CM-P3 / CM-EP3
Conventional Fire Alarm Control Panel
Manual Book
2016.03.02 REV.1
71114-023-E
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
CONTENTS
A. Metal Cabinet Dimensions ……………………………………..2
B. Plastic Cabinet Dimensions ……………………………………3
C. Description …........................................................................4
D. Electric Characteristics …………………………………………4
E. Panel Functions ………...………………………………………4
F. Specification .…..………………………………………………..7
G. Basic Troubleshooting .…..……………………………………..8
H. Fuse Specification .…..………………………………………….9
I. Wiring Diagram of the Central Control unit .…..…………….10
1. 1 ~ 8L .…..……………………………………………………10
2. 9 ~ 16L .…..………………………………………………….11
3. 17 ~ 24L .…..………………………………………………...12
4. 25 ~ 32L .…..………………………………………………...13
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
A. Metal Cabinet Dimensions
Size
H (mm) * W (mm) * D (mm)
Number of zone
1L / 2L / 4L / 5L / 8L 330 * 280 * 120
12L / 16L 400 * 300 * 120
20L / 24L 495 * 300 * 120
Box size according to site selection,
please confirm with the company!
2
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
B. Plastic Cabinet Dimensions
Size
H (mm) * W (mm) * D (mm)
Number of zone
1L / 2L / 4L / 5L / 8L 260 * 330 * 96
12L / 16L / 20L 400 * 300 * 126
24L / 28L / 32L 370 * 480 * 90
Box size according to site selection,
please confirm with the company!
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
C. Description
The concept of module design is applied to each circuit board.
The automatic testing function makes operation and
maintenance easily and effectively.
D. Electric Characteristics
Input Power : AC 240V
Stand-by Power : DC 24V
Normal Operation Voltage : DC 18V ~ 32V
Charging Method : Tickle Charging at Rated Voltage
E. Panel Functions
As the control unit turns on, the “POWER” light is on.
Fire Alarm
When the specific zone received an in-coming signal and
confirm that there is fire, zone fire LED for that specific zone
and fire light will be on. The buzzer of the unit and alarm area
will sound as well.
Each circuit with three state light and one test button are for
indicating circuit fire, open circuit fault, short circuit fault.
Turn “CONTROL” switch on and press test button in specific
zone to do fire alarm test or the zone.
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
Mute
When fire or error has happened, the control unit will sound as
warning. Press “PANEL MUTE” button to stop the sound.
When fire is happened, the fire alarm bell will ring on the spot.
Press “BELL MUTE” button to stop the ring.
When fire has happened, the reporting contact point “C.NO”
will be connected. Press “RELAY DISABLE” button to stop the
connection.
When fire has happened, the control unit will lock the state of
ZONE FIRE light, FIRE indicator, BELL sound, bell ring on the
spot, reporting contact point “C.NO”.
Press “SIGNAL HOLD DISABLE” button to release the lock.
As the detector detects a fire signal, the unit will automatically
reset the detector. If another fire signal is received within 45
seconds later, the control unit will confirm the fire alarm signal.
This function is to prevent false alarms. Press “DELAY DISABLE”
button to remove the function.
Press down the “RESET” button to reset the unit.
All the detector circuits should be connected with a 10KΩ
terminal resistor.
SND 1 and SND2 should be connected with a 10KΩ terminal
resistor.
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
Indicator
ZONE FIRE ALARM:light on indicating fire happened in specific zone.
ZONE OPEN CIRCUIT:light on indicating detector broken circuit
happened in specific zone.
ZONE SHORT CIRCUIT:light on indicating detector short circuit
happened in specific zone.
AC POWER FAULT:light on indicating battery charging is abnormal.
BATTERY FAULT:light flashes indicating battery error.
OPEN CIRCUIT:light flashes indicating detector broken circuit in
the specific zone.
SOUNDER OPEN CIRCUIT:light on indicating open circuit
happened in alarm bell wiring.
SOUNDER SHORT CIRCUIT:light on indicating short circuit
happened in alarm bell wiring.
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
F. Specification
Item Specification
Model CM-P3 / CM-EP3
Category Conventional Fire Alarm Control Panel
Type Wall-mount
Power Source 240V AC 50 / 60 Hz ±10%
Standby Battery 24V DC
Charging Voltage Below 26V DC 450mA, trickle charging
Circuit Voltage 24V DC operation voltage, under 10~11V DC 32mA
Rated Impedance Below 50Ω
No limitation for Conventional Rate of Rise or Fixed
Detector Temperature Heat Detectors; Up to 30 Photoelectric Smoke
Connection Detectors can be connected per zone
(monitor current for detectors : 24V DC 40μA)
E.O.L Resistor 10KΩ
No. of Indicators The same as the number of zones (LED indicating lamp)
No. of Bells The same as the number of zones
Color Red
Buttons Push-button
Powder coating steel (up to 24L only) /
Cabinet Material
Flame retardant ABS enclosure (up to 32L only)
Main Audio Mono tone sounder (above 85dB for 1m distance)
Alarm Relay
No-Voltage NO contact, capacity 250V AC / 7A
Contact
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
G. Basic troubleshooting
1. The indicator of “Mains Healthy” doesn’t light up:
(1) Check whether the mains of AC 230V and the battery power
in working normally.
(2) Check whether Fuse 1, Fuse 2 or Fuse 3 is burned.
If so, please replace with a new fuse.
2. The indicator of “Battery Fault ” flashes:
Check whether the barrery and Fuse 2 are working normally.
3. The indicator of “ZONE O/C FAULT ” lights up and the buzzer
sounds:
(1) Check whether the terminal resistor is disconnected from
the circuit.
(2) Check whether a detector of the circuit is not (correctly)
installed.
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
H. Fuse Specification
Charging Voltage F1 2A
ZONE 1 Sounder 1 Fuse F2 1A
TO Sounder 2 Fuse F3 1A
ZONE 8 Fuse-BATTERY 2A
Fuse-AC 1A
Charging Voltage F1 3A
ZONE 9 Sounder 1 Fuse F2 1.5A
TO Sounder 2 Fuse F3 1.5A
ZONE 16 Fuse-BATTERY 3A
Fuse-AC 1A
Charging Voltage F1 4A
ZONE 17 Sounder 1 Fuse F2 2A
TO Sounder 2 Fuse F3 2A
ZONE 24 Fuse-BATTERY 4A
Fuse-AC 1.5A
Charging Voltage F1 5A
ZONE 25 Sounder 1 Fuse F2 2.5A
TO Sounder 2 Fuse F3 2.5A
ZONE 32 Fuse-BATTERY 5A
Fuse-AC 2A
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
I. Wiring Diagram of the Central Control unit
1. 1 ~ 8L
10
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
2. 9 ~ 16L
11
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
3. 17~24L
12
Manual Book
CM-P3/ CM-EP3
Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment
4. 25 ~ 32L
13
Manual Book