
Solder the signal lead.
* 3.9KΩ 1/4W
TXD 2 SD
TXD 2 SD
RXD 3 RD
RXD 3 N.C.
RTS 8
RTS 8 N.C.
CTS 7
CTS 7 RD
GND 5 SG GND 5 SG
TXD 2 1 SD
RXD 3 2 RD
RTS 8 3 RS
CTS 7 4 CS
GND 5 7 SG
Reference For the pin assignment number of the connectors on the VT3 series/DT series, please see
the Appendix at the end of this manual.
KV-L20
terminal block NO.
TMC TMR
RXD N.C. Orange (dot: red 1)
Orange (dot: red 1) TMC TMR RTS 3 RS CS
ON
RTS N.C. Orange (dot: red 3) ER
Orange (dot: red 3) ON CTS 4 CS
CTS RD Orange (no dot) DR
OFF Orange (no dot) SG 7 SG
SG SG OFF 7 SG
1 2 3 DTR
DTR 1 2 3 KV-XL202
DSR Terminal block
DSR
N.C.
N.C.
N.C.
N.C.
(2) (4)
RDA RDB
KV-L20
terminal block NO.
SDA-
TXDA
Orange (dot: black 1)
1 SDA( ) 1 /SR-
Orange (dot: black 2) SDB+
TXDB 2 SDB( ) /SR-
Orange (dot: black 3) RDA-
ON RXDA 3 RDA( )
Orange (dot: black 4)
RXDB 4 RDB( ) RDB+
Orange (no dot)
SG 5 SG 5 SG
TERM. Orange (dot: red 1)
RTSA
Orange (dot: red 2) KV-XL402
RTSB
Orange (dot: red 3) Terminal block N
CTSA
Orange (dot: red 4)
CTSB
Connection to VT3-V7R
Reference For the pin assignment number of the connectors on the VT3 series/DT series, please see
the Appendix at the end of this manual.
Wiring Diagram R5
(RS-422A: VT-C5R2/C15R2)
Wiring Diagram R6
(RS-232C: VT-C5R1)
1
Point Please use the following recommended cables for the connection. Using cables other than
the recommended ones may lead to a shorter cable run distance.
Item Description
Type of Cable Shielded cable
Logarithmic 3P
Resistance (20°C) Below 52.0/km
Insulating resistance 10.000M/km
Withstand voltage DC500V 1minute
Electrostatic Capacity (1kHz) Below 135nF/km
Characteristics Impedance (100kHz) 43
Reference For the pin assignment number of the connectors on the VT3 series/DT series, please see
the Appendix at the end of this manual.
VT5 +
KV-8000/8000A/ KV-XLE02/XD02*2
7500/7300
STP/UTP cable
+ +
Soft-VT
VT3 KV-5500/5000
(VT3 handy Series
excluded)
STP/UTP cable*1
+ +
KV-5500 KV-EP21V
/5000/3000 /LE2*V
VT2-E1/E2,
VT3-E3
+
KV-1000/700 KV-LE20(V/A)
KV-NC32T KV-NC1EP
*1 The VT5 Series and VT3-E3 whose serial numbers end in an "A", support the MDI/MDI-X auto switching function.
To connect any other device directly to a PLC, use an STP/UTP cross cable.
*2 The KV-XD02 can only be connected to the KV-8000.
Point • When building an Ethernet connection using 10 Base-T, use a Category 3 or higher STP/UTP cable.
• When building an Ethernet connection using 100 Base-TX, use a Category 5 or higher STP/UTP cable.
• When building an Ethernet connection using 1000 Base-T, use a Category 5e or higher STP/UTP
cable. If it is considered that there is a noise influence in the installed environment, select an STP
cable with the double shield.
STP/UTP
straight cable KV-8000/8000A/7500
VT5
+
KV-8000/8000A/ KV-XLE02/XD02*1
7500/7300
Soft-VT
+ +
VT2-E1/E2, +
VT3-E3
KV-5500 KV-EP21V
/5000/3000 /LE2*V
KV-NC32T KV-NC1EP
Point • When building an Ethernet connection using 10 Base-T, use a Category 3 or higher STP/UTP cable.
• When building an Ethernet connection using 100 Base-TX, use a Category 5 or higher STP/UTP cable.
• When building an Ethernet connection using 1000 Base-T, use a Category 5e or higher STP/UTP
cable. If it is considered that there is a noise influence in the installed environment, select an STP
cable with the double shield.
Start up the Unit Editor and select the base unit to set up.
Set the operating mode of the internal serial port to "KV STUDIO mode (*).
KV-XL402 setting
KV-XL402
Item
Port 1/Port 2
Operation mode KV STUDIO mode
Interface RS-422A/485 (4-wire)
Baud Rate Auto (set on VT5/VT3/DT side) *1
Data bit 8 bits
Start bit 1 bits
Stop bit 1 bits
Parity Even
CheckSum None
RS/CS flow control Disable
*1 Set baud rate with the PLC communication condition in VT system setting of VT STUDIO.
VT 5 Series Reference Manual" 12 - 5 Peripheral Device Connection "
VT3 Series Reference Manual" 12-4 VT main unit system setting "
KV-XL202 setting
The KV-XL202 communication settings are configured with the KV STUDIO ladder software Unit Editor.
Set the operation mode of the port to be used to "KV STUDIO mode".
Set Value
Item
Port 1/Port 2
Operation mode KV STUDIO mode
Interface RS-232C
Baud Rate Auto (set on VT5/VT3/DT side) *1
Data bit 8 bits
Start bit 1 bits
Stop bit 1 bits
Parity Even
CheckSum None
RS/CS flow control Disable
*1 Set baud rate with the PLC communication condition in VT system setting of VT STUDIO.
VT 5 Series Reference Manual" 12 - 5 Peripheral Device Connection "
VT3 Series Reference Manual" 12-4 VT main unit system setting "
KV-L20R
PORT2
232C 422A VT 422A
232C 485(4) 485(2)
Point "PORT2 Selector Switch" and "Unit Editor" should be set separately when connecting
KV-L20(R) via PORT2. The PLC will malfunction if both settings do not match.
1 KV-LM20(V)/LM21V
KV-LM20(V)/LM21V front view KV-LM20(V)/LM21V side view
CONNECTING TO THE KV & KZ SERIES
KV-N10L
The KV-N10L communication settings are configured with the KV STUDIO ladder software Unit Editor.
Start the Unit Editor and select the base unit and you will be able to configure the extension cassette settings.
Port1 can be used with the KV-N14/N24. Port1 and Port2 can be used with the KV-N40/N60.
The initial value for the extension cassette is "None".
1 KV-N11L
CONNECTING TO THE KV & KZ SERIES
Start the Unit Editor and select the base unit and you will be able to configure the extension cassette settings.
Port1 can be used with the KV-N14/24. Port1 and Port2 can be used with the KV-N40/N60.
The initial value for the extension cassette is "None".
KV-NC10L
The KV-NC10L communication settings are configured with the ladder software KV STUDIO Unit Editor.
1
1 KV-NC20L
CONNECTING TO THE KV & KZ SERIES
When the KV-NC20L PORT2 and the VT3 are connected by RS-485 (2-wire), set the terminator
switch to ON. ON
The KV-NC20L communication settings are configured with the KV STUDIO Unit Editor.
Start the Unit Editor and select the base unit to configure the extension adapter settings.
Port1 (RS-232C) and Port2 (RS-232C/RS-422A/485) can be used with the KV-NC20L.
The initial value for the extension adapter is "None".
(3) Terminator
(2) PORT2 selector selector switch
switch
422A 232C ON OFF STATION NO. F012
B CDE
3456
INTERFACE TERMINATOR
ON SET. A SET. B 78
9A
A1 A2 A3 A4 B1 B2 B3 B4 B5 B6 B7 B8
1 2 3 4 1 2 3 4 5 6 7 8
SELECT
2
RUN STOP
RUN/ SELECT
ERROR
BATT. A B
0
1
0
1 1
2 2
3 3
4 4 X Y
ON OFF
5 5
6 6
7 7
8 8
9 9
A A
B B
C
D
C
D Switch No.
E E
Baud Rate
F F
1 2
Baud rate OFF OFF 9600 bit/s
BAUD RESET
1 KZ-L10
(5) Terminator
CONNECTING TO THE KV & KZ SERIES
B CDE
3 4 56
INTERFACE TERMINATOR
ON SET. A SET. B 78
9A
A1 A2 A3 A4 B1 B2 B3 B4 B5 B6 B7 B8
ON ECE ON ECE
(6) Node No. setup
switch
1 2 3 4 1 2 3 4 5 6 7 8
ON SET. C
(3) Modem/
C1 C2 C3 C4 C5 C6 C7 C8
ON ECE
1 2 3 4 5 6 7 8
communications
procedure setup (2) Communications
switch specifications setup
switch
(1) Operation mode
setup switch
The following table shows setting ranges for each communications condition and their defaults. STATION
No.
KV-5500/5000/3000(KV-LM2V),
KV-5500/5000/3000(KV-LM2V) <XYM>,
1
KV-1000/700(KV-LM20/21V), KV-1000(KV-LM20/21V) <XYM>
KV-10/16/24/40, KV-P16
Item Setting Range Default
PLC No. None None
VT No. None None
PLC I/F RS-232C RS-232C
Baud Rate 9600, 19200, 38400, 57600 bit/s 57600 bit/s
Data bit 8 bits 8 bits
Stop bit 1 bit 1 bit
Parity Even Even
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -
VT No. - -
PLC I/F RS-232C, RS-422A 4 wire *1 RS-232C
Baud Rate 9600, 19200, 38400 bit/s 38400 bit/s
Data bit 8 bits 8 bits
Stop bit 1 bit 1 bit
Parity Even Even
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -
*1 RS-422A 4 wire can be selected when PORT2 on the KZ-L2 is used on the RS-422A interface.
KZ-A500
Item Setting Range Default
PLC No. None None
VT No. - -
PLC I/F RS-232C RS-232C
Baud Rate 4800, 9600, 19200, 38400 bit/s 9600 bit/s
Data bit 8 bits 8 bits
Stop bit 1 bit 1 bit
Parity Odd Odd
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -
KZ-L10
Item Setting Range Default
PLC No. ON (0 to 9) ON (0)
VT No. - -
PLC I/F RS-232C, RS-422A 4 wire RS-232C
Baud Rate 1200, 2400, 4800, 9600, 19200, 38400 bit/s 38400 bit/s
Data bit 7 bits, 8 bits 7 bits
Stop bit 1 bit, 2 bits 1 bit
Parity None, odd, even Even
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -
Point Make sure that the "IP address assigned to VT5/VT3/Soft-VT (PC)" differs from "the IP
address assigned to the PLC".
Item Description
Send VT setting When checked, the VT settings are sent to the VT5.
IP Address Set the IP address to be assigned to the VT5.
Use the default settings to make a direct connection.
Subnet mask For all other connections, set a subnet mask whose operation you
Ethernet settings have verified.
Use the default settings to make a direct connection.
Default gateway For all other connections, set a default gateway whose operation you
have verified.
If required, set a port number for communications with VT STUDIO
Editor Port number and other PC applications.
communication Be sure to set a port number that is not also used for PLC communications.
settings Keep Alive Set as necessary.
Timeout Set as necessary.
Point • You can use VT5 system mode to check and change Ethernet settings such as IP
addresses to be assigned to the VT5 Series.
The setting items are the same as those in VT STUDIO.
"5-3 VT Machine Setup", VT5-WX Hardware Manual
"5-3 VT Machine Setup", VT5 Series Hardware Manual
• These settings are not required for Soft-VT since it uses the Ethernet settings of the PC it
runs on.
• If the VT model setting is VT5-WX15/WX12, it is equipped with two LAN ports, and an IP address
can be set for each port. Set the IP address of the LAN port that is connected with PLC.
Reference In the VT3 Series, IP addresses to be assigned to the VT3 were set only in the system mode screen.
In the VT5 Series, they are set in the "VT setting" in VT STUDIO.
Item Description
Station No. Select the station number (0 to 15) you want to use.
Set the IP address to be assigned to the connected PLC (the checked
IP Address *1
station number).
Target PLC Set the port number (1024 to 65535) of the connected PLC (the
Port number *2
checked station number).
List of connected Select connected targets from the list of connected targets or add
targets targets to the list.
VT port numbers (for Set VT5/Soft-VT port numbers (for PLC communications) (1024 to
PLC communications) 65535).
Normally, this does not need to be set.
Timeout
Set a long timeout when the communications load on the network is large.
Ethernet settings Normally, this does not need to be set.
Send Wait
Set a long timeout when the communications load on the network is large.
Normally, this does not need to be set.
Retry Increase the number of retries when the unit is used in an
environment with a lot of noise.
PLC communications special settings
Normally, this does not need to be set.
(set on VT STUDIO)
Specify a device to
In an interval with no communications, select a device to check
troubleshoot Target word device *3
connections. Normally, this does not need to be set.
Ethernet connections
When checked, communications with a station number causing a
Disconnects / reconnects the PLC No. where communication error are shut down. A station number that has been
communication error occurs *4 shut down is regularly monitored and communications are resumed
when the station recovers.
*1 Be sure to set unique IP addresses for each device in the same LAN.
IP addresses are expressed as XXX.XXX.XXX.XXX (XXX indicates a number in the range 0 to 255).
*2 Do not change the port number to a number between 0 to 1023. Also, take care not to use a port number already used
by another device.
*3 Select "PLC device".
"6-7 Device Setup", VT5 Series Reference Manual
*4 Can be set up when a PLC model supporting 1-to-N connection is selected.
Point You can use VT5 system mode to check and change PLC communication condition settings.
The setting items are the same as those in VT STUDIO.
"5-5 PLC Communication Setup", VT5-WX Hardware Manual
"5-5 PLC Communication Setup", VT5 Series Hardware Manual
1 Use the VT3 System mode to set an IP address to be assigned to the VT3 or make other settings.
Set at "Option Setup" in the System mode on the VT3 unit.
"Chapter 5 SYSTEM MODE", VT3 Series Reference Manual
Default Gateway 0 0 0 0
MAC address ** : ** : ** : ** : ** : **
Routing setup
Item Description
Normally, select "100/10M bps Auto". Selects "10 Mbps" only when communications is
Baud rate unstable.
Selects "10 Mbps" only when communications is unstable.
IP Address Sets the IP address to be assigned to the VT3.
Use the default setting as it is in the case of a direct connection.
Subnet Mask
Sets a pre-acknowledged subnet mask for other connections.
Use the default setting as it is in the case of a direct connection.
Default Gateway
Sets a pre-acknowledged default gateway for other connections.
MAC address This is the ID No. unique to VT3 Series. This cannot be set.
Please set the port No. for communicating with a PC application such as VT STUDIO as
Port no.
required. Duplication with the PLC communication port No. must be avoided.
Time-out Set as necessary.
Keep Alive Set as necessary.
FTP Setup Set as necessary.
Routing Setup*1 Selects "Enable" only when using a router.
*1 "Chapter 8 ETHERNET", VT3 Series Hardware Manual
Item Description
PLC No. Selects the PLC No. (0 to 15) to be used.
IP address*1 Sets the IP address to be assigned to the connection destination PLC (marked PLC No.).
Target PLC Port No.*2 Sets the port No. (1024 to 65535) of the connection destination PLC (marked PLC No.).
Selects the connection destination from the connection destination list file, or
Connect to
adds connection destinations.
VT port No. (for PLC
Sets the port No. (for PLC communications) (1024 to 65535) of the VT3.
communications)
Normally, this does not need to be set.
Timeout
Set a long time-out when the communications load on the network is large.
Ethernet Settings
Normally, this does not need to be set.
Send Wait
Set a long time-out when the communications load on the network is large.
Normally, this does not need to be set.
Retry
Increase the number of retries when the unit is used in an environment with a lot of noise.
PLC communications special settings
Normally, this does not need to be set.
(set on VT STUDIO)
Specify a device to
troubleshoot Target word Used to set up a device that troubleshoots Ethernet connections. Normally
Ethernet device*3 no need to be set up
connections
VT3 disconnects / reconnects the PLC Once selected, the communication with an erroneous station is cut off. And this
No. where communication error occurs*4 number is regularly monitored and re-connected once the error is removed.
*1 Be sure to set only unique IP addresses to each device within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range 0 to 255).
*2 When changing the port No., do not use numbers 0 to 1023 as the new port No. Also, take care not to use another port
No. that is already in use.
*3 Select "PLC Devices"
"6-7 Set up the Devices", VT3 Series Reference Manual
*4 Can be set up when a PLC model supporting 1-to-N connection is selected.
Point You can use VT3 system mode to check and change PLC setting conditions.
The setting items are the same as those when setting on VT STUDIO.
"5-4 PLC Communication Condition", VT3 Series Hardware Manual
Item Description
IP Address *1 Set the IP address to be assigned to the connected PLC.
Use the PLC communication condition setting to set the port number to be assigned to the target
Port No. (VT) *2
PLC.
*1 Be sure to set unique IP addresses for each device in the same LAN.
IP addresses are expressed as XXX.XXX.XXX.XXX (XXX indicates a number in the range 0 to 255).
*2 Do not change the port number to a number between 0 to 1023. Also, take care not to use a port number already used
by another device.
KV-XLE02 setting
This is set up via the Unit Editor in KV STUIDO.
1
Communication is possible with both port 1 and port 2. Here, we will describe for port 1 as an example.
1 KV-XD02 setting
This is set up via the Unit Editor in KV STUIDO.
Communication is possible with both port 1 and port 2. Here, we will describe for port 1 as an example.
CONNECTING TO THE KV & KZ SERIES
Item Description
IP address*1 Set the IP address to be assigned to KV-XD02.
Set up whether to enable VT connection on the current Ethernet port.
VT connection * Normally, it is unnecessary to change from the default setting "Enable".
Set this to disable the VT connection port No. of the Ethernet port not used for VT connection.
Port No. (VT) Set up the port No. *2 set for the target PLC with the PLC communication condition setting.
*1 Be careful that the IP address does not overlap with other devices within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range 0 to 255).
*2 When changing the port No., do not use 0 to 1023. Also, be careful not to duplicate the number if there is
another port number you are using.
1 KV-EP21V/LE21V/LE20V Settings
This is set up via the Unit Editor in KV STUIDO.
CONNECTING TO THE KV & KZ SERIES
Item Description
IP Address*1 Set the IP address to be assigned to the connection destination PLC.
Use the PLC communication condition setting to set the port number to be assigned to the
Port No. (VT)*2
target PLC.
*1 Be sure to set only unique IP address to each equipment within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range of 0 to 255).
*2 When changing the port No., do not use numbers of 0 to 1023 as the new port No. Also, do not use another port No. that
is already in use.
KV-LE20(V/A) settings
Set up with Unit Editor in KV BUILDER or KV STUDIO.
1
Item Description
IP address*1 Sets the IP address to be assigned to the connection destination PLC.
Use the PLC communication condition setting to set the port number to be assigned to the
Port No. (VT)*2
target PLC.
*1 Be sure to set only unique IP addresses to each device within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range 0 to 255).
*2 When changing the port No., do not use numbers 0 to 1023 as the new port No. In addition, the port numbers should be
unique when other ports need to be used.
1 KV-NC1EP setting
This is set up via the Unit Editor in KV STUIDO.
CONNECTING TO THE KV & KZ SERIES
Item Description
IP Address*1 Set the IP address to be assigned to the connection destination PLC.
Use the PLC communication condition setting to set the port number assigned to the target
Port No. (VT)*2
PLC.
*1 Be sure to set only unique IP address to each equipment within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range of 0 to 255).
*2 When changing the port No., do not use the number of 0 to 1023 as the new port No. Also, do not use another port No.
that is already in use.
1 *9 The high-order 2 digits are the unit ID, the medium-order 2 digits are the bank number and the low-order 5 digits are the
device number.
*10 The device number is set as described below.
ZG483132767
CONNECTING TO THE KV & KZ SERIES
Available Variable
When the CPU unit of the PLC to be connected is KV-8000/8000A, and it is connected with VT5 Series/Soft-VT by
Ethernet, reading and writing can be done using a variable. Data types of available variables are as follows.
Type name Description Support
BOOL Bit
UINT 1 word unsigned integer *
INT 1 word signed integer *
UDINT 2 words unsigned integer *
DINT 2 words signed integer *
REAL Single-precision float point type
LREAL Double-precision float point type
STRING String
TIMER Timer
COUNTER Counter
ARRAY Array
STRUCTURE Structure
FUNCTION BLOCK Function block
* When handled as a bit data, set it as “variable name + period (.) + bit position”.
Point • Because the local variable cannot be referred from VT5 Series, register a variable to be
referred from VT5 Series as a global variable.
• When an array is specified, specify a suffix by a constant.
• When a structure is specified, specify it up to the end member.
• No variable set to a constant can be specified.
• The string length that can be specified by a variable is 255 characters at maximum. Set the
variable which is defined by an array suffix "[]" and "period (.)" which locates between a
structure type variable name and member name, and an integer (UINT, INT, UDINT, and
DINT), using 255 characters or less, including "." which locates between a variable name
and bit position when the variable is handled as a bit data.
• For details on variables, see "VT5 Series Reference Manual".
• Variables can be used only when the version is VT STUDIO Ver. 8.0 or later, and the
supported model is VT5 Series/Soft-VT, and the VT main unit system program version is
Ver. 4.00 or later.
• Variables can be used only when performing the Ethernet connection to KV-8000/8000A
with the CPU function version of 2.0 or later.
*11 For CPU function version 2.2 or earlier, the relay range is R00000 to R99915, the input relay (bit device) range is X0000
to X999F, the output relay (bit device) range is Y0000 to Y999F, the input relay (word device) range is X0000 to X9990,
and the output relay range (word device) is Y0000 Y9990.
Device KV-5500/5000/3000
KV-5500/5000/3000
<XYM>
1
Relay *4 R00000 to R99900 R00000 to R99900
ZG483132767
KV-1000
Device KV-1000 KV-700
<XYM>
Relay 00000 to 59915 R00000 to R59915 00000 to 59915
Input relay *1 - X0000 to X599F -
Output relay *1 - Y0000 to Y599F -
Internal auxiliary relay MR00000 to MR99915 M00000 to M15999 -
Latch relay LR00000 to LR99915 L00000 to L15999 -
Control relay CR0000 to CR3915 CR0000 to CR3915 CR0000 to CR3915
Timer (contact) T0000 to T3999 T0000 to T3999 T000 to T511
Bit device
Counter (contact) C0000 to C3999 C0000 to C3999 C000 to C511
CTC (contact) *2 CTC0 to CTC3 CTC0 to CTC3 CTC0 to CTC3
KZ-A500, KZ-L10
Address
1
*1 Be sure to use expansion unit buffer memory (that support banks) that have been manufactured after September 12,
2008 with the KV-5000 and KV-LE20V.
This section describes the PLC communications errors that occur when a KV or KZ series PLC is connected.
Names of Parts
MT-T2 MT-T3
MT-T2 MT-T3
(1) Port selector switch (1) Port selector switch
ACCESS 1+2 1ONLY ACCESS 1+2 1ONLY
(2) Operation indicator (2) Operation indicator
PLC EXT. (7) Power supply selector
POWER
switch
PORTA
(3)PORT A[PLC] PORTA
(3)PORT A[PLC]
(PLC) (PLC)
PORT2 A1 PORT2
(8) Baud rate selector
(TOOL) (TOOL) switch
2
Connecting by MT-T2
1
MT-T2 is used to connect VT3 (excluding VT3-W4□) or programming tools to KZ series (excluding KZ-A500).
VT3
(excluding VT3-W4□)
MT-T2
PORT1
ACCESS 1+2 1ONLY
KZ-10/16/24
KZ-40/80 PLC connector cable*1 PORTA
PORTA
(PLC)
PORT1
KV BUILDER*3
(MT)
for KZ
KZ Ladder
PORT2 Dedicated connector cable*2 KZ-P3
2-port adapter
MT-T2
PORT2
KZ-300/350 OP-26484(5m)
OP-35403(1m)
VT3
(excluding VT3-W4□)
*1 Connector cable OP-26487 can also be used. (An external power supply is needed for the MT-T2.)
*2
Connected Old type OP number Current type OP number
OP
Machine OP-96368 - OP-26487
For PC98 OP-26482 or OP-26487 + OP-26485 OP-96369 - OP-26485
For DOS/V machine OP-26487 + OP-26486 OP-23085 - OP-26482
For KZ-P3 OP-26487 OP-23086 - OP-26486+OP-26487
1 Connecting by MT-T3
MT-T3 is used to connect VT3 (excluding VT3-W4□) or programming tools to KZ-A500.
CONNECTING TO THE KV & KZ SERIES
PORT2
OP-26484(5m)
OP-35403(1m)
PORT1 VT3
ACCESS 1+2
MT-T3
1ONLY
(excluding VT3-W4□)
PLC EXT.
POWER
PORTA
MITSUBISHI
PORT1
BAUO (MT)
RATE
A1 PORT2
24V 0V
(TOOL)
ELECTRIC
CORPORATION
PORT2 Dedicated connector cable*2 GX-Developer
KZ-A500 Ladder Builder
2-port adapter for KZ-A
MT-T3
MITSUBISHI
KZ-C2O+ ELECTRIC
MITSUBISHI ELECTRIC CORPORATION
CORPORATION GPP
AC30R4
PORT2
OP-26484(5m)
OP-35403(1m)
VT3
(excluding VT3-W4□)
*1 Connector cable OP-26487 can also be used. (An external power supply is needed for the MT-T3.)
*2 Old type OP number Current type OP number
Connected
OP
Machine OP-96368 - OP-26487
For PC98 OP-26482 or OP-26487 + OP-26485 OP-96369 - OP-26485
For DOS/V machine OP-26487 + OP-26486 OP-23085 - OP-26482
OP-23086 - OP-26486+OP-26487
How to Use 1
1
2 When using PORT2, set the PORT selector switch to "1+2". In other cases, set to "1ONLY".
Point Set the baud rate at "Communication Setting" in the VT3 unit system mode. The VT3 does not
operate in the following states when MT-T2 is used.
• When the time chart monitor is being used by the ladder support software
• While the program is being transferred between the KZ and ladder support software
“5-4 PLC Communication Conditions” in the VT3 Series Hardware Manual
3 Set the baud rate by the DIP switch on the top panel of the MT-T3.
The baud rates of PORTA [PLC] and PORT1 [MT] are set in common. The baudrate of PORT2 [TOOL] can be set individually.
1 4800bit/s
PORT A•1
2
3 9600bit/s
PORT 2
4
19200bit/s
38400bit/s
Troubleshooting
If the system does not function properly with the VT3/DT connected to the KZ seriesand MT-T2/T3, and power is
supplied, an error message is displayed on the VT3'sscreen. In the case of the DT, this can be confirmed by "Unit
Monitor" on DT BUILDERand "Error State" on the Web server.
For details on how to remedy error messages, refer to "Troubleshooting".
“Appendix-1 Error Troubleshooting and Removal” in the VT3 Series Hardware Manual
Providing a separate power supply or connecting a noise filter as follows will proveeffective as a noise
countermeasure.
VT3 series
1 4
Power Noise filter
supply
2 3
(FG must not be earthed.)
Recommended filter: OP-25841
1 Specifications
CONNECTING TO THE KV & KZ SERIES
Insulating resistance 5 M or more by 500 VDC megger (across power terminal and case)
Noise resistance 1500 Vp-p pulse width 1 sec (by common mode noise simulator) *1
Vibrating resistance 10 to 55 Hz peak-to-peak, 1.5 mm, for 2 hours each in X, Y and Z directions
Operating atmosphere Free from excessive dust/dirt and corrosive gases
Ambient operating
0 to 55°C
temperature
Operating surrounding
35 to 85% RH (condensation not allowed)
air humidity
Applicable PLCs KZ-10, 16, 24, 40, 80, 300, 350 KZ-A500
* The specification values vary according to the system configuration and wiring method.
*1 The power supplied from PORT2 [TOOL] on the MT-T3 is 5 V 400 mA or less.