Pulsar - Extreme - 1500 - Va (2022 - 07 - 21 08 - 32 - 57 UTC)
Pulsar - Extreme - 1500 - Va (2022 - 07 - 21 08 - 32 - 57 UTC)
Pulsar EXtreme
1500/2000 VA
2500/3000 VA
French
German
Italian
Spanish
Netherlands
5103321100/AA - Page 1
Introduction
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Pulsar EXtreme range has been designed with the utmost care. We recommend that you take the time
to read this manual to take full advantage of the many features of your UPS.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have
made Pulsar EXtreme a reference in environmental protection include:
◗ the eco-design approach used in product development;
◗ production in an ISO 14001 certified factory;
◗ recycling of Pulsar EXtreme at the end of its service life.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar
EXtreme range, we invite you to visit our web site at Erreur! Signet non défini. or contact your MGE UPS
SYSTEMS representative.
Page 2 - 5103321100/AA
Safety
Safety rules
Safety of persons
A UPS has its own internal power source (the battery). Consequently, the power outlets may be energized
even if the UPS is disconnected from the AC-power source.
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified
service personnel.
The UPS must be properly earthed. If it is connected to the AC-power source via a wall outlet,
measurements are required to ensure that the total leakage current of the UPS and the protected
equipment does not exceed 3.5 mA. If the total leakage current exceeds this value, the INSTALL
version is mandatory and the earth wire must be connected to the input terminal block.
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents,
the directives listed below must be observed.
◗ Never operate the UPS if the ambient temperature and relative humidity are higher than the levels
specified in the documentation.
◗ Never burn the battery (risk of explosion).
◗ Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
◗ Comply with all applicable regulations for the disposal of the battery.
Product safety
UPSs connected to the AC-power source via a wall outlet must remain in the immediate vicinity of the outlet.
The outlet must be easily accessible. For UPSs connected to the AC-power source via a terminal block,
a protection circuit breaker must be installed upstream and be easily accessible.
The UPS can be disconnected from the AC-power source by removing the power cord or the UPS
power cable.
◗ Never install the UPS near liquids or in an excessively damp environment.
◗ Never let a liquid or foreign body penetrate inside the UPS.
◗ Never block the ventilation grates on the front or back of the UPS.
◗ Never expose the UPS to direct sunlight or a source of heat.
Special precautions
The UPS connection instructions contained in this manual must be followed in the indicated order.
Check that the indications on the rating plate correspond to your AC-power system and to the actual
electrical consumption of all the equipment to be connected to the UPS.
If the UPS is positioned flat, check that not more than five modules are stacked on top of each other.
If the UPS must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -40° C to +50° C.
If the UPS remains de-energized for a long period, we recommend that you energize the UPS
for a period of 24 hours, at least once every month.
This charges the battery, thus avoiding possible irreversible damage.
5103321100/AA - Page 3
Foreword
Pictograms
Visual indication.
Action.
Audio indication.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
Page 4 - 5103321100/AA
Contents
1. Presentation
1.1 Pulsar EXtreme range ................................................................................................................. 7
1.2 Connection modules .................................................................................................................. 8
Fault tolerant ................................................................................................................................... 8
Hot swap ......................................................................................................................................... 8
Install ............................................................................................................................................... 8
1.3 Back ............................................................................................................................................. 9
1.4 Control panel ............................................................................................................................... 10
2. Installation
2.1 Unpacking and checks ............................................................................................................... 11
"Tower" model ............................................................................................................................... 11
"Rack" model ................................................................................................................................ 11
2.2 Installation (rack version) .......................................................................................................... 13
2.3 Connection to the RS 232 communications port (optional) ................................................... 14
2.4 Installation of the communications-card option ...................................................................... 14
2.5 Securing and connecting the connection modules ................................................................. 15
Securing the connection modules ................................................................................................. 15
Fault tolerant ................................................................................................................................. 15
Hot swap ....................................................................................................................................... 16
Install ............................................................................................................................................. 17
3. Operation
3.1 Operating mode .......................................................................................................................... 18
ON-LINE mode ............................................................................................................................. 18
ECO mode .................................................................................................................................... 18
3.2 Start-up ........................................................................................................................................ 19
3.3 Bargraph indications .................................................................................................................. 19
5103321100/AA - Page 5
Contents
4. Maintenance
4.1 Troubleshooting .......................................................................................................................... 24
4.2 UPS replacement ........................................................................................................................ 26
Fault-tolerant connection module .................................................................................................. 26
Hot-swap and Install connection modules .................................................................................... 26
5. Environment ..................................................................................................................................... 28
6. Appendices
6.1 Glossary ....................................................................................................................................... 29
6.2 Index ............................................................................................................................................. 31
Page 6 - 5103321100/AA
1. Presentation
1.1 Pulsar EXtreme range
Tower model
Dimensions in mm
(H x W x D)
EXtreme 1500 to 3000 443 x 173 x 465
Weight in kg
Rack model
Dimensions in mm
(H x W x D)
EXtreme 1500 to 3000 177 (4U) x 483 x 462
Weight in kg
5103321100/AA - Page 7
1. Presentation
1.2 Connection modules
Fault tolerant
1 socket for connection to AC-power source.
1
4 input terminal block with cable clamp.
Hot swap
5
2
Install
Page 8 - 5103321100/AA
1. Presentation
1.3 Back
7 rating plate.
9
8
10 connector for connection modules.
9
11 RS232 communications port.
10
11
5103321100/AA - Page 9
1. Presentation
1.4 Control panel
24 ON/OFF.
Page 10 - 5103321100/AA
2. Installation
2.1 Unpacking and checks
Tower model
29
26
25 27 28
28 documentation.
5103321100/AA - Page 11
2. Installation
Rack model
30
29
26
25 27 28
28 documentation.
Page 12 - 5103321100/AA
2. Installation
2.2 Installation (rack version)
Rack mounting diagram with rails.
3
3
4
3
2
The rails and the necessary mounting hardware are supplied with the UPS in the package.
5103321100/AA - Page 13
2. Installation
2.3 Connection to the RS 232 communications port (optional)
1. Connect the RS 232 communications cable 25 to the serial
port on the computer.
The UPS can now communicate with all MGE UPS SYSTEMS
supervision, set-up or safety software.
RTS
Page 14 - 5103321100/AA
2. Installation
2.5 Securing and connecting the connection modules
Securing the connection modules
31
31
Fault tolerant
Before carrying out any connections, check that the battery circuit breaker 8 is OFF and that the
electrical power cord to the AC-power source is disconnected.
Connection of equipment:
5103321100/AA - Page 15
2. Installation
Hot swap
Before carrying out any connections, check that the battery circuit breaker 8 is OFF
and that the electrical power cord to the AC-power source is disconnected.
33
Always connect the earthing wire first.
Page 16 - 5103321100/AA
2. Installation
Install
This type of connection must be carried out by qualified electrical personnel.
Before carrying out any connections, check that the battery circuit breaker 8 is OFF
and that the upstream protection devices (AC distribution system) are open (OFF).
Earthing wires
5
4
5103321100/AA - Page 17
3. Operation
3.1 Operating mode
ON-LINE mode
This is the standard operating mode, set by default in the factory.
It makes use of electronic double conversion of the input power.
23
ECO mode
The main advantage of this mode is that it reduces the consumption of electrical power. The protected
equipment is supplied directly by the AC-power source as long as it remains within the tolerances set
by the user.
ECO mode is selected and tolerance levels are set using the "UPS Driver" software 27 for UPS
personalization (see section 3.5).
The AC-power source is not within the set tolerances. The UPS
automatically shifts to ON-LINE mode. LED 22 is ON.
22
23
Page 18 - 5103321100/AA
3. Operation
3.2 Start-up
The protected equipment connected to the UPS can be energized, whether AC input power is available
or not.
Prior to initial start-up, check the UPS voltage settings. If the protected equipment voltage is other
than 230 V / 50 Hz, the UPS settings must be modified using the "UPS Driver" software 27
(see section 3.5).
If LEDs 21 , 22 and 23 do not go ON or if LEDs 14 , 15 , 16 or 17 flash, there is a fault (see section 4.1).
15 UPS fault.
16 Battery fault.
23
Sleep mode
This operating mode may be personalized using the "UPS Driver" software (see section 3.5).
It saves battery power when no equipment is connected to the UPS.
The UPS automatically restarts when the AC-power source returns to within tolerances.
Page 20 - 5103321100/AA
3. Operation
3.5 Personalization
Function
Personalization parameters can be set and modified using the "UPS Driver" software installed on a computer
that is connected to the UPS (see section 2.3 Connection to the RS 232 communications port).
Check that the RS 232 cable 25 is correctly connected and that the battery circuit breaker 8
is closed.
Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing
a number of tabs, each presenting a set of parameters.
5103321100/AA - Page 21
3. Operation
"Battery" tab
Personalizable function Default setting Options
Once a week
"Battery test" intervals Every day Once a month
No test
"Low-battery shutdown warning" threshold 20% remaining battery 40% remaining battery
backup time backup time
Charger Standard CLA (2, 4 or 8 hours)
"Output" tab
Rated AC-power source voltage (see figure 1) 230 V 200 V-208 V-220 V-240 V
Rated AC-power source frequency 50 Hz 60 Hz
Tolerance for AC-power source frequency (fig. 2) ± 5% ± 1% to ± 10% , in 1% steps
Frequency-regulation rate Standard Redundancy (see section 6.1)
Seuil d'alarme surcharge utilisation 100% 0 to 100%, in 10% steps
Redémarrage onduleur après court-circuit Disabled Enabled (click to add check)
"By-pass" tab
Authorized voltage range for transfer to bypass 187 V to 265 V (for 187 V to 265 V,
(see figure 3) if fault or overload 230 V rated voltage) in 1V steps
Authorized frequency range for transfer to bypass ± 10% ± 1% to ± 10%, in 1% steps
(see figure 2) if fault or overload
Transfer to bypass if overload Enabled Disabled (click to remove check)
Transfer to bypass following a fault, whatever Disabled Enabled (click to add check)
the conditions on the AC-power source
The value selected for the rated UPS voltage impacts on the power available at UPS output
(see the diagram below).
Mini Maxi
Voltage in V
Fig. 1 Fig. 2
Page 22 - 5103321100/AA
3. Operation
"ECO mode" tab
ECO mode is not possible unless it has first been authorized using the "UPS Driver" software
Voltage in V
Minimum authorized voltage Rated Maximum authorized voltage
for transfer to the bypas voltage for transfer to the bypass
Fig. 3
3.6 Shutdown
5103321100/AA - Page 23
4. Maintenance
4.1 Troubleshooting
If any of LEDs 14 , 15 , 16 or 17 flash, there is a operating anomaly or an alarm.
The ambient temperature is higher than Install the UPS in a room where
40° C. the ambient temperature is not
LED 17 flashes. greater than 40° C.
The UPS is not designed to
operate more than eight hours
under these conditions.
Page 24 - 5103321100/AA
4. Maintenance
A battery fault was detected during the Make sure that the battery
LED 16 flashes. battery test. circuit breaker(s) is closed.If that
is the case, call the after-sales
support department because the
battery is not OK
5103321100/AA - Page 25
4. Maintenance
4.2 UPS replacement
Fault-tolerant connection module
Before carrying out this operation, the supply of power to the connected equipment must be cut.
Disconnection:
1. Shut down the UPS by pressing button 24 (return to the OFF
position).
2. Open the battery circuit breaker(s) 8 .
24 3. Remove the two fixing screws 31 and the connection module
from the UPS.
Reconnection:
1. Insert the connection module in the connector 10 and secure
using the two screws 31 .
8 2. Close the battery circuit breaker(s) 8 .
31
Page 26 - 5103321100/AA
4. Maintenance
Hot-swap and Install connection modules
Before turning the switch, Disconnection:
see the manual
1. Turn the manual bypass switch 3 from the NORMAL
to the intermediate position.
NORMAL BY-PASS 2. Check that LED 21 is ON before continuing to the BYPASS
position.
Reconnection:
1. Insert the connection module in the connector 10 and secure
using the two screws 31 .
3. Close the battery circuit breaker(s) 8 .
24
Check that UPS personalization settings still
correspond to the equipment to be supplied
(see section 3.5).
MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable
regulations, all UPS products recovered at the end of their service life (contact your branch office).
Packing:
UPS packing materials must be recycled in compliance with all applicable regulations.
Warning:
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not
correctly recycled by specialized companies.
Page 28 - 5103321100/AA
6. Appendices
6.1 Glossary
Authorized voltage The range of voltage supplied by the AC-power source within which the UPS
range for operation in ECO can operate in ECO mode. In ECO mode, the equipment connected to the
in ECO mode UPS is supplied directly by the AC-power source, via the automatic bypass.
Authorized voltage Upper and lower voltage thresholds within which the UPS can operate
range for transfer to on theautomatic bypass in the event of a UPS fault or overload.
bypass if fault or overload
Automatic bypass Automatic switch controlled by the UPS, used to connect the equipment
directly to the AC-power source.
Automatic start following When AC input power returns following shutdown at the end of the battery
return of AC input power backup time, UPS automatic start can be enabled or disabled.
Backup time Time that the connected equipment can operate on battery power.
Bargraph Device on the front panel indicating the percent remaining backup time
or the percent load.
Battery test Internal UPS test on battery status.
CLA (Long backup- Module incorporating a charger for long backup times. The charger is powerful
time charger) enough to charge battery extension modules offering very long backup times.
Cold start See "Start on battery power".
Connection module Unit grouping the receptacles for connection to the AC-power source
and the equipment.
Dialog box A window in a computer program displayed for selection by the user of various
options and parameter settings.
Double conversion The power supplied to the connected equipment is completely regenerated
by continuous double conversion, i.e. the AC power from the AC-power source
is rectified (AC - DC), then converted back (DC - AC) to AC power.
ECO mode Operating mode by which the equipment is supplied directly by the AC-power
source if it is within the tolerances defined by the user. This mode reduces
the consumption of electrical power.
Equipment Devices or systems connected to the UPS output.
Fault tolerant Connection module (without manual bypass) offering receptacles
for connection to the AC-power source and the equipment.
Forced shutdown Ten-second interruption in the supply of power to the connected equipment
following a system shutdown, even if AC input power returns during
the interruption period.
5103321100/AA - Page 29
6. Appendices
Frequency-regulation rate The rate at which the UPS frequency is synchronized with that
of the AC-power source. Two possible cases:
1. The installation comprises a single UPS. The frequency-regulation rate
is set to "Standard".
2. The installation comprises two UPSs connected in series. The AC-power
source supplies power to the first UPS which in turn supplies the second UPS.
The connected equipment is supplied by the second UPS.
The frequency regulation rate of the first UPS must be set to "Standard",
the frequency regulation rate of the second UPS must be set to "Redundancy".
Hot swap Connection module (with manual bypass) offering a socket for connection
to the AC-power source and outlets or a terminal block for connection
to the equipment.
Install Connection module (with manual bypass) offering terminal blocks
for connection to the AC-power source and the equipment.
Manual bypass Rotary switch controlled by the user, used to connect the equipment directly
to the AC-power source. Transfer of the load to the manual bypass enables
UPS maintenance or replacement, without interrupting the supply of power
to the connected equipment.
ON-LINE mode The normal UPS operating mode, by which the AC-power source supplies
the UPS, which in turn, following double conversion of the AC power,
supplies the connected equipment.
Percent load Ratio between the power drawn by the connected equipment and the total
power that the UPS can supply.
Personalization A number of UPS functions can be modified using the "UPS Driver" software
to better meet the user's needs.
Redundancy See "Frequency-regulation rate".
Sleep mode This function shuts down the UPS when it operates on battery power
and no load is detected on the UPS output.
Start on battery power This function makes it possible to energize the connected equipment even
when AC input power is not available (operation exclusively on battery power).
Tolerance for AC-power The range of frequency supplied by the AC-power source within which
source frequency the UPS can operate in ON-LINE mode (double conversion).
UPS Uninterruptible Power Supply.
UPS ON / OFF It is possible to enable or disable use of UPS ON / OFF controls
via software by the computer-system protection software.
Page 30 - 5103321100/AA
6. Appendices
6.2 Index
A L
AC power LEDs
Failure ........................................................... 20 Lamp test ....................................................... 10
Frequency tolerance ..................................... 22
Rated frequency ............................................ 22 M
Rated voltage ................................................ 22 Mode
Return ............................................................ 20 ECO mode .......................................... 10-18-23
B O
Bargraph .............................................................. 19 Overload .................................................... 10-22-24
Battery
Battery test .................................................... 22 P
End of backup time ....................................... 20
Personalization ................................................... 21
Fault ......................................................... 10-19
Battery .......................................................... 22
Low-battery shutdown warning ..................... 20
ECO mode .................................................... 23
Recycling ....................................................... 28
ON / OFF conditions ..................................... 21
Transfer to battery power .............................. 20
Output ........................................................... 22
Buzzer ......................................................... 4-10-20
By-pass
Automatic bypass ..................................... 18-25 R
Manual bypass ......................................... 10-26 Rack .................................................................. 7-13
C S
Communication .................................................... 14 Safety .................................................................... 3
Connection Shutdown
Communications card ................................... 14 Forced shutdown ........................................... 21
Connection modules ................................ 16-17 UPS ON / OFF via software .......................... 21
RS 232 communications port ........................ 14 UPS shutdown ......................................... 10-23
Sleep mode ................................................... 20-21
Software
E
UPS Driver .......................................... 11-12-21
ECO mode ................................................ 10-18-23
Start-up
Automatic start .............................................. 21
F
Fault (UPS) T
Load .............................................................. 10
Temperature
Transfer to automatic bypass ........................ 25
Excessive ambient temp .................... 10-19-24
Fault tolerant ............................................... 8-15-26
U
H
UPS Driver ................................................ 11-12-21
Hot swap ..................................................... 8-16-27
I
Install ........................................................... 8-17-27
5103321100/AA - Page 31
Publication : MGE UPS SYSTEMS, 09/99.