Keyence Serial Ethernet

The document is a PLC Connection Manual for the VT5/VT3 Series by Keyence Corporation, detailing connection methods via serial and Ethernet interfaces. It includes system configuration, wiring diagrams, unit settings, and troubleshooting for various target PLC models. The manual emphasizes the importance of verifying connection compatibility and settings before establishing communication with the PLC.

Uploaded by

bahemudt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views70 pages

Keyence Serial Ethernet

The document is a PLC Connection Manual for the VT5/VT3 Series by Keyence Corporation, detailing connection methods via serial and Ethernet interfaces. It includes system configuration, wiring diagrams, unit settings, and troubleshooting for various target PLC models. The manual emphasizes the importance of verifying connection compatibility and settings before establishing communication with the PLC.

Uploaded by

bahemudt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 70

Touch Panel Display

VT5/VT3 Series
PLC Connection Manual
Keyence Corporation Serial Connection
Ethernet Connection
Checking Operation before Connection
System Configuration
Wiring Diagrams for Connections
Unit Settings
Available Devices
Error Messages and Remedies
About the 2-port Adapter MT-T2/T3

Target PLC
KV-8000 Series (Ethernet)
KV-8000 Series (Serial)
KV-7000 Series (Ethernet)
KV-7000 Series (Serial)
KV-5500/5000/3000(Ethernet)
KV-5500/5000/3000/L2*V
KV-1000/700(Ethernet)
KV-1000/700, KV-L20*/L21V
KV Nano Series [KV-N*](Ethernet)
KV Nano Series [KV-N*]
KV-10/16/24/40, KV-P16
KZ-300/350, KZ-L2
KZ-10/16/24/40/80
KZ-A500
Refer to “PLC Connection Manual” for
KZ-L10
other chapters and the appendix.

A82GB-001 2111-1
1-1 Checking Operation before Connection
1 This section describes how to check the items required for connecting VT5/VT3/Soft-VT/DT and PLC via serial
interface or Ethernet.
For the connection of other interfaces (Multi-Link or VT2 Multi-Link), see each chapter.
"Chapter 19 MULTI-LINK"
CONNECTING TO THE KV & KZ SERIES

"Chapter 20 VT2 MULTI-LINK"


(1) Make sure that the VT5, VT3, Soft-VT and DT can be connected to the PLC, link unit or Ethernet unit.
(2) Check whether or not CPU, link unit or Ethernet settings are required.
(3) Confirm the name of the model to set as the target PLC.
Please ensure to check the above 3 points before connecting to PLC.
"Procedure before Starting Communication", page 20

Serial connections
Series Connection
CPU Unit Setting Target PLC
Name Methods
KV-XL402
KV-XL202 KV-8000 Series (Serial)*5 *7
P.1-27
*6
KV-L21V KV-8000 Series (Serial) <XYM>*3 *5 *7
KV-8000/8000A KV-L20V
KV-LM21V KV-8000 Series (KV-LM2V)*4 *5 *7
P.1-30
KV-LM20V KV-8000 Series (KV-LM2V) <XYM>*3 *4 *5 *7
KV-XL402
KV-XL202 KV-7000 Series (Serial)*5 *7
P.1-27
*6
KV-L21V KV-7000 Series (Serial) <XYM>*3 *5 *7
KV-7500 KV-L20V
KV-LM21V KV-7000 Series (KV-LM2V)*4 *5 *7
P.1-30
KV-LM20V KV-7000 Series (KV-LM2V) <XYM>*3 *4 *5 *7
Built-in serial port
P.1-27
direct link
KV-XL402 KV-7000 Series (Serial)*5 *7
*6 KV-XL202 KV-7000 Series (Serial) <XYM>*3 *5 *7
KV-7300 P.1-27
KV-L21V
KV-L20V
KV-LM21V KV-7000 Series (KV-LM2V)*4 *5 *7
P.1-30
KV-LM20V KV-7000 Series (KV-LM2V) <XYM>*3 *4 *5 *7
KV-5500/5000/3000/L2V*2 *7
KV-L21V
P.1-29 KV-5500/5000/3000/
KV-L20V
L2V<XYM>*2 *3 *7
KV-5500/5000 KV-5500/5000/3000
KV-LM21V (KV-LM2V)*1 *4 *7
P.1-30
KV-LM20V KV-5500/5000/3000
(KV-LM2V)<XYM>*1 *3 *4 *7
KV PLC port direct link Not required KV-5500/5000/3000/L2V*2 *7
KV-L21V KV-5500/5000/3000/
P.1-29 L2V<XYM>*2 *3 *7
KV-L20V
KV-3000 KV-5500/5000/3000
KV-LM21V (KV-LM2V)*1 *4 *7
P.1-30
KV-LM20V KV-5500/5000/3000
(KV-LM2V)<XYM>*1 *3 *4 *7
PLC port direct link Not required
KV-1000/700, KV-L20/L21V *7
KV-L21V KV-1000, KV-L20/
KV-L20V P.1-29 L21V<XYM>*2 *3 *7
KV-1000
KV-L20R
KV-LM21V KV-1000/700(KV-LM20/21V)*1 *4 *7
P.1-30
KV-LM20V KV-1000(KV-LM20/21V)<XYM>*1 *3 *4 *7
PLC port direct link Not required
KV-L21V
KV-L20V KV-1000/700, KV-L20/L21V *7
P.1-29
KV-L20R
KV-L20
KV-700
KV-LM21V
KV-LM20V P.1-30 KV-1000/700(KV-LM20/21V)*1 *4 *7
KV-LM20
KV-L20
P.19-13 KV-L20 (VT Multi-link)*1 *4 *7
(VT Multi-link)
Built-in serial port
P.1-31
KV Nano Series direct link KV Nano Series[KV-N] *7
(KV-N14/24/40/60) KV-N10L P.1-31 KV Nano Series[KV-N]<XYM>*3 *7
KV-N11L P.1-32

1-2 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-1 Checking Operation before Connection

Series
Name
CPU
Connection
Methods
Unit Setting Target PLC 1
Built-in serial port
P.1-31

CONNECTING TO THE KV & KZ SERIES


KV Nano Series direct link KV Nano Series[KV-N*] *7
(KV-NC32) KV-NC10L P.1-33 KV Nano Series[KV-N*]<XYM>*3 *7
KV KV-NC20L P.1-34
KV-10/16/24/40 PLC port direct link Not required
KV-10/16/24/40, KV-P16*4 *7
KV-P Series PLC port direct link Not required
PLC port direct link Not required
KZ-300/350, KZ-L2*4 *7
KZ-300/350 KZ-L2 P.1-35
VT-L16Z P.19-11 KZ-300/50(VT-L16Z)*1 *4 *7
KZ KZ-10/16/24/40/80 PLC port direct link Not required KZ-10/16/24/40/80*4 *7
PLC port direct link Not required KZ-A500*4 *7
KZ-A500 KZ-L10 P.1-36 KZ-L10*4 *7
VT-L16Z P.19-11 KZ-A500(VT-L16Z)*1 *4 *7
*1 Not supported by DT-80/80A and DT-100.
*2 Not supported by DT-80 and DT-100.
*3 Support the XYM display mode of KV STUDIO ladder support software.
*4 Not supported by the VT5 Series.
*5 Not supported by the DT Series.
*6 A bus connection unit is required when using a KV-5000/3000 Series expansion unit to connect to the VT5/VT3 Series.
*7 Not supported by VT5-WX15/WX12 or Soft-VT.

Ethernet connections

Point DT Series is not supported for the Ethernet connection.

Series
PLC Connection Methods Unit Setting Target PLC
Name
Internal Ethernet port direct link P.1-46
KV-LE21V/KV-LE20V KV-8000 Series (Ethernet)
KV-8000/8000A*3 KV-EP21V
P.1-50 KV-8000 Series (Ethernet) <XYM>*2
KV-XLE02
KV-XD02
Internal Ethernet port direct link P.1-46
KV-7500*3 KV-LE21V/KV-LE20V
KV-EP21V P.1-50
KV-7000 Series (Ethernet)
KV-XLE02
KV-7000 Series (Ethernet) <XYM>*2
KV-LE21V/KV-LE20V
KV-7300*3 KV-EP21V P.1-50
KV KV-XLE02
Internal Ethernet port direct link P.1-49
KV-5500/5000 KV-5500/5000/3000
KV-LE21V/KV-LE20V
P.1-50 (EtherNet)
KV-EP21V
KV-5500/5000/3000
KV-LE21V/KV-LE20V (EtherNet) <XYM>*2
KV-3000 P.1-50
KV-EP21V
KV-LE20/KV-LE20A KV-1000/700 (EtherNet)
KV-1000/700 P.1-51
KV-LE20V/KV-LE21V KV-1000 (EtherNet) <XYM>*2
KV Nano Series KV Nano Series [KV-N*]
(KV-N24/40/60)*1 (EtherNet),
KV-NC1EP P.1-52
KV Nano Series KV Nano Series [KV-N*]
(KV-NC32) (EtherNet) <XYM>*2

*1 A KV-N1 connection conversion unit is required when using KV-NC1EP to connect to the VT5/VT3 Series.
*2 Support the XYM display mode of KV STUDIO ladder support software.
*3 A bus connection unit is required when using a KV-5000/3000 Series expansion unit to connect to the VT5/VT3 Series.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-3


1-2 System Configuration
1 This section describes the system configuration of the VT5 Series/VT3 Series/DT Series and the KV and KZ Series.

System configuration for serial connections


CONNECTING TO THE KV & KZ SERIES

 KV-7300 Series (built-in serial port direct link)

KV-7300

VT5(COM1)/VT3-W4 : Wiring diagram W20*1


REALTIME
Logic Controller
CARD
MENU ENTER KV, KZ series PLC port direct link cable VT3(PORT2)/VT-T1 : Wiring diagram 1
CARD SW

USB
VT3(PORT3) : Wiring diagram 31
SD/RD

VT3-V6H(G)/Q5H(G) : Wiring diagram H20


SERIAL
VT5/VT3
KV-7300 VT3-V7R : Wiring diagram R1 Series
*1 Not supported by the VT5-WX.

 KV-8000/8000A/7500/7300+KV-XL202/XL402

*2
RS-232C VT5(COM1)/VT3-W4Wiring diagram W28
(PORT1/PORT2) VT3(PORT2)/VT-T1Wiring diagram 12
VT3(PORT3) Wiring diagram 35
VT3-V6H(G)/Q5H(G)Wiring diagram H27
KV-XL202 VT3-V7RWiring diagram R13
*1*2
VT5(COM2)/VT3-W4AWiring diagram W44
RS-422A
(PORT1/PORT2) VT3(PORT2)/VT-T1Wiring diagram 13 VT5/VT3
KV-8000/8000A/
7500/7300 VT3-V6H(G)/Q5H(G)Wiring diagram H44 Series
VT3-V7RWiring diagram R14
*1 Not supported by the VT5-W07M.
*2 Not supported by the VT5-WX.
KV-XL402

 KV-8000/8000A/7500/7300+KV-L2*V (KV STUDIO mode)


VT5(COM1)/VT3-W4 : Wiring diagram W24 *2
VT3(PORT2)/VT-T1 : Wiring diagram 6
PORT1 RS-232C
VT3(PORT3) : Wiring diagram 32
VT3-V6H(G)/Q5H(G) : Wiring diagram H24
VT3-V7R : Wiring diagram R7
VT5(COM1)/VT3-W4 : Wiring diagram W25 *2
VT3(PORT2)/VT-T1 : Wiring diagram 7
PORT2 RS-232C
VT3(PORT3) : Wiring diagram 33
VT3-V6H(G)/Q5H(G) : Wiring diagram H25 VT5/VT3
VT3-V7R : Wiring diagram R8 Series
KV-8000/8000A/ Bus connection KV-L2V
7500/7300 unit VT5(COM2)/VT3-W4A : Wiring diagram W41 *1*2
PORT2 RS-422A VT3(PORT2)/VT-T1 : Wiring diagram 9
VT3-V6H(G)/Q5H(G) : Wiring diagram H41
VT3-V7R : Wiring diagram R10
*1 Not supported by the VT5-W07M.
*2 Not supported by the VT5-WX.

1-4 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-2 System Configuration

 KV-3000/1000/700 (PLC port direct link)


1

CONNECTING TO THE KV & KZ SERIES


VT5(COM1)/VT3-W4 : Wiring diagram W20 *1
VT5/VT3
KV, KZ series PLC port direct link cable VT3(PORT2)/VT-T1/DT : Wiring diagram 1 Series
VT3(PORT3) : Wiring diagram 31
RUN
STOP
RUN

MEMORY CARD
VT3-V6H(G)/Q5H(G) : Wiring diagram H20 PLC
LINK
ACT
KL RD
KL SD

KV-3000/1000/700 VT3-V7R : Wiring diagram R1 CARD

*1 Not supported by the VT5-WX.

DT series

 KV-5500/5000/3000+KV-L2V(KV BUILDER/KV STUDIO mode)


VT5(COM1)/VT3-W4 : Wiring diagram W24 *2
VT3(PORT2)/VT-T1/DT : Wiring diagram 6
PORT1 RS-232C
VT3(PORT3) : Wiring diagram 32
VT3-V6H(G)/Q5H(G) : Wiring diagram H24
VT3-V7R : Wiring diagram R7
VT5/VT3 Series
VT5(COM1)/VT3-W4 : Wiring diagram W25 *2
ˇ VT3(PORT2)/VT-T1/DT : Wiring diagram 7
PORT2 RS-232C RUN
STOP
RUN

MEMORY CARD
PLC

VT3(PORT3) : Wiring diagram 33 LINK


ACT
KL RD
KL SD
CARD

VT3-V6H(G)/Q5H(G) : Wiring diagram H25


KV-5500/5000/3000 KV-L2V VT3-V7R : Wiring diagram R8

VT5(COM2)/VT3-W4A : Wiring diagram W41 *1*2


PORT2 RS-422A VT3(PORT2)/VT-T1/DT : Wiring diagram 8 DT series
VT3-V6H(G)/Q5H(G) : Wiring diagram H41
VT3-V7R : Wiring diagram R9
*1 Not supported by the VT5-W07M.
*2 Not supported by the VT5-WX.

 KV-1000+KV-L20R/KV-L2V (KV BUILDER/KV STUDIO mode)


VT5(COM1)/VT3-W4 : Wiring diagram W24 *2
VT3(PORT2)/VT-T1/DT : Wiring diagram 6
PORT1 RS-232C
VT3(PORT3) : Wiring diagram 32
VT3-V6H(G)/Q5H(G) : Wiring diagram H24
VT3-V7R : Wiring diagram R7
VT5/VT3 Series
VT5(COM1)/VT3-W4 : Wiring diagram W25 *2
ˇ VT3(PORT2)/VT-T1/DT : Wiring diagram 7
PORT2 RS-232C RUN
STOP
RUN
MEMORY CARD

PLC

VT3(PORT3) : Wiring diagram 33 LINK


ACT
KL RD
KL SD

VT3-V6H(G)/Q5H(G) : Wiring diagram H25


CARD

KV-1000 KV-L20R/L2V VT3-V7R : Wiring diagram R8

VT5(COM2)/VT3-W4A : Wiring diagram W41 *1*2


PORT2 RS-422A VT3(PORT2)/VT-T1/DT : Wiring diagram 8 DT series
VT3-V6H(G)/Q5H(G) : Wiring diagram H41
VT3-V7R : Wiring diagram R9
*1 Not supported by the VT5-W07M.
*2 Not supported by the VT5-WX.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-5


1-2 System Configuration

1  KV-700+KV-L20/L2V (KV BUILDER mode)


VT5(COM1)/VT3-W4 : Wiring diagram W24 *2
CONNECTING TO THE KV & KZ SERIES

VT3(PORT2)/VT-T1/DT : Wiring diagram 6


PORT1 RS-232C
VT3(PORT3) : Wiring diagram 32
VT3-V6H(G)/Q5H(G) : Wiring diagram H24
KEYENCE KV-700
0
1
2
3
4
5
0
1
2
3
4
5
VT3-V7R : Wiring diagram R7
VT5/VT3 Series
6 6
7 7
8 8
9 9
10 10

VT5(COM1)/VT3-W4 : Wiring diagram W25 *2


11 11
12 12
HYPER ACCESS WINDOW 13 13
14 14
15 15

RUN
STOP
ˇ VT3(PORT2)/VT-T1/DT : Wiring diagram 7
PORT2 RS-232C
RUN
STOP
RUN

MEMORY CARD
CARD RD SD USB

PLC

SERIAL
VT3(PORT3) : Wiring diagram 33 LINK
ACT
KL RD
KL SD

VT3-V6H(G)/Q5H(G) : Wiring diagram H25


CARD

KV-700 KV-L20(R)/L2V VT3-V7R : Wiring diagram R8

VT5(COM2)/VT3-W4A : Wiring diagram W41 *1*2


PORT2 RS-422A VT3(PORT2)/VT-T1/DT : Wiring diagram 8 DT series
VT3-V6H(G)/Q5H(G) : Wiring diagram H41
VT3-V7R : Wiring diagram R9
*1 Not supported by the VT5-W07M.
*2 Not supported by the VT5-WX.

 KV-8000/8000A/7500/7300/5500/5000/3000+KV-LM20V/KV-LM21V
KV-LM20V/KV-LM21V
: Dedicated cable
+ KPEV-SB(1P)
: Connecting cable for VT3
handy Series/VT-C5R1

KV-8000/8000A/7500/7300/ Daisy-chain cable


Connecting cable for
VT3 handy Series 5500/5000/3000 (OP-30590,OP-32985)

Communication cable RUN


STOP
RUN

MEMORY CARD
KPEV-SB (1P)
PLC
LINK
ACT
KL RD
KL SD
CARD

Total length of cable


≤ 1000m Adaptor KL-B1
(including VT-C5R1, for connecting
connecting cable for VT3 cable
DT-100A
VT3 Series VT3 Series handy Series, and link cable) VT3 Series (Terminator ON)
VT3 handy Series
(terminator ON)

Up to 15 units

Point • For KV-8000/8000A/7500/7300, a bus connection unit is required when using a KV-5000/
3000 series expansion unit to connect to the VT5/VT3 Series.
• The VT5 Series is not supported.
• Not supported by VT2 series and VT1 series (including the VT-7SR).
• Not supported by DT-80/80A and DT-100.
• Cannot connect to VT3-W4T/W4M(T)/W4G(T) (RS-232C).
• Max. speed of communication is 115200bit/s when connecting VT3-W4TA/W4M(T)A/
W4G(T)A (RS-422A/485). Be sure that the communication speed of other connecting
devices complies with VT3-W4TA/W4M(T)A/W4G(T)A.
• For one MegaLink, only one DT-100A can be connected.
• DT-100A, when used as the terminator of DT-500, can also use the MegaLink connection.
• VT3 handy Series and VT3-V7R can only be connected to both ends of the wiring.
• For connection with VT3 handy Series using VT-T1, never remove VT-T1 and OP-87194/
87195/87196 in power on status.

Reference For setting and connection, see "Chapter 21 MEGALINK".

1-6 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-2 System Configuration

 KV-1000/700+KV-LM20(V)/LM21V
1
KV-LM20(V)/LM21V

CONNECTING TO THE KV & KZ SERIES


: Dedicated cable
+ KPEV-SB(1P)
: Connecting cable for VT3
handy Series/VT-C5R1
KV-1000/700
Connecting cable for Cable
VT3 handy Series (OP-30590, OP-32985)

Communication cable RUN


STOP
RUN

MEMORY CARD
KPEV-SB (1P)
PLC
LINK
ACT
KL RD
KL SD
CARD

Total length
≤ 1000m Cable Adapter
(including VT-C5R1, KL-B1
connecting cable for VT3
DT-100A
handy Series, and link cable)
VT3 series VT2 series VT3 series (terminator ON)
VT3 handy Series
(terminator ON)

Up to 15 units

Point • The VT5 Series is not supported.


• The VT1 Series (including VT-7SR) is not supported.
• DT-80/80A and DT-100 are not supported.
• VT3-W4T/W4M(T)/W4G(T) (RS-232C type) cannot be connected.
• The maximum connection speed is 115,200 bit/s when the VT3-W4TA/W4M(T)A/W4G(T)A
(RS-422/485 type) is connected. Align the communication speed of other connected
devices with the VT3-W4TA/W4M(T)A/W4G(T)A.
• The VT3 handy Series/V7R can only be connected on both ends of the wiring.
• When VT-T1 is used to connect the VT3 handy Series, do not remove or connect VT-T1 and
OP-87194/87195/87196 when the power is on.
• Only one DT-100A unit can be connected to one MegaLink connection.
• When DT-100A is used as the terminator of DT-500, it can use the MegaLink connection.

Reference For setting and connection, see "Chapter 21 MEGALINK".

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-7


1-2 System Configuration

1  KV-700+KV-L20 (VT multi-link mode)


KEYENCE KV-700
0 0
1 1
2 2
CONNECTING TO THE KV & KZ SERIES

3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11

HYPER ACCESS WINDOW


12 12
13 13
14 14
15 15 KV-L20
RUN
STOP
+ : Dedicated cable
CARD RD SD USB

SERIAL
KPEV-SB(1P)

Connecting cable for : Connecting cable for VT3


KV-700 handy Series/VT-C5R1
VT3 handy Series

Communication cable
KPEV-SB (1P)
VT-C5R1
(5m)
Total cable length
≤ 500 m
(including VT-C5R1 and
VT1 series connecting cable for VT3 series VT2 series
VT3 handy Series)
VT3 handy Series (terminator ON)
(terminator ON) VT3-V7R

Up to 16 units

Point • The VT5 Series is not supported.


• VT3-W4T/W4M(T)/W4G(T) (RS-232C type) are not supported.
• Not supported by DT series.
• Not supported by KV-L20R/KV-L20V/KV-L21V.
• VT3 handy Series can only be connected to both ends of the wiring.
• For connection with VT3 handy Series using VT-T1, never remove VT-T1 and OP-87194/
87195/87196 in power on status.

Reference For settings and connections, see "Chapter 19 MULTI-LINK"

1-8 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-2 System Configuration

 KV Nano Series
VT5(COM1)/VT3-W4: Wiring diagram W20 *3
1

CONNECTING TO THE KV & KZ SERIES


KV Nano Series VT3(PORT2)/VT-T1/DT: Wiring diagram 1
Built-in serial port direct cable
VT3(PORT3): Wiring diagram 31
VT3-V6H(G)/Q5H(G): Wiring diagram H20
VT3-V7R: Wiring diagram R1

VT5(COM1)/VT3-W4: Wiring diagram W24 *3


VT3(PORT2)/VT-T1/DT: Wiring diagram 6
RS-232C
VT3(PORT3): Wiring diagram 32
VT5/VT3 Series
VT3-V6H(G)/Q5H(G): Wiring diagram H24

KV-N10L VT3-V7R: Wiring diagram R7 RUN


STOP
RUN

MEMORY CARD
PLC
LINK

VT5(COM2)/VT3-W4A: Wiring diagram W42 *2*3


ACT
KL RD
KL SD
CARD

VT3(PORT2)/VT-T1/DT: Wiring diagram 9


KV-N14/24/40/60
RS-422A VT3-V6H(G)/Q5H(G): Wiring diagram H42
VT3-V7R: Wiring diagram R10
DT Series
VT5(COM2)/VT3-W4A: Wiring diagram W43 *2*3
RS-485*1
VT3(PORT4)/VT-T1: Wiring diagram 10
KV-N11L
VT3-V6H(G)/Q5H(G): Wiring diagram H43
VT3-V7R: Wiring diagram R11
*1 Not supported by DT Series.
*2 Not supported by the VT5-W07M.
*3 Not supported by the VT5-WX.

VT5(COM1)/VT3-W4 : Wiring diagram W20 *3


KV Nano Series
VT3(PORT2)/VT-T1/DT : Wiring diagram 1
Built-in serial port direct cable
VT3(PORT3) : Wiring diagram 31
VT3-V6H(G)/Q5H(G) : Wiring diagram H20
VT3-V7R : Wiring diagram R1
VT5(COM1)/VT3-W4 : Wiring diagram W24 *3
VT3(PORT2)/VT-T1/DT : Wiring diagram 6
PORT1 RS-232C
VT3(PORT3) : Wiring diagram 32
VT3-V6H(G)/Q5H(G) : Wiring diagram H24
VT5/VT3 Series
VT3-V7R : Wiring diagram R7
KV-NC10L
VT5(COM1)/VT3-W4 : Wiring diagram W24 *3 RUN
STOP
RUN
MEMORY CARD

PLC

VT3(PORT2)/VT-T1/DT : Wiring diagram 6 LINK


ACT
KL RD
KL SD
CARD

VT3(PORT3) : Wiring diagram 32


KV-NC32 PORT1 RS-232C VT3-V6H(G)/Q5H(G) : Wiring diagram H24
VT3-V7R : Wiring diagram R7
VT5(COM1)/VT3-W4 : Wiring diagram W27 *3 DT Series
KV-NC20L
VT3(PORT2)/VT-T1/DT : Wiring diagram 11
PORT2 RS-232C
VT3(PORT3) : Wiring diagram 34
VT3-V6H(G)/Q5H(G) : Wiring diagram H26
VT3-V7R : Wiring diagram R12
VT5(COM2)/VT3-W4A : Wiring diagram W42 *2*3
PORT2 RS-422A VT3(PORT2)/VT-T1/DT : Wiring diagram 9

VT3-V6H(G)/Q5H(G) : Wiring diagram H42


VT3-V7R : Wiring diagram R10
VT5(COM2)/VT3-W4A : Wiring diagram W43 *2*3
PORT2 RS-485 *1 VT3(PORT4)/VT-T1/DT : Wiring diagram 10

VT3-V6H(G)/Q5H(G) : Wiring diagram H43


VT3-V7R : Wiring diagram R11
*1 Not supported by DT Series.
*2 Not supported by the VT5-W07M.
*3 Not supported by the VT5-WX.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-9


1-2 System Configuration

1  KV-10/16/24/40 and KV-P series (PLC port direct link)


CONNECTING TO THE KV & KZ SERIES

C1 001 003 005 007 009 IN


000 002 004 006 008
0ch
EYENCE 0 1 2 3 4 5 6 7 8 9

0 1 2 3 4 5
KV-16AR
5ch
500 501 502 504
24V-OUT-OV C3 C4 503 505 OUT

VT3(PORT2)/VT-T1/DT : Wiring diagram 1 VT3 Series


KV-10/16/24/40
KV series PLC port direct link cable VT3(PORT3) : Wiring diagram 31
VT3-V6H(G)/Q5H(G) : Wiring diagram H20
RUN
STOP
RUN

MEMORY CARD
VT3-W4 : Wiring diagram W20 PLC
LINK
ACT
NEXT RESET ENTER KL RD
KL SD

VT3-V7R : Wiring diagram R1


CARD

F1 F2 F3 F4 F5

KV-P Series
(KV-P16T/16R/ DT Series
16TL/16RL)

 KZ series (PLC port direct link)

KEYENCE
KZ - 10R

VT3(PORT2)/VT-T1/DT : Wiring diagram 1

KZ, series PLC port direct link cable VT3-V6H(G)/Q5H(G) : Wiring diagram H20
VT3-W4 : Wiring diagram W20
KZ-10/16/24 VT3 Series
VT3-V7R : Wiring diagram R1
KZ-40/80 MT-T2
KZ Series
ACCESS 1+2 1ONLY

PLC port RUN


STOP
RUN

MEMORY CARD
PORTA
(PLC)
direct link cables VT3(PORT2)/VT-T1/DT : Wiring diagram 1
PLC

+
LINK

PORT1 ACT
(MT) KL RD
KL SD
PORT2
(TOOL) CARD

24V 0V
VT3-V6H(G)/Q5H(G) : Wiring diagram H20
VT3-V7R : Wiring diagram R1

2-port adapter
KZ-300/350 MT-T2
DT Series

1-10 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-2 System Configuration

 KZ-300/350+KZ-L2
1
VT3(PORT2)/VT-T1/DT : Wiring diagram 2

CONNECTING TO THE KV & KZ SERIES


PORT1 RS-232C VT3-V6H(G)/Q5H(G) : Wiring diagram H21
VT3-W4 : Wiring diagram W21
VT3-V7R : Wiring diagram R3

VT3(PORT2)/VT-T1/DT : Wiring diagram 3 VT3 Series


+
PORT2 RS-232C VT3-V6H(G)/Q5H(G) : Wiring diagram H22
RUN
STOP
RUN

MEMORY CARD
VT3-W4 : Wiring diagram W22 LINK
PLC

ACT
KL RD

KZ-300/350 KZ-L2 VT3-V7R : Wiring diagram R4 KL SD


CARD

VT3(PORT2)/VT-T1/DT : Wiring diagram 4


PORT2 RS-422A VT3-V6H(G)/Q5H(G) : Wiring diagram H40
VT3-W4A : Wiring diagram W40
DT Series
VT3-V7R : Wiring diagram R5

 KZ-A500 (PLC port direct link)

VT3(PORT2)/VT-T1/DT : Wiring diagram 1


KZ, KV series PLC port direct link cable
VT3-W4 : Wiring diagram W26
VT3 Series
VT3-V7R : Wiring diagram R2
MT-T2
KZ, KV series
ACCESS 1+2 1ONLY
PLC port RUN
STOP
RUN

MEMORY CARD
PLC

+ direct link cables LINK

PORTA
(PLC)
VT3(PORT2)/VT-T1/DT : Wiring diagram 1 ACT
KL RD
KL SD
CARD
PORT1
(MT)

PORT2
VT3-V7R : Wiring diagram R2
KZ-A500 24V 0V
(TOOL)

2-port adapter DT Series


MT-T3

 KZ-A500+KZ-L10
VT3(PORT2)/VT-T1/DT: Wiring diagram 5
PORT1 RS-232C VT3-V6H(G)/Q5H(G): Wiring diagram H23
VT3-W4: Wiring diagram W23
VT3-V7R: Wiring diagram R6

VT3(PORT2)/VT-T1/DT: Wiring diagram 3 VT3 Series


PORT2 RS-232C VT3-V6H(G)/Q5H(G): Wiring diagram H22
RUN
STOP

VT3-W4: Wiring diagram W22 RUN


MEMORY CARD

PLC
LINK
ACT

VT3-V7R: Wiring diagram R4


KL RD
KL SD
CARD

KZ-A500 KZ-L10
VT3(PORT2)/VT-T1/DT: Wiring diagram 4
PORT2 RS-422A VT3-V6H(G)/Q5H(G): Wiring diagram H40
VT3-W4A: Wiring diagram W40
VT3-V7R: Wiring diagram R5 DT Series

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-11


1-2 System Configuration

1  VT-L16Z (Multi-link Unit)


CONNECTING TO THE KV & KZ SERIES

KZ-A500
READY/
SELECT

ERROR

VT No.
0-7 8-15

S.ERR

B.ERR 0/8 4/12


1/9 5/13

VT-L16Z
2/10 6/14
VT-L16Z
3/11 7/15

1
2
SELECT
3
4 1 1 1 1
5 2 2 2 2
115.2 57.6 38.4 19.2
6
[kbit/s]
ON OFF

: Dedicated cable
KZ-350/300 KPEV-SB(1P)
A B SG

A B

: Connecting cable for VT3


Connecting cable for
VT3 handy Series handy Series/VT-C5R1

Communication cable
KPEV-SB (1P)
VT-C5R1
(5m)
Total cable length
≤ 500 m
(including VT-C5R1 and
VT1 series connecting cable for VT3 series VT2 series
VT3 handy Series)
(terminator ON)
VT3 handy Series VT3-V7R
(terminator ON)

Up to 16 units

Point • The VT5 Series is not supported.


• VT3-W4T/W4M(T)/W4G(T) (RS-232C type) are not supported.
• Not supported by the DT Series.
• VT3 handy Series can only be connected to both ends of the wiring.
• For connection with VT3 handy Series using VT-T1, never remove VT-T1 and OP-87194/
87195/87196 in power on status.

Reference For details on settings and connections, see "Chapter 19 MULTI-LINK"

1-12 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-2 System Configuration

System configuration for Ethernet connections 1

CONNECTING TO THE KV & KZ SERIES


 KV-8000/8000A/7500/7300 (Ethernet)

*1

Soft-VT VT5*3 VT3 *2


VT2-E1/E2VT3-E3

Ethernet STP/UTP cable

Max. 16 units

KV-8000/8000A/ KV-8000/8000A/ KV-XLE02/ KV-8000/8000A/ Bus connection KV-EP21V


7500 7500/7300 XD02 *5 7500/7300 unit *4 /LE2*V

*1 Please note that with the increase in the number of VT5/VT3 Series and Soft-VT units connected, the communications
load also increases.
*2 VT3 handy Series has built-in Ethernet function, so VT2-E1/E2 and VT3-E3 are not required.
*3 The VT5 Series has a built-in Ethernet function and does not require the VT2-E1/E2 and VT3-E3.
*4 A bus connection unit is required when using a KV-5000/3000 Series expansion unit to connect to the VT5/VT3 Series
and Soft-VT.
*5 The KV-XD02 can only be connected to the KV-8000.

Point When the serial number of the VT3-E3 ends in A or later, the VT3 system program must be in
Ver. 4.51 or later to enable connection to the VT3 Series.

 KV-5500/5000/3000/1000/700 (Ethernet)

*1
+

VT5*3 VT3
Soft-VT VT2-E1/E2, VT3-E3*2

Ethernet STP/UTP cable

STP/UTP cable

ˇ ˇ
Max. 16 units

KV-5500/5000 KV-5500 KV-EP21V KV-1000/700 KV-LE20(V/A)


/5000/3000 /LE2*V

*1 The KV-1000/700 cannot be connected to multiple VT5/VT3 Series.


Please note that with the increase in the number of VT5/VT3 Series and Soft-VT units connected, the communications
load also increases.
*2 VT3 handy Series has built-in Ethernet function, so VT2-E1/E2 and VT3-E3 are not required.
*3 The VT5 Series has a built-in Ethernet function and does not require the VT2-E1/E2 and VT3-E3.

Point • KV-LE20 that can be connected to VT3 via Ethernet connection aremarked with the letter
"A" preceding the lot No..
• When the serial number of the VT3-E3 ends in A or later, the VT3 system program must be
in Ver. 4.51 or later to enable connection to the VT3 Series.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-13


1-2 System Configuration

1  KV Nano Series (Ethernet)


CONNECTING TO THE KV & KZ SERIES

*2

Soft-VT VT5*4 VT3


VT2-E1/E2 VT3-E3 *3

Ethernet STP/UTPcable

Max. 16 units

KV-N24/40/60 Connection KV-NC1EP KV-NC32T KV-NC1EP


conversion unit
KV-N1*1

*1 The KV-N1 connection conversion unit is required when using a KV-N24/40/60 and KV-NC1EP to connect the VT5/VT3
Series and Soft-VT.
*2 Please note that with the increase in the number of VT5/VT3 Series and Soft-VT units connected, the communications
load also increases.
*3 VT3 handy Series has built-in Ethernet function, so VT2-E1/E2 and VT3-E3 are not required.
*4 The VT5 Series has a built-in Ethernet function and does not require the VT2-E1/E2 and VT3-E3.

Point When the serial number of the VT3-E3 ends in A or later, the VT3 system program must be in
Ver. 4.51 or later to enable connection to the VT3 Series.

1-14 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-3 Wiring Diagrams for Connections
This section describes wiring of connector cables.
1
Wiring diagrams for serial connections

CONNECTING TO THE KV & KZ SERIES


 Connection to VT5 Series (COM1) and VT3-W4 (RS-232C)
 Wiring diagram W20 (PLC port direct link  Wiring diagram W21 (RS-232C)
OP-86917: 5m, OP-86916: 1m)
VT5(COM1)/VT3-W4 KV, KZ, KV-P VT3-W4 KZ-L2
(terminal block) (modular 6-pin) (terminal block) PORT1 (25-pin)
View from cable
Blue connector
* 5 SD side
TXD TXD 2 SD (1) (13)
Yellow
RXD 3 RD RXD 3 RD
RTS RTS 4 RS
CTS CTS 5 CS (14) (25)
Shielded cable D-sub 25-pin
SG 4 SG SG 7 SG
(6) (5) (4) (3) (2) (1) connector
DTR (only shielded on the DTR
Modular connector of kz, kv
DSR end using black hose) DSR
N.C. N.C.
N.C. N.C.

* indicates a terminal diagram for the VT5 Series.

The shielded cable must be


connected to SG when
disconnecting the
NOTICE cables.Shielded cables must be
insulated with heat shrinkable
hose in order to avoid contacting
with other cables or terminals.

 Wiring diagram W22 (RS-232C)  Wiring diagram W23 (RS-232C)


VT3-W4 KZ-L2 (KZ-L10) PORT2 VT3-W4 KZ-L10
(terminal block) (terminal block) (terminal block) PORT1 (25-pin)

TXD 1 SG (1) (3) (5) TXD 2 SD (1) (13)


SG SDA RDA
RXD (SG) (SD) (RD) RXD 3 RD
RTS 3 SD (2) (4) RTS 4 RS
CTS SDB RDB
CTS 5 CS (14) (25)
D-sub 25-pin
SG 5 RD KZ-L2 (KZ-L10) SG 7 SG
connector
DTR Terminal block No. DTR
DSR DSR
N.C. N.C.
N.C. N.C.

 Wiring diagram W24 (RS-232C)  Wiring diagram W25 (RS-232C)


VT5(COM1)/VT3-W4 KV-L20(R)/L2*V PORT1 (9-pin) VT5(COM1)/VT3-W4 KV-L20(R)/L2∗V PORT2
(terminal block) KV-N10L (9-pin) (terminal block) (terminal block)
KV-NC10L/NC20L PORT1 (9-pin)
* 2 RD (1) * (1) (3) (5)
TXD (6) TXD 1 SG
SG SD RD
RXD 3 SD RXD SDA(-) SDB(+)
S/R(-) S/R(+)
RTS 5 SG Front RTS 3 SD (2) (4)
CTS 7 RS CTS RDA(-) RDB(+)
S/R(-)* S/R(+)*
SG 8 CS (5) (9) SG 5 RD KV-L20R/L2∗V
DTR D-Sub 9-pin DTR Terminal block No.
DSR connector *KV-L20R only
DSR
N.C. N.C. (1) (3) (5)
SG SDA SDB
N.C. N.C. (SG) (SD) (RD)

(2) (4)
* indicates a terminal diagram for the VT5 Series. * indicates a terminal diagram for the VT5 Series. RDA RDB

KV-L20
Terminal block No.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-15


1-3 Wiring Diagrams for Connections

1  Wiring diagram W26


(PLC port direct link)
 Wiring diagram W27 (RS-232C)
VT5(COM1)/VT3-W4 KV-NC20L PORT2
(terminal block) (terminal block)
CONNECTING TO THE KV & KZ SERIES

VT3-W4 KZ
(terminal block) Modular 6-pin *
View from cable TXD SD
connector RXD N.C.
TXD 5 SD side
RTS N.C.
RXD 3 RD
CTS RD
RTS 1 RS
SG SG
CTS 6 CS
SG 4 SG DTR
(6) (5) (4) (3) (2) (1)
DTR 2 5V DSR
Modular connector of kz,kv
DSR N.C.
N.C. N.C.
N.C.
* indicates a terminal diagram for the VT5 Series.

Point KZ internal circuit will be damaged


if the wiring is wrong. This is must
be noted when wiring the cable.

 Wiring diagram W28 (RS-232C)


VT5(COM1)/VT3-W4 KV-XL202
㸦terminal block㸧 PORT1/PORT2㸦terminal block㸧

* 1 SD
TXD 1 SD RD

RXD 2 RD RS

RTS 3 RS CS

ER
CTS 4 CS
DR
SG 7 SG
7 SG

DTR
KV-XL202
DSR Terminal block No.
N.C.
N.C.

* indicates a terminal diagram for the VT5 Series.

 Connection to VT5 Series (COM2) and VT3-W4 (RS-422A)


 Wiring diagram W40 (RS-422A)  Wiring diagram W41 (RS-422A)
VT3-W4A KZ-L2 (KZ-L10) PORT2 VT5(COM2)/VT3-W4A KV-L20(R)/L2∗V PORT2
(terminal block) (terminal block) (terminal block) (terminal block)

TXDA 1 SG (1) (3) (5) TXDA 1 SG (1) (3) (5)


SG SDA RDA SG SD RD
TXDB 2 SDB (SG) (SD) (RD) TXDB 2 RDA(-) SDA(-) SDB(+)
S/R(-) S/R(+)
ON RXDA 3 SDA (2) (4) ON RXDA 3 SDA(-) (2) (4)
4 RDB SDB RDB RDA(-) RDB(+)
RXDB RXDB 4 RDB(+) S/R(-)* S/R(+)*
SG 5 RDA SG 5 SDB(+) KV-L20R/L2∗V
TERM. KZ-L2 (KZ-L10) TERM.
RTSA Terminal block No. RTSA Terminal block No.
*KV-L20R only
RTSB RTSB
CTSA CTSA (1) (3) (5)
SG SDA SDB
CTSB CTSB (SG) (SD) (RD)

(2) (4)
RDA RDB

KV-L20
Terminal block No.

1-16 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-3 Wiring Diagrams for Connections

 Wiring diagram W42 (RS-422A)  Wiring diagram W43 (RS-485: 2-wire)


1
VT5(COM2)/VT3-W4A*1 KV-N11L VT5(COM2)/VT3-W4A*1 KV-N11L
(terminal block) KV-NC20L PORT2 (terminal block) KV-NC20L PORT2

CONNECTING TO THE KV & KZ SERIES


(terminal block) (terminal block)

TXDA SG *2 TXDA S/R(+) *2

TXDB RDA(-) TXDB S/R(-)


ON RXDA SDA(-) ON RXDA
RXDB RDB(+) RXDB SG
SG SDB(+) SG
TERM. TERM.
RTSA RTSA Shield
RTSB RTSB D-type ground
CTSA CTSA (the third-type grounding)
CTSB CTSB

*1 Turn on the terminator switch. *1 Turn on the terminator switch.


*2 Turn on the terminal resistance switch. *2 Turn on the terminal resistance switch.
 Wiring diagram W44 (RS-422A)
VT5(COM2)/VT3-W4A KV-XL402
㸦terminal block㸧 PORT1/PORT2㸦terminal block㸧

SDA-
TXDA
Orange (dot: black 1)
1 SDA( ) 1 /SR-
Orange (dot: black 2) SDB+
TXDB 2 SDB( ) /SR-
Orange (dot: black 3) RDA-
ON RXDA 3 RDA( )
Orange (dot: black 4)
RXDB 4 RDB( ) RDB+
Orange (no dot)
SG 5 SG 5 SG
TERM. Orange (dot: red 1)
RTSA
Orange (dot: red 2) KV-XL402
RTSB
Orange (dot: red 3) Terminal block No
CTSA
Orange (dot: red 4)
CTSB

 Connection to VT3 series (PORT2)/DT series


 Wiring Diagram 1  Wiring Diagram 2
(PLC Port Direct Link OP-26484: 5m, (RS-232C: OP-24027)
OP-35403: 1m)
VT3 PORT2 (20-pin) VT3 PORT2 (20-pin)
DT PLC port (20-pin) KZ,KV,KV-P modular 6-pin DT PLC port (20-pin) KZ-L2 PORT1 (25-pin)
View from
cable
TXD 2 5 SD connector Red
TXD 2 2 SD
RXD 3 3 RD side Red/white (1) (13)
RXD 3 3 RD
*
RTS 4 1 RS Green
RTS 4 * 4 RS
CTS 5 6 CS Green/white
CTS 5 5 CS
GND 7 4 SG Black (14) (25)
GND 7 7 SG D-sub 25-pin
DR 6 2 5V (6) (5) (4) (3) (2) (1)
connector
ER 10 KZ/KV modular connector
* Not wired for loopback test inside the connector.
*
Solder the signal lead.
* 1/4W 3kΩ

 Wiring Diagram 3  Wiring Diagram 4


(RS-232C: OP-24027) (RS-422A: OP-24028)
VT3 PORT2 (20-pin) VT3 PORT2 (20-pin)
KZ-L2 (KZ-L10) DT PLC port (20-pin) KZ-L2 (KZ-L10)
DT PLC port (20-pin)
PORT2 (terminal block) PORT2 (terminal block)

Red Black
TXD 2 1 SG GND 7 1 SG
(1) (3) (5) Red
Red/white SG SDA RDA TXDA 11 2 SDB
RXD 3 (SG) (SD) (RD) Red/white
Green TXDB 12 3 SDA
RTS 4 3 SD (2) (4) Green (1) (3) (5)
Green/white * RXDA 13 4 RDB SG SDA RDA
CTS 5 SDB RDB
Green/white (SG) (SD) (RD)
Black RXDB 14 5 RDA
GND 7 5 RD KZ-L2 (KZ-L10) (2) (4)
TMR1 19 SDB RDB
terminal block No.
TMR2 20
* Not wired for loopback test inside the connector. KZ-L2 (KZ-L10)
RTSA 15
Solder the signal lead. terminal block No.
RTSB 16
CTSA 17
CTSB 18

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-17


1-3 Wiring Diagrams for Connections

1  Wiring Diagram 5
(RS-232C: OP-24027)
 Wiring Diagram 6
(RS-232C: OP-24027)
CONNECTING TO THE KV & KZ SERIES

VT3 PORT2 (20-pin) KV-L20(R)/L2ΩV PORT1 (9-pin)


DT PLC port (20-pin) KZ-L2 PORT1 (25-pin) VT3 PORT2 (20-pin) KV-N10L (9-pin)
DT PLC port (20-pin) KV-NC10L/NC20L PORT1 (9-pin)
Red
TXD 2 2 TXD Red
Red/white (1) (13) TXD 2 2 RD (1) (6)
RXD 3 3 RXD Red/white
Green RXD 3 3 SD
RTS 4 4 RTS Green
Green/white RTS 4 5 SG Front
CTS 5 5 CTS Green/white * view
Black (14) (25) CTS 5 7 RS
GND 7 7 GND D-sub 25-pin Black (9)
GND 7 8 CS (5)
connector
D-sub 9-pin connector
* Not wired for loopback test inside the connector. Solder the signal lead.

Reference For the pin assignment number of the connectors on the VT3 series/DT series, please see
the Appendix at the end of this manual.
 Wiring Diagram 7  Wiring Diagram 8
(RS-232C: OP-24027) (RS-422A: OP-24028)
VT3 PORT2 (20-pin) KV-L20(R)/L2ΩV PORT2 (terminal block) VT3 PORT2 (20-pin) KV-L20(R)/L2ΩV PORT2 (terminal block)
DT PLC port (20-pin) DT PLC port (20-pin)

Red (1) (3) (5) Black (1) (3) (5)


TXD 2 1 SG GND 7 1 SG SG SD RD
Red/white SG SD RD Red SDA(-) SDB(+)
RXD 3 SDA(-) SDB(+) TXDA 11 2 RDA(-) S/R(-) S/R(+)
Green S/R(-) S/R(+) Red/white
RTS 4 3 SD (2) (4) TXDB 12 3 SDA(-) (2) (4)
Green/white * Green RDA(-) RDB(+)
CTS 5 RDA(-) RDB(+) RXDA 13 4 RDB(+) S/R(-)* S/R(+)*
S/R(-)* S/R(+)* Green/white
Black RXDB 14 5 SDB(+)
GND 7 5 RD KV-L20R/L2ΩV KV-L20R/L2ΩV
terminal block No. TMR1 19 terminal block No.
*KV-L20R only *KV-L20R only
* Not wired for loopback test inside the connector. TMR2 20
Solder the signal lead. (1) (3) (5) RTSA 15 (1) (3) (5)
SG SDA SDB
SG SDA SDB RTSB 16 (SG) (SD) (RD)
(SG) (SD) (RD)
CTSA 17 (2) (4)
(2) (4) RDA RDB
RDA RDB CTSB 18
KV-L20
KV-L20
terminal block No.
terminal block No.

 Wiring Diagram 9  Wiring Diagram 10


(RS-422A: OP-24028) (RS-485)
VT3 PORT2 (20-pin) KV-N11L VT3 PORT4 KV-N11L
DT PLC port (20-pin) KV-NC20L PORT2 KV-NC20L PORT2
(terminal block) (terminal block)
Black
GND 7 SG A S/R(+) *2
Red Terminal resistance
TXDA 11 RDA(-) (220Ω 1/2W) B S/R(-)
Red/white
TXDB 12 SDA(-) *1
Green
RXDA 13 RDB(+) SG SG
Green/white
RXDB 14 SDB(+)
TMR1 19 Shield
TMR2 20
RTSA 15 *1 Attach terminal resistance (220 1/2W) between
RTSB 16 AB for PORT4.
CTSA 17
*2 Turn on the terminal resistance switch.
CTSB 18

 Wiring Diagram 11  Wiring Diagram 12


(RS-232C: OP-24027) (RS-232C-OP-24027)
VT3 PORT2 (20-pin) KV-NC20L PORT2 VT3 PORT2(20P) KV-XL202
DT PLC port (20-pin) (terminal block) DTPLC port(20P) PORT1/PORT2 terminal block
Red 1 SD

Red TXD 2 1 SD RD
TXD 2 SD Red/white
RXD 3 2 RD RS
Red/white Green
RXD 3 N.C. RTS 4 3 RS CS
Green Green/white *
RTS 4 * N.C. CTS 5 4 CS ER

Green/white Black DR
CTS 5 RD GND 7 7 SG
Black 7 SG

GND 7 SG
* Not wired for loopback test inside the connector. KV-XL202
Solder the signal lead. Terminal block No.
* Not wired for loopback test inside the connector.
Solder the signal lead.

1-18 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-3 Wiring Diagrams for Connections

 Wiring Diagram 13(RS-422A-OP-24028)


VT3 PORT2(20P) KV-XL402
1
DTPLC port(20P) PORT1/PORT2 terminal block

CONNECTING TO THE KV & KZ SERIES


SDA-
TXDA 11
Red
1 SDA( ) 1 /SR-
Red/white SDB+
TXDB 12 2 SDB( ) /SR-
Green RDA-
RXDA 13 3 RDA( )
Green/white
RXDB 14 4 RDB( ) RDB+
Black
GND 7 5 SG 5 SG
TMR1 19
KV-XL402
TMR2 20
Terminal block No.
RTSA 15
RTSB 16
CTSA 17
CTSB 18

 Connection to VT3 series (PORT3)


 Wiring Diagram 31
(PLC Port Direct Link OP-26486+
 Wiring Diagram 32 (RS-232C)
OP-24045: 1m, OP-24025: 5m)
VT3 PORT3 (9-pin) PLC (modualr 6-pin) VT3 PORT3 (9-pin) KV-L20(V/R) PORT1 (9-pin)
KV-N10L (9-pin)
KV-NC10L/NC20L PORT1 (9-pin)
TXD 2 5 SD
RXD 3 3 RD TXD 2 2 RD
RXD 3 3 SD
RTS 8 2 +5V
RTS 8 7 RS
CTS 7
* CTS 7 8 CS
GND 5 4 SG
GND 5 5 SG

* 3.9KΩ 1/4W

 Wiring Diagram 33 (RS-232C)  Wiring Diagram 34 (RS-232C)


VT3 PORT3 (9-pin) KV-L20/L2ΩV PORT2 VT3 PORT (9-pin) KV-NC20L PORT2
(terminal block) (terminal block)

TXD 2 SD
TXD 2 SD
RXD 3 RD
RXD 3 N.C.
RTS 8
RTS 8 N.C.
CTS 7
CTS 7 RD
GND 5 SG GND 5 SG

 Wiring Diagram 35(RS-232C)


VT3 PORT 9P KV-XL202
PORT1/PORT2 (terminal block)

TXD 2 1 SD
RXD 3 2 RD
RTS 8 3 RS
CTS 7 4 CS
GND 5 7 SG

Reference For the pin assignment number of the connectors on the VT3 series/DT series, please see
the Appendix at the end of this manual.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-19


1-3 Wiring Diagrams for Connections

1  Connection with VT3 Handy Series

Point FG2 must be grounded.


CONNECTING TO THE KV & KZ SERIES

 Wiring diagram H20  Wiring diagram H21 (RS-232C)


(PLC port direct link) OP-87185: 3m, OP-87186: 5m,
OP-87180: 1m, OP-87181: 5m OP-87187: 10m
OP-87191: 3m, OP-87192: 5m,
OP-87193: 10m
VT3 (CN2A) KV, KZ, KV-P VT3 (CN2A) KZ-L2
(modular 6-pin) View from cable PORT1 (25-pin)
Orange (dot: black) connector Orange (dot: black 1)
TXD 5 SD side TXD 2 SD (1) (13)
Orange (dot: red) Orange (dot: black 3)
RS-422 RS-485 RXD 3 RD RS-422 RS-485 RXD 3 RD
TMC TMR RTS Orange (dot: red 1)
TMC TMR RTS 4 RS
Orange (dot: red 3)
ON CTS ON CTS 5 CS (14) (25)
Shielded cable Orange (no dot) D-sub 25-pin
SG 4 SG SG 7 SG
OFF Orange (no dot) (6) (5) (4) (3) (2) (1) OFF connector
DTR DTR
1 2 3 Modular connector of KZ, KV 1 2 3
DSR DSR
N.C. N.C.
N.C. N.C.

 Wiring diagram H22 (RS-232C)  Wiring diagram H23 (RS-232C)


OP-87185: 3m, OP-87186: 5m, OP-87185: 3m, OP-87186: 5m,
OP-87187: 10m OP-87187: 10m
OP-87191: 3m, OP-87192: 5m, OP-87191: 3m, OP-87192: 5m,
OP-87193: 10m OP-87193: 10m
VT3 (CN2A) KZ-L10
VT3 (CN2A) KZ-L2 (KZ-L10) PORT1(25-pin)
PORT2 (terminal block)
Orange (dot: black 1)
Orange (dot: black 1) (1) (3) (5) TXD 2 SD (1) (13)
TXD 1 SG Orange (dot: black 3)
SG SDA RDA 3 RD
Orange (dot: black 3) (SG) (SD) (RD)
RS-422 RS-485 RXD
RS-422 RS-485 RXD Orange (dot: red 1)
Orange (dot: red 1) TMC TMR RTS 4 RS
TMC TMR RTS 3 SD (2) (4) Orange (dot: red 3)
Orange (dot: red 3) SDB RDB ON CTS 5 CS (14) (25)
ON CTS Orange (no dot) D-sub 25-pin
SG
Orange (no dot)
5 RD SG 7 SG
OFF KZ-L2 (KZ-L10) OFF connector
DTR terminal block NO. DTR
1 2 3 1 2 3
DSR DSR
N.C. N.C.
N.C. N.C.

 Wiring diagram H24 (RS-232C)  Wiring diagram H25 (RS-232C)


OP-87185: 3m, OP-87186: 5m, OP-87185: 3m, OP-87186: 5m,
OP-87187: 10m OP-87187: 10m
OP-87191: 3m, OP-87192: 5m, OP-87191: 3m, OP-87192: 5m,
OP-87193: 10m OP-87193: 10m

VT3 (CN2A) KV-L20 (R) /L2∗V VT3 (CN2A) KV-L20(R)/L2∗V


PORT1 (9-pin) PORT2 (terminal block)
KV-N10L (9-pin) Orange (dot: black 1)
KV-NC10L/NC20L PORT1 (9-pin) TXD 1 SG (1) (3) (5)
Orange (dot: black 3) SG SD RD
RS-422 RS-485 RXD SDA(ˉ) SDB(+)
Orange (dot: black 1) Orange (dot: red 1) S/R(ˉ) S/R(+)
TXD 2 RD (1) TMC TMR RTS 3 SD
Orange (dot: black 3) (6) Orange (dot: red 3)
(2) (4)
RS-422 RS-485 RXD 3 SD ON CTS RDA(ˉ) RDB(+)
S/R(ˉ)* S/R(+)*
Orange (dot: red 1) Orange (no dot)
TMC TMR RTS 5 SG Front SG 5 RD
OFF KV-L20R/L2∗V
Orange (dot: red 3)
ON CTS 7 RS DTR terminal block NO.
Orange (no dot) 1 2 3
SG 8 CS (5) (9) DSR * only KV-L20R
OFF
DTR N.C.
1 2 3 D-sub 9-pin (1) (3) (5)
DSR connector N.C. SG SDA SDB
(SG) (SD) (RD)
N.C. (2) (4)
N.C. RDA RDB

KV-L20
terminal block NO.

1-20 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-3 Wiring Diagrams for Connections

 Wiring diagram H26 (RS-232C)


OP-87185: 3m, OP-87186: 5m,
 Wiring diagram H27 (RS-232C)
OP-87185: 3m, OP-87186: 5m,
1
OP-87187: 10m OP-87187: 10m

CONNECTING TO THE KV & KZ SERIES


OP-87191: 3m, OP-87192: 5m, OP-87191: 3m, OP-87192: 5m,
OP-87193: 10m OP-87193: 10m
KV-NC20L PORT2
VT3 (CN2A) KV-XL202
VT3 (CN2A) PORT1/PORT2㸦terminal block㸧
(terminal block)
Orange (dot: black 1) 1 SD
Orange (dot: black 1) TXD 1 SD RD
TXD SD Orange (dot: black 3)
RS-422 RS-485 RS-422 RS-485 2 RD
Orange (dot: black 3) RXD RS

TMC TMR
RXD N.C. Orange (dot: red 1)
Orange (dot: red 1) TMC TMR RTS 3 RS CS

ON
RTS N.C. Orange (dot: red 3) ER
Orange (dot: red 3) ON CTS 4 CS
CTS RD Orange (no dot) DR
OFF Orange (no dot) SG 7 SG
SG SG OFF 7 SG

1 2 3 DTR
DTR 1 2 3 KV-XL202
DSR Terminal block
DSR
N.C.
N.C.
N.C.
N.C.

 Wiring diagram H40 (RS-422A)  Wiring diagram H41 (RS-422A)


OP-87185: 3m, OP-87186: 5m, OP-87185: 3m, OP-87186: 5m,
OP-87187: 10m OP-87187: 10m
OP-87191: 3m, OP-87192: 5m, OP-87191: 3m, OP-87192: 5m,
OP-87193: 10m OP-87193: 10m
VT3 (CN2B) KZ-L2 (KZ-L10) VT3 (CN2B) KV-L20(R)/L2∗V
PORT2 (terminal block) PORT2(terminal block)

Orange (dot: black 1) (1) (3) (5) Orange (dot: black 1)


TXDA 1 SG RS-422 RS-485 TXDA 1 SG (1) (3) (5)
Orange (dot: black 2) SG SDA RDA SG SD RD
(SG) (SD) (RD) Orange (dot: black 2)
RS-422 RS-485 TXDB 2 SDB TMC TMR TXDB 2 RDA(ˉ) SDA(ˉ) SDB(+)


Orange (dot: black 3) Orange (dot: black 3) S/R(ˉ) S/R(+)


TMC TMR RXDA 3 SDA (2) (4) ON RXDA 3 SDA(ˉ) (2) (4)
Orange (dot: black 4) SDB RDB Orange (dot: black 4) RDA(ˉ) RDB(+)
ON RXDB 4 RDB RXDB 4 RDB(ˇ)
Orange (no dot) OFF S/R(ˉ)* S/R(+)*
Orange (no dot)
SG 5 RDA SG 5 SDB(ˇ)
OFF Orange (dot: red 1) KZ-L2(KZ-L10) 1 2 3 KV-L20R/L2∗V
Orange (dot: red 1)
RTSA terminal block NO. RTSA terminal block NO.
1 2 3 Orange (dot: red 2) Orange (dot: red 2)
RTSB RTSB * only KV-L20R
Orange (dot: red 3) Orange (dot: red 3)
CTSA CTSA
Orange (dot: red 4) Orange (dot: red 4) (1) (3) (5)
CTSB CTSB SG SDA SDB
(SG) (SD) (RD)

(2) (4)
RDA RDB

KV-L20
terminal block NO.

 Wiring diagram H42 (RS-422A)  Wiring diagram H43 (RS-485: 2-wire)


OP-87185: 3m, OP-87186: 5m,
OP-87187: 10m
OP-87191: 3m, OP-87192: 5m,
OP-87193: 10m

VT3 (CN2B) *1 KV-N11L*2 VT3 (CN1) *1 KV-N11L


KV-NC20L PORT2*2 KV-NC20L PORT2
(terminal block) Shield (terminal block)
Orange (dot: black 1) Pink (dot: red 1)
RS-422 RS-485 TXDA SG RS-422 RS-485 A S/R(+) *2
Orange (dot: black 2) Pink (dot: red 2)
TMC TMR TXDB RDA(-) TMC TMR B S/R(-)
Orange (dot: black 3) ON
ON RXDA SDA(-)
Orange (dot: black 4)
RXDB RDB(+) SG
OFF Orange (no dot) OFF Pink (dot: red 3)
SG SDB(+) G
1 2 3 Orange (dot: red 1) 1 2 3
RTSA
Orange (dot: red 2)
RTSB D-type ground
Orange (dot: red 3) (the third-type grounding)
CTSA
Orange (dot: red 4)
CTSB *1 Turn on the terminator.
*2 Turn on the terminal resistance switch.
*1 Turn on the terminator.
*2 Turn on the terminal resistance switch.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-21


1-3 Wiring Diagrams for Connections

1  Wiring diagram (H44-RS-422A)


OP-87185: 3m, OP-87186: 5m,
OP-87187: 10m
CONNECTING TO THE KV & KZ SERIES

OP-87191: 3m, OP-87192: 5m,


OP-87193: 10m
VT5(COM2)/VT3-W4A KV-XL402
㸦terminal block㸧 PORT1/PORT2㸦terminal block㸧

SDA-
TXDA
Orange (dot: black 1)
1 SDA( ) 1 /SR-
Orange (dot: black 2) SDB+
TXDB 2 SDB( ) /SR-
Orange (dot: black 3) RDA-
ON RXDA 3 RDA( )
Orange (dot: black 4)
RXDB 4 RDB( ) RDB+
Orange (no dot)
SG 5 SG 5 SG
TERM. Orange (dot: red 1)
RTSA
Orange (dot: red 2) KV-XL402
RTSB
Orange (dot: red 3) Terminal block N
CTSA
Orange (dot: red 4)
CTSB

 Connection to VT3-V7R

Point Before connecting the unit cables (VT-C5K1/C5K2/C5R1/C5R2/C15R2/C5A/C5F/OP-75039), be


sure to read "Connection Precautions", page A-13

 Wiring Diagram R1  Wiring Diagram R2


(PLC port direct link: VT-C5K1) (PLC port direct link: VT-C5K2)
VT3-V7R (CN2) KV and KZ modular connector VT3-V7R (CN2) KZ-A500 modular connector
View from the View from the
RS-422A RS-485 Red
cable connector RS-422A RS-485 Red
cable connector
TXD 1 5 SD side TXD 1 5 SD side
TMC TMR Red/white TMC TMR Red/white
RXD 2 3 RD RXD 2 3 RD
ON ON Green
RTS 3 1 RS
OFF OFF 6 CS
Light blue Light blue
1 2 3 SG 9 4 SG 1 2 3 SG 9 4 SG
2 5V (6) (5) (4) (3) (2) (1) 2 5V (6) (5) (4) (3) (2) (1)
Yellow Yellow
DR 5 KZ modular DR 5 KZ-A500 modular connector
Green/white
ER 6 connector CTS 4
CTS 4

An error may occur when using The KV and KZ series may be


the PLC Port Direct Link cable damaged when using the PLC Port
NOTICE NOTICE
(VT-C5K1) of the KV and KZ series Direct Link cable (VT-C5K2) of
to connect with KZ-A500. KZ-A500 to connect them.

 Wiring Diagram R3  Wiring Diagram R4


(RS-232C: VT-C5R1) (RS-232C: VT-C5R1)
VT3-V7R(CN2) KZ-L2 PORT1 (25-pin) VT3-V7R(CN2) KZ-L2 PORT2 (terminal block)
(KZ-L10)
RS-422A RS-485 Red RS-422A RS-485 Red
TXD 1 2 SD TXD 1 1 SG (1) (3) (5)
TMC TMR Red/white (1) (13) TMC TMR Red/white SG SDA RDA
RXD 2 3 RD RXD 2 (SG) (SD) (RD)
ON Green ON Green
RTS 3 4 RS RTS 3 3 SD (2) (4)
Green/white * Green/white * SDB RDB
OFF CTS 4 5 CS OFF CTS 4
Light blue (14) (25) Light blue
1 2 3 SG 9 7 SG 1 2 3 SG 9 5 RD
Yellow Yellow KZ-L2 (KZ-L10)
DSR 5 D-sub 25-pin DSR 5
terminal block No.
connector
* Not wired for loopback test inside the connector. * Not wired for loopback test inside the connector.
Solder the signal lead. Solder the signal lead.

Reference For the pin assignment number of the connectors on the VT3 series/DT series, please see
the Appendix at the end of this manual.

1-22 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-3 Wiring Diagrams for Connections

 Wiring Diagram R5
(RS-422A: VT-C5R2/C15R2)
 Wiring Diagram R6
(RS-232C: VT-C5R1)
1

CONNECTING TO THE KV & KZ SERIES


VT3-V7R (CN3) KZ-L2 (KZ-L10) VT3-V7R(CN2) KZ-L10 PORT1 (25-pin)
PORT2 (terminal block)
RS-422A RS-485 Light blue RS-422A RS-485 Red
SG 9 1 SG (1) (3) (5) TXD 1 2 TXD
TMC TMR Light blue/black SG SDA RDA TMC TMR Red/white (1) (13)
DSR 11 2 SDB (SG) (SD) (RD) RXD 2 3 RXD
ON Red ON Green
TXDA 1 3 SDA (2) (4) RTS 3 4 RTS
Red/white SDB RDB Green/white
OFF TXDB 2 4 RDB OFF CTS 4 5 CTS
Green Light blue (14) (25)
1 2 3 RXDA 5 5 RDA KZ-L2 (KZ-L10) 1 2 3 SG 9 7 GND D-sub 25-pin
Green/white Yellow
RXDB 6 terminal block No. DSR 5 connector
Yellow
RTSA 3
Yellow/black
RTSB 4
Grey/black *
CTSA 7
White/black *
CTSB 8

* Not wired for loopback test inside the connector.


Solder the signal lead.

 Wiring Diagram R7  Wiring Diagram R8


(RS-232C: VT-C5R1) (RS-232C: VT-C5R1)
VT3-V7R (CN2) KV-L20(R)/L2ΩV PORT1 (9-pin) VT3-V7R (CN2) KV-L20(V/R) PORT2
KV-N10L (9-pin) (terminal block)
KV-NC10L/NC20L PORT1 (9-pin) RS-422A RS-485 Red
TXD 1 1 SG (1) (3) (5)
RS-422A RS-485 Red (1) TMC TMR SG SDA SDB
TXD 1 2 RD (6) Red/white
TMC TMR RXD 2 (SG) (SD) (RD)
Red/white ON Green
RXD 2 3 SD RTS 3 3 SD (2) (4)
ON Green Front Green/white * RDA RDB
RTS 3 5 SG OFF CTS 4
Green/white * view Light blue
OFF CTS 4 7 RS 1 2 3 SG 9 5 RD
Light blue (5) (9) Yellow KV-L20
1 2 3 SG 9 8 CS DSR 5 terminal block No.
Yellow
DSR 5 D-sub 9-pin
connector
* Not wired for loopback test inside the connector.
* Not wired for loopback test inside the connector. Solder the signal lead. Solder the signal lead.

 Wiring Diagram R9  Wiring Diagram R10


(RS-422A: VT-C5R2/C15R2) (RS-422A: VT-C5R2/C15R2)
VT3-V7R (CN3) KV-L20(V/R) PORT2 VT3-V7R (CN3)*1 KV-N11L*2
(terminal block) KV-NC20L PORT2
RS-422A RS-485 Light blue (terminal block)
SG 9 1 SG (1) (3) (5)
TMC TMR Light blue/black SG SDA SDB RS-422A RS-485 Light blue
DSR 11 2 RDA (SG) (SD) (RD) SG 9 SG
ON Red TMC TMR Light blue/black
TXDA 1 3 SDA (2) (4) DSR 11 RDA(-)
Red/white RDA RDB ON Red
OFF TXDB 2 4 RDB TXDA 1 SDA(-)
Green Red/white
1 2 3 RXDA 5 5 SDB OFF TXDB 2 RDB(+)
Green/white KV-L20 Green
RXDB 6 terminal block No. 1 2 3 RXDA 5 SDB(+)
Yellow Green/white
RTSA 3 RXDB 6
Yellow/black Yellow
RTSB 4 RTSA 3
Grey/black *
*
Yellow/black
CTSA 7 RTSB 4
White/black *
*
Grey/black
CTSB 8 CTSA 7
White/black
CTSB 8

* Not wired for loopback test inside the connector.


Solder the signal lead.
* Not wired for loopback test inside the connector.
Solder the signal lead.
*1 Turn on the terminator.
*2 Turn on the terminal resistance switch.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-23


1-3 Wiring Diagrams for Connections

1  Wiring Diagram R11 (RS-485: 2-wire)  Wiring Diagram R12


(RS-232C: VT-C5R1)
CONNECTING TO THE KV & KZ SERIES

VT3-V7R (CN2) KV-N11L KV-NC20L PORT2


VT3-V7R (CN2)
KV-NC20L PORT2 (terminal block)
(terminal block)
RS-422A RS-485*1 Grey/black
Red
TXD 1 SD
A 7 S/R(+) RS-422A RS-485 Red/white
TMC TMR White/black *2 RXD 2 N.C.
B 8 S/R(-) TMC TMR Green
ON Light blue RTS 3 N.C.
SG 9 SG ON *
Green/white
OFF CTS 4 RD
OFF Light blue
1 2 3 Shield SG 9 SG
1 2 3 Yellow
DSR 5
D-type ground
(third-type grounding)
*1 Turn on the terminator switch.
*2 Turn on the terminal resistance switch.

 Wiring Diagram R13  Wiring Diagram R14


(RS-232C: VT-C5R1) (RS-422A: VT-C5R2/C15R2)

VT3-V7R (CN2) KV-XL202 VT3-V7R (CN3) KV-XL402


PORT1/PORT2 (terminal block) PORT1/PORT2 (terminal block)
RS-422A RS-485 Red
1 SD TXDA 1 1 SDA( ) 1 SDA-
/SR-
RS-422A RS-485 Red TMC TMR Red/white SDB+
TXD 1 1 SD RD
TXDB 2 2 SDB( ) /SR-
TMC TMR Red/white RS ON Green RDA-
RXD 2 2 RD RXDA 5 3 RDA( )
ON Green CS
Green/white RDB+
RTS 3 3 RS ER OFF RXDB 6 4 RDB( ) 5 SG
Green/white * Light blue
OFF CTS 4 4 CS DR 1 2 3 SG 9 5 SG
Light blue Light blue/black KV-XL402
1 2 3 SG 9 7 SG 7 SG
DSR 11
Yellow terminal block N
DSR 5 KV-XL202 Yellow
RTSA 3 *
terminal block NO Yellow/black
RTSB 4 *
Grey/black
CTSA 7
* Not wired for loopback test inside the connector. White/black
CTSB 8
Solder the signal lead.

* Not wired for loopback test inside the connector.


Solder the signal lead.

Point Please use the following recommended cables for the connection. Using cables other than
the recommended ones may lead to a shorter cable run distance.
Item Description
Type of Cable Shielded cable
Logarithmic 3P
Resistance (20°C) Below 52.0/km
Insulating resistance 10.000M/km
Withstand voltage DC500V 1minute
Electrostatic Capacity (1kHz) Below 135nF/km
Characteristics Impedance (100kHz) 43

Reference For the pin assignment number of the connectors on the VT3 series/DT series, please see
the Appendix at the end of this manual.

1-24 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-3 Wiring Diagrams for Connections

Ethernet Connection Methods 1

CONNECTING TO THE KV & KZ SERIES


 Direct connection (1:1)
Use STP/UTP cable for connection.

STP/UTP cable*1 KV-8000/8000A/7500

VT5 +

KV-8000/8000A/ KV-XLE02/XD02*2
7500/7300
STP/UTP cable

+ +
Soft-VT

KV-8000/8000A/ Bus connection unit KV-EP21V


7500/7300 /LE2*V

VT3 KV-5500/5000
(VT3 handy Series
excluded)
STP/UTP cable*1
+ +

KV-5500 KV-EP21V
/5000/3000 /LE2*V
VT2-E1/E2,
VT3-E3
+

KV-1000/700 KV-LE20(V/A)

Ethernet connection cable


(OP-87188/87189/87190), or + +
VT3 handy Series RS-232C/422/485/Ethernet connection
cable (OP-87191/87192/87193)
KV-N24/40/60 KV-N1 connection KV-NC1EP
conversion unit

KV-NC32T KV-NC1EP
*1 The VT5 Series and VT3-E3 whose serial numbers end in an "A", support the MDI/MDI-X auto switching function.
To connect any other device directly to a PLC, use an STP/UTP cross cable.
*2 The KV-XD02 can only be connected to the KV-8000.

Point • When building an Ethernet connection using 10 Base-T, use a Category 3 or higher STP/UTP cable.
• When building an Ethernet connection using 100 Base-TX, use a Category 5 or higher STP/UTP cable.
• When building an Ethernet connection using 1000 Base-T, use a Category 5e or higher STP/UTP
cable. If it is considered that there is a noise influence in the installed environment, select an STP
cable with the double shield.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-25


1-3 Wiring Diagrams for Connections

1  Connection using a hub (multiple connections)


CONNECTING TO THE KV & KZ SERIES

STP/UTP
straight cable KV-8000/8000A/7500

VT5
+

KV-8000/8000A/ KV-XLE02/XD02*1
7500/7300

Soft-VT
+ +

KV-8000/8000A/ Bus connection unit KV-EP21V


7500/7300 /LE2*V
STP/UTP
VT3 STP/UTP
straight cable
(VT3 handy Series straight cable
excluded)
Hub
+
KV-5500/5000

VT2-E1/E2, +
VT3-E3

KV-5500 KV-EP21V
/5000/3000 /LE2*V

Ethernet connection cable


(OP-87188/87189/87190), or KV-1000/700 KV-LE20(V/A)

VT3 handy Series RS-232C/422/485/Ethernet connection


cable (OP-87191/87192/87193)
+ +

KV-N24/40/60 KV-N1 connection KV-NC1EP


conversion unit

KV-NC32T KV-NC1EP

Connection of VT5 Series,VT2-E1/E2, VT3-E3, VT3 handy Series, Soft-VT to a hub


• Use the STP/UTP straight cable.
• Please connect to where other than cascade port of hub.
Connecting KV-8000/8000A/7500/5500/5000 Ethernet port to the hub on KV-XLE02/XD02/EP21V/LE21V/LE20(V/A)
• Use the STP/UTP straight cable.
• Please connect to where other than cascade port of hub.
*1 The KV-XD02 can only be connected to the KV-8000.

Point • When building an Ethernet connection using 10 Base-T, use a Category 3 or higher STP/UTP cable.
• When building an Ethernet connection using 100 Base-TX, use a Category 5 or higher STP/UTP cable.
• When building an Ethernet connection using 1000 Base-T, use a Category 5e or higher STP/UTP
cable. If it is considered that there is a noise influence in the installed environment, select an STP
cable with the double shield.

1-26 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings
The following describes the settings of the Link Unit matched to the default communications conditions.
1
Method for making serial connections

CONNECTING TO THE KV & KZ SERIES


KV-3000/1000/700 (PLC port direct link), KV-10/16/24/40, KV-P Series
Setting is not required.

KV-7300 (built-in serial port direct link)


Use the Unit Editor in the ladder software (KV STUDIO) to set up the KV-7300 (built in serial port direct link).

Start up the Unit Editor and select the base unit to set up.
Set the operating mode of the internal serial port to "KV STUDIO mode (*).

KV-XL402 setting

KV-XL402

(1) Terminator selector switch

Communication is possible with both Port 1 and Port 2.

(1) Terminator selector switch


Turn on the terminator selection switch of the port to be used.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-27


1-4 Unit Settings

1 (2) Unit Editor


Set the operation mode of the port to be used to "KV STUDIO mode".
Set Value
CONNECTING TO THE KV & KZ SERIES

Item
Port 1/Port 2
Operation mode KV STUDIO mode
Interface RS-422A/485 (4-wire)
Baud Rate Auto (set on VT5/VT3/DT side) *1
Data bit 8 bits
Start bit 1 bits
Stop bit 1 bits
Parity Even
CheckSum None
RS/CS flow control Disable

*1 Set baud rate with the PLC communication condition in VT system setting of VT STUDIO.
VT 5 Series Reference Manual" 12 - 5 Peripheral Device Connection "
VT3 Series Reference Manual" 12-4 VT main unit system setting "

KV-XL202 setting
The KV-XL202 communication settings are configured with the KV STUDIO ladder software Unit Editor.
Set the operation mode of the port to be used to "KV STUDIO mode".
Set Value
Item
Port 1/Port 2
Operation mode KV STUDIO mode
Interface RS-232C
Baud Rate Auto (set on VT5/VT3/DT side) *1
Data bit 8 bits
Start bit 1 bits
Stop bit 1 bits
Parity Even
CheckSum None
RS/CS flow control Disable

*1 Set baud rate with the PLC communication condition in VT system setting of VT STUDIO.
VT 5 Series Reference Manual" 12 - 5 Peripheral Device Connection "
VT3 Series Reference Manual" 12-4 VT main unit system setting "

1-28 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

KV-L20(R)/L2V (KV BUILDER/KV STUDIO mode)


1
KV-L20(R)/L2∗V front view KV-L20(R)/L2∗V side view

CONNECTING TO THE KV & KZ SERIES


(2) PORT2 selector switch

(1) Terminator selector KV-L20


switch 232C 422A VT

KV-L20R
PORT2
232C 422A VT 422A
232C 485(4) 485(2)

*Not exist for KV-L2∗V

(1) Terminator selector switch


Set to ON when PORT2 is used on the RS-422A interface and to OFF when PORT2 is used on ON
the RS-232C interface.

Used on RS-422A interface: Up (ON)


Used on RS-232C interface: Down

(2) PORT2 selector switch (KV-L20(R) only)


KV-L20 KV-L20R
Set whether to use PORT2 on the RS-422A interface or on the 422A
232C 422A VT 232C 485(4) 485(2)
RS-232C interface.

Used on RS-232C interface: Left side (232C)


Used on RS-422A interface: Center (422A)

(3) Unit Editor


Set the operation mode to "KV BUILDER/KVSTUDIO mode".
Set Value
Item
Port 1 Port 2
Operation mode KV BUILDER/KV STUDIO mode KV BUILDER/KV STUDIO mode
Interface RS-232C RS-232C, RS-422A, 4-wire
PLC No. - 0
Baud Rate Auto (set on VT5/VT3/DT side) *1 Auto (set on VT5/VT3/DT side) *1
Data bit 8 bits 8 bits
Start bit 1 bit 1 bit
Stop bit 1 bit 1 bit
Parity Even Even
CheckSum None None
RS/CS flow control Disable -
*1 Set the Baud rate for the VT5/VT3 in the PLC communications conditions in the VT system parameters in VT STUDIO.
"12-5 Connecting Peripheral Devices", VT5 Series Reference Manual
“12-4 Setup of VT Main Unit System in the VT3 Series Reference Manual
In the case of the DT, set the baud rate in the PLC communicationsconditions in the system parameters on DT
BUILDER.
DT-100/100A User's Manual - Advanced Operation "3-2 System Parameters"

Point "PORT2 Selector Switch" and "Unit Editor" should be set separately when connecting
KV-L20(R) via PORT2. The PLC will malfunction if both settings do not match.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-29


1-4 Unit Settings

1 KV-LM20(V)/LM21V
KV-LM20(V)/LM21V front view KV-LM20(V)/LM21V side view
CONNECTING TO THE KV & KZ SERIES

(1) Terminator selector


switch

(1) Terminator selector switch


When KV-LM20(V)/LM21V is at the MegaLink side, be sure to set to ON. Otherwise, set to OFF. ON

(2) Unit Editor


Item Set Value Default
Operation mode MegaLink MegaLink
Baud Rate 19200, 115200, 0.5M, 1.0M, 2.0Mbit/s 2.0Mbit/s
Retry Times 0 to 99 3

1-30 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

KV Nano Series (Built-in serial port direct connection)


The KV Nano Series (PLC port direct link) settings are configured with the KV STUDIO ladder software Unit Editor.
1

CONNECTING TO THE KV & KZ SERIES


Start the Unit Editor and select the base unit to configure its settings.
Set the built-in serial port (Port0) operation mode to "KV STUDIO mode(*)".

KV-N10L
The KV-N10L communication settings are configured with the KV STUDIO ladder software Unit Editor.

Start the Unit Editor and select the base unit and you will be able to configure the extension cassette settings.
Port1 can be used with the KV-N14/N24. Port1 and Port2 can be used with the KV-N40/N60.
The initial value for the extension cassette is "None".

Configure the settings by referring to the table below.


Communications settings
Item
Setting Range Default
Additional cassette KV-N10L(RS-232C) None
Operation mode KV STUDIO mode KV STUDIO mode
Interface RS-232C RS-232C
Baud Rate Auto Auto
Data bit 8 bits 8 bits
Start bit 1 bit 1 bit
Stop bit 1 bit 1 bit
Parity Even Even
RS/CS flow control Disable Disable
* When the extension cassette is set to "None" in Unit Editor, communication is performed with the initial settings.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-31


1-4 Unit Settings

1 KV-N11L
CONNECTING TO THE KV & KZ SERIES

(1) Terminator selector switch

(1) Terminator selector switch


When connecting KV-N11L to VT5/VT3 using RS-485 (2-wire), set the terminator switch to On.

(2) Unit editor


The KV-N11L communication settings are configured with the KV STUDIO ladder software Unit
Editor.

Start the Unit Editor and select the base unit and you will be able to configure the extension cassette settings.
Port1 can be used with the KV-N14/24. Port1 and Port2 can be used with the KV-N40/N60.
The initial value for the extension cassette is "None".

Configure the settings by referring to the table below.


Communications settings
Item
Setting Range Default
Additional cassette*1 KV-N11L (RS-422A/485) None
Operation mode KV STUDIO mode KV STUDIO mode
RS-485(2-wire)
Interface RS-485(2-wire)
RS-422A/485(4-wire) *2
Baud Rate Auto Auto
Data bit 8 bits 8 bits
Start bit 1 bit 1 bit
Stop bit 1 bit 1 bit
Parity Even Even
RS/CS flow control Disable Disable
KV mode station number 0 0
*1 When the extension cassette is set to "None" in Unit Editor, communication is performed with the initial settings.
*2 The DT Series can only use RS-422A/485 (4-wire).

1-32 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

KV-NC10L
The KV-NC10L communication settings are configured with the ladder software KV STUDIO Unit Editor.
1

CONNECTING TO THE KV & KZ SERIES


Start the Unit Editor and select the base unit to configure the extension adapter settings.
Use only PORT1 (RS-232C) for KV-NC10L.
The initial value for the extension adapter is "None".

Configure the settings by referring to the table below.


Communications settings
Item
Setting Range Default
Extension adapter KV-NC10L (RS-232C) None
Operation mode KV STUDIO mode KV STUDIO mode
Interface RS-232C RS-232C
Baud Rate Auto Auto
Data bit 8 bits 8 bits
Start bit 1 bit 1 bit
Stop bit 1 bit 1 bit
Parity Even Even
RS/CS flow control Disable Disable
* When the extension adapter is set to "None" in Unit Editor, communication is performed with the initial settings.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-33


1-4 Unit Settings

1 KV-NC20L
CONNECTING TO THE KV & KZ SERIES

(1) Terminator selector switch

(1) Terminator selector switch

When the KV-NC20L PORT2 and the VT3 are connected by RS-485 (2-wire), set the terminator
switch to ON. ON

(2) Unit editor

The KV-NC20L communication settings are configured with the KV STUDIO Unit Editor.

Start the Unit Editor and select the base unit to configure the extension adapter settings.
Port1 (RS-232C) and Port2 (RS-232C/RS-422A/485) can be used with the KV-NC20L.
The initial value for the extension adapter is "None".

Configure the settings by referring to the table below.


Communications settings
Item
Setting Range Default
Extension adapter*1 KV-NC20L (RS-232C + RS-232C/422A/485) None
PORT Extension adapter (Port1) Extension adapter (Port2) -
Operation mode KV STUDIO mode KV STUDIO mode KV STUDIO mode
RS-232C
Port1: RS-232C
Interface RS-232C RS-485 (2-wire)*2
Port2: RS-485 (2-wire)*2
RS-422A/485 (4-wire)
Baud Rate Auto Auto
Data bit 8 bits 8 bits
Start bit 1 bit 1 bit
Stop bit 1 bit 1 bit
Parity Even Even
RS/CS flow control Disable - Disable
KV mode station
- 0 0
number
*1 When the extension adapter is set to "None" in Unit Editor, communication is performed with the initial settings.
*2 The DT Series cannot be connected with RS-485 (2-wire).

1-34 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

KZ-10/16/24/40/80, KZ-300/350 (PLC port direct link)


Setting is not required.
1

CONNECTING TO THE KV & KZ SERIES


KZ-L2

(3) Terminator
(2) PORT2 selector selector switch
switch
422A 232C ON OFF STATION NO. F012

B CDE

3456
INTERFACE TERMINATOR
ON SET. A SET. B 78
9A
A1 A2 A3 A4 B1 B2 B3 B4 B5 B6 B7 B8

(4) Node No. setup


ON ECE ON ECE

1 2 3 4 1 2 3 4 5 6 7 8

(1) Communications switch


mode setup switch
(5) Communications
specifications
setup switch

(1)Communications mode setup switch


ON
Set the port to be used to the KZ mode.
Set all switches to OFF. OFF
A1 A2 A3 A4
(2)PORT2 selector switch
Set whether to use PORT2 on the RS-422A interface or on the RS-232Cinterface.

Used on RS-422A interface: Left side (422A)


Used on RS-232C interface: Right side (232C) 422A 232C
INTERFACE
(3)Terminator selector switch
Set to when PORT2 is used on the RS-422A interface and to OFF when PORT2 is used on
the RS-232C interface.

Used on RS-422A interface: Left side (ON) ON OFF


Used on RS-232C interface: Right side (OFF)

(4)Node No. setup switch


Set to "0".

(5)Communications specifications setup switch


Always set switch B8 to OFF. Node No. setup switch (STATION No.)

KZ-A500 (PLC port direct link)


Setting the baud rate selector switch

SELECT

2
RUN STOP
RUN/ SELECT
ERROR

BATT. A B
0
1
0
1 1
2 2
3 3
4 4 X Y

ON OFF
5 5
6 6
7 7
8 8
9 9
A A
B B
C
D
C
D Switch No.
E E
Baud Rate
F F
1 2
Baud rate OFF OFF 9600 bit/s
BAUD RESET

selector switch ON OFF 4800 bit/s


OFF ON 19200 bit/s
ON ON 38400 bit/s

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-35


1-4 Unit Settings

1 KZ-L10

(5) Terminator
CONNECTING TO THE KV & KZ SERIES

(4) PORT2 selector switch


selector switch
422A 232C ON OFF STATION NO. F 0 12

B CDE

3 4 56
INTERFACE TERMINATOR
ON SET. A SET. B 78
9A
A1 A2 A3 A4 B1 B2 B3 B4 B5 B6 B7 B8

ON ECE ON ECE
(6) Node No. setup
switch
1 2 3 4 1 2 3 4 5 6 7 8

ON SET. C

(3) Modem/
C1 C2 C3 C4 C5 C6 C7 C8

ON ECE

1 2 3 4 5 6 7 8

communications
procedure setup (2) Communications
switch specifications setup
switch
(1) Operation mode
setup switch

(1) Operation mode setup switch ON


Set the operation mode of the port to be used to Protocol
Mode 1. OFF
C1 C2 C3 C4 C5 C6 C7 C8
(2) Communications specifications setup switch Port 1 Port 2
Set the communications specifications of the port to be used.

Switch No. Setting Item Set Value


B1 OFF
B2 Baud Rate 38400 bit/s ON
ON
B3 ON
B4 Bit length 7 bits OFF OFF
B5 ON B1 B2 B3 B4 B5 B6 B7 B8
Parity check Even
B6 ON
B7 Stop bit 1 bit OFF
B8 OFF at all times OFF

(3) Modem/communications procedure setup switch


Set as follows:

Switch No. Setting Item Set Value


A1 Communications Normal OFF ON
A2 settings communications OFF
OFF
Device data
A3 Enabled ON
rewritingin Run mode A1 A2 A3 A4
A4 CheckSum ON ON

(4) PORT2 selector switch


Set whether to use PORT2 on the RS-422A interface or on the RS-232Cinterface.

Used on RS-422A interface: Left side (422A) 422A 232C


INTERFACE
Used on RS-232C interface: Right side (232C)

(5) Terminator selector switch


Set to when PORT2 is used on the RS-422A interface and to OFF when PORT2 is used on
the RS-232C interface.
ON OFF
TERMINATOR
Used on RS-422A interface: Left side (ON)
Used on RS-232C interface: Right side (OFF)

(6) Node No. setup switch


Set to "0".

The following table shows setting ranges for each communications condition and their defaults. STATION
No.

1-36 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

Communication Condition Setting Ranges and Defaults During Serial Communication 1

CONNECTING TO THE KV & KZ SERIES


KV-8000 Series (serial), KV-8000 Series (serial) <XYM>

Item Setting Range Default


Station No. None None
VT No. - -
PLC serial I/F RS-232C, RS-422A 4-wire*1 RS-232C
Communication speed 9600, 19200, 38400, 57600, 115200 bit/s 115200 bit/s
Data Bits 8 bits 8 bits
Stop bits 1 bit 1bit
Parity Even Even
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -
*1 RS-422A 4-wire type can be selected when using KV-L2*V PORT 2 or KV-XL402.

KV-8000 Series (KV-LM2V), KV-8000 Series (KV-LM2V) <XYM>

Item Setting Range Default


Station No. None None
VT No. 1 to 15 1
PLC serial I/F RS-485 RS-485
Communication speed 19200, 115200, 0.5M, 1.0M, 2.0Mbit/s*1 2.0M bit/s
Data Bits 8 bits 8 bits
Stop bits 1 bit 1bit
Parity Odd Odd
Flow Control Flow control is not performed. Flow control is not performed.
CR - -
LF - -
CheckSum - -
*1 All connecting devices in a MegaLink connection must be set to the same value.

KV-7000 Series (serial), KV-7000 Series (serial) <XYM>

Item Setting Range Default


Station No. None None
VT No. - -
PLC serial I/F RS-232C, RS-422A 4-wire*1 RS-232C
Communication speed 9600, 19200, 38400, 57600, 115200 bit/s 115200 bit/s
Data Bits 8 bits 8 bits
Stop bits 1 bit 1bit
Parity Even Even
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -
*1 RS-422A 4-wire type can be selected when using KV-L2 * V PORT 2 or KV-XL402.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-37


1-4 Unit Settings

1 KV-7000 Series (KV-LM2V), KV-7000 Series (KV-LM2V) <XYM>

Item Setting Range Default


CONNECTING TO THE KV & KZ SERIES

Station No. None None


VT No. 1 to 15 1
PLC serial I/F RS-485 RS-485
Communication speed 19200, 115200, 0.5M, 1.0M, 2.0Mbit/s*1 2.0M bit/s
Data Bits 8 bits 8 bits
Stop bits 1 bit 1bit
Parity Odd Odd
Flow Control Flow control is not performed. Flow control is not performed.
CR - -
LF - -
CheckSum - -
*1 All connecting devices in a MegaLink connection must be set to the same value.

KV-5500/5000/3000/L2V, KV-5500/5000/3000/L2V <XYM>

Item Setting Range Default


Station No. None None
VT No. - -
PLC serial I/F RS-232C, RS-422A 4-wire*1 RS-232C
2400, 4800, 9600, 19200, 38400, 57600,
Baud Rate 115200 bit/s
115200 bit/s
Data Bits 8 bits 8 bits
Stop bits 1 bit 1bit
Parity Even Even
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -
*1 RS-422A 4-wire can be selected when the PORT2 on KV-L2V is used on the RS-422A interface.

KV-1000/700, KV-KV-L20/L21V, KV-1000, KV-KV-L20/L21V <XYM>

Item Setting Range Default


PLC No. None None
VT No. - -
PLC I/F RS-232C, RS-422A 4 wire *1 RS-232C
2400, 4800, 9600, 19200, 38400, 57600,
Baud Rate 57600 bit/s
115200bit/s*2
Data bit 8 bits 8 bits
Stop bit 1 bit 1 bit
Parity Even Even
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -
*1 RS-422A 4-wire can be selected when the PORT2 on KV-L20/L21V is used on the RS-422 A interface.
*2 115200 bit/s can be selected when a CPU direct link to a KV-1000 or a KV-L20*/L21V is in use. It cannot be selected
when a CPU direct link to a KV-700 is in use.

1-38 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

 KV-5500/5000/3000(KV-LM2V),
KV-5500/5000/3000(KV-LM2V) <XYM>,
1
KV-1000/700(KV-LM20/21V), KV-1000(KV-LM20/21V) <XYM>

CONNECTING TO THE KV & KZ SERIES


Item Setting Range Default
PLC No. None None
VT No. 1 to 15 1
PLCSeries I/F RS-485 RS-485
Baud Rate 19200, 115200, 0.5M, 1.0M, 2.0M bit/s* 2.0Mbit/s
Data bit 8 bits 8 bits
Stop bit 1 bit 1 bit
Parity Odd Odd
Flow Control Not perform flow control Not perform flow control
CR - -
LF - -
CheckSum - -
* All the connected equipment via MegaLink should be set to the same value.

KV Nano Series [KV-N], KV Nano Series [KV-N]<XYM>

Item Setting Range Default


PLC No. None None
VT No. - -
PLC serial I/F RS-232C, RS-422A 4-wire, RS-485*1 RS-232C
Baud Rate 9600, 19200, 38400, 57600, 115200bit/s 115200bit/s
Data bit 8 bits 8 bits
Stop bit 1 bit 1 bit
Parity Even Even
Control mode ER control ER control
CR - -
LF - -
CheckSum - -
*1 RS-485 cannot be selected on the DT Series.

KV-10/16/24/40, KV-P16
Item Setting Range Default
PLC No. None None
VT No. None None
PLC I/F RS-232C RS-232C
Baud Rate 9600, 19200, 38400, 57600 bit/s 57600 bit/s
Data bit 8 bits 8 bits
Stop bit 1 bit 1 bit
Parity Even Even
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-39


1-4 Unit Settings

1 KZ-300/350, KZ-L2, KZ-10/16/24/40/80


Item Setting Range Default
PLC No. None None
CONNECTING TO THE KV & KZ SERIES

VT No. - -
PLC I/F RS-232C, RS-422A 4 wire *1 RS-232C
Baud Rate 9600, 19200, 38400 bit/s 38400 bit/s
Data bit 8 bits 8 bits
Stop bit 1 bit 1 bit
Parity Even Even
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -
*1 RS-422A 4 wire can be selected when PORT2 on the KZ-L2 is used on the RS-422A interface.

KZ-A500
Item Setting Range Default
PLC No. None None
VT No. - -
PLC I/F RS-232C RS-232C
Baud Rate 4800, 9600, 19200, 38400 bit/s 9600 bit/s
Data bit 8 bits 8 bits
Stop bit 1 bit 1 bit
Parity Odd Odd
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -

KZ-L10
Item Setting Range Default
PLC No. ON (0 to 9) ON (0)
VT No. - -
PLC I/F RS-232C, RS-422A 4 wire RS-232C
Baud Rate 1200, 2400, 4800, 9600, 19200, 38400 bit/s 38400 bit/s
Data bit 7 bits, 8 bits 7 bits
Stop bit 1 bit, 2 bits 1 bit
Parity None, odd, even Even
Flow Control ER control ER control
CR - -
LF - -
CheckSum - -

1-40 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

Ethernet Connection Methods 1

CONNECTING TO THE KV & KZ SERIES


This section describes how to connect the VT5/VT3 Series and Soft-VT to a PLC via Ethernet.

 Checks to perform before making setting


For the Ethernet connection, the IP address and port No. of the connected units should be determined in advance.
The following table shows the setting items corresponding to the connection type. Check these settings with your
system administrator.

Connection mode Setting Item


• IP address assigned to VT5/VT3/Soft-VT (PC)
Direct connection • IP address to be assigned to PLC
• Port No. for communication
• IP address assigned to VT5/VT3/Soft-VT (PC)
• IP address to be assigned to PLC
Other connection • Port No. for communication
• Subnet Mask
• Default Gateway

Point Make sure that the "IP address assigned to VT5/VT3/Soft-VT (PC)" differs from "the IP
address assigned to the PLC".

 Required Settings for Ethernet Connections


The following settings must be made when connecting the VT5/VT3 Series and Soft-VT to a PLC via Ethernet.
VT5 Series/Soft-VT
Required settings Description
VT5 Series:
Set the IP address, port number and other settings to be assigned to the
VT5. P.1-42
In "Ethernet/Language/Video," select "System settings"  "VT individual
VT5/Soft-VT settings" in VT STUDIO. *1
Ethernet Settings
Soft-VT:
Set the IP address assigned to the PC that Soft-VT is running on.
Use "Control Panel"  "Network and Sharing Center" in Windows to make -
this setting.
Set the IP address, port number and other settings of the connected PLC.
Setting Communication
In "PLC Communication Conditions," select "System settings" P.1-43
Conditions with PLC
"Peripheral equipment connection" in VT STUDIO. *2
Make Ethernet settings on the PLC to connect it to the VT5 Series/Soft-VT.
PLC Ethernet Settings P.1-46
Use the "Unit Editor" in KV Studio to do this.
*1 Select "VT Individual Settings"  "Ethernet settings" in VT5 system mode to confirm and change settings.
*2 You can also use "PLC Communication Conditions" in VT5 system mode to confirm and change settings.
VT3 Series
Required settings Description
Set the IP address, port number and other settings to be assigned to the
VT3 Ethernet settings VT3. P.1-44
Use the "Option settings" in VT3 system mode.
Set the IP address, port number and other settings of the connected PLC.
Setting Communication
Select "System settings"  "VT individual settings" in "PLC Communication P.1-45
Conditions with PLC
Conditions" in VT STUDIO. *1
Make Ethernet settings on the PLC to connect it to the VT3 Series.
PLC Ethernet settings P.1-46
Use the "Unit Editor" in KV Studio to do this.
*1 You can also use "PLC Communication Conditions" in VT3 system mode to confirm and change settings.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-41


1-4 Unit Settings

1 Making Ethernet settings for the VT5 Series


Use the following steps to make Ethernet settings for the VT5 Series.
CONNECTING TO THE KV & KZ SERIES

1 Use VT STUDIO to set the IP address to be assigned to the VT5.


In VT STUDIO, select [Resource (R)][VT setting(J)][Ethernet/Language/Video (E)] and make the following
settings.
"12-6 VT setting", VT5 Series Reference Manual

Item Description
Send VT setting When checked, the VT settings are sent to the VT5.
IP Address Set the IP address to be assigned to the VT5.
Use the default settings to make a direct connection.
Subnet mask For all other connections, set a subnet mask whose operation you
Ethernet settings have verified.
Use the default settings to make a direct connection.
Default gateway For all other connections, set a default gateway whose operation you
have verified.
If required, set a port number for communications with VT STUDIO
Editor Port number and other PC applications.
communication Be sure to set a port number that is not also used for PLC communications.
settings Keep Alive Set as necessary.
Timeout Set as necessary.

Point • You can use VT5 system mode to check and change Ethernet settings such as IP
addresses to be assigned to the VT5 Series.
The setting items are the same as those in VT STUDIO.
"5-3 VT Machine Setup", VT5-WX Hardware Manual
"5-3 VT Machine Setup", VT5 Series Hardware Manual
• These settings are not required for Soft-VT since it uses the Ethernet settings of the PC it
runs on.
• If the VT model setting is VT5-WX15/WX12, it is equipped with two LAN ports, and an IP address
can be set for each port. Set the IP address of the LAN port that is connected with PLC.

Reference In the VT3 Series, IP addresses to be assigned to the VT3 were set only in the system mode screen.
In the VT5 Series, they are set in the "VT setting" in VT STUDIO.

1-42 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

2 Use VT STUDIO to set communication conditions with PLC.


1
In VT STUDIO, select [Resource (R)][Periphery connection][PLC Communication Condition (C)] and make the
following settings.

CONNECTING TO THE KV & KZ SERIES


"Chapter 17 Ethernet Connections", VT5 Series Reference Manual

Item Description
Station No. Select the station number (0 to 15) you want to use.
Set the IP address to be assigned to the connected PLC (the checked
IP Address *1
station number).
Target PLC Set the port number (1024 to 65535) of the connected PLC (the
Port number *2
checked station number).
List of connected Select connected targets from the list of connected targets or add
targets targets to the list.
VT port numbers (for Set VT5/Soft-VT port numbers (for PLC communications) (1024 to
PLC communications) 65535).
Normally, this does not need to be set.
Timeout
Set a long timeout when the communications load on the network is large.
Ethernet settings Normally, this does not need to be set.
Send Wait
Set a long timeout when the communications load on the network is large.
Normally, this does not need to be set.
Retry Increase the number of retries when the unit is used in an
environment with a lot of noise.
PLC communications special settings
Normally, this does not need to be set.
(set on VT STUDIO)
Specify a device to
In an interval with no communications, select a device to check
troubleshoot Target word device *3
connections. Normally, this does not need to be set.
Ethernet connections
When checked, communications with a station number causing a
Disconnects / reconnects the PLC No. where communication error are shut down. A station number that has been
communication error occurs *4 shut down is regularly monitored and communications are resumed
when the station recovers.
*1 Be sure to set unique IP addresses for each device in the same LAN.
IP addresses are expressed as XXX.XXX.XXX.XXX (XXX indicates a number in the range 0 to 255).
*2 Do not change the port number to a number between 0 to 1023. Also, take care not to use a port number already used
by another device.
*3 Select "PLC device".
"6-7 Device Setup", VT5 Series Reference Manual
*4 Can be set up when a PLC model supporting 1-to-N connection is selected.

Point You can use VT5 system mode to check and change PLC communication condition settings.
The setting items are the same as those in VT STUDIO.
"5-5 PLC Communication Setup", VT5-WX Hardware Manual
"5-5 PLC Communication Setup", VT5 Series Hardware Manual

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-43


1-4 Unit Settings

1  VT3 Series Ethernet connection settings


Use the following steps to make Ethernet settings for the VT3 Series.
CONNECTING TO THE KV & KZ SERIES

1 Use the VT3 System mode to set an IP address to be assigned to the VT3 or make other settings.
Set at "Option Setup" in the System mode on the VT3 unit.
"Chapter 5 SYSTEM MODE", VT3 Series Reference Manual

Ethernet Setup (1/3) OK Ethernet Setup (2/3) OK


Cancel Cancel
Next page Next page
Baud rate 100/10 Mbps Auto Port No. 8500

IP Address 192 168 1 10 Time-out 10 s

Subnet Mask 255 255 255 0 Keep alive 600 s

Default Gateway 0 0 0 0

MAC address ** : ** : ** : ** : ** : **

Ethernet Setup (3/3) OK


Cancel
Next page
FTP Setup Enable Password

Routing setup

No.0 (Disabled) Setup

No.1 (Disabled) Setup

No.2 (Disabled) Setup

No.3 (Disabled) Setup

Item Description
Normally, select "100/10M bps Auto". Selects "10 Mbps" only when communications is
Baud rate unstable.
Selects "10 Mbps" only when communications is unstable.
IP Address Sets the IP address to be assigned to the VT3.
Use the default setting as it is in the case of a direct connection.
Subnet Mask
Sets a pre-acknowledged subnet mask for other connections.
Use the default setting as it is in the case of a direct connection.
Default Gateway
Sets a pre-acknowledged default gateway for other connections.
MAC address This is the ID No. unique to VT3 Series. This cannot be set.
Please set the port No. for communicating with a PC application such as VT STUDIO as
Port no.
required. Duplication with the PLC communication port No. must be avoided.
Time-out Set as necessary.
Keep Alive Set as necessary.
FTP Setup Set as necessary.
Routing Setup*1 Selects "Enable" only when using a router.
*1 "Chapter 8 ETHERNET", VT3 Series Hardware Manual

1-44 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

2 Use VT STUDIO to set communication conditions with PLC.


1
In VT STUDIO, select [Resource (R)][VT System Settings (S)][PLC Communication Condition (C)] and make the
following settings.

CONNECTING TO THE KV & KZ SERIES


"Chapter 17 Ethernet Connection", VT3 Series Reference Manual

Item Description
PLC No. Selects the PLC No. (0 to 15) to be used.
IP address*1 Sets the IP address to be assigned to the connection destination PLC (marked PLC No.).
Target PLC Port No.*2 Sets the port No. (1024 to 65535) of the connection destination PLC (marked PLC No.).
Selects the connection destination from the connection destination list file, or
Connect to
adds connection destinations.
VT port No. (for PLC
Sets the port No. (for PLC communications) (1024 to 65535) of the VT3.
communications)
Normally, this does not need to be set.
Timeout
Set a long time-out when the communications load on the network is large.
Ethernet Settings
Normally, this does not need to be set.
Send Wait
Set a long time-out when the communications load on the network is large.
Normally, this does not need to be set.
Retry
Increase the number of retries when the unit is used in an environment with a lot of noise.
PLC communications special settings
Normally, this does not need to be set.
(set on VT STUDIO)
Specify a device to
troubleshoot Target word Used to set up a device that troubleshoots Ethernet connections. Normally
Ethernet device*3 no need to be set up
connections
VT3 disconnects / reconnects the PLC Once selected, the communication with an erroneous station is cut off. And this
No. where communication error occurs*4 number is regularly monitored and re-connected once the error is removed.
*1 Be sure to set only unique IP addresses to each device within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range 0 to 255).
*2 When changing the port No., do not use numbers 0 to 1023 as the new port No. Also, take care not to use another port
No. that is already in use.
*3 Select "PLC Devices"
"6-7 Set up the Devices", VT3 Series Reference Manual
*4 Can be set up when a PLC model supporting 1-to-N connection is selected.

Point You can use VT3 system mode to check and change PLC setting conditions.
The setting items are the same as those when setting on VT STUDIO.
"5-4 PLC Communication Condition", VT3 Series Hardware Manual

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-45


1-4 Unit Settings

1 KV-8000/8000A/7500 internal Ethernet port setting


Use the KV STUDIO Unit Editor to set up.
CONNECTING TO THE KV & KZ SERIES

Item Description
IP Address *1 Set the IP address to be assigned to the connected PLC.
Use the PLC communication condition setting to set the port number to be assigned to the target
Port No. (VT) *2
PLC.
*1 Be sure to set unique IP addresses for each device in the same LAN.
IP addresses are expressed as XXX.XXX.XXX.XXX (XXX indicates a number in the range 0 to 255).
*2 Do not change the port number to a number between 0 to 1023. Also, take care not to use a port number already used
by another device.

1-46 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

KV-XLE02 setting
This is set up via the Unit Editor in KV STUIDO.
1
Communication is possible with both port 1 and port 2. Here, we will describe for port 1 as an example.

CONNECTING TO THE KV & KZ SERIES


Item Description
Select items that can use general Ethernet (TCP / IP) such as "Not use (*)" and "EtherNet / IP
(Scanner)".
Industrial Ethernet
* If you select a function that can not be mixed with general Ethernet, such as "EtherCAT (slave)",
you can not connect with VT.
IP address*1 Set the IP address to be assigned to KV-XLE02.
Set up whether to enable VT connection on the current Ethernet port.
VT connection * Normally, it is unnecessary to change from the default setting "Enable".
Set this to disable the VT connection port No. of the Ethernet port not used for VT connection.
Port No. (VT) Set up the port No. *2 set for the target PLC with the PLC communication condition setting.
*1 Be careful that the IP address does not overlap with other devices within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range 0 to 255).
*2 When changing the port No., do not use 0 to 1023. Also, be careful not to duplicate the number if there is
another port number you are using.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-47


1-4 Unit Settings

1 KV-XD02 setting
This is set up via the Unit Editor in KV STUIDO.
Communication is possible with both port 1 and port 2. Here, we will describe for port 1 as an example.
CONNECTING TO THE KV & KZ SERIES

Item Description
IP address*1 Set the IP address to be assigned to KV-XD02.
Set up whether to enable VT connection on the current Ethernet port.
VT connection * Normally, it is unnecessary to change from the default setting "Enable".
Set this to disable the VT connection port No. of the Ethernet port not used for VT connection.
Port No. (VT) Set up the port No. *2 set for the target PLC with the PLC communication condition setting.
*1 Be careful that the IP address does not overlap with other devices within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range 0 to 255).
*2 When changing the port No., do not use 0 to 1023. Also, be careful not to duplicate the number if there is
another port number you are using.

1-48 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

KV-5500/5000 Ethernet port setting


This is set up via the Unit Editor in KV STUIDO.
1

CONNECTING TO THE KV & KZ SERIES


Item Description
Communication Mode Select "Ethernet (*)".(Only KV-5000)
IP Address*1 Set the IP address to be assigned to the connection destination PLC.
*2 Use the PLC communication condition setting to set the port number to be assigned to the
Port No. (VT)
target PLC.
*1 Be sure to set only unique IP address to each equipment within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range of 0 to 255).
*2 When changing the port No., do not use the number of 0 to 1023 as the new port No. Also, do not use another port No.
that is already in use.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-49


1-4 Unit Settings

1 KV-EP21V/LE21V/LE20V Settings
This is set up via the Unit Editor in KV STUIDO.
CONNECTING TO THE KV & KZ SERIES

Item Description
IP Address*1 Set the IP address to be assigned to the connection destination PLC.
Use the PLC communication condition setting to set the port number to be assigned to the
Port No. (VT)*2
target PLC.
*1 Be sure to set only unique IP address to each equipment within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range of 0 to 255).
*2 When changing the port No., do not use numbers of 0 to 1023 as the new port No. Also, do not use another port No. that
is already in use.

1-50 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-4 Unit Settings

 KV-LE20(V/A) settings
Set up with Unit Editor in KV BUILDER or KV STUDIO.
1

CONNECTING TO THE KV & KZ SERIES


Point Use KV BUILDER Ver.3.52 or higher.

Item Description
IP address*1 Sets the IP address to be assigned to the connection destination PLC.
Use the PLC communication condition setting to set the port number to be assigned to the
Port No. (VT)*2
target PLC.
*1 Be sure to set only unique IP addresses to each device within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range 0 to 255).
*2 When changing the port No., do not use numbers 0 to 1023 as the new port No. In addition, the port numbers should be
unique when other ports need to be used.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-51


1-4 Unit Settings

1 KV-NC1EP setting
This is set up via the Unit Editor in KV STUIDO.
CONNECTING TO THE KV & KZ SERIES

Item Description
IP Address*1 Set the IP address to be assigned to the connection destination PLC.
Use the PLC communication condition setting to set the port number assigned to the target
Port No. (VT)*2
PLC.
*1 Be sure to set only unique IP address to each equipment within the same LAN.
IP addresses are expressed as XXX.XXX.XXXX.XXX (XXX is a number within the range of 0 to 255).
*2 When changing the port No., do not use the number of 0 to 1023 as the new port No. Also, do not use another port No.
that is already in use.

1-52 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-5 Available Devices
This section describes available devices.
1
 KV-8000 Series (serial), KV-8000 Series (serial) <XYM>

CONNECTING TO THE KV & KZ SERIES


KV-8000 Series (KV-LM2V), KV-8000 Series (KV-LM2V) <XYM>
KV-8000 Series (Ethernet), KV-8000 Series (Ethernet) <XYM>
Device KV-8000 Series KV-8000 Series <XYM>
Relay R00000 to R199915
Input relay *1 - X0000 to X1999F
Output relay *1 - Y0000 to Y1999F
Internal auxiliary relay MR000000 to MR399915 M00000 to M63999
Latch relay LR00000 to LR99915 L00000 to L15999
Control relay CR0000 to CR7915
Timer (contact) T0000 to T3999
Counter (contact) C0000 to C3999
Data memory *2 DM00000.00 to DM65534.15 D00000.00 to D65534.15
Bit device
Extended data memory *2 EM00000.00 to EM65534.15 E00000.00 to E65534.15
File register *2 FM00000.00 to FM32767.15 F00000.00 to F32767.15
Link relay B0000 to B7FFF
Work relay VB0000 to VBF9FF
File register (CONT mode) *2 ZF000000.00 to ZF524287.15
Link register *1 W0000.0 to W7FFF.F
Control memory *2 CM0000.00 to CM7599.15
Temporary data memory *2 TM000.00 to TM511.15
Work memory *2 VM000000.00 to VM589823.15
Relay *3 R00000 to R199900
Input relay *4 - X0000 to X19990
Output relay *4 - Y0000 to Y19990
Internal auxiliary relay MR00000 to MR399900 *3 M00000 to M63984 *5
Latch relay *5 LR00000 to LR99900 L00000 to L15984
Control relay *3 CR0000 to CR7900
Trimmer *6 TRM0 to TRM7
Timer (set value) TS0000 to TS3999
Timer (current value) TC0000 to TC3999
Counter (set value) CS0000 to CS3999
Counter (current value) CC0000 to CC3999
Data memory DM00000 to DM65534 D00000 to D65534
Word device Extended data memory EM00000 to EM65534 E00000 to E65534
File register FM00000 to FM32767 F00000 to F32767
Control memory CM0000 to CM7599
Temporary data memory TM000 to TM511
The index register *7 Z1 to Z12
Link relay *4 B0000 to B7FF0
Work relay *4 VB0000 to VBF9F0
File register (CONT mode) ZF000000 to ZF524287
Link register W0000 to W7FFF
Work memory VM000000 to VM589823
Expansion unit buffer memory *8 UG0000000 to UG4859999
Expansion unit buffer memory
(bank support)*9 ZG000000000 to ZG483159999

*1 Low-order 1 digit becomes "0 to F".


*2 Low-order 2 digits become "00 to 15".
*3 Low-order 2 digits become "00".
*4 Low-order 1 digit becomes "0".
*5 Only numbers divisible by 16 can be set.
*6 Only reading is possible.
*7 The index register is a 2-word device. Since the KV-1000 Series index register is a 1-word device, a change from the
KV-1000 to the KV-8000 model will make it an unset device.
*8 The high-order 2 digits are the unit ID and the low-order 5 digits are the device number.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-53


1-5 Available Devices

1 *9 The high-order 2 digits are the unit ID, the medium-order 2 digits are the bank number and the low-order 5 digits are the
device number.
*10 The device number is set as described below.
ZG483132767
CONNECTING TO THE KV & KZ SERIES

Unit ID Device No.


Bank No.

Available Variable
When the CPU unit of the PLC to be connected is KV-8000/8000A, and it is connected with VT5 Series/Soft-VT by
Ethernet, reading and writing can be done using a variable. Data types of available variables are as follows.
Type name Description Support
BOOL Bit 
UINT 1 word unsigned integer *
INT 1 word signed integer *
UDINT 2 words unsigned integer *
DINT 2 words signed integer *
REAL Single-precision float point type 
LREAL Double-precision float point type 
STRING String 
TIMER Timer 
COUNTER Counter 
ARRAY Array 
STRUCTURE Structure 
FUNCTION BLOCK Function block 

* When handled as a bit data, set it as “variable name + period (.) + bit position”.

Point • Because the local variable cannot be referred from VT5 Series, register a variable to be
referred from VT5 Series as a global variable.
• When an array is specified, specify a suffix by a constant.
• When a structure is specified, specify it up to the end member.
• No variable set to a constant can be specified.
• The string length that can be specified by a variable is 255 characters at maximum. Set the
variable which is defined by an array suffix "[]" and "period (.)" which locates between a
structure type variable name and member name, and an integer (UINT, INT, UDINT, and
DINT), using 255 characters or less, including "." which locates between a variable name
and bit position when the variable is handled as a bit data.
• For details on variables, see "VT5 Series Reference Manual".
• Variables can be used only when the version is VT STUDIO Ver. 8.0 or later, and the
supported model is VT5 Series/Soft-VT, and the VT main unit system program version is
Ver. 4.00 or later.
• Variables can be used only when performing the Ethernet connection to KV-8000/8000A
with the CPU function version of 2.0 or later.

1-54 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-5 Available Devices

 KV-7000 Series (serial), KV-7000 Series (serial) <XYM>


KV-7000 Series (KV-LM2V), KV-7000 Series (KV-LM2V) <XYM>
1
KV-7000 Series (Ethernet), KV-7000 Series (Ethernet) <XYM>

CONNECTING TO THE KV & KZ SERIES


Device KV-7000 Series KV-7000 Series <XYM>
Relay R00000 to R199915*11
Input relay *1 - X0000 to X1999F*11
*1
Output relay - Y0000 to Y1999F*11
Internal auxiliary relay MR000000 to MR399915 M00000 to M63999
Latch relay LR00000 to LR99915 L00000 to L15999
Control relay CR0000 to CR7915
Timer (contact) T0000 to T3999
Counter (contact) C0000 to C3999
Data memory *2 DM00000.00 to DM65534.15 D00000.00 to D65534.15
Bit device
Extended data memory *2 EM00000.00 to EM65534.15 E00000.00 to E65534.15
File register *2 FM00000.00 to FM32767.15 F00000.00 to F32767.15
Link relay B0000 to B7FFF
Work relay VB0000 to VBF9FF
File register (CONT mode) *2 ZF000000.00 to ZF524287.15
Link register *1 W0000.0 to W7FFF.F
Control memory *2 CM0000.00 to CM5999.15
Temporary data memory *2 TM000.00 to TM511.15
Work memory *2 VM00000.00 to VM63999.15
Relay *3 R00000 to R199900*11
Input relay *4 - X0000 to X19990*11
Output relay *4 - Y0000 to Y19990*11
Internal auxiliary relay MR00000 to MR399900 *3 M00000 to M63984 *5
Latch relay *5 LR00000 to LR99900 L00000 to L15984
Control relay *3 CR0000 to CR7900
Trimmer *6 TRM0 to TRM7
Timer (set value) TS0000 to TS3999
Timer (current value) TC0000 to TC3999
Counter (set value) CS0000 to CS3999
Counter (current value) CC0000 to CC3999
Data memory DM00000 to DM65534 D00000 to D65534
Word device Extended data memory EM00000 to EM65534 E00000 to E65534
File register FM00000 to FM32767 F00000 to F32767
Control memory CM0000 to CM5999
Temporary data memory TM000 to TM511
The index register *7 Z1 to Z12
Link relay *4 B0000 to B7FF0
Work relay *4 VB0000 to VBF9F0
File register (CONT mode) ZF000000 to ZF524287
Link register W0000 to W7FFF
Work memory VM00000 to VM63999
Expansion unit buffer memory *8 UG0000000 to UG4859999
Expansion unit buffer memory
(bank support)*9 ZG000000000 to ZG483159999

*1 Low-order 1 digit becomes "0 to F".


*2 Low-order 2 digits become "00 to 15".
*3 Low-order 2 digits become "00".
*4 Low-order 1 digit becomes "0".
*5 Only numbers divisible by 16 can be set.
*6 Only reading is possible.
*7 The index register is a 2-word device. Since the KV-1000 Series index register is a 1-word device, a change from the
KV-1000 to the KV-7500/7300 model will make it an unset device.
*8 The high-order 2 digits are the unit ID and the low-order 5 digits are the device number.
*9 The high-order 2 digits are the unit ID, the medium-order 2 digits are the bank number and the low-order 5 digits are the
device number.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-55


1-5 Available Devices

1 *10 The device number is set as described below.


ZG483132767
CONNECTING TO THE KV & KZ SERIES

Unit ID Device No.


Bank No.

*11 For CPU function version 2.2 or earlier, the relay range is R00000 to R99915, the input relay (bit device) range is X0000
to X999F, the output relay (bit device) range is Y0000 to Y999F, the input relay (word device) range is X0000 to X9990,
and the output relay range (word device) is Y0000 Y9990.

 KV-5500/5000/3000/L2V, KV-5500/5000/3000/L2V <XYM>


KV-5500/5000/3000 (KV-LM2V), KV-5500/5000/3000 (KV-LM2V) <XYM>
KV-5500/5000/3000 (Ethernet), KV-5500/5000/3000 (Ethernet) <XYM>
KV-5500/5000/3000
Device KV-5500/5000/3000
<XYM>
Relay R00000 to R99915 R00000 to R99915
Input relay *1 - X0000 to X999F
Output relay *1 - Y0000 to Y999F
Internal auxiliary relay MR00000 to MR99915 M00000 to M15999
Latch relay LR00000 to LR99915 L00000 to L15999
Control relay CR0000 to CR3915 CR0000 to CR3915
Timer (contact) T0000 to T3999 T0000 to T3999
Counter (contact) C0000 to C3999 C0000 to C3999
Bit device CTC (contact) *2 CTC0 to CTC3 CTC0 to CTC3
Data memory *3 DM00000.00 to DM65534.15 D00000.00 to D65534.15
Extended data memory *3 EM00000.00 to EM65534.15 E00000.00 to E65534.15
File register *3 FM00000.00 to FM32767.15 F00000.00 to F32767.15
Link relay B0000 to B3FFF B0000 to B3FFF
Work relay VB0000 to VB3FFF VB0000 to VB3FFF
File register (CONT mode) *3 ZF000000.00 to ZF131071.15
Link register *1 W0000.0 to W3FFF.F
Work memory *3 VM00000.00 to VM59999.15

1-56 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-5 Available Devices

Device KV-5500/5000/3000
KV-5500/5000/3000
<XYM>
1
Relay *4 R00000 to R99900 R00000 to R99900

CONNECTING TO THE KV & KZ SERIES


Input relay *5 - X0000 to X9990
Output relay *5 - Y0000 to Y9990
Internal auxiliary relay MR00000 to MR99900 *4 M00000 to M15984 *6
Latch relay LR00000 to LR99900 *4 L00000 to L15984 *6
Control relay *4 CR0000 to CR3900 CR0000 to CR3900
Trimmer *7 TRM0 to TRM7 TRM0 to TRM7
Timer (set value) TS0000 to TS3999 TS0000 to TS3999
Timer (current value) TC0000 to TC3999 TC0000 to TC3999
Counter (set value) CS0000 to CS3999 CS0000 to CS3999
Counter (current value) CC0000 to CC3999 CC0000 to CC3999
High-speed counter (current value) CTH0 to CTH1 CTH0 to CTH1
CTC (set value) CTC0 to CTC3 CTC0 to CTC3
Word device Data memory DM00000 to DM65534 D00000 to D65534
Extended data memory EM00000 to EM65534 E00000 to E65534
File register FM00000 to FM32767 F00000 to F32767
Control memory CM0000 to CM5999 CM0000 to CM5999
Temporary data memory TM000 to TM511 TM000 to TM511
Index register *8 Z1 to Z12 Z1 to Z12
Link relay *5 B0000 to B3FF0 B0000 to B3FF0
Work relay *5 VB0000 to VB3FF0 VB0000 to VB3FF0
File register (CONT mode) ZF000000 to ZF131071 ZF000000 to ZF131071
Link register W0000 to W3FFF W0000 to W3FFF
Work memory VM00000 to VM59999 VM00000 to VM59999
Expansion unit buffer memory *9 G0000000 to G4832767 G0000000 to G4832767
Expansion unit buffer memory
(bank support) *10 ZG000000000 to ZG483132767 ZG000000000 to ZG483132767

*1 Low-order 1 digit becomes "0 to F".


*2 The high-speed counter comparator of a bit device is read only.
*3 Low-order 2 digits become "00 to 15".
*4 Low-order 2 digits become "00 to F".
*5 Low-order 1-digit becomes "0".
*6 Only numbers divisible by 16 can be set.
*7 Only reading is possible.
*8 The index register is a 2-word device. Since the KV-1000 Series index register is a 1-word device, a change from the
KV-1000 to the KV5000/3000 model will make it an unset device.
*9 The high-order 2 digits are the unit ID and the low-order 5 digits are the device number.
*10 KV-5000 and KV-LE20V can be used with KEYENCE products shipped on or after September 12th 2008.
When expansion unit buffer memory (bank support) is used, a port number (system extension) is used in addition to the
PLC "port number (VT)".
The device number is set as described below.

ZG483132767

Unit ID Device No.


Bank No.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-57


1-5 Available Devices

1  KV-1000/700, KV-L20/L21VKV-1000/700, KV-L20/L21V <XYM>


KV-1000/700 (KV-LM20/21V), KV-1000 (KV-LM20/21V) <XYM>
KV-1000/700 (Ethernet), KV-1000 (Ethernet) <XYM>
CONNECTING TO THE KV & KZ SERIES

KV-1000
Device KV-1000 KV-700
<XYM>
Relay 00000 to 59915 R00000 to R59915 00000 to 59915
Input relay *1 - X0000 to X599F -
Output relay *1 - Y0000 to Y599F -
Internal auxiliary relay MR00000 to MR99915 M00000 to M15999 -
Latch relay LR00000 to LR99915 L00000 to L15999 -
Control relay CR0000 to CR3915 CR0000 to CR3915 CR0000 to CR3915
Timer (contact) T0000 to T3999 T0000 to T3999 T000 to T511
Bit device
Counter (contact) C0000 to C3999 C0000 to C3999 C000 to C511
CTC (contact) *2 CTC0 to CTC3 CTC0 to CTC3 CTC0 to CTC3

Data memory *3 DM00000.00 to D00000.00 to DM00000.00 to


DM65534.15 D65534.15 DM39999.15

Extended data memory *3 EM00000.00 to E00000.00 to


-
EM65534.15 E65534.15

Extended data memory *3 FM00000.00 to F00000.00 to


-
FM32766.15 F32766.15
*4
Relay 00000 to 59900 R00000 to R59900 00000 to 59900
Input relay - X0000 to X5990 *5 -
Output relay - Y0000 to Y5990 *5 -
Internal auxiliary relay MR00000 to MR99900 *4 M00000 to M15984 *6 -
Latch relay * LR00000 to LR99900 *4 L00000 to L15984 *6 -
Control relay *4 CR0000 to CR3900 CR0000 to CR3900 CR0000 to CR3900
Trimmer *7 TRM0 to TRM7 TRM0 to TRM7 TRM0 to TRM7
Timer (set value) TS0000 to TS3999 TS0000 to TS3999 TS000 to TS511
Timer (current value) TC0000 to TC3999 TC0000 to TC3999 TC000 to TC511
Counter (set value) CS0000 to CS3999 CS0000 to CS3999 CS000 to CS511
Word device Counter (current value) CC0000 to CC3999 CC0000 to CC3999 CC000 to CC511
High-speed counter
(current value) CTH0 to CTH1 CTH0 to CTH1 CTH0 to CTH1

CTC (set value) CTC0 to CTC3 CTC0 to CTC3 CTC0 to CTC3


Data memory DM00000 to DM65534 D00000 to D65534 DM00000 to DM39999
Extended data memory EM00000 to EM65534 E00000 to E65534 -
Extended data memory FM00000 to FM32766 F00000 to F32766 -
Control memory CM00000 to CM11998 CM00000 to CM11998 CM0000 to CM3999
Temporary data
memory TM000 to TM511 TM000 to TM511 TM000 to TM511

Index register Z1 to Z12 Z1 to Z12 -

*1 low-order 1 digit becomes "0 to F".


*2 The high-speed counter comparator of a bit device is read only.
*3 Low-order 2 digits become "00 to 15".
*4 Low-order 2-digit becomes "00".
*5 Low-order 1-digit becomes "0".
*6 Only numbers divisible by 16 can be set.
*7 Only reading is possible.

1-58 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-5 Available Devices

 KV Nano Series [KV-N], KV Nano Series [KV-N] <XYM>


KV Nano Series [KV-N] (Ethernet), KV Nano Series [KV-N] (Ethernet) <XYM>
1

CONNECTING TO THE KV & KZ SERIES


KV Nano
Device KV Nano
<XYM>
Relay R00000 to R59915 R00000 to R59915
Input relay - X0000 to X599F
Output relay - Y0000 to Y599F
Internal auxiliary relay MR00000 to MR59915 M0000 to M9599
Latch relay LR00000 to LR19915 L0000 to L3199
Control relay CR0000 to CR8915 CR0000 to CR8915
Timer (contact) T000 to T511 T000 to T511
Counter (contact) C000 to C255 C000 to C255
Bit device
CTC (contact) *1 *6
CTC0 to CTC7 CTC0 to CTC7
Data memory *2 DM00000.00 to DM32767.15 D00000.00 to D32767.15
Control memory *2 CM0000.00 to CM8999.15 CM0000.00 to CM8999.15
Temporary data memory *2 TM000.00 to TM511.15 TM000.00 to TM511.15
Link relay B0000 to B1FFF B0000 to B1FFF
Work relay VB0000 to VB1FFF VB0000 to VB1FFF
Link register W0000.0 to W3FFF.F W0000.0 to W3FFF.F
Work memory *2 VM0000.00 to VM9999.15 VM0000.00 to VM9999.15
Relay *3 R00000 to R59900 R00000 to R59900
Input relay - X0000 to X5990
Output relay - Y0000 to Y5990
Internal auxiliary relay *3 MR00000 to MR59900 M0000 to M9584
Latch relay *3 LR00000 to LR19900 L0000 to L3184
Control relay *3 CR0000 to CR8900 CR0000 to CR8900
Timer (set value) TS000 to TS511 TS000 to TS511
Timer (current value) TC000 to TC511 TC000 to TC511
Counter (set value) CS000 to CS255 CS000 to CS255
Counter (current value) CC000 to CC255 CC000 to CC255
Word device High-speed counter (current value) *6 CTH0 to CTH3 CTH0 to CTH3
CTC (set value) *6 CTC0 to CTC7 CTC0 to CTC7
Data memory DM00000 to DM32767 D00000 to D32767
Control memory CM0000 to CM8999 CM0000 to CM8999
Temporary data memory TM000 to TM511 TM000 to TM511
Index register *5 Z1 to Z12 Z1 to Z12
Link relay B0000 to B1FF0 B0000 to B1FF0
Work relay VB0000 to VB1FF0 VB0000 to VB1FF0
Link register W0000 to W3FFF W0000 to W3FFF
Work memory VM0000 to VM9999 VM0000 to VM9999
Extension unit buffer memory *7 G0000000 to G4832767 G0000000 to G4832767

*1 The high-speed counter comparator of a bit device is read only.


*2 Low-order 2 digits become "00 to 15".
*3 Low-order 2-digit becomes "00".
*4 Only reading is possible.
*5 The index register is a 2-word device.
The KV-1000 Series index register is a 1-word device so if moved from the KV-1000 to a KV Nano Series model, it will
become an unset device.
*6 Available models are restricted according to the product model. Check the specifications for the respective model.
*7 High order of 2 digits are to be the unit ID, whereas the low order of 5 digits are to be the device No.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-59


1-5 Available Devices

1  KZ-10/16/24/40/80, KZ-300/350, KV-10/16/24/40, KV-P series


Address
Device
CONNECTING TO THE KV & KZ SERIES

KV-10/16/24/40, KV-P KZ-300/350 KZ-24/40/80 KZ-10/16


00000 to 00915
I/O relay 00000 to 00915
07000 to 17915
Internal auxiliary relay 01000 to 01915, 03000 to 06915 01000 to 01915
Bit Devices

Special auxiliary relay *1 02000 to 02915


Timer (contact) T000 to T249 T000 to T119 T000 to T063
Counter (contact) C000 to C249 C000 to C119 C000 to C063
High-speed counter
comparator CTC0 to CTC3
(contact) *2
00000 to 00900
I/O relay *3 -
07000 to 17900
*3
Internal auxiliary relay 01000 to 01900, 03000 to 06900 -
Analog trimmer *4 - AT0 to AT1 AT0
Digital trimmer AT0 to AT1 -
Timer (set) TS000 to TS249 TS000 to TS119 TS000 to TS063
Timer (current) TC000 to TC249 TC000 to TC119 TC000 to TC063
Devices

Counter (set) CS000 to CS249 CS000 to CS119 CS000 to CS063


Counter (current) CC000 to CC249 CC000 to CC119 CC000 to CC063
High-speed counter
CTH0 to CTH1
(current)
High-speed counter
comparator CTC0 to CTC3
(Setup Value)
Data memory DM0000 to DM1999 DM0000 to DM9999 DM0000 to DM1999 DM0000 to DM0999
Temporary data memory TM00 to TM31
*1 An error response is sometimes returned when the special auxiliary relay is written to.
*2 Only reading is possible on the high-speed counter comparator for bit devices.
*3 Lower two digits become "00".
*4 Read-only.

1-60 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-5 Available Devices

 KZ-A500, KZ-L10
Address
1

CONNECTING TO THE KV & KZ SERIES


Device KZ-A500
KZ-L10
(PLC port direct link)
Input relay X000000 to X0007FF
Output relay Y000000 to Y0007FF
Internal relay M000000 to M008191
Latch relay L000000 to L008191
Link relay B000000 to B000FFF
Internal auxiry relay -
Bit Devices
Special auxiliary relay -
Timer (contact) TS00000 to TS02047
Timer (coil) TC00000 to TC02047
Counter (contact) CS00000 to CS01023
Timer (coil) CC00000 to CC01023
High-speed counter comparator -
Input relay *1 X000000 to X0007F0
Output relay *1 Y000000 to Y0007F0
Internal relay *2 M000000 to M008176
Latch relay *2 L000000 to L008176
Link relay *1 B000000 to B000FF0
Data register (data memory) D000000 to D006143
Link register W000000 to W000FFF
File register - R000000 to R008191
Word Devices Internal auxiliary relay -
Temporary data memory -
Digital trimmer -
Timer (set) - TX00000 to TX00255
Timer (current) TN00000 to TN02047
Counter (set) - CX00000 to CX00255
Counter (current) CN00000 to CN01023
High-speed counter (current) -
High-speed counter comparator (set) -
*1 Lower one digit becomes "0".
*2 Value divisible by 16

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-61


1-6 Error Messages and Remedies
1 This section describes communication errors occurring in VT5/VT3 Series, Soft-VT and KV, KZ Series connections.
CONNECTING TO THE KV & KZ SERIES

List of Communication Errors in Serial Connections


Error messages are displayed at the bottom left of the VT5/VT3 unit screen when a communications error occurs.
The error messages are shown as follows.

Display message Causes How to handle


The device that is set is outside the range of the
device setting range. Please set it again within the device
setting range.
PLC Error [**] A nonexistent device has been set.
For the error code[**], see "Details of the
[**]: Error code of PLC
communication error[**]", page 1-34.
Please check again whether the cable is
Cable is not connected with PLC correctly.
connected correctly.
Power of the PLC is OFF. Turn the PLC ON.
Please clear the error or fault on the
The PLC side is in error or fault status.
PLC side.
Time Out Error /
Unit Time Out Error Keep the communication settings
Communication setting error. consistent between the PLC and VT5/
VT3.
Verify whether there is a noise source. If
Affected by noise. there is a noise source, then it must be
separated from the main unit.
Checksum is not correct. The calculation method for Please check the checksum calculation
checksum is wrong. method.
Connection status of the connection cables is not Verify whether there is wire break or bad
good. contact.
Sum Check Error Keep the communication settings
Communication setting error. consistent between the PLC and VT5/
VT3.
Verify whether there is a noise source. If
Affected by noise. there is a noise source, then it must be
separated from the main unit.
A parity error occurred during communicating with PLC. Verify whether there is wire break or bad
Connection status of the connection cables is not good. contact.
Keep the communication settings
Parity Error Communication setting error. consistent between the PLC and VT5/
VT3.
Verify whether there is a noise source. If
Affected by noise. there is a noise source, then it must be
separated from the main unit.
Please decrease the communication
VT5/VT3 receive buffer overrun.
speed (baud rate).
Verify whether there is wire break or bad
Connection status of the connection cables is not contact. Keep the communication
Over Run Error good. Communication setting error. settings consistent between the PLC
and VT5/VT3.
Verify whether there is a noise source. If
Affected by noise. there is a noise source, then it must be
separated from the main unit.
The stop bit cannot be detected during communicating
with PLC. Verify whether there is wire break or bad
contact.
Connection status of the connection cables is not good.
Keep the communication protocol
Framing Error Communication protocol setting error. consistent between the PLC and VT5/
VT3.
Verify whether there is a noise source. If
Affected by noise. there is a noise source, then it must be
separated from the main unit.
Communication Please refer to the handling methods
Multiple communication errors occurred.
Error mentioned above.
* • When MultiTalk function is used, in order to determine the connected equipment on which an error occurs, "A:" or "B:"
will be added in front of the above error messages.
• For details on error messages other than communication errors, refer to the following manuals.
"Appendix-1 Error Messages and Troubleshooting", VT5 Series Hardware Manual
"Appendix-1 Error Messages and Troubleshooting", VT3 Series Hardware Manual

1-62 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-6 Error Messages and Remedies

List of Communication Errors in Ethernet Connections 1

CONNECTING TO THE KV & KZ SERIES


The following error messages may appear when a PLC is connected via the Ethernet.
Error messages are displayed at the bottom left of the VT5/VT3/Soft-VT unit screen when a communications error
occurs.

Display Message Cause Remedy


A time-out occurred on PLC No. • Check the network for any problems.
TimeOutError(++)
++. • Review the communications setup.
Ethernet Unit VT2-E1/E2/VT3-E3 • Turn the VT3 unit OFF, mount VT2-E1/E2/VT3-E3, and
No Ethernet unit
is not connected. then turn VT3 ON again.
The protocol is in the startup
Protocol stack error Wait a while in this state.
process.
• Make sure that the connector cables are correctly
connected.
A linking error has occurred to the
Link error • Make sure that LINK LED on the VT5 Series, VT2-E1/
Ethernet unit.
E2, VT3-E3, VT3 handy Series and the connected PLC
is on.
There was not error response** For more information about the response **, please refer
PLCError[**(++)]
from PLC No.++. to relevant PLC and Ethernet unit manuals.
The used CPU unit and Ethernet
Ethernet unit not unit do not support read/write Please use the products manufactured after Sep 12,
support(++) *1 operation of expansion unit buffer 2008.
memory (support bank).
The read source of a defined device
communications error expansion unit buffer memory
Please check device No. or unit configuration.
[Unit not support] *1 (support bank) or write destination
unit does not support bank.
PLCError[70(++)] • The variable set by VT STUDIO
does not exist in PLC of the
station No. ++.
Confirm whether the variable set by VT STUDIO matches
Specified variable does • A larger value than the element
the variable set by KV STUDIO.
not exist. number of the array set in PLC
of the station No. ++ is specified
to the array suffix.
Specified variable type The variable types are different Confirm whether the variable set by VT STUDIO matches
is incorrect. between PLC and VT STUDIO. the variable set by KV STUDIO.
* • When MultiTalk function is used, in order to determine the connected equipment on which an error occurs, "A:" or "B:"
will be added in front of the above error messages.
• For details on error messages other than communication errors, refer to the following manuals.
"Appendix-1 Error Messages and Troubleshooting", VT5-WX Hardware Manual
"Appendix-1 Error Messages and Troubleshooting", VT5 Series Hardware Manual
"Appendix-1 Error Messages and Troubleshooting", VT3 Series Hardware Manual

*1 Be sure to use expansion unit buffer memory (that support banks) that have been manufactured after September 12,
2008 with the KV-5000 and KV-LE20V.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-63


1-6 Error Messages and Remedies

1 Details of the communication error[**]


CONNECTING TO THE KV & KZ SERIES

This section describes the PLC communications errors that occur when a KV or KZ series PLC is connected.

 KV-8000 Series (serial), KV-8000 Series (serial) <XYM>,


KV-7000 Series (serial), KV-7000 Series (serial) <XYM>,
KV-5500/5000/3000/L2V, KV-5500/5000/3000/L2V <XYM>,
KV-1000/700, KV-L20/L21V, KV-1000, KV-L20/L21V <XYM> Connections

Error messages Cause Measures


PLC communications error A model other than KV-700or KV-L20 is selected Please select the target PLC from KV-1000/700,
[01] as the target PLC specified on VT STUDIO. KV-L20(R), KV-1000, and KV-L20R<XYM>
When KV-700-specific extended memory
Please install the KV-700-specific extended
(OP-42138) is not installed, devices beyond
memory (OP-42138) or specify the devices
the DM20000 is limited to the VT5/VT3/
between DM00000 to 19999.
PLC communications error Soft-VT/DT.
[02] In KV-700, the above devices cannot be used
when accessing 40000 to 65534 of Cannot use the device.
MR,LR,EM,FM,Z, and DM; 512 to 3999 of T/ page 1-58
C,TS,TC,CS, and CC; and 4000 to 11998 of CM.
The Baud rate in the communication
PLC communications error
conditions specified for the VT5/VT3/Soft-VT/ Please change the set baud rate value.
[04]
DT cannot be specified for the KV Series.
An attempt is being made to change the Remove the write-protection from the
PLC communications error
counter, timer or CTC set values on a write- program on the KV unit before changing set
[1D]
protected program on the KV unit. values.
The devices (the counter, timer, CTH and
PLC communications error Define the devices specified with the VT5/
CTC) specified with the VT5/VT3/Soft-VT/DT
[31] VT3/Soft-VT/DT in the KV program.
have not been defined in the KV program.
The unit that is the read source or write
PLC communications error
destination for the drawn device (expansion Correct the device number.
[49]
unit buffer memory) does not exist.
The read source of a defined device expansion
communications error Please check device No. or unit
unit buffer memory (support bank) or write
[Unit not support] configuration.
destination unit does not support bank.

Reference For DT-100 (A)


Can be confirmed through the "Main Unit Monitor" in DT BUILDER and "Error States" in the WEB server.
For DT-500/80 (A)
Can be confirmed through the "Main Unit Monitor" in DT STUDIO and "Error States" in the WEB server.

1-64 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-6 Error Messages and Remedies

 KV-8000 Series (KV-LM2V), KV-8000 Series (KV-LM2V) <XYM>,


KV-7000 Series (KV-LM2V), KV-7000 Series (KV-LM2V) <XYM>,
1
KV-5500/5000/3000 (KV-LM2V), KV-5500/5000/3000 (KV-LM2V) <XYM>,

CONNECTING TO THE KV & KZ SERIES


KV-1000/700 (KV-LM20/21V), KV-1000 (KV-LM20/21V) <XYM> Connections
Description Cause Measures
Other connected VT5/VT3 is set as the Correctly select the target PLC for the VT5/
PLC communications error
master station (Station Number 0) of VT2 VT3/Soft-VT and set "Multi-Link" to "Not
[01]
Multi-Link. Used" in the System Mode Window.
PLC communications error
The drawn device doesnít exist in the PLC. Please modify the device number.
[02]
An attempt is being made to change the
PLC communications error Please disable the write protection of the
counter, timer or CTC set values on a write-
[1D] PLC before changing the set value.
protected program on the unit.
PLC communications error The drawn device (the counter, timer, CTH, Define the devices specified with the VT5/
[31] and CTC) is not defined in the program. VT3/Soft-VT/DT in the KV program.
The unit that is the read source or write
PLC communications error
destination for the drawn device (expansion Correct the device number.
[49]
unit buffer memory) does not exist.

 When KV Nano Series [KV-N] or KV Nano Series [KV-N]<XYM> is connected


Description Cause Measures
PLC communications error A model other than KV Nano Series is Please select the target PLC from KV Nano
selected as the target PLC specified on VT
[01] Series
STUDIO.
A device type or device number in a range that
PLC communications error
cannot be used with the connected model is Correct the device type or device number.
[02]
specified.
The communication speed in the
PLC communications error communication conditions specified for the
Please change the set baud rate value.
[04] VT5/VT3/DT cannot be specified for the KV
Series.
An attempt is being made to change the Remove the write-protection from the
PLC communications error
counter, timer or CTC set values on a write- program on the KV unit before changing set
[1D]
protected program on the KV unit. values.
The devices (the counter, timer, CTH and
PLC communications error Define the devices specified with the VT5/
CTC) specified with the VT5/VT3/Soft-VT/DT
[31] VT3/Soft-VT/DT in the KV program.
have not been defined in the KV program.
The unit that is the read source or write
PLC communications error
destination for the drawn device (expansion Correct the device number.
[49]
unit buffer memory) does not exist.

 When a KZ series, KV-10/16/24/40 or KV-P series is connected


Error messages Cause Measures
The VT3 and DT are run con-tinuously
PLC communications error Register the program to theKZ, KV unit, and
without a programregistered to the KZ, KV
[02] connect andrun the VT3 and DT.
unit.
The device (relay, counter,timer, DM, CTH or
PLC communications error Define the device specified on the VT3 and
CTC) speci-fied by the VT3 and DT are not
[04] DT in the program.
defined in the program on theKZ, KV.
An attempt is being made to change the Remove the write-protection from the
PLC communications error
counter, timer or CTC set values on a write- program on the KZ,KV unit before changing
[13]
protected program on the KZ,KV unit. set values.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-65


1-7 About the 2-port Adapter MT-T2/T3
1 The following describes the 2-port Adapter MT-T2/T3 for the KZ series.

Point Not supported by the VT5 Series/Soft-VT.


CONNECTING TO THE KV & KZ SERIES

Names of Parts

MT-T2 MT-T3

MT-T2 MT-T3
(1) Port selector switch (1) Port selector switch
ACCESS 1+2 1ONLY ACCESS 1+2 1ONLY
(2) Operation indicator (2) Operation indicator
PLC EXT. (7) Power supply selector
POWER
switch
PORTA
(3)PORT A[PLC] PORTA
(3)PORT A[PLC]
(PLC) (PLC)

PORT1 (4)PORT1[MT] PORT1 (4)PORT1[MT]


(MT) BAUO (MT)
RATE

PORT2 A1 PORT2
(8) Baud rate selector
(TOOL) (TOOL) switch
2

24V 0V (5)PORT2[TOOL] 24V 0V


(5)PORT2[TOOL]

(6) Power input terminals (6) Power input terminals

(1) Port selector switch


When only PORT2 [MT] (connected with VT3) is used, please choose “1 ONLY”; when both PORT 1 [MT] (connected
with VT3) and PORT2 [TOOL] (connected with application tool) are used, please choose “1 + 2”.

(2) Operation indicator


Indicates the operation state.
Blinking (green): Blinks when communications is being performed on PORT1[MT].
Blinking (red): Blinks when communications is being performed on PORT2[TOOL].
Lit (orange): Lights when MT-T2 is not connected to the PLC. (MT-T2 only).

(3) PORTA [PLC]


Connect to PLC using the PLC connector cable provided with the VT series.

(4) PORT1 [MT]


Connected with VT3.

(5) DPORT2 [TOOL]


Can be used for connecting to the programming console or ladder software running on a personal computer using the
connector cable provided with the VT2 series.

(6) Power input terminals


Supplies 24 VDC power.

(7) Power supply selector switch


Selects whether to use an external power supply or the power supplied from the PLC port.
Be sure to use an external power supply when the distance between the PLC and the MT-T3 exceeds 60 cm.

(8) Baud rate selector switch


Selects the baud rate of PORTA [PLC], PORT1 [MT] and PORT2 [TOOL].
When a programming console or ladder software is not connected to PORT2, set the port selector switch to "1ONLY".
The following connection is not possible: connector cable connected to PORT1 [MT]or PORT2 [TOOL] on MT-T2/T3,
and another MT-T2/T3 connected.
1-66 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -
1-7 About the 2-port Adapter MT-T2/T3

 Connecting by MT-T2
1
MT-T2 is used to connect VT3 (excluding VT3-W4□) or programming tools to KZ series (excluding KZ-A500).

CONNECTING TO THE KV & KZ SERIES


PORT2
OP-26484(5m)
KEYENCE
KZ - 10R
OP-35403(1m)

VT3
(excluding VT3-W4□)
MT-T2
PORT1
ACCESS 1+2 1ONLY

KZ-10/16/24
KZ-40/80 PLC connector cable*1 PORTA
PORTA
(PLC)

PORT1
KV BUILDER*3
(MT)

PORT2 Ladder Builder


(cable provided with unit 0.6 m) 24V 0V
(TOOL)

for KZ
KZ Ladder
PORT2 Dedicated connector cable*2 KZ-P3
2-port adapter
MT-T2
PORT2
KZ-300/350 OP-26484(5m)
OP-35403(1m)

VT3
(excluding VT3-W4□)
*1 Connector cable OP-26487 can also be used. (An external power supply is needed for the MT-T2.)
*2
Connected Old type OP number Current type OP number
OP
Machine OP-96368 - OP-26487
For PC98 OP-26482 or OP-26487 + OP-26485 OP-96369 - OP-26485
For DOS/V machine OP-26487 + OP-26486 OP-23085 - OP-26482
For KZ-P3 OP-26487 OP-23086 - OP-26486+OP-26487

*3 KV BUILDER is not supported by KZ-10/16/24/40/80.

Point • 2-port adaptor cannot to be connected to VT3-W4□.


• The 2-port adapter cannot be connected to PORT3 of VT3.

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-67


1-7 About the 2-port Adapter MT-T2/T3

1  Connecting by MT-T3
MT-T3 is used to connect VT3 (excluding VT3-W4□) or programming tools to KZ-A500.
CONNECTING TO THE KV & KZ SERIES

PORT2
OP-26484(5m)
OP-35403(1m)

PORT1 VT3
ACCESS 1+2
MT-T3

1ONLY
(excluding VT3-W4□)
PLC EXT.
POWER

PORTA

PLC connector cable*1 PORTA


(PLC)

MITSUBISHI
PORT1
BAUO (MT)
RATE

A1 PORT2

(cable provided with unit 0.6 m) 2

24V 0V
(TOOL)

ELECTRIC
CORPORATION
PORT2 Dedicated connector cable*2 GX-Developer
KZ-A500 Ladder Builder
2-port adapter for KZ-A
MT-T3

MITSUBISHI
KZ-C2O+ ELECTRIC
MITSUBISHI ELECTRIC CORPORATION
CORPORATION GPP
AC30R4

PORT2
OP-26484(5m)
OP-35403(1m)

VT3
(excluding VT3-W4□)

*1 Connector cable OP-26487 can also be used. (An external power supply is needed for the MT-T3.)
*2 Old type OP number Current type OP number
Connected
OP
Machine OP-96368 - OP-26487
For PC98 OP-26482 or OP-26487 + OP-26485 OP-96369 - OP-26485
For DOS/V machine OP-26487 + OP-26486 OP-23085 - OP-26482
OP-23086 - OP-26486+OP-26487

Point • The 2-port adapter cannot be connected to PORT3 of VT3.


• The 2-port adaptor cannot be connected to VT3-W4□.

1-68 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -


1-7 About the 2-port Adapter MT-T2/T3

How to Use 1
1

CONNECTING TO THE KV & KZ SERIES


Connect the cable to each modular connector.

2 When using PORT2, set the PORT selector switch to "1+2". In other cases, set to "1ONLY".

Point Set the baud rate at "Communication Setting" in the VT3 unit system mode. The VT3 does not
operate in the following states when MT-T2 is used.
• When the time chart monitor is being used by the ladder support software
• While the program is being transferred between the KZ and ladder support software
“5-4 PLC Communication Conditions” in the VT3 Series Hardware Manual

3 Set the baud rate by the DIP switch on the top panel of the MT-T3.
The baud rates of PORTA [PLC] and PORT1 [MT] are set in common. The baudrate of PORT2 [TOOL] can be set individually.

1 4800bit/s
PORT A•1
2
3 9600bit/s
PORT 2
4

19200bit/s

38400bit/s

Troubleshooting

If the system does not function properly with the VT3/DT connected to the KZ seriesand MT-T2/T3, and power is
supplied, an error message is displayed on the VT3'sscreen. In the case of the DT, this can be confirmed by "Unit
Monitor" on DT BUILDERand "Error State" on the Web server.
For details on how to remedy error messages, refer to "Troubleshooting".

“Appendix-1 Error Troubleshooting and Removal” in the VT3 Series Hardware Manual
Providing a separate power supply or connecting a noise filter as follows will proveeffective as a noise
countermeasure.

VT3 series

1 4
Power Noise filter
supply
2 3
(FG must not be earthed.)
Recommended filter: OP-25841

- VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual - 1-69


1-7 About the 2-port Adapter MT-T2/T3

1 Specifications
CONNECTING TO THE KV & KZ SERIES

Model No. MT-T2 MT-T3


Power voltage 24 VDC+10%-20% 24 VDC+10%-10%
Rating
Power consumption 150 mA max. 250 mA max.
Indicator 2-color communications status LEDs (red: tool, green: MT(VT))
Withstand voltage 1500 VAC for 1 min (across external terminal and case)
Operating environment

Insulating resistance 5 M or more by 500 VDC megger (across power terminal and case)
Noise resistance 1500 Vp-p pulse width 1 sec (by common mode noise simulator) *1
Vibrating resistance 10 to 55 Hz peak-to-peak, 1.5 mm, for 2 hours each in X, Y and Z directions
Operating atmosphere Free from excessive dust/dirt and corrosive gases
Ambient operating
0 to 55°C
temperature
Operating surrounding
35 to 85% RH (condensation not allowed)
air humidity
Applicable PLCs KZ-10, 16, 24, 40, 80, 300, 350 KZ-A500
* The specification values vary according to the system configuration and wiring method.
*1 The power supplied from PORT2 [TOOL] on the MT-T3 is 5 V 400 mA or less.

1-70 - VT5, VT3 Series/Soft-VT/DT Series PLC Connection Manual -