Power Factor Regulator
www.itmikro.com
PFR140
120
80
60
Features
• Microprocessor based intelligent auto switching
control
• Automatic C/K and rated step adjustment
• Automatic CT polarity correction
• Display of power factor, current & total harmonic
distortion of current
• Programmable sensitivity
• Last step can be used as alarm/fan output
• Under/over voltage alarm, under/over compensate
alarm & high harmonic distortion alarm
• User-friendly setting
• Complies with IEC 61000-6-2 standard
Technical Data
ENVIRONMENTAL CONDITIONS
RATINGS AUXILIARY POWER SUPPLY CURRENT INPUT Temperature : -10°C to 55°C
Current Supply voltage : 220~240 V AC / Rated current ( In ) :5A Humidity : 5% to 95%,
380~415 V AC Operating Limits : 0.05 A to 6.5 A non-condensing
Operating Limits : -15% + 10% Rated Frequency : 50 Hz or 60 Hz
Consumption : 10 VA max
Rated frequency : 50 Hz or 60 Hz MECHANICAL
m
CONTROL RANGE Mounting : Panel mounting
PFR 140 / 120 / 80 / 60
Power factor setting : 0.8 Ind - 0.8 Cap Dimension (mm) : 144(w) x 144(h) x 90(d)
co
OUTPUT CONTACTS C/K setting : 0.03 - 1.20 / Automatic Enclosure protection : IP54 at the panel
Numbers of outputs : 6 / 8 / 12 / 14 Switching sensitivity : 5 - 600 s/step Approximate weight : 1.2 kg
(PFR60/PFR80 Reconnection time for
u.
/PFR120/PFR140 ) same step : 5 - 240 s
Rated voltage : 250 V AC THD threshold : 0.20 - 3.00 ( 20% -
ia
Contact rating :5 A 300% ) / OFF
Expected electrical life : 100,000 operations Switching Program : Automatic / Automatic
ha
at rated current Rotate / 4-quadrant /
Expected mechanical life : 5 x 106 operations Manual
en
Max current for the Rated step coefficient : 0 / 1 / 2 / 3 / 4 / 5 / 6 /
common terminals : 12 A continuous 8 / 12 / 16
( Automatic if C/K set
di
to Auto )
Co
Power Factor Regulator
www.itmikro.com
Typical Application Diagram
Case Dimensions Ordering Information
MODEL DESCRIPTION
PFR60 - 415 - 50 6 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR80 - 415 - 50 8 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR120 - 415 - 50 12 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR140 - 415 - 50 14 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR60 - 220 - 50 6 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR80 - 220 - 50 8 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR120 - 220 - 50 12 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR140 - 220 - 50 14 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
m
PFR60 - 415 - 60 6 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR 140 / 120 / 80 / 60
co
PFR80 - 415 - 60 8 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
u.
PFR120 - 415 - 60 12 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
ia
PFR140 - 415 - 60 14 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR60 - 220 - 60 6 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
ha
PFR80 - 220 - 60 8 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
en
PFR120 - 220 - 60 12 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
di
PFR140 - 220 - 60 14 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
Co