0% found this document useful (0 votes)
3 views47 pages

Power Transformer - Rev 6.1

Uploaded by

Venkatesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3 views47 pages

Power Transformer - Rev 6.1

Uploaded by

Venkatesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 47

POWER TRANSFORMER

May 2022

Engineering Department
WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

Regd. Office: VidyutBhawan, Block – DJ, Sector-II, Bidhannagar, Kolkata – 700091.


CIN: U40101WB2007SGC113474; Website: www.wbsetcl.in

WBSETCL / TECH SPEC / Rev.-6.1 Page 1of 47 Power Transformer


TECHNICAL SPECIFICATION FOR
POWER TRANSFORMER

1. SCOPE:

This specification covers design, engineering, manufacture &assembly of 3-Phase,


400/220/33KV, 220/132/33 KV, 220/33 KV, 132/33 KV and 132/66 KVPower/Auto
Transformer complete with all fittings and accessories required for efficient and trouble free
operations of the transformer, testing at manufacturer’s works and customer’s premises,
supply, loading at factory, delivery at site, unloading, handling, dragging for proper storage at
site on the plinth of transformer if the same is ready at respective site or at suitable location as
per direction of site-in-charge ofcustomer.

2. GENERALREQUIREMENT:

The Transformer shall be multi-winding, oil immersed complying as per Specific Technical
parameters and suitable for outdoor installation.

Rated Capacity and Voltage of the Transformers shall be guided by the respective Tender
Documents. The specificationcovers for the following transformers as per present requirement
of thecompany:

a) 400/220/33KV and 220/132/33 KV Auto Transformer with loaded 33 KV tertiarywinding.

b) 220/33KV and 132/33 KV PowerTransformer

c) 132/66 KV Auto Transformer with unloaded stabilizing winding having two terminals taken
out.

Type Test: The transformers should be Type Tested as per IS 2026 or IEC 60076 in
conjunction with their relevant Part. Necessary test documents shall have to be submitted
with thebid.

Dynamic Effect of ShortCircuit

For400kVClassAutotransformer:
Bidder should have successfully carried out Dynamic Short Circuit test on offered t
rans former or similar transformer (as defined in IS 2026 part-5) as on the date of NIT and
shall enclose the relevant Test Report and certificate along with bid. Otherwise their bid shall
be considered technically non responsive .This shall be applicable for 400kV class Auto
transformerofMVAratingsimilartoorhigherthanthetenderedtransformer.

For 220 kV Class Transformer:


Bidders should have successfully carried out Dynamic Short Circuit Test offered t
rans former or similar transformer (as defined in IS 2026 part-5) as on the date of NIT and
shall enclose the relevant Test Report and Certificatealong with bid. Otherwise theirbid shall
be considered technically non- responsive. This shall be applicable for 220 kV class
transformerofMVAratingsimilartoorhigherthanthetenderedtransformer.

WBSETCL / TECH SPEC / Rev.-6.1 Page 2of 47 Power Transformer


For 132 kV Class Transformer:
Bidders should have successfully carried out Dynamic Short Circuit Test offered t
rans former or similar transformer (as defined in IS 2026 part-5) as on the date of NIT and
shall enclose the relevant Test Report and Certificate along with bid. Otherwise their bid shall
be considered technically non- responsive. This shall be applicable for 132kV class
TransformerofMVAratingsimilartoorhigherthanthetenderedtransformer.

Sweep Frequency Response Analysis (SFRA/FRA) shall have to be carried out as special
test for each transformer at manufacturer’s premises in presence of representative of
WBSETCL free of cost. Test result shall have to be handed over to WBSETCL. Before
commissioning of the Transformer at site, the same SFRA/FRA test will have to be carried by
the test engineers of the manufacturer in presenceof customer’s representative for comparing
the results to take the decisions of the commissioning. The Testing Engineers &FRA kit for
such pre-commissioning site testing shall have to be arranged by the manufacturer free ofcost.

Tests at Manufacturer’s works: The Transformers shall be subjected to type &routinetest,


special tests and no load & load loss measurement as per relevant IS / IEC asmentioned in
the Clause “TEST AT FACTORY AND TESTCERTIFICATES”.

Guaranteed Technical Particulars: The Bidder shall furnish all guaranteed technical
particulars as called for in this specification along with each copy of Bid submission. Bids
lacking information in this respect may not beconsidered.

Core Materials: Core materials should be directly procured from either the manufacturer or
their accredited reputed marketing organization and not through any agencies.

3. STANDARD:

The Power Transformer covered under this specification shall comply with the requirements
ofthe latest edition of theStandards.

i) IS:2026 (Part ItoIV) - Specification for PowerTransformer


ii) IS:2099&IS:3347 - Bushing for alternating voltage above 1000volt
iii) IS:6600 - Guide for loading of oil immersedtransformer
iv) IS:335 - Specification for transformeroil
v) CBIP - Manual ontransformer.
vi) IEC-60076 - PowerTransformer
vii) IEC-60214 - On Load Tapchanger.
viii) IEC-354 - Loading Guide for Oil immersedTransformer
ix) IEC-551 - Tr. SoundLevel.

4. DEVIATION:

Normally the offer should be as per Technical Specification without any deviation. But any
deviation felt necessary to improve performance, efficiency and utility of equipment must be
mentioned in the 'Deviation Schedule' with reasons, duly supported by documentary evidences
and advantages of such Deviation shall be mentioned. Such deviations suggested may or may
not be accepted. But deviations not mentioned in Deviation Schedule will not be considered.

WBSETCL / TECH SPEC / Rev.-6.1 Page 3of 47 Power Transformer


5. GENERALDESIGN:

a) The Transformer and accessories shall be designed tofacilitate easy inspection, cleaning
and repairs. All fittings and accessories shall be designed to ensure satisfactory
operation underworst conditions of load and voltage as may be met under working
conditions in thesystem.

b) All materials used shall be of best quality and of the class most suitable for working
under the conditions specified. It shall withstand the variations of temperature and
atmospheric conditions without undue stressing etc. i.e. not affecting the
workability/durability of the various parts of thetransformer.

c) All outdoor fittings and accessories, including bushings insulators with their mounting, shall
be so designed as to avoid pockets in which water can collect. All electrical connections
shall be of ample cross sections for carrying the specified currents continuously without
undue heating. All fixing bolts and screws shall be reliable under worst conditions of
operations.

d) Transformers shall be suitable for continuous operation with a frequency of 50 Hz and


variation of± 3% without exceeding specified temperaturerise.

e) Transformer with tertiary winding and all its accessoriesincluding Bushing CTs etc. shall
be design to withstand without injury, the mechanical and thermal effects and any external
short circuit to earth and of short circuits at the terminals of any winding. Transformer
shall be capable of withstanding thermal and mechanical stresses caused by symmetrical or
asymmetrical faults on anywinding.

f) The short circuit level of the HV & IV System to which the transformers will be
connected is asfollows:
• 400kV system - 63kA for 1 sec (sym, rms, 3 phase fault)
• 220kV system - 50 kA for 1 sec / 40 kA for 3 sec (sym, rms, 3 phasefault)
• 132kV system - 40 kA for 1 sec / 31.5 kA for 3 sec (sym, rms, 3 phasefault)
• 66kV system - 31.5 kA for 3 sec (sym, rms, 3 phasefault)
• 33kV & 11kV system - 25 kA for 3 sec (sym, rms, 3 phasefault)

g) For parallel operation with other transformers, necessary provision is to be kept in


transformerRTCC panel for tap changing operation in any of Master/Follower/Independent
mode.

h) Clearances of line terminals inAir:

The clearance of HV, IV & LV terminal shall be maintained as specified below :

Highest System voltage of Phase to Phase clearance Phase to earth clearance


equipment (KV rms) (mm) (mm)
420 4000 3500
245 2000 1800
145 1220 1050
72.5 700 660
36 350 320
52 530 480

i) Transformer shall be designed for full lightning impulse voltage as well as chopped and
reducedchoppedimpulsevoltageasperrelevantclausesofIS:2026(Pt.-III)/IEC:60076-3

WBSETCL / TECH SPEC / Rev.-6.1 Page 4of 47 Power Transformer


j) VIBRATION AND NOISE: Transformer when energizes at normal voltageand frequency
with fans & pumps running, shall have minimum hum. Under standard operating condition
the abnormal noise shall not exceed the value specified at latest NEMA standard
publicationTR-1.
k) Over loading of transformer shall be guided by latestIS-6600.
l) Only type tested accessories shall be supplied. All accessories mounted out door shall
have contact enclosure tested with IP-55 as per IS: 13947 in order to avoid mal operation
during rain orcondensation.
m) Insulation resistance of core-clamp link shall be more than 1Giga ohm (independent of
temperature variation) and the value can be verified atsite.
n) If not specified, the location of conservator may be fixed on left side of the transformer
when viewed from HVside.

6. TERTIARYWINDINGS:

The 400/220/33KV and 220/132/33 KV transformers shall be provided with delta connected
loaded tertiary windings of 33 KV voltage class and shall be suitably rated to withstand the
stresses due to short circuit in the system. Transformer with 3-windings shall be of loaded
tertiary design.

This stabilizing winding shall be capable of carrying continuously the rated load as specified
under S.T.P. The design of the stabilizing winding shall be such that to take care of the effect
of transfer surge. Tertiary winding shall be designed to withstand mechanical and thermal
stresses due to dead short circuit on itsterminals.

7. TEMPERATURERISE:

Each Transformer shall be capable of operating continuously at its normal rating without
exceeding temperature rise and hot spot limits.

Type of Maximum Maximum Maximum Maximum Maximum


Cooling Ambient Top Oil Winding/ Core Winding permissible value of
Temp. Temp. Temp Rise Temp. Avg. Temp. of
Rise Winding after 3 sec
of short ckt. upto
160 MVA
ONAN 50oC 50oC 55oC 105oC 250oC
ONAF 50oC 50oC 55oC 105oC 250oC
OFAF 50oC 50oC 55oC 105oC 250oC

WBSETCL / TECH SPEC / Rev.-6.1 Page 5of 47 Power Transformer


8. THERMAL ABILITY TO WITHSTAND SHORTCIRCUIT:

a) Thermal ability to withstand short circuit shall be demonstrated by calculation and


shallbefurnishedalongwiththedrawingafterplacementofL.O.A.
b) Designed time period for Short circuit withstand and fault current will be taken as
per General Technical Specification. The maximum permissible value of the highest
average temp of winding after withstandingthe above stipulated Short Circuit shall not
o
exceed 250 C and the submitted calculations shall be as per Cl.No. 9.1 of IS:
2026(Part-I)

9. DETAILED TRANSFORMER PARTICULARS. TANK AND TANKCOVER:

a) The tank and cover shall be fabricated from low- carbon mild steel plate of adequate
size and suitable for welded construction. The tank so welded shall be reinforced by
stiffener of structural steel for general rigidity. Each tank cover shall be of adequate
strength and shall not distort whenlifted.
b) The tank shall be designed to have sufficient strength to withstand without
distortion-
(i) Under full vacuum at an internal pressure. of 3.33KN/sq.mm. absolute (25 torr) for
one hour and permanent deflection of flat plate after the vacuum has been
releasedshall notexceedthevaluesspecifiedbelow:

Horizontal Length of flat plate(in Permanent deflection ( in mm.)


Up to and including 750 5.0
751 to 1250 6.5
1251 to 1750 8.0
1751 to 2000 9.5
2001 to 2250 11.0
2251 to 2500 12.5
2501 to 3000 16.0
Above 3000 19.0

(ii) Transformer tank of each size, its radiator, conservator vessel and other fittings
together or separately shall be subjected to a pressure corresponding to twice the
normal head of oil or to the normal pressure plus 35 KN/m2 whichever is lower
measured at the base of the tank and maintained for one hour. The permanent
deflection of flat plates after the excess pressure has been released shall not exceed
the figures specified under vacuum test aboveand
(iii) The tank shall be designed to have sufficient strength to withstand mechanical shock
duringtransport.
c) The internal and external surface including structural steel work and oil filled
chambers are to be painted after removing all rust and scale of foreign adhering matter
or grease by sand blasting or other approved method. All steel surfaces in contact
with insulating oil shall be painted with two coats of heat resistant oil insoluble
insulatingpaint.
d) All steel surface exposed to weather shall be given a primary coat of zinc chromate
and shall be applied immediately after cleaning. The second coat shall be of an
oil and weather resisting nature and of shade or colour easily distinguishable from
the primary. The final coat shall be of epoxy paint of minimum thickness of 80 microns
and weather resisting non-fading paint of shade No. 631 ofIS:5.

WBSETCL / TECH SPEC / Rev.-6.1 Page 6of 47 Power Transformer


e) All paints shall be carefully selected to withstand heat and weather. The paint shall
notscaleofforcrinkleorberemovedbyabrasionduetonormalhandling.
f) The tank construction of Power Transformer up to 100 MVA rating shall be of
Conventional type Top Cover or Bell Tank construction. The tank construction of
transformer having rating of more than 100 MVA irrespective of voltage classes and
no. of winding shall be of Bell Tank construction. Adequate number of inspection
cover shall be provided to give easy access to the bushing or other parts as may
be necessary. To make joints oil tight, nitrile rubber gaskets shall be cut to size and
shape to avoid joints on gaskets as far as practicable. It shall be fitted with pockets
for thermometer and for the bulbs of oil and winding temperature indicators. The
thermometer pockets shall be fitted sufficiently above on the surface of the top cover
of main tank with a captive screwed top to prevent ingress of water. The pockets
shall be located in position of maximum temperature and it shall be possible to
remove bulb without lowering the oil in thetank.
g) Bi-directional flanged rollers for moving the transformer on rail gauge (1676 mm) shall
be provided. The direction of the roller through 90o (degrees) can be changed by
jacking up the assembly. Bi-directional rollers can be locked in required direction
by bolting the roller mounting pad welded on the base of the tank and bi-directional
flanged rollers bracket with bolts. The tank shall be provided with all fittings and
accessories.
h) Lifting lugs shall be provided on all parts of transformer requiring independent
handling during assembly or dismantling. In addition, the transformer shall be provided
with lifting lugs and bosses properly secured to the side of the tank for lifting
complete transformer assembly filled with oil either by crane or by pulley. Pulling lugs
shallalsobeprovidedtofacilitatemovementoftransformerhorizontally.
i) Thetransformertankshallbe equippedwiththefollowingvalvesandplugswithstandard screw
connection forpiping:

1) Drain valve at thebottom


2) Filter valve attop
3) Filter valve atbottom
4) Sampling valve attop
5) Sampling valve atbottom
6) Radiatorshutoffvalveattopandbottom
7) Buchholzrelayshutoffvalveatbothendsoftherelay
8) Air release plugs ontank.
9) One no. oil inletvalve

Any other valves & plugs other than those mentioned above, are also to be
provided as perrequirement.

j) ForThreewindingTransformer6no.thermometerpocketshouldbeprovidedforWTI&2 no. for


OTI. Amongst 6 no. pocket for WTI, three (3) will be used for direct connection with
the WTI in MK of Transformer. Balance three no. (3) shall be provided with PT 100
sensor and Current Converter Unit (CCU) at MK for WTI repeater at the RTCC panel to
be installed in Control Room. Similarly amongst Two (2) no. pocket for OTI, one will be
used for direct connection with OTI in MK of Transformer. Balance one no. shall be
provided with PT 100 sensor and Current Converter Unit (CCU) at MK for OTI
repeater at the RTCC panel to be installed in ControlRoom.

k) ForTwowindingTransformer4no.thermometerpocketshouldbeprovidedforWTI&
2 no. for OTI. Amongst 4 no. pocket for WTI, Two (2) will be used for direct
connection with the WTI in MK of Transformer. Balance Two (2) shall beprovided

WBSETCL / TECH SPEC / Rev.-6.1 Page 7of 47 Power Transformer


with PT 100 sensor and Current Converter Unit (CCU) at MK for WTI repeater at the
RTCC panel to be installed in Control Room. Similarly amongst Two (2) no. pocket for
OTI, one (1) will be used for direct connection with OTI in MK of Transformer. Balance
one no. (1) shall be provided with PT 100 sensor and Current Converter Unit (CCU) at
MK for OTI repeater at the RTCC panel to be installed in ControlRoom..

l) Design shall be such that Tank cover can be lifted independently without lifting active
part of core, windingetc.

m) Astepladdershallbeprovidedwitheachtransformertostepintothetopofthetank.

10. CORE:

The magnetic circuit shall be core type. Each limb shall be joined with top and bottom
yokes. The laminations shall be made from high grade non-ageing cold rolled grain
oriented silicon alloy of HI -B or its equivalent grade steel. The insulation of lamination
shall be coated with oxide/silicate/phosphate coating or any coating inert to the action of
hottransformeroil.Thecoreshouldbebottommounted.
The core shall be of stepped cross-section. The yokes shall be clamped by means of end
frames and yoke bolts and limbs shall be clamped by means of clamp plates. Sufficient
number of lifting lugs is to be provided on end frames so that core with windings can be
lifted whenrequired.
The design of magnetic circuit shall be such as to avoid static discharges, development of
short circuit paths within itself or to theearthed clamping structure and production of
fluxcomponentat rightanglestotheplaneoflaminationwhichmaycauselocalheating.
The insulation for the core to bolts and core to clamps shall be such as to withstand a test
voltage of 2 (two) KV rms at 50 Hz for one minute.
The maximum flux density in any part of the core and yoke at the rated MVA, voltage &
frequency shall be such that less than 10% continuous over voltage condition does not
exceed 1.9Tesla.
For consideration of over fluxing, the transformer shall be suitable for continuous
operation for values of over fluxing at (i) 110% (ii) one minute for 125% and (iii) 5 seconds
for 140% of ratedvoltage.
The prime core materials are only to be used. Bidder’s should furnish following document as
applicable as a proof towards use of prime Core material to be submitted before the
stageinspection:
(a) Invoice ofsupplier
(b) Mill’s testcertificate
(c) PackingList
(d) Bill oflading
(e) Bill of entry certificate byCustom.
(f) Description of material, electrical analysis, physical inspection, certificate for surface
defects,thicknessandwidthofthematerials.
(g) Place of cutting of corematerials

WBSETCL / TECH SPEC / Rev.-6.1 Page 8of 47 Power Transformer


11. WINDINGS:

The Material of winding conductor should be of electrolytic grade copper of minimum


99.90% purity and free from scales, spills, splits and other defects. The windings shall be
so designed that all coil assemblies of identical voltage ratings shall be interchangeable
and field repair is possible. The coils shall be supported between adjacent sections by
insulating spacers, and the barriers. Bracing and other insulation used in the assembly of
the windings shall be arranged to ensure a free circulation of the oil and to reduce hot
spots in the windings. The stacks of windings shall receive adequate shrinkage treatment
beforefinalassemblyandthesameshallbeassembledindustcontrolledchamber.
The insulation of the coils shall be such as to withstand the full electrical strength of the
windings. All materials used in the insulation and assembly of the windings shall be
insoluble, non-catalytic and chemically inactive in the hot transformer oil, and shall not
soften or otherwise be adversely affected under the operating conditions. The dielectric
strength of winding insulation shall confirm to values given in IS: 2026, as amended up to
date,orasperspecificTechnicalParameters.
All threaded connections shall be provided with locking facilities.
All leads from the windings to the terminal board and bushings shall be rigidity supported
to prevent injury from vibration. Guide tubes shall be used wherepracticable.
The windings shall be clamped securely in place so that they will not be displaced ordeformed
during short circuits. The assembled core and windings shall be vacuum dried and suitably
impregnated with insulating oil. The copper conductors used in the coil assembly shall be
best suited to the requirements and all permanent current carrying joints in the windings
and the leads shall be welded or brazed. Oil ducts shall be such as
willnotimpedethefreecirculationofoilthroughwindingsassembly.
The conductor shall be transposed at sufficient intervals in order to minimize eddy currents
andtoequalizethedistributionofcurrentsandtemperaturealongthewinding.

12. TAP CHANGINGMECHANISM:

The transformer shall give full load output on all taps. The transformer shall operate
withoutdangeronanyparticulartappingattheratedMVAwithinavoltagevariationof
±10% of the rated nominal voltage.
For 132/33KV, 132/66KV & 220/33 KV transformer ON LOAD TAP CHANGER with bi-
directional power flow shall be provided on the 132KV voltage winding & 220KV winding
respectively. The tapping range shall be +10% and –10% in 1.25% equal steps. Remote
TapChangerPanelshallalsobeprovidedtobeinstalledatourControlRoom.
For 132/66KV, 220/132/33 KV & 400/220/33KV Auto Transformer Tap coil with bi-
directional power flow shall be provided at 1 3 2 K V , 132 KV and 400 KV sides respectively
of the transformer. The tapping range shall be + 10% and –10% in 1.25% equal steps.
Transformers with constant ohmic impedance characteristics are preferred.
However,tomatchwithexistingsystemothertypemayhavetobesupplied.

Remote Tap Changer Panel shall also be provided to be installed at our Control Room. In Tap
Position Indicator sufficient terminals are to be provided for sending inputs for SCADA/SAS.

WBSETCL / TECH SPEC / Rev.-6.1 Page 9of 47 Power Transformer


13. ON LOAD TAPCHANGER:

This shall be designed suitable for remote control operation from RTCC Panel in the control
room to be supplied by the manufacturer in addition to being capable of local manual as
well as local electricaloperation.
The on-load tap changer shall include the following :-
a) An oil immersed tap selector and arcing switch or arc suppressing tap selector, provided
with reactor or resistor for reduction of make and break arcing voltages and short
circuits.
b) Motor drivenmechanism
c) Control and protectiondevices
d) Local/Remotetapchangerpositionindicator
e) Manual/Electrical operatingdevice.
The on-load tap changer shall be designed so that the contacts do not interruptarc within the
main tank of the transformer. The tap selector and arcing switch or arc suppressing tap
selector switch shall be located in one or more oil filled compartments. The compartment
shall be provided with Oil Surge relay. Those compartments shall be designed so as to
prevent the oil in tap selector compartment from mixing with the oil in the transformer
maintank.
An oil surge relay with trip float arrangement shall be provided for the OLTC unit.
The tap changer shall be capable of permitting parallel operation with either existing or
futuretransformersofthesametypeasMasterorFollower.
The manual operating device shall be so located on the transformer that it can be operated
by a man standing at the level of the transformer track. It shall be strong and robust in
construction.
The control scheme for the tap changer shall be provided for independent control of the tap
changers when the transformers are in independent service. In addition, provision shall
be made so that under parallel operation the tap changer will give alarm and visual
indication for becoming out of step. Visual indication during the operation of motor shall
also be incorporated. The tap change control must ensure step by step operation under all
operatingconditions.
Necessary interlock blocking independent control when the units are in parallel shall be
provided.
Under parallel operation, as may occur if the contactor controlling one tap changer sticks, the
arrangement must be such as to switch off supply to the motor so that an out of step
condition is limited to one tap difference between the units. Details of out of step protection
providedforthetapsshouldbefurnishedinthebid.
The contactors and associated gear for the tap change driving motors shall be housed in a
local kiosk mounted on the transformer. The motors shall be suitable for operationwith
3-phase 400 volts, 50 cycle external power supply.

RTCC Panel:
The supplier shall furnish, in addition to the equipment above, the following accessories
mounted in a separate Remote Tap Changer Control (RTCC) panel to be installed in each of
theWBSETCL’sControlRoomforremoteoperation.
a) Bay Control Unit (IED should be latest IEC61850 compliant having rear port)–
i) BCU shall be provided for data acquisition and control of Power Transformer.The

WBSETCL / TECH SPEC / Rev.-6.1 Page 10of 47 Power Transformer


BCU must be supplied from Relay manufacturer, already enlisted in WBSETCL
maker’s list as on date of NIT conforming all the requirements of latest IS/IEC and
the latest WBSETCL Control & relay specification . It is also to be taken into account
that the sub-station may be required to run without air-conditioningplant.
ii) Live demonstration of offered IED has to be arranged by the Bidder at the laboratory
of Central Testing Department of WBSETCL prior to approval, if felt necessary. The
bidder shall be required to make necessary arrangement without any extraprice.
iii) Communication Port: BCU shall be PRP compliant for SAS with latest 61850 protocol
including one front port for direct access with proprietary protocol. Supply of Red Box
is also to be considered for integration of the BCU to a non-PRP compliant network.
Allinputsandoutputsmustbeuserprogrammable.Thebaycontrolunitsshallbe
equipped with sufficient number of programmable I/O modules for interfacing with
the process inputs and outputs. Extension should be possible with additional I/Os via
fibre-optic communication and processbus.
iv) If it is designed with draw out type modules, it should take care of shorting all CT
inputs automatically while drawing out. The CT / VT ratio shall be field programmable
and Relay shall display the actual HV Voltage and current considering suitable
multiplying factors. The system shall be self sufficient and shall not require any
additional devices like parallel balancing moduleetc.
v) A graphic user interface (GUI) display shall be provided in each bay control unit. All
alarms related to the respective bay shall be displayed in the BCU through its LED’s
or in its GUI display as an alarmlist/scroll.
vi) The exact number of digital inputs shall be as per detailed engineering requirement.
Apart from that, BCU wise 20% spare I/Os shall be kept for WBSETCL use in future.
General note and signal lists for BCU are available in clause no. 45 and 46.
b) The RTCC Panel shall be provided with Raise and Lower Push Button Switch, Manual/
Automatic mode selection features, Master / Follower/ Independent/ Off mode selection
features for control ofOLTC.
c) Remote tap position indicator and other required devices. One chart showing the
voltage corresponding to tap position indicator shall be engraved on a metal sheet
and the same shall be fixed near the tap position indicator on the RTCC (Panel). In Tap
Position Indicator sufficient terminals are to be provided for sending inputs for
SCADA/SAS.
d) An indication lamp showing tap changing in a progress.
e) Name plate of each component& relays.
f) Winding & Oil temperature (0o –150oC) repeaters to be connected to winding and oil
Temperature meter housed in the main Transformer Marshalling Box at outdoor. In
addition to above necessary arrangements are to be made in RTCC panel for Hot spot
temperature indication and alarm by optical sensormethod.

Complete particulars of the tap changing gear and capacity of the motor shall be stated in
GTP. An under voltage relay shall be incorporated to monitor the AC control circuit voltage
of tap changer. Audible Alarm and annunciation shall be provided for failure of control
circuit supply, failure of 400 V AC supply to the motor. All the relays requisite for remote tap
changeoperationshallbeprovidedinRTCCpanel.TheOLTCshouldhavebeenTypeTested.

In addition to other requirements, following minimum indications/alarms shall be provided:


a. INCOMPLETE STEPalarm
b. OLTC motor overload protectionalarm
c. Supply to DM Motor failalarm
d. OLTC IN PROGRESSalarm
e. Local / Remote Selector switch positions in DMBox
f. OLTC upper/lower limits reachedalarm

WBSETCL / TECH SPEC / Rev.-6.1 Page 11of 47 Power Transformer


g. OLTC Tap position indications for transformerunits
h. Independent-combined-remote selector switch positions ofCMB
i. j. 415V, AC Mail SupplyFail.
k. 415V, AC Standby Supply Fail

In case of parallel operation or 1-Phase Transformer unit banks, OLTC out of step alarm shall
be generated for discrepancy in the tap positions.

14. INSULATING OIL:

Oil for first filling together with 5% extra oil shall be supplied with each transformer. The oil
shall comply in all respect with the provisions of the latest edition IS:335 (as amended up-to-
date) of specification for New Insulation oils for transformers and switchgears. Particular
attention shall be taken to deliver the oil free from moisture having uniform quality
throughout in non-returnable steel drums. The quantity of oil for first filling of each
transformershallbe statedintheoffer.

The oil should have the following characteristics:

SL.
NO. CHARACTERISTICS REQUIREMENT

1. Interfacial tension at 27oC (min) 0.04 N/m


2. Electrical strength (Breakdown voltage) 60 KV (rms) after treatment
3. o o
Resistivity at 90 C /27 C 35x1012 /1500x1012 Ohm-cm

4. Dielectric dissipation factor (tan delta at 90oC max.) 0.002

After site processing through filtration and before commissioning, the moisture content
shall be as follows :

a) Less than 72.5 KV : 25 ppm


b) 72.5 KV to 145 KV : 20 ppm
c) Above 145 KV : 15 ppm

15. CONSERVATORVESSEL:

a) The conservator is a vessel for oil preservation. The oil level in the conservator shall not
be below the level of theH.V. bushing caps unless the bushings are of oil sealed type
construction. The size of the conservator tank shall have adequate capacity with highest
and lowest visible level to meet the requirement of expansion of total cold oil volume in
the transformer and cooling equipment from minimum ambient temperature to100oC.
b) The conservator shall have one filter valves at suitable location, in addition to the valve
specified in the accessories for the main tank. The conservator with sump shall also have
asmalldrainvalveandsamplingcock,thelattersoarrangedasnottointerferewithoil

WBSETCL / TECH SPEC / Rev.-6.1 Page 12of 47 Power Transformer


lines. The oil level gauge shall be mounted on the conservator. The oil level at gauge
shall have three indication viz., oil level at 30oC shall be marked on the gauge and
indicating range shall be minimum to maximum level.
c) There shall be one “Atmoseal type” sealing to prevent direct contact of transformer oil
withtheatmosphericairtoretardoxidationandcontaminationofoil.
d) The oil connection from the transformer tank to the conservator vessel shall
be arranged at a rising angle of 3 to 9 degree to the horizontal upto the Buchhlozrelay.
The inside diameter shall be 50mm/80mm as per capacity of the transformer and
IS:3639.
e) Valves shall be provided at the conservator to cut off the oil supply to the
transformer after providing a straight run of pipe for at least five times internal
diameter of the pipe on the tank side of the Buchholz relay and at least three times
the internal diameter of the pipe on the conservator side of the Buchholz relay. The
pipe connecting the transformer tank with conservator will project above the lowest
point in the conservator such that the portion below the pipe acts as a sump where the
impurities in conservator will becollected.
f) Magnetic oil level gauge with low oil level alarm suitable for 220Volt ± 10% DC
supplyshall beprovided.
g) Atmoseal type conservator shall be filled with oil to a level appropriate to the filling
temperature. The oil shall be separated from atmosphere by a flexible aircell of
nitrile rubber reinforced with nylon cloth air cell. Flexible aircellof nitrile rubber shall be
able to withstand max temp of oil considering continuous operation as well as
considering overloading of transformer as per relevant IS/IEC. The connection of air cell
to the top of the conservator is to be made by air proof seal to prevent entry of air to the
conservator.
h) OLTCConservatorshallhaveoilindicatormadeofglass.
i) Dehydrating Filter Breather: Conservator shall be fitted with a dehydrating filter
breather. It shall be designed to facilitate thefollowings:
(ii) Passage of air through silicagel.
(iii) Silicagelisisolatedfromatmospherebyanoilseal.
(iv) Two breathers (of identical size) shall be connected in parallel for main
conservator tank. A stop valve shall be provided for each breather and also
for the common pipe line. The same arrangement shall be made for OLTC
tank conservator by providing adequate size of two identicalbreathers.
(v) Breathersaretobemaintainedapproxataheightof1200mm.aboverailtoplevel.
(vi) Moisture absorption indicated by a change in colour of the silica gel can be
easily observed from groundlevel.

16. BUSHING:

Bushing shall have high factor of safety against leakage to groundand shall be so located as
to provide adequate electrical clearances between bushing and grounded parts. Bushings
of identical voltage rating shall be interchangeable. All bushings shall be equipped with
suitable terminals of approved type and size and shall be suitable for bimetallic connection, if
necessary. The insulation class of thehigh voltage neutral bushing shall be properly
coordinated with the insulation class of the neutral of thehigh voltage winding.
All main windings, tertiary windings and neural leads shall be brought out to outdoor
through bushings which shall be so located that the full flashover strength will be utilised
and phase to phase and phase to earth clearance shall be more than minimum value
specifiedbelow.LocationandarrangementofbushingshallfollowIndianStandards.

WBSETCL / TECH SPEC / Rev.-6.1 Page 13of 47 Power Transformer


Each bushing shall be so coordinated with the transformer insulation that flashovers will
occur outside thetank.
All porcelain used in the bushings shall be made of the wet process, be homogeneous and
free from cavities or other flaws. The glazing shall be uniform in colour and free from
blisters, burns, and other defects. Upper portion of Bushing made of Porcelain & lower
portionmadeofEpoxy/porcelainisalsoacceptable.
If not specifically mentioned, the offered bushings shall be of Resin Impregnated
Polymer (RIP) / Resin Impregnated Synthetic (RIS) type for 52KV and above.
HV Neutral bushing shall be of 36 KV class for 400 KV & 220 KV class transformers. Bushing
for 33 KV delta tertiary winding i.r.o. 160 MVA, 200 MVA, 315 MVA or higher Transformer
shall be of 52 KVclass.
RIPtypebushingshallbeprovidedwithtapforcapacitanceandtandeltatest.Testtapsrelying
onpressurecontactsagainsttheouterearthlayerofthebushingisnotacceptable.
All OIP bushings are to be hermetically sealed and shall have provision of
measurement of capacitance and tan-delta without dismantling ofthe bushing.
Rating plate of bushing shall be provided near each type of bushing with terminal marking
andphysical position as perIS:2026.
Bushing for 36KV shall be Solid porcelain or oil communicating type.
The electrical and mechanical characteristic of bushings shall conform to IS:2099 and
IS:3347. The characteristic of the oil used in the bushing shall be the same as that of the
oil in thetransformer.
Main terminals shall be solder less and “Terminal Connectors” shall be as per cl. No. 19 of
this technical specification. The spacing between the bushings must be adequate to prevent
flashoverbetweenphasesunderallconditionsofoperation.
All bushings shall be suitable for heavily polluted atmosphere and minimum creepage
distanceshallbetakenas25mmperKV.
Where Bushing mounted Current Transformers are specified, the bushing shall be
removablewithoutdisturbingthecurrenttransformers.
Bushings of identical rating shall be interchangeable to optimise the requirement of spares.
Polymer/composite insulator shall be seamless sheath of a silicone rubber compound. The
housing & weather sheds should have silicon content of minimum 30% by weight. It should
protect the bushing against environmental influences, external pollution and humidity. The
interface between the housing and the core must be uniform and without voids. The strength
of the bond shall be greater than the tearing strength of the polymer.
RIP Bushing shall be specially packed to avoid any damage during transit and suitable for long
storage, with non-returnable packing wooden boxes with hinged type cover. Without any gap
between wooden planks. Packing Box opening cover with nails/screws type packing
arrangement shall not be acceptable. Bushing oil end portion shall be fitted with metal housing
with positive dry air pressure and a suitable pressure monitoring device shall be fitted on the
metalhousingduringstoragetoavoiddirect contactwithmoisturewithepoxy.Alternatively,oil filled
metal housing with suitable arrangement for taking care oil expansion due to temperature
variationsshallalsobeacceptable.Manufacturershallsubmitdrawing/documentsofpackingfor
approval during detail engineering. Detail method for storage of bushing including accessories
shall be brought out in the instructionmanual.
Tan delta measurement at variable frequency (in the range of 20 Hz to 350 Hz) shall be carried
out on each condenser type bushing (OIP & RIP) at Transformer manufacturing works as
routine test before despatch and the result shall be compared at site during commissioning to
verify the healthiness of thebushing.

WBSETCL / TECH SPEC / Rev.-6.1 Page 14of 47 Power Transformer


Tan delta value of RIP condenser bushing shall be 0.005 (max.) in the temperature range of
20°Cto90°C.ThemeasuredTan_valueatsiteshouldnotexceedby.001w.r.t.factoryresults
(measured at approx. similar temperature conditions) and in no case shall exceed 0.005 during
warrantee period. No temperature correction factor isapplicable.
Tan delta value of OIP condenser bushing shall be 0.004 (max.) at ambient temperature. The
measured Tan _ value at site should not exceed by 0.001 w.r.t. factory results and in no case
shall exceed 0.004 during warrantee period. No temperature correction factor is applicable.
Bushing Current Transformer:
i) CurrenttransformershallcomplywithIS:2705/IEC-185.
ii) It shall be possible to remove the turret mounted current transformers from the Tr.
Tank without removing the tank cover. Necessary precautions shall be taken to
minimizeeddycurrentsandlocalheatgeneratedintheturret.
iii) Current transformer secondary leads shall be brought out to a weather proof terminal
box near each bushing. These terminals shall be wired out to cooler control
cabinet/marshallingboxusingseparatecablesforeachcore.
iv) The technical parameters of Bushing current transformer indicated under Specific
Technical Parameters are to be followed One no. Bushing CT (One core, Class:PS) for
each phase of 220KV, 132KV, 33KV (tertiary winding) as well as LV winding of
50MVA , 31.5MVA & 20MVA and Neutral side shall beprovided.
v) No of Bushing CT’s requiredfor
a. 400/220/33KV Transformer and 220/132/33KVTransformer
HVwinding - 3no
IVWinding - 3no
LV winding (Tertiary) - 3no
Neutral winding - 3no
b. 220/33KV transformer
HV winding - 3no
LV winding - 3no
Neutral winding - 3no
c. Other transformer
HV winding - 3no
LV winding - 3no
Neutral winding - 1no

In case of 400/220/33KV, 220/132/33KV and 220/33KV Power Transformer, for


each phase one Neutral CT, i.e altogether 3- NCTs are to be provided for
circulating current protection.

The voltage and current rating of the bushings shall be as follows :


Highest System Voltage (KVrms) Current Rating (Amps.)

A. For 315 MVA TR :


420( HV) 800
245(IV) 1250
52(LV) 3150
36(Neutral) 2000

B. For 200/160MVA TR. :


245(HV) 800
145(IV) 1250
52(LV) 3150
36(Neutral) 2000

WBSETCL / TECH SPEC / Rev.-6.1 Page 15of 47 Power Transformer


C. For 80 MVA , 50MVA , 31.5MVA &20MVA

145(HV) 800
36(LV) 2000
36(Neutral) 2000

D. For 100/80/50MVA, 220/33KV TR :


245(HV) 800
36(LV) 2000
36(Neutral) 2000

E. For 31.5MVA, 132/66KV TR :


132(HV) 800
66(LV) 800
66(Neutral) 800

The minimum withstand value of cantilever load of bushings for 60 sec. shall be as follows
(refer IS:2099-1986 Cl. 5.5)
420KV - 2500N
245KV - 1600N(for 315MVA Tr.) & 1250N (for 200/160MVA TR).
145KV - 1250N
72.5KV - 3150N
52KV - 3150N
36KV - 1250N/2000N

17. CABLE ENDBOX:

If specifically mentioned in BOQ, Transformer will be fitted with cable end box
suitable for cable termination as per required size of cable. Cable box arrangement
shallbewithsuitabletypeofbushinganddrytypeterminationofsuitablesize&runforHVand LV of
Transformer. The cable box entry shall be of suitable type and shall be designed such that it
shall be able to withstand without any deformity the electrical, thermal and mechanical
stresses & forces developed due to rated short circuit current during any terminal fault inside
the cable box. The flange joints of cable boxes shall be secured with suitable & proper sized
and nos. of stainless steel HTS nuts andbolts.

18. TERMINALCONNECTOR:

i) The bushing shall be equipped with suitable terminals for connector as specifiedherein.
ii) Each terminal (including the neutral) shall be distinctly marked on both the primary and
secondary side in accordance with the diagram of connection supplied with the
transformers.
iii) Vertical/horizontal/universal type bi-metallic, rigid connector for bushing stud shall be
provided.
iv) Clamp and connector shall be made from Cold forged Aluminum Alloy Plate i.e Extruded
AluminumClampandConnectorshallbeprocessedthroughColdforgingfor220KV,132KV,

WBSETCL / TECH SPEC / Rev.-6.1 Page 16of 47 Power Transformer


72.5KV, 52KV & 36KV Bushing and Casting type connector for 400KV class bushing.
v) The Nuts & Bolts associated with equipment of connector pieces shall be MS Hot dip
galvanized. Quality of Nuts & bolts shall conform to relevant IS of latestedition.
vi) Minimum thickness at any point of current carrying part of any clamp & connector shall not
be less than12mm.
vii) From outermost hole edge to nearest edge of any clamp & connector the distance shall not
be less than10mm.
viii)The current density of Aluminum/Copper shall be considered as 0.75/1.75A/sq.mm.
ix) Minimum thickness of Bimetal in bimetallic connection shall be2mm.
x) Approved vendor for Clamp & Connector are mentioned in WBSETCLportal.

19. COOLINGSYSTEM&COOLERGROUP:

Type of cooling for this transformer (as per capacity rating) under this specification shall be as
follows:
a) Three winding transformer (220/132/33 KV of 200/160 MVA Tr. & 400/220/33KV 315MVA)
capacity transformer shall employ ONAN/ONAF/OFAF type cooling. ONAN rating shall be
about 60% of OFAF rating. ONAF rating shall be 80% of OFAF rating and OFAF shall be
100% rating of capacity oftransformer.
b) Two winding transformer (132/33KV) of 50MVA Capacity transformer & 220/33KV of
80/50MVA capacity transformer shall employ ONAN/ONAF/OFAF type cooling. ONAN rating
shall be about 60% of OFAF rating. ONAF rating shall be 80% of OFAF rating and OFAF
shall be 100% rating of capacity oftransformer.
c) Two winding/Auto transformer (132/33KV & 132/66KV) of 20MVA & 31.5MVA capacity
transformer shall employ ONAN/ONAF type cooling. ONAN rating shall be about 65% of
ONAFrating.
The whole cooler plant shall be grouped as indicated below:
For ONAN/ONAF cooling: 2×50% cooling banks consisting of radiators & fans. 1(one) standby
fan for each bank shall be provided.
For ONAN/ONAF/OFAF cooling: 2 x 50% cooling banks consisting of radiators, adequate no.
of fans and oil pumps. There shall be at least one stand by pump and fan for each bank of
radiators. There would be 2 x 100% oil pumps and motors for cooling and one such oil pump
shall feed both the radiator banks. The other pump would remain asstandby.

20. RADIATORS:

The transformers up to 50 MVA Capacity shall have body mounted radiators, whereas
transformers above 50 MVA capacity shall have separate plinth &structure mounted radiator and
all transformers shall be fitted with detachable radiator consisting of a series of separate
circular/elliptical/rectangular, etc. tubes or fins, welded at their top and bottom into headers
which in turn are connected to the tank by means of bolted, oil tight, flanged joints. There
shall be indicating butterfly or similar valves fitted in between the tank and the headers,
which can be kept in open or closed position. There shall also be filter valves for
circulationofoil,ateachoftopandbottomheader.Oneairreleaseplugatthetopheader

WBSETCL / TECH SPEC / Rev.-6.1 Page 17of 47 Power Transformer


shall be provided.
The radiator tubes/fins shall be seamless and made of mild steel/CRCA and in order to
prevent rusting epoxy paint of 80 micron shall be applied and minimum wall thickness not
less than 1.2 mm, with a clean bright internal surface free from rust and scale. They shall be
suitably braced to protect them from mechanical shocks normally met intransportation.
A separate blanking plate shall be supplied to permit the blanking of the main oil connection
to each cooler unit when the same is detached. Each cooler unit shall have a lifting eye, oil
drainvalveatthebottomandaventat thetop.

The bid shall clearly specify the time limit for operation of a transformer carrying full load
without forced cooling. The motor operated fans shall be provided for AF rating and oil
circulation pumps for OF rating.
All Power transformers shall be installed at new/old substation of WBSETCL anywhere in West
Bengal.For50MVAtransformers,radiatorassemblyshallbeplacedalongthe bushingsides
(preferably on HV sides only) . For transformers above 50 MVA rating, in case of separate
plinth &structure mounted radiators, actual orientationof radiatorbank shall be finalised
during approval of drawings based on site condition and related approved drawings.

21. COOLING FANS:

a) The radiator stacks shall be provided with A.C.3 Phase Motor driven Fans for Forced
Air cooling. The fan motors shall be suitable for continuous operation. Blades shall be
suitably painted for outsideuse.
b) The fans shall operate without any abnormal noise. They shall be fitted with guards of
close mesh-wire-netting for safety. The terminal connections and the greasing caps of
thefanmotorsshallbeaccessiblewithouttheneedofremovinganyfanguard.
c) Fanshallbesolocatedsothattheyarereadilyaccessibleforinspectionandrepair.
d) Cooling fans shall not be directly mounted on radiator bank to avoid undue vibration on
the same. These shall be located in such a manner as to prevent ingress of rain
water. The exhaust air flow from cooling fan shall not be directed towards the main
tank in anycase.

22. OIL PUMPS:

Each cooler unit shall consist of a totally enclosed, oil immersed motor- pump, and a
forced air cool heat exchanger. Motor & pump shall be enclosed in an oil tight container
with motor leads brought through hermetically sealed bushings. Moving parts of motor &
pump shall be readily removable without dismantling of cooler and with minimum spillage
of oil. Pump shall have open type impeller to permit oil circulation when pump is idle. Heat
exchangers,fansandoilpumpsshallbecompletelyinterchangeable.
Radiators shall be connected to the tank by machined steel flanges welded to Radiator
Bank and to the tank through proper gaskets. At each such connection there shall be
provided on the tank an indicating shut off valve which can be fastened in either open or
closedposition.
An oil flow indicator with alarm contacts shall be furnished with each pump assembly to
indicate normal pump operation and direction of oil flow. An indication shall be providedin
theflowindicatortoindicatereverseflowofoil/lossofoilflow.

WBSETCL / TECH SPEC / Rev.-6.1 Page 18of 47 Power Transformer


Oil pump shall be capable of dealing with the maximum output of the transformer and
total head which may occur in service and with the varying head due to change in the
viscosity of theoil.
Suitable precautionary arrangement should be provided to arrest mal-operation of the
maintankBuchholzrelayduetostartingoftheforcedoilpumps.

23. COOLERCONTROL:
a) Cooler units shall be suitable for operation with a 400 volts, 3 phase, 50 Hz. A.C.
power supply Main and standby power supply shall be given for cooler control and source
selected throughcontactor.
b) Cooler control equipment for oil pump and fan motors shall be mounted in a marshalling
cabinet adjacent to the transformer and shall include necessary MCB with automatic
controlandannunciationequipmentandswitchesforremoteandlocalcontrol.
c) Main 400 Volt, 3- phase supply for control of cooler banks shall be taken to cooler control
cabinet through a MCB of suitable rating. The supply to cooler fans and oil pumps motors
shall be made through individual MCB with overload trip arrangements. The control
scheme for the cooler shall be so designed to ensure satisfactory operation of cooler
groupsasspecifiedinthespecification.
d) The switching in or out of the cooling equipment shall be controlled by winding
temperature and there shall be provision for automatic switching in or out at
predetermined temperature differences which should be capable of adjustment and
settingatwill.Huntingofthetransformercoolingequipmentshouldbeavoided.
e) The bidder shall specify the loading of the transformer in case of failure of one or more
set of fans orpumps.
f) Remote control of cooling equipment and its alarm and indicating devices shall beprovided
in the RTCC panel. Indication for operation of individual fan group and oil pump
shallalsobeprovidedintheRTCCpanel.

24. NITROGEN INJECTION FIRE PREVENTION SYSTEM(NIFPS)


If not specifically mentioned in BOQ, the 100MVA and above rated transformers shall be
equipped with FIRE FIGHTING SYSTEM in line with Clause No. 7.4 of ‘Manual on
Transformers’, latest edition, issued by Central Board of Irrigation & Power.

Necessary provision for incorporating fire prevention and extinguishing system by Nitrogen
injectiondrain&stirsystem-NIDS(alsoreferredasNitrogeninjectionfirepreventionsystem-
NIFPS)shallbeprovided.Theflanges/gatevalvesshallbeprovidedwithblankingplates.

Sufficient quantity of valves, flanges, pipelines shall have to be provided to protect the whole
portion of transformer & surroundings from fire hazard. Details of location & size of the
flanges, valves, dummy pipe and other pipelines for incorporating the NIDS / NIFPS shall be
finalizedduringdetailedengineering.Theexactdetailsincludingsizeofadditionaloutlet/inlet pipes,
valve with flange and other features like provision of non-return valve in conservator,
spare‘NO’contactinPRVetc.,forthefireprotectionsystemshallbehavetobeconsidered.

WBSETCL / TECH SPEC / Rev.-6.1 Page 19of 47 Power Transformer


25. TEMPERATUREMETERS:

a) One dial type gas thermometer ( having 150 º scale, with accuracy of 1.5% of FSD)of
robust design andin weather proof casing shall be provided for temperature indication
of oil of all type power transformers shall be housed in the ground mounted marshalling box to
indicate the hot oil temperature. Both alarm and trip contacts shall be provided. Maximum oil
temperature indicating pointer shall also be provided. Remote indication of oil temperature
shall be provided in RTCC and as such the oil temperature indicatorshallbesuitableforthesame.
b) Indicating type winding temperature indicator: All transformers shall be provided with a
device for indicating the combination of top oil temperature and heating by winding
current calibrated to follow the hottest spot temperature of the transformer winding. The
device shall have a dial type indicator, and in addition a indicating pointer to register the
h o t t e s t temperature reached. The temperature indicator shall be connected to CT
secondary current in one phase of each winding of the transformer. It s h a l l have
sufficient contacts for switching in and switching out the cooling employing
ONAF/OFAF system with Alarm as well as trip contacts.
c) For 315MVA, 400/220/33KV and 200/160MVA, 220/132/33KV transformers having three
separate winding temperature indicator shall be provided each with potential free contacts
for control, indication, alarm and trip with independent facility for setting the contacts at
any temperature over the whole working range of 20oC to 150oC Each mercury contact /
micro switch shall have adjustable 10oC overlapping (between ON & OFF ) to prevent
hunting of cooling fans and/or forced oil pump motors.The winding temperature
indicator shall be connected to one phase of each winding of HV/IV/LV windings. Those
temperature indicators shall be housed in ground mounted marshalling box. The Accuracy
Class of WTI shall be ± 1.5% or better temperature indicator diashall have linear
gradationstoclearlyreadatleastevery2°C.
d) Two separate winding temperature indicators with potential free mercury contacts / micro
switches for control, indication, alarm & trip shall be provided in two winding transformer
with independent facility for setting the contacts at any temperature over the whole working
range of 20°C to 150°C. Each mercury contact / micro switches shall have adjustable 10°C
overlapping (between ON & OFF) to prevent hunting of cooling fans and/or Oil pump motors.
Boththe Windingtemperatureindicatorshallbehousedingroundmountedmarshallingboxfor all
two winding transformer shall be connected to one phase of each HV & LV windings. The
accuracy class of WTI shall be ±1.5% or better temperature indicator did shall have
lineargradationtoclearlyreadatleastevery2°C.

e) In addition to WTI & OTI, optical sensors are to be used for hotspot temperaturemeasurement:
1. Adequate no of optical temperature sensors of at least 14 numbers with the unit as
specified below:
Two winding transformer: 7+7 spares (1+1 spare in each phase of HV & LV winding & 1+1
spare in topoil)
For Auto Transformer: 7+7 spares (1+1 spare in each phase of HV & IV winding & 1+1
spare in topoil)
Number of channels in display box shall be minimum 7.
2. Probes shall be all silica, Teflon jacketed fiber with perforation/slits in outer jackets to allow
complete filling. The probes shall not get damaged / affected during filtration of the
transformer. The fiber with Teflon jacket shall be strong enough to withstand the severe
conditions prevailing inside an EHVTransformer.

3. This optical sensors measuring system shall be of direct measurement non calibrating
type. Temperature range of the system should be – 30oC to + 200oC & accuracy of+/- 2o C.

WBSETCL / TECH SPEC / Rev.-6.1 Page 20of 47 Power Transformer


4. A temperature measuring system having at least 7 channels shall be mounted on a
separate enclosure having degree of protection IP 56 (preferably type tested unit) to
measurethetemperaturefromtheopticalsensors.
5. The measuring unit shall be capable to retain temperature data for at least 90 days at 1
minute interval for all channels and shall have facility to download these data. The
system shall have following keyfeatures:
a) Fixing arrangement of sensor at suitable location of the winding in such a way that it
will be mechanically protected allowing efficient and secure mounting of sensor tip in the
winding in compliance with the annexure E of IEC60076-2.
b) The temperature recording of the monitor channels will be obtained in RTCC Panel in
control room throughrepeater.
c) Alarm output with programmable set points as per user’schoice.
d) IEC 61850 Protocol on RS 485 or RS 232ports.
e) User friendly software to allow easy configuration to monitor for data logging and
retrieval.
6. Location of optical temperature sensors inside the transformer shall be finalised during
detailedengineering.

26. VALVES:
(i) TwoNos.oil inletvalveslocatedinsuitablelocations
(ii) Oneoildrainvalveeachsuitablylocatedattopandbottom
(iii) Onefiltervalvesuitablylocatednearthetopofthetank
(iv) Onefiltervalvesuitablylocatednearthebottomofthetank
(v) Onevalveeachforoilsamplingsuitablylocatedatbottomandtop
vi) Radiatorshutoffvalveattopandbottom.
vii) Buchholzrelayandoilsurgerelayshut-offvalvesatbothendsoftherelays
viii) MainConservator–filter,drain,samplevalve,airreleasevalve,airreleaseplug.
ix) OLTCConservator–Oilfillingvalve,Drainvalve,Suctionvalve
x) One drain valve forOLTC
xi) One oil inletvalve
xii) Oneno.BleedvalvewithpetcockforBuchholzrelay.
xiii) Any other valves other than those mentioned above for improvement of operation
and maintenance facility if required & pointed during drawing approval stage shall
alsobewithinthescopeofsupplyofmanufacturer.

27. PRESSURE RELIEF DEVICES/GAS ACTUATED RELAY:


 Adequate nos. of pressure relief device with two sets of electrically insulated NO contacts
shall be provided for Alarm/Tripping. It shall be of sufficient size to release pressure
rapidly that may be generated within the tank to prevent damage to any part of the
transformer. It shall operate at a static pressure less than the hydraulic test pressure of
the tank. Design shall be such as to prevent ingress of rain water. It shall be mountedon

WBSETCL / TECH SPEC / Rev.-6.1 Page 21of 47 Power Transformer


the cover of main tank and shall be designed to prevent gas accumulation.
 Gas actuated relay: One double float gas detector relay (Buchholz relay) of reputed
make with alarm and tripping contacts to detect accumulation of gas and sudden
changes of oil pressures, complete with two shut-off valves and flange coupling to permit
easy removal without lowering oil level in the conservator tank. A bleed valve for gas
venting and a test valve are to be provided. Pressure relief device & Buchholz relay shall
be tested for IP: 55 protection in accordance with IS: 13947 to avoid mal operation due
to ingress ofmoisture.

28. GROUNDINGTERMINALS/EARTHINGARRANGEMENT:

a. Two grounding terminals capable of carrying for 3 (three) seconds the full short circuit
current of the transformer shall be provided at positions close to the bottom at two
corners of the tank for bolting the earthing terminals to the tank structure to suit local
condition.
b. Neutral Earthing Arrangement: The neutral terminal of auto-transformer & two
winding transformer shall be brought to the ground level by adequate sized brass/tinned
copper grounding bar (considering the system fault level as stated in STP) supported
from the tank by using porcelain insulators. The end of the tinned copper bar shall be
brought to the bottom of the tank at the convenient point for making bolted connection
to two nos. galvanized steel grounding flat connected to sub-station groundingmat.

29. RATING,DIAGRAMANDPROPERTYPLATES:

The following plates shall be fixed to the transformer tank at an average height readable from
the transformer base level.
a) A rating plate bearing the data specified in the appropriate clauses of IS:2026
b) A diagram plate showing the internal connections and also the voltage vector relationship of
the several windings in accordance with the IS and in addition, a plan view of the
transformer giving the correct physical location of the terminals. No load voltage shall be
indicated in each tap. The winding temperature C.T. and the thermometer pocket shall also
be indicated in the saidplate.
c) A plate showing the location and function of all valves and air release plugs and plate
material preferably in stainlesssteel.
d) An indoor cubicle for remote control of coolers, position of tap, alarm and indicating devices
with the help of control equipments, annunciation, relays, indicating instrument,etc.
e) A separate rating plate embossing different losses obtained after relevant test for each
transformer is to be provided.
f) A rating plate for each type of bushing shall be provided and to be fixed at the base of the
bushing.

WBSETCL / TECH SPEC / Rev.-6.1 Page 22of 47 Power Transformer


30. GROUNDMOUNTEDMARSHALLINGBOX:

a. A suitable weather proof cubicle for housing the control, equipment, terminal block etc.,
made of 3 mm sheet steel, shall be provided for each transformer. The box shall
accommodate all (i) winding and oil temperature indicators and (ii) control and
protection equipment for coolingplant.
b. All terminal blocks for cable connection shall be located in this box. Terminal blocks shall
be of 1100 Volt grade “Elmex/Connectwell” make and have continuous rating to carry
the maximum expected current on the terminals. The terminal block shall be fully
enclosed with removable covers of transparent, non-deteriorating type plastic material.
Insulating barrier shall be provided between the terminals. The terminal blocks shall
have locking arrangement to prevent its escape from the rails. 20% spare terminals are
to be provided. These spare terminal blocks shall be uniformly distributed on all the
terminal block column. All terminal blocks shall be numbered for easy identification.
Terminal blocks shall be arranged with at least 100 mm clearance between two sets of
terminalblock.
c. The marshalling box shall be provided with cubicle lamp with door switch, space heater
with differential thermostat and removable cable gland plate etc. Cable shall enter from
the bottom of thebox.
d. Marshalling box of each type shall be tested for IP-55 in accordance withIS:13947.
e. All internal wiring shall be carried out with 1100 Volt grade PVC insulated stranded
copper conductor of 2.5 sq. mm or larger size as per schemerequirement.

31. WIRING:
All control, alarm and indicating devices provided with the transformer shall be wired up to the
terminal blocks in the marshalling box.
Wiring from transformer to the cubicle shall be done with PVC wires in conduit or by PVC
2
armoured cable of 1100 V grade. Minimum wire size shall be 2.5mm copper. Not more than
two wires shall be connected to a terminal. 20% spare terminals shall be provided.
All devices and terminal blocks within the marshalling box shall be identified by marking
corresponding to the circuit in schematic or wiring diagram. All fuses shall be of cartridge type
and IS marked.
Phase marking on each terminal bushing (including neutral) shall be distinctly made on both
the primary, secondary and tertiary winding side in accordance with the connection diagram of
thetransformer.
Interconnection of wires in between transformer and marshalling box will be in the scope of the
contractor.

32. CENTER OFGRAVITY:


The centre of gravity of the assembled transformer shall be low and as near the vertical centre
line as possible. The transformer shall be stable with or without oil. Location of Centre of
Gravity shall be shown on the outline general arrangement drawing.

WBSETCL / TECH SPEC / Rev.-6.1 Page 23of 47 Power Transformer


33. CLEANING ANDPAINTING:
Before painting or filling with oil, all non-galvanised parts shall be completely clean and free
from rust, scale and grease and all external rough surfaces on castings, shall be made smooth.
The interior of all transformer tanks and other oil filled chambers and internal structural steel
work shall be cleaned of all scale and rust by sand blasting or other approved method. These
surfaces shall be painted with an oil resisting varnish or paint.
Except for nuts, bolts, and washers, which may have to be removed for maintenance
purposes, all external surfaces shall receive a minimum of three coats of paint. The
primary coat shall be applied immediately after cleaning. The second coat shall be of oil paint
of weather resisting nature and of a shade or colour easily distinguishable from the primary,
and the final coats shall be applied after the primary coat has been touched up where
necessary. The final coat shall be of a glossy, oil and weather resisting non-fading paint of
battle ship greycolour.
All interior surfaces of mechanism chamber and kiosks except those which have received anti-
corrosion treatment shall receive three coats of paints applied to the thoroughly cleaned metal
surface. The final coat shall be of light colored anti-condensation paint.

34. PACKING & TRANSPORTATIONLIMITATIONS:


Power Transformer is to be transported in an atmosphere of nitrogen or dry air at positive
pressure.
Necessary arrangement shall be ensured by the manufacturer to take care of pressure drop of
nitrogen or dry air during transit and storage till completion of oil filling during erection. The
nitrogen or dry air cylinder provided to maintain positive pressure can be taken back by the
contractor after oil filling. A gas pressure testing valve with necessary pressure gauge and
adaptor valve shall be provided.
The Transformer during transportation shall also be fitted with at least one Electronic impact
recorders (on returnable basis) to measure the movement due to impact in all three
directions. The acceptance criteria and limits of impact in all three directions which can be
withstood by the equipment during transportation and handling shall be submitted by
the manufacturer before delivery. The recording shall commence in the factory before
despatch and must continue till the unit is installed on its foundation. The data of electronic
impact recorder(s) shall be down loaded at site and a soft copy of it shall be handed over to
Engineer-in-charge. Further, within three weeks from the placement of the Transformer on
the foundation, manufacturer shall communicate the interpretation of thedata.
The transformer Main Tank with Core-coil assembly shall be shipped/ transported filled with
inert gas due to transport weight regulation. If the transformer is equipped with inert gas
pressure system, than a low pressure alarm device is to be provided. The alarm device shall
be required for extended storage atsite.
Special attention shall be paid in packing the accessories & spares to avoid moisture ingress.
All parts shall be adequately marked to facilitate field erection. Boxes and crates shall be
marked with the contract number and shall have a packing list enclosed showing the parts
contained therein.
The Bushings shall be crated & packed and transported as per standard guide line of the
Bushing Manufacturer. All care should be taken to avoid any damage of the porcelain due to
vibration during transport.
The weights & dimensions of the packages to be transported to site shall be governed by
facilities available for the routes by road/rail/ship.

WBSETCL / TECH SPEC / Rev.-6.1 Page 24of 47 Power Transformer


35. LABELS:

Labels shall be provided for all apparatus such as relays, switches, fuses contained in any
cubicle or marshalling kiosk.
Descriptive labels for mounting indoor or inside cubicles and kiosks shall be of material that
will ensure permanence of the lettering. A mat or stain finish shall be provided to avoid dazzle
from reflected light. Labels mounted on dark surfaces shall have white lettering on a black
background Danger notices shall have red lettering on a white background. All plates shall be
of material which will not be corroded. Labeling shall be clear, concise andadequate.
Labels for mounting outdoors shall be weather and corrosion proof formed by etching to
ensure permanence.
Labels shall be attached to panels with brass screws or with steel screws which have received
rust preventive treatment.
Labels should have lettering sizes of at least 1 to 1.5mm stroke width and 3 to 6mm height.

36. CONTRACT DRAWINGS ANDMANUALS:

After placement of P.O., six copies of following drawings ,manuals and literatures shall be
submitted to the Chief Engineer, Engg. Deptt., BidyutVhaban (9thfloor), Salt Lake, Kolkata -
700091.

Drawing for Controls:


i) Schematic diagram of transformer coolercontrol
ii) Schematic diagram and location of WTI andOTI.
iii) General arrangementof ground mounted Marshalling Box for all type of
transformer.
iv) Schematic diagram of manual and push button control of on load tapchanger.
v) Abbreviation table for OLTC andRTCC.
vi) Explanatory note forRTCC
vii) General Arrangement & scheme drawing forRTCC
viii) Explanatory note for transformercooler
ix) Wiring diagram of ground mounted Marshalling Box for each type ofTransformer.
x) Wiring diagram of RTCCpanel.
xi) Drawings other than there mentioned above if required as per provision of Technical
Specification for Erection & Maintenance are also to besubmitted.

Drawings of Transformer:
(i) General outline drawing showing front, side elevation, plan of the transformer and
accessories with detailed dimensions and detailedlegend.
(ii) Detailed foundationplan.
(iii) Drawing of each type of bushings, lifting dimensions, clearance between Terminals of
different voltage level and ground, quantity of insulation oil, name plate, detailsetc.
(iv) Operation and maintenance guide for transformer and ON LOAD TAPCHANGER.
(v) Transport OutlineDrawing
(vi) Valve SchedulePlate
(vii) Measured LossPlate

WBSETCL / TECH SPEC / Rev.-6.1 Page 25of 47 Power Transformer


(viii) Clamp &connectors
(ix) Rating Platediagram
(x) Oil filling instructionplate
(xi) Roller lockingarrangement
(xii) Foundation Plandrawing.
(xiii) Drawings other than those- mentioned above if required as per provision of
Technical Specification for Erection & Maintenance is also to besubmitted.

Four (04) copies of approved drawings and literatures for each transformer along with soft
copy shall be submitted for our record and distribution to site.

Instruction Manuals:

Six (06) copies of operation, maintenance and erection manuals in English language shall be
supplied for each transformer against each P.O. The manuals shall be bound volumes and
shall contain the drawings and information required for erection, operation and maintenance
of the power transformer. The manuals shall include amongst other, the followingparticulars.

a) Marked erection prints identifying the components parts of the power transformers as
dispatched, with assemblydrawings.
b) Detailed dimensional drawings, assembly and descriptions of all thecomponents.

37. TENDER DRAWING, LITERATURE AND TYPE TESTCERTIFICATES:

One copy of each drawings incorporating the following particulars along with one set of
complete type test report on similar transformer carried out as per IS & IEC in Govt.
Recognized Test House or Laboratory/NABL accreditated Laboratory shall be submitted by
each bidder with each copy the bid to the Purchaser for the purpose of evaluation of bid as
follows:
General outline drawing showing dimensions, net weights of transformers, tap changing gear,
marshalling box and their shipping weights.
Sectional views showing the general construction features and disposition of various
fittings andaccessories.
Bushing drawing showing full details of construction of HV/LV/Tertiary condenser
bushing and other technical data, weight of bushing assemblyetc.
Dimension of the largest part to be shipped and the position in which these are to be
transported.
Technical literature on tap changing control, cooling system, relays meters and general
construction feature for winding temperature indicators, Buchholz relays, oil temperature
indicator, Oil pumps, pressure release device (where required) etc.
Transformer similar to offered one should have type tested as per relevant IS.

WBSETCL / TECH SPEC / Rev.-6.1 Page 26of 47 Power Transformer


38. TRANSFORMER LOSSES, EVALUATION OF BID &ACCEPTANCE

Guaranteed Guaranteed Maximum Load Guaranteed


Rating of Transformer Maximum NoLoad Losses (Copper + stray loss)at Maximum
Loss on principal rated current on principal tap at Auxiliary/Cooler
tap at Rated 75 oC in HV-IV combination for Loss in KW
Voltage and Auto Transformer & HV-LV
frequency, inKW combination for Two winding
Transformer, in KW
20 MVA 132/33 KV 17 130 -

31.5 MVA 132/66 KV Auto


Transformer 20 150 5
50 MVA 132/33KV 25 140 5

80 MVA 132/33 KV 32 230 5


80/100 MVA 220/33 KV 35 235 5

50 MVA 220/33 KV 30 140 5

160 MVA 220/132/33 KV 35 205 8


Auto Tr
200 MVA 220/132/33 KV
Auto Tr 40 330 12
315 MVA 400/220/33 KV
Auto Tr 65 445 15

500 MVA 400/220/33 KV 90 500 15


Auto Tr

a) The Transformers are to be designed with maximum permissible losses as indicated


above.
b) The bidder must clearly specify that the offered losses are "Maximum"(including IS/IEC
tolerance) and no further positive tolerance as per IS/IEC shall be applicable on the
offered values during evaluation as well as during testing oftransformer.
c) Bids offering with losses beyond the maximum limits mentioned above shall be treated as
non-responsive andrejected.
d) Loss Capitalization shall be done with the accepted bids with loss values within specified
limit . For the purpose of evaluation of bids, the capitalized cost of iron loss, load loss and
auxiliary loss (KW) shall be added to the quoted price of the transformer at the following
rates:
i) Capitalized value of No Load loss per KW – Rs. 4,95,943/-

ii) Capitalized value of load loss perKW – Rs. 2,02,345/-


iii) Capitalized value of Auxiliary loss per KW – Rs. 1,98,377/-
e) However once a bidder becomes successful on the basis of loss capitalization with certain
declared loss value, they have to strictly achieve the same loss value during the course of
testing of transformers, offered for supply. No tolerance as per IS/IEC will beapplicable.
f) If they fail to do so, the offered transformer will be rejected and only replaced
transformer with declared loss value will beaccepted.
g) In this process, the delay so occurred will be on the vendor'saccount.
h) If the vendor fails to achieve the declared loss during second time, the contract will be
terminated at the vendor's risk andcost.

WBSETCL / TECH SPEC / Rev.-6.1 Page 27of 47 Power Transformer


39. STAGEINSPECTION:

Stage inspection will be carried out by the customer on Core, Coil & Tank during the
manufacturing stages of the transformer. The manufacturer will have to call for the stage
inspection and shall arrange the inspection at manufacturer’s premises or manufacturer’s
bidders premises free of cost. Stage inspection of core and coil will be carried out on 1 (one)
number Transformer against each Purchase order or a particular design. On the basis of
satisfactory Stage Inspection, manufacturer will proceed further. The following stage
inspection shall be carried in oneinspection.
Prior to stage inspection following documents shall have to be submitted by
manufacturer forverification:
1) Document related to prime core, procurement establishing traceability vide relevant Cl.
of Technical Specification of PowerTransformer.
2) Documents for coil establishingtraceability.
Following tests have to be carried out in stage inspection.

I. On Core

1) Flux density checking of assembled core (without having any insulating tape etc. rapped
around the core) vis-à-vis measurement of step thickness, lamination widthetc.
2) Window height, leg center dimension, core diameter of assembledcore.
3) Physical verification of core in respect of lamination thickness, bend, camber and
wavinessetc.
4) Carlite test, Watt loss and ageing test on the sample of prime core. (Core sample shall be
selected during stage inspection and sent to any NABL accredited laboratory for tests
under Sl.No.4)
5) Loss measurement of Prime core(Loss/Kg).
6) 2KV test between core and Yokeclamps.

II. On Coil

1) Physical verification of HV, IV and LV wound coil for 160MVA,200 MVA and
315MVA Power Transformer (without any outerinsulation).
2) Measurement of resistance of each finished coil (HV, IV &LV).
3) Measurement and current density calculation of eachwinding.
4) Copper purity test (after cutting from finished coil offered forinspection).

Calibration Certificates of all measuring instrument to be used during stage and final
inspection shall be produced and that will be in conformity to our relevant Clauses of
GCC/TechnicalSpecification.

III. OnTank

1) Physical inspection & Dimension Checking of MainTank


2) Vacuum Withstand Test on the MainTank.
3) Pressure Withstand Test on the MainTank.
4) Leakage Test of the mainTank.

WBSETCL / TECH SPEC / Rev.-6.1 Page 28of 47 Power Transformer


40. TEST AT FACTORY AND TESTCERTIFICATES:

All Routine and Acceptance tests at manufacturer’s works shall be carried out in presence of
WBSETCL’s representative in compliance with IS: 2026/ IEC 60076 (as amended up-to- date)
on the transformers. The entire cost of acceptance test, routine test and special test as follows
that are to be carried out as per relevant IS shall be treated as included in quoted price of
transformer.
1. The Contractor shall offer the transformer for final testing with at least 15 (fifteen) days
prior to the actual date when the tests will be carriedout.
2. Internal test report of each transformer and test reports of prime core and coil from NABL
accredited laboratory shall be submitted at least 7(seven) day prior to date of testing.
Offer for final test shall be accepted after receiving abovedocuments.
3. After final testing 6 (six) copies of test reports of each transformer along with soft copy and
soft copy of final drawing shall be submitted to the Chief Engineer, Engg. Deptt. prior to
issuance of formal MICC & DIletter.
The following tests are to be carried out as a part of routine tests as per IS:2026 / IEC 60076
and as per our standard requirement:

i) Resistance of each winding at all taps (whereverapplicable).


ii) Turns ratio for all sets of windings on eachtap
iii) Polarity and phase vectorrelationship
iv) Measurement of No Load Loss and No Load Current at 90, 100 and 110 percent rated
voltage.
v) Impedance voltage at normal, maximum and minimum tap for each pair ofwinding.
vi) Measurement of insulation resistance between windings and between windings and
earth. IR value is to be measured before and after impulsetest.
vii) Measurement of aux.losses.
viii) Regulation at rated load and at unity, 0.8 lagging powerfactors
ix) Efficiencies at u.p.f. and 0.8 p.f. at 50%, 75% and 100%loading.
x) Measurement of LoadLosses.
xi) Separate source voltage withstandtest.
xii) Induced over voltage withstand test with Partial Dischargemeasurement.
xiii) Tests on on-load Tapchanger.
xiv) Magnetic Balancetest.
xv) Oil leakage test on tanks and all oil filled compartment of transformer shall be tested
as per CBIP for 12 hours (minimum) filled with oil for which no oil leak shalloccur.
xvi) Test on pressure reliefdevice.
xvii) Operation of Tap changer from RTCC as well as fromOLTC
xviii) Test on RTCC, Cooler Control Cabinet and MarshallingBox.
xix) Measurement of Tan Delta Capacitance of Windings andBushings.
xx) Zero Sequence Impedance measurement.
xxi) Frequency Response Analysis (FRA) in factory and field (sub-station) for all voltage
classes & rating for all transformers against eachP.O.
xxii) Switching Impulse test for 315MVA, 400/220/33KV transformer
xxiii) Full wave Lightning Impulse test for the line terminal for 80/50 MVA 132/33 KV, 31.5
MVA 132/66KV, 200/160 MVA 220/132/33 KV & 315MVA, 400/220/33KV transformer as
perIS/IEC
xxiv) BDV measurement of transformeroil.
xxv) DGA of Transformer oil after typetest
xxvi) Functional test of Fiber Optic sensor type hot spot measurementsystem
xxvii) Visual, dimensional checking oftransformer.

The following Type tests are to be carried out for at least on one of each type of transformer
against each purchase order without any price implication:

WBSETCL / TECH SPEC / Rev.-6.1 Page 29of 47 Power Transformer


a) Temperature rise test (cl.no.16.8 of IS2026)
b) Full wave Lightning Impulse withstand Tests in all phases (including chopped and reduced
chopped wave) for 132KV class & below ( IEC 60076-3/ IS:2026, Part- III,2009
(Included in Routine test) Cl. 12 & 13): This test shall be carried out on HV, IV & LV
limb in case of three winding transformer and HV & LV limb in case of two winding
transformer.
c) Checking of acoustics noiselevel.
d) Pressure & vacuum test on finished empty tank during stageinspection.
The pressure & vacuum test on remaining finished empty tank of each type against each P.O.
shall also to be carried out at the tank manufacturer premises in presence of representative of
transformer manufacturer. Tanks under same P.O. may be supplied by maximum two
different manufacturers to facilitate delivery schedule. In that case, pressure & vacuum test of
at least on tank from each manufacturer shall have to be carried out at the tank manufacturer
premises. Test reports of all the tanks are to be submitted to the Chief Engineer, Engg. Deptt
for approval and clearance towards use of the saidtank.

41. TEST ON ASSOCIATEDEQUIPMENT:

Porcelain Bushings, Windings Temperature Indicating Devices. Dial Thermometers, Buchholz


Relays, Auxiliary Meters, Motor Starting Contactors, Control devices, Insulating oil and other
associated equipment covered by the contract shall be certified by the contractor to have been
tested in accordance with the relevant IS specification by the manufacturer. The contractor
shall furnish a certificate of compliance of the relevant tests, for all auxiliary apparatus. Six
certified copies of the aforesaid test reports shall have to be furnished.

42. TOLERENCES

As per the clause of the IS 2026/ IEC 60076 tolerances will be applicable to certain
guaranteed values as depicted in the followingtables:

SL Item Tolerance

1 Voltage ratio at no load on principal The lower of the following values:


tapping for a specified first pair of ±0.5 % of declared ratio
windings ±1/10 of the actual percentage impedance on
the principaltapping

2 Voltage ratio on other tapings, same pair To be agreed, but not less than the lesser of
the values in a) and b)above

3 Voltage ratio for further pairs To be agreed, but not less than the lesser of
the values in a) and b)above

WBSETCL / TECH SPEC / Rev.-6.1 Page 30of 47 Power Transformer


4 Short-circuit impedance for:
– a separate-winding transformer with two
windings, or
– a specified first pair of separate windings
in a multi-windingtransformer
When the impedance value is ≥10 % : ±7,5 %
of the declaredvalue
a) principaltapping When the impedance value is <10 % : ±10 %
of the declaredvalue

When the impedance value is ≥10 % : ±10 %


b) any other tapping of thepair of the declaredvalue
When the impedance value is <10 %: ±15 %
of the declaredvalue

5 Short-circuit impedance for:


– an auto-connected pair of winding,or
– a specified second pair of separate
windings in a multi-windingtransformer
a) principaltapping ±10 % of the declared value
b) any other tapping of thepair ±15 % of the declared value for that tapping
c) further pairs ofwindings To be agreed, but ≥15 %

6 No-load current +30 % of the declared value

NOTE - For certain auto-transformers and booster transformers the smallness of their impedance
justifies more liberal tolerance. Transformers having large tapping ranges, particularly if the range
is asymmetrical, may also require special consideration. On the other hand, for example, when a
transformer is to be combined with previously existing units, it may be justified to specify and
agree on narrower impedance tolerances. Matters of special tolerances shall be brought to
attention at the tender stage, and revised tolerances agreed upon between manufacturer
andpurchaser.

NOTE - 'Declared value' should be understood as meaning the value declared by the
manufacturer.

43. DRYING OUT AT THE MANUFACTURER’SWORKS:

All the Tests shall be conducted after complete Drying out at the works. The transformer shall be
despatched complete after being dried out under vacuum and filed with inert gas, ready to be put
into commission, without further drying out at site.

44. SUPERVISION OF ERECTION, TESTING &COMMISSIONING:

The MANUFACTURER shall arrange for the services of their Supervisor/Engineer from the
manufacturer during erection, testing and commissioning of the equipment at sites at free of cost
as many time as required by WBSETCL.

WBSETCL / TECH SPEC / Rev.-6.1 Page 31of 47 Power Transformer


45. General Note

A) A tentative I/O signal list of BCU of RTCC is mentioned in the technical specification.
However the detail exhaustive I/O signal list will be finalized during detail Engineering.
All ICD files should be ready and configured based on the final I/O signal list before
offering final inspection of the transformer.

B) The manufacturer of the transformer should be responsible for making necessary


arrangement to depute the Engineer from the OEM for BCU of RTCC towards extending
active support at the site level while integration of the same with SAS during
commissioning stage of the transformer at the respective sites without any additional
cost implication.

WBSETCL / TECH SPEC / Rev.-6.1 Page 32of 47 Power Transformer


46. Signal lists
Status DI Hard AI Hard DO Remarks
Wired Wired
WTI Temperature of each
winding (HV,IV & LV)
OTI Temperature
FO equipment Temperature
of R-Ph HV winding
FO equipment Temperature
of Y-Ph HV winding
FO equipment Temperature
of B-Ph HV winding
FO equipment Temperature
of R-Ph IV winding
FO equipment Temperature
of Y-Ph IV winding
FO equipment Temperature
of B-Ph IV winding
FO equipment Temperature
of Oil
OLTC Main Supply ON
OLTC Main Supply OFF
OLTC Control Supply ON
OLTC Control Supply OFF
OLTC Tap Position Indication
Tap Changer Out of Step
Tap Changer in progress
Tap Changer ON LOCAL
Tap Changer ON REMOTE
Tap Changer STUCK UP
Tap Changer MOTOR O/L
TRIP
Tap Changer UPPER LIMIT
REACHED
Tap Changer LOWER LIMIT
REACHED
Tap Changer in Independent
mode
Tap Changer in master mode
Tap Changer in follower
mode
OLTC Tap Raise
OLTC Tap Lower
Cooler control Main AC
Supply Fail
Cooler control S/By AC
Supply Fail
Cooler control Main AC
Supply ON
Cooler control S/By AC
Supply ON
Cooler control FAILED TO
TRANSFER
MB Main DC Supply ON
MB Main DC MCB Trip
MB Ind. DC Supply ON
WBSETCL / TECH SPEC / Rev.-6.1 Page 33of 47 Power Transformer
Status DI Hard AI Hard DO Remarks
Wired Wired
MB Ind. DC MCB Trip
MB CCU DC Supply ON
MB CCU DC MCB Trip

Fan Control Local Auto


Fan Control Local Manual
Pump Control Local Auto
Pump Control Local Manual
Cooler control Main Oil Pump
ON
Cooler control Main Oil Pump
OFF
Cooler control Main Oil Pump
STUCK
Cooler control S/By Oil Pump
ON
Cooler control S/By Oil Pump
OFF
Cooler control S/By Oil Pump
STUCK
Cooler control Main Fan ON
of each Fan
Cooler control Main Fan OFF
of each Fan
Cooler control S/By Fan ON
of each Fan
Cooler control S/By Fan OFF
of each Fan
Fan Control in AUTO in RTCC
Fan Control in MANUAL in
RTCC
Pump Control in AUTO in
RTCC
Pump Control in MANUAL in
RTCC
Operate Fan Control from These contacts shall
RTCC be configured to
operate, when the
Operate Pump Control from Current value
RTCC exceeds a pre-set
limit/Oil Temp
exceeds a preset
value

WBSETCL / TECH SPEC / Rev.-6.1 Page 34of 47 Power Transformer


SPECIFIC TECHNICAL PARAMETERS

Sl. NO DESCRIPTION ITEMS TECHNICAL PARAMETERS

3-ph Auto transformer with


a) 500/315MVA
tertiarywinding
3-ph Auto transformer with
1 Rated capacity b) 200/160 MVA
tertiarywinding
c) 80/50/31.5/20MVA 3-ph Two winding
transformer/AutoTr
a) 500/315 MVA 400/220/33 KV
b) 200/160 MVA 220/132/33 KV
2 Voltage Rating :
220/33KV, 132/ 33 &
c) 80/50/31.5/20MVA
132/66KV ( as per Tender)

For 400 KV/ 220 KV/ 132


3 Maximum system voltage (KV) 420/245/145/72.5/36
KV/ 66/33 KV
For 500/315 MVA/200/160
ONAN/ONAF/OFAF
4 Cooling MVA/ 80 MVA / 50MVA
31.5 / 20 MVA ONAN/ONAF

Rating at different type of 60% / 80% / 100%;


5
cooling For All Rating 65%/100% for31.5/20MVA,
132/33KV & 132/66 KVTR.

Outdoor Type
6 Type of Transformer For All Rating
Interconnection Power
Transformer
7 Tertiary winding voltage (KV) for 160 MVA,200 MVA& 33
315MVA

Tertiary winding capacity For 500/315MVA 5 MVA


(MVA) for 315MVA,160MVA
8
(Combined loading shall not
exceed the ratedcapacity)
For 200 MVA 60 MVA

For 160MVA 45MVA


9 System frequency (Hz) For All Rating 50 ± 3%
10 No. of phases in system For All Rating 3
(i) Effectively earthed,
For 500/315 MVA,200 Neutral is Solidly earthed.
MVA & 160MVA Tertiary of 33 KV winding is
ungrounded.
11 System Earthing
(ii) 33KV system is earthed
through grounding
For 80/50/31.5/20MVA transformer for
220/132/33KV &132/33KV
transformer

WBSETCL / TECH SPEC / Rev.-6.1 Page 35of 47 Power Transformer


Insulation level of the winding (withstand)

i) 1.2x50 micro-second For 400/220/132/66/33


1300/950/550/350/170 KV
lightning impulse(KVP) KV
ii) Tertiary winding of
400/220/33 & 220/132/33 KV For 52 KV Tertiary 250 KV
12 Transformer (KVP)

iii) Power frequency withstand FOR 400/220/132/66/33 570/395/230/155/70


(KVrms) KV
iv) Power frequency withstand For 33 KV Tertiary 95
- Tertiary winding of
220/132/33 KV Transformer
(KVrms) & 400/220/33KV
Transformer
400 KV 63 KA FOR 1 SEC
220 KV 40 KA FOR 3 SEC
13 System fault level (KA).
132 KV 31.5 KA FOR 3 SEC
66 KV 31.5 KA FOR 3 SEC
33 KV 25 KA FOR 3 SEC
250/2500 micro sec.
14 Switching Surge withstand for 315 MVA,400 KV 1050 for HV side of 400KV
voltage(KVp) Tr.

15 Partial Discharge level


500 Pc.

i) 1.2×50 micro-
Insulation level of HV(N) 95
16 second Lightning impulse
winding
(KVp)
ii) Power Frequency
18 withstand(KVrms) 38

Maximum hot spot o


98 Centigrade
temperature (o Centigrade)
19 over weighted averagetemp
of 32
Degree C

i) For transformer of all


On Load Type
rating
20 Type of tap changer
+ /- 10% in 16 equal steps
ii) Tappingrange
@ 1.25%

21 Partial Discharge level For 220 & 132 KV 500 Pc.

500/315 MVA YNaod11

WBSETCL / TECH SPEC / Rev.-6.1 Page 36of 47 Power Transformer


200 MVA YNaod11
22 Vector group 160 MVA YNaod11

80MVA/50MVA/31.5/20 YNd1
31.5 MVA 132/66 KV Auto YNa0
Transformer

400KV(1 Sec) 63
220KV(3 Sec) 40
23 Short circuit level (KA)
132 KV (3 Sec) 31.5
66 KV (3 Sec) 31.5
33KV (3 Sec.) 25

400KV 13020
220 KV 7595

24 Minimum creepage Distance 132 KV 4495


(mm) ofbushing 66 KV 2248
33 KV 1116
52KV 1612
10.3 at max voltage tap
12..5 at principal tap
15.4 at min voltage tap
( Between HV –IV)
500/315 MVA
Impedance voltage at 75°C 200 MVA 12.5 Between HV-IV
(The impedance volt at HV-IV
25 for 3 winding transformer 160 MVA 12.5 Between HV-IV
(Guaranteed)
80MVA/50MVA/31.5MVA 13.2 at max voltage tap
12..5 at principal tap
11.8 at min voltage tap
( Between HV –LV)

26 Type of insulating media For All Rating Mineral insulating oil


immersed.

27 Indoor or outdoor type For All Rating Outdoor

Insulation level to earth of Similar to 33KV bushing for


28 For All Rating
neutralterminal transformer above 31.5MVA
.
Auxiliary AC supply to Fans,
29 For All Rating 3-ph, 400 ±10%
tap changer etc.(volt)

Auxiliary DC supply for alarm


30 For All Rating 220 ±10%
and tripping(volt)

WBSETCL / TECH SPEC / Rev.-6.1 Page 37of 47 Power Transformer


31 Altitude above mean sea level For All Rating Less than 1000 mtr.
For ACSR Moose / ACSR
400/220/33KV
Moose. For ACSR
Transformer
Moose/Moose or suitable
&
32 Terminal Connectors Cable
220/132/33KV
For 1.5 inch Aluminium
33 KV Tertiary pipe/ACSRMoose.
Acoustic noise level (DB) of all As per NEMA Publication TR-
33 For All Rating
transformers 1.

400 KV 1425

Insulating level of bushing : 220 KV 1050


1.2/50 micro second lightning 132 KV 650
34 impulse withstand voltage
(KVP) 66 KV 350
33 KV 170
Tertiary 33 KV 250
HV Neutral 170

400 KV 630

220 KV 460
Insulating level of bushing:
35 One minute Power frequency 132 KV 275
withstand voltage
(KVrms)(dry 66 KV 155
& wet).
33 KV 70

Tertiary 33 KV 95

HV Neutral 70

400 KV 10500
220 KV 6125
132 KV 3625
Minimum Total Creepage
36
distance (mm) forBushing 66 KV 1815
33 KV 900

Tertiary 33 KV 1300

HV Neutral 900

37 Width of Rail Gauge (mm) For All Rating 1676

WBSETCL / TECH SPEC / Rev.-6.1 Page 38of 47 Power Transformer


Annexure- 1

Definitions of a similar transformer

[ As per IS-2026 PART-5 ]

Transformers similar to a reference transformer can be identified by comparison using the following
non-exclusive list of critical features:

1. Same type of operation, for example generator step-up unit,


distribution, interconnection transformer as the referenceunit;

2. Same arrangement of main windings and geometrical sequence as the referenceunit:

3. Same type of main windings for example, helical, disc, layer, pancake, as the referenceunit.

4. Absorbed power at short-circuit (rated power per unit short-circuit impedance)


between 30% and 130 % of that of the referenceunit;

5. Axial forces and relative winding stresses (ratio of actual stress to critical stress) at short-
circuit not exceeding 120% of those in the referenceunit;

6. Same type of winding conductors, for example, aluminum, aluminum alloy, annealed or
hardened copper, metal foil, wire, flat conductor, continuously transposed conductors and
epoxy bonding, if used, as the referenceunit;

7. Same manufacturing processes as the referenceunit;

8. Same clamping and supporting arrangement.

9. Same conceptual design, for example dry-type, oil-immersed type, core type with concentric
windings, sandwich type, shell type, circular coils, non-circular coils as the referenceunit.

WBSETCL / TECH SPEC / Rev.-6.1 Page 39of 47 Power Transformer


CORE DETAILS OF BUSHING CT

Sl Description No Core Application Current Output ISF Accuracy Min Knee Max CT Max
. . No. Ratio Burden (<) Classas point excitation
N of (VA) at per IS Voltage Secy current at
o Co Lower 2705 (V) Winding Knee point
re Ratio Resistance Voltage
i) 400KV side, 220KV 1 1 Protection 1600/1A PS Class 1600V 4.0 30 at Vk/2
side & Neutral of 500
MVA, 400/220/33KV
Transformer

ii) 400KV side, 220KV 1 1 Protection 1000/1A PS Class 1000V 2.5 30 at Vk/2

side & Neutral of 315


MVA, 400/220/33KV
Transformer
iii) 220KV side, 132KV 1 1 Protection 1000/1A PS Class 1000V 2.5 30 at Vk/2
side & Neutral of
200MVATransformer

iv) 220KV side, 132 KV 1 1 Protection 800/1A PS Class 1000V 2.5 30 at Vk/2
side & Neutral of

v) 132KV side of 50MVA 1 1 Protection 400- PS Class 800 - 1.5 30 at Vk/2


Transformer 300/1A 600V

vi) 220KV side & Neutral 1 1 Protection 400/1A PS Class 800V 1.5 30 at Vk/2

of 80MVA / 50MVA

vii)33KV side of 50MVA 1 1 Protection 1000/1A PS Class 500V 2.5 30 at Vk/2


Transformer

viii 132KV side & Neutral 1 1 Protection 150/1A PS Class 600 1.5 30 at Vk/2
of 31.5MVA /20MVA
ix) 33KV side of1 1 Protection 800/1A PS Class 400 2.5 30 at Vk/2

31.5MVA /20MVA

x) 33KV side of 80 MVA 1 1 Protection 1600/1A PS Class 1000 4 30 at Vk/2


Transformer

xi) 66 KV side of 31.5 1 1 Protection 300- PS Class 300 4 30 at Vk/2


150/1A
MVATransformer

xii)Tertiary winding of 1 1 Protection 2000/1A PS Class 2000 2.5 30 at Vk/2


315MVA

xiii Tertiary
200MVA
winding of 1 1 Protection 1200/1A PS Class 1200 2.5 30 at Vk/2

Tertiary winding of 1 1 Protection 1000/1A PS Class 1000 2.5 30 at Vk/2


xi 160MVA
v

WBSETCL / TECH SPEC / Rev.-6.1 Page 40of 47 Power Transformer


Guaranteed Technical Particulars (GTP) of Offered Transformer
( To be submitted separately for separate MVA capacity of Transformer in case of common
Tender)

SL DESCRIPTION SUBMISSION

1 General Data of Bidder

a Name & Address of Company

b Country of Origin

Business Type of Company (eg.


c Manufacturer/ Supplier / Transporteretc.)

2 General Data of Transformer

Conforming Applicable Standards


a
(including Bushing &other)

Conceptual Design of Transformer


b ( e.g. Outdoor oil immersed core type
/Indoor dry core type/etc)

Type of Operation of the Transformer


(e.g. Interconnection / Distribution/
c Generatorstep-up)
* Interconnection means used in
Transmission Grid SS

d Rated Frequency (in Hz)

e Number of Phase

f Rated MVA Capacity Of the Transformer


(ONAN/ONAF/OFAF)

Rated No-load Voltage of the Transformer


g
(HV/IV/LV)

WBSETCL / TECH SPEC / Rev.-6.1 Page 41 of 47 Power Transformer


No Load Current in percent of Full Load
h current at rated KV & rated frequency at
Normal Tap

i Vector Group

j Type of Cooling

k Rating at Different Cooling

3 Thermal Data

Temperature rise of top oil (in ⁰ C) above


ambient temperature of 50 ⁰ C measured
a
by thermometer with ONAN/ONAF/OFAF
cooling

Temperature rise of winding measured by


resistance : With ONAN/ONAF/OFAF
b cooling,
in ⁰ C

Limit of hot spot temperature in ⁰ C for


c which the transformer isdesigned

4 Impedance Data

A Percentage Impedance Between HV & IV


at highest tap/normal tap/lowesttap

Percentage Impedance Between HV & LV


B

C Percentage Impedance Between IV & LV

Zero Sequence Impedance at 75 ⁰ C for


D Highest Tap/Normal Tap/Lowest Tap at
100% rating

5 Guaranteed Loss

Guaranteed no load loss (KW) on principal


a tap at rated voltage andFrequency

WBSETCL / TECH SPEC / Rev.-6.1 Page 42 of 47 Power Transformer


Guaranteed load loss at rated current at
b principal tap at 75°C (KW) in HV-IV
combination for Auto Transformer & HV-
LV combination for Two Winding
Transformer

c Maximum Cooler Loss (KW)

6 Efficiency & Regulation

Efficiency (in percent) at unity power


e
factor at75°C

f a) At 50% Full Load

g b) At 75% Full Load

h c) At Full Load

i Regulation at Unity Power factor

j Regulation at 0.8 lagging Power factor

7 Core

a Net core area in sq. metre

b Material & Grade of core Laminations

c Thickness of stampings (mm)

Maximum flux density (in Tesla) at 100%


d rated no load voltage and ratedfrequency

Maximum flux density (in Tesla) at 110%


e rated no load voltage and rated frequency

f Over Excitation withstand time (secs) at


110% / 125%/140%

Noise level ( in db) when energized at


g normal voltage and normal frequency at
no load.

WBSETCL / TECH SPEC / Rev.-6.1 Page 43 of 47 Power Transformer


8 Main Winding

a Number of Winding

Type of Winding ( eg. Helical / Disc/ layer


b /pancake) in HV/IV/LV

c Arrangement of main winding &


Geometricalsequence

Brief Details of Material of Winding


d Conductors (as per tech spec Page-8/46)

Conductor Area (Sq. cm) of Winding


e (HV/IV/LV)

Maximum Current Density ( in A/Sq.cm)


f of Winding ( HV/IV/LV)

g Winding Insulation for HV - Type & Class,


Graded orungraded

h Winding Insulation for IV - Type & Class,


Graded orungraded

Winding Insulation for Tertiary Winding


i
- Type & Class, Graded or ungraded

j Insulation Material Between HV-IV-


Tertiary

Insulation Material Between Core &


k
Winding

Type of Axial Support of winding :


l
HV/IV/Tertiary

m Type of Radial Coil support :


HV/IV/Tertiary

WBSETCL / TECH SPEC / Rev.-6.1 Page 44 of 47 Power Transformer


9 Tertiary Winding

a Rated KV

b Maximum continuous MVA Capacity

10 Insulation Level

Lightning Impulse (LI) Withstand KV


peak of HV Winding /IV/ LV Tertiary/HV
Neutral Winding For 400/220/33 KV or
a 220/132 /33 KV Auto Transformer HV
Winding/ LV/ HV Neutral winding for
220/33 KV or 132 /33 KV Two Wndg.

Switching Surge withstand KV peak (for


b 400 KV Transformer) for HVWinding

Power Frequency Withstand Voltage KV


c rms for HV/IV/Tertiary/ HV Neutral
Winding

d Partial Discharge Level (in pc) at 364


KV Between phase &Ground

e RIV (in micro Volts) at 1.1 times


minimum phase to groundvoltage

11 Bushings

a Manufacturer of HV/IV/Tertiary/HV
Neutral/LVNeutral

b Type of HV/IV/Tertiary/HV Neutral/LV


Neutral

c Rated KV of HV/IV/Tertiary/HV Neutral/


LVNeutral

WBSETCL / TECH SPEC / Rev.-6.1 Page 45 of 47 Power Transformer


Rated Current of HV/IV/Tertiary/HV
d Neutral/LV Neutral

LI Voltage (1.2/50 micro-sec):


e HV/IV/Tertiary/HV Neutral/ LV Neutral
(KVp)

Power Frequency Withstand Voltage(Dry)


f : HV/IV/Tertiary/HV Neutral/ LV Neutral
(KVrms)

Power Frequency Withstand Voltage


g (Wet) : HV/IV/Tertiary/HV Neutral/ LV
Neutral(KVrms)

h Minimum clearance between phases in


AIR: HV/IV/Tertiary(mm)

i Minimum clearance between phases in


OIL: HV/IV/Tertiary(mm)

Minimum clearance between Bushing Line


j Terminal to Tank: HV/IV/Tertiary (mm)

k Creepage Distance (in mm):


HV/IV/Tertiary/HVN/LVN

12 Tap Changer

a Manufacturer

b Type

c Total Tap Range


( + ) percent to ( - ) percent of Voltage

d Percent of Voltage per tap step

e Time (in second) for total tap change

WBSETCL / TECH SPEC / Rev.-6.1 Page 46 of 47 Power Transformer


f Tapping provided on (winding)

13 TANK

Type of Transformer Tank (eg Bell Type /


a TopCover)

b Thickness of Top Cover plates (mm)

c Thickness of Tank Bottom Plates (mm)

d Thickness of Tank side Plates (mm)

e Thickness of Radiator Fin (mm)

f Approximate weight : Core (in Kg)

g
Approximate weight : Windings (in Kg)

Approximate weight : Tank & Fittings (in


h
Kg)

i Approximate weight : Oil (in Kg)

Approximate weight : Total weight (in Kg)


j

Approximate required quantity of oil, in


k
Litres

Radiator Fitting arrangement (Tank


l mounted/Separate)

Whether optical sensor for Hot Spot


14 temperature measurement provided?
(yes/no)

Whether Electronic Impact Recorder


15 provided? (yes/no)

WBSETCL / TECH SPEC / Rev.-6.1 Page 47 of 47 Power Transformer

You might also like