198963197 Inspection Report for Air Conditioning Equipment Ag Pro

The report details the results of the inspection of 8 air conditioning systems at the El Progreso Agency for the Bank of Credit of Peru. Seven of the systems are operational, while one does not turn on and requires a review of the evaporator unit. The technician recommends checking the evaporator unit of the fourth system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views3 pages

198963197 Inspection Report for Air Conditioning Equipment Ag Pro

The report details the results of the inspection of 8 air conditioning systems at the El Progreso Agency for the Bank of Credit of Peru. Seven of the systems are operational, while one does not turn on and requires a review of the evaporator unit. The technician recommends checking the evaporator unit of the fourth system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

REPORT

DE TEOFILO PEREZ GUEVARA


Air Conditioning Technician

FOR CREDIT BANK OF PERU, OMAR IGUNZA CAÑOLI

SUBJECT AIR CONDITIONING INSPECTION REPORT.

AGENCY: THE PROGRESS

FECHA : LIMA 30 DE OCTUBRE DEL 2013.

I take this opportunity to address you and express my warmest regards.


greet, while informing him.

1. Carrier brand ducted air conditioning unit model 38CKC036551


series 2903E10437 with a capacity of 36000 Btu high pressure 237 Psi low pressure 65
Psi, current 11.4 - 9.33 - 10.9 equipment is operational.

2. Carrier brand ducted air conditioning unit model 38CKC036551


series 2903E10429 with a capacity of 36000 Btu high pressure 210 Psi low pressure 61
Psi, amperage 11.0 - 10.9 - 10.7 equipment is operational.

3. Carrier brand ducted air conditioning unit model 38CKC036551


Series 2903E10435 with a capacity of 36000 Btu high pressure 226 Psi low pressure 65
Psi, amperage 10.6 - 11.7 - 12.7 equipment is operational.

4. Equipo de aire acondicionado marca Carrier tipo ducto modelo 38CKC018-3Y1


series 2103E16636 with a capacity of 18000, the equipment does not turn on and requires diagnosis.
Well, the team needs to review the evaporator unit that is located
inside the agency and it has to be outside of office hours, the
The capacitor turns on by pressing the contactor but does not activate, remains under observation.
and to check the evaporator.

5. Carrier brand air conditioning unit, duct type model 38CKC018-3Y1


series 2103E16644 with a capacity of 18000 Btu high pressure 225 Psi low pressure 65
Psi, amperage 7.8 - 7.6 equipment is operational.

SALE, INSTALLATION, MAINTENANCE OF AIR CONDITIONING EQUIPMENT


6. Air conditioning team brand York type mini split wall model
YSDA18FS-ADA series 100002155121200152 with a capacity of 18000 Btu pressure
Pressure drops to 56 Psi, amperage 6.36 – 5.85, equipment is operational.

7. Gree brand air conditioning unit type mini split wall model
GWC12MA-D1NNAYA series no visible of capacity 12000 Btu low pressure 50
Psi, amperage 4.1 - 3.7 equipment is operational.

8. Air conditioning unit brand York duct type model YAU-36CRD series
no visible capacity 36000 Btu high pressure 222 Psi low pressure 54 Psi
current 12.6 – 11.6 – 12.7 equipment is operational.

Conclusion

Review the evaporator unit of equipment four.

SALE, INSTALLATION, MAINTENANCE OF AIR CONDITIONING EQUIPMENT


That's all I have to report.

Sincerely;

SALE, INSTALLATION, MAINTENANCE OF AIR CONDITIONING EQUIPMENT