MIC 1162 1/16 Din High/Low Limit Controller Reference Manual
MIC 1162 1/16 Din High/Low Limit Controller Reference Manual
136107
TABLE OF CONTENTS
TABLE OF CONTENTS ................................................................................................... i SECTION 1: PRODUCT DESCRIPTION ....................................................................... 1 1.1 General................................................................................................................. 1 1.2 Displays ................................................................................................................ 1 1.3 Alarms .................................................................................................................. 1 1.4 Process Variable/Setpoint Value Retransmission Output .................................... 2 SECTION 2: INSTALLATION AND WIRING.................................................................. 3 2.1 General Information.............................................................................................. 3 2.2 Wiring Guidelines ................................................................................................. 5 2.2.1 Installation Considerations............................................................................. 5 2.2.2 AC Power Wiring ........................................................................................... 6 2.2.3 Wire Isolation................................................................................................. 6 2.2.4 Use Of Shielded Cable .................................................................................. 7 2.2.5 Noise Suppression At The Source................................................................. 7 2.3 Sensor Placement (Thermocouple or RTD) ......................................................... 9 2.4 Input Connections............................................................................................... 10 2.5 Output Connections............................................................................................ 13 SECTION 3: OPERATION ........................................................................................... 15 3.1 Power Up Procedure .......................................................................................... 15 3.2 Keypad Operation............................................................................................... 15 3.3 Displays .............................................................................................................. 16 3.3.1 Alarm Status Display.................................................................................... 16 3.3.2 Over-Range/Under-Range Display .............................................................. 16 3.4 Front Panel Indicators ........................................................................................ 17 3.5 Exceeding Limit Setpoint .................................................................................... 17 3.6 Annunciator ........................................................................................................ 18 3.7 Remote Reset (Optional).................................................................................... 18 SECTION 4: CONTROL MODE ................................................................................... 19 SECTION 5: SETPOINT CHANGE MODE................................................................... 21 SECTION 6: CONFIGURATION .................................................................................. 23 SECTION 7: SET-UP MODE........................................................................................ 27 SECTION 8: ENABLE MODE........................................................................................ 31 SECTION 9: CALIBRATION ........................................................................................ 33 APPENDIX A: BOARD LAYOUT - JUMPER POSITIONING......................................... 37 APPENDIX B: HARDWARE DEFINITION CODE ......................................................... 41 APPENDIX C: INPUT RANGE CODES......................................................................... 43 APPENDIX D: SPECIFICATIONS................................................................................. 45 APPENDIX E: ORDER MATRIX.................................................................................... 49 APPENDIX F: SOFTWARE REFERENCE SHEET....................................................... 51 Despatch Product Warranty.......................................................................................... 53
ii
1.2 Displays
Each instrument is provided with dual displays and status indicators as shown in Figure 1 -1. Typically, the upper display displays the value of the process variable, while the lower display displays the setpoint value. Alternate displays can be selected in the Setup Mode.
1.3 Alarms
Alarm indication is standard on all instruments. Up to two alarm outputs are optional. Alarm type may be set as Process Direct or Reverse (high or low), Logical Combination of the two alarms, Annunciator Direct or Reverse, High Limit, or Low Limit. Alarm status is indicated by LED.
Before using any instrument near the device listed, the instructions below should be followed:
1. If the instrument is to be mounted in the same panel as any of the listed devices, separate them by the largest distance possible. For maximum electrical noise reduction, the noise generating devices should be mounted in a separate enclosure. 2. If possible, eliminate mechanical contact relay(s) and replace with solid state relays. If a mechanical relay being powered by an instrument output device cannot be replaced, a solid state relay can be used to isolate the instrument. 3. A separate isolation transformer to feed only instrumentation should be considered. The transformer can isolate the instrument from noise found on the AC power input. 4. If the instrument is being installed on existing equipment, the wiring in the area should be checked to insure that good wiring practices have been followed.
The only wires that should run together are those of the same category. If they need to be run parallel with any of the other lines, maintain a minimum 6 inch space between the wires. If wires must cross each other, do so at 90 degrees. This will minimize the contact with each other and reduces "cross talk". "Cross Talk" is due to the EMF (Electro-Magnetic Flux) emitted by a wire as current passes through it. This EMF can be picked up by other wires running in the same bundle or conduit. In applications where a High Voltage Transformer is used (i.e. ignition systems) the secondary of the transformer should be isolated from all other cables.
This instrument has been designed to operate in noisy environments, however, in some cases even with proper wiring it may be necessary to suppress the noise at its source.
FIGURE 2-4
Contacts - Arcing may occur across contacts when the contact opens and closes. This results in electrical noise as well as damage to the contacts. Connecting a RC network properly sized can eliminate this arc. For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor (1 000 volts) is recommended. For circuits from 3 to 5 amps, connect 2 of these in parallel. See Figure 2-5.
FIGURE 2-5
FIGURE 2-7A Main Supply The instrument will operate on 90-264V AC 50/6OHz main supply. The power consumption is approximately 4 VA. Connect the line voltage, hot and neutral, to terminals 9 to 10 respectively as illustrated below.
FIGURE 2-7B 24V (Nominal) AC/DC Supply The supply connections for the 24V AC/DC versions of the instrument are shown below.
FIGURE 2-8 Thermocouple (T/C) Input Make thermocouple connections as illustrated below. Connect the positive leg of the thermocouple to terminal 5 and the negative leg to terminal 4.
10
FIGURE 2-9 RTD Input Make RTD connections as illustrated below. For a three wire RTD, connect the resistive leg of the RTD to terminal 6 and the common legs to terminals 4 and 5. For a two wire RTD, connect one leg to terminal 5 and the other leg to terminal 6 as shown below. A jumper wire supplied by the customer must be installed between terminals 4 and 5. Input conditioning jumper must be positioned correctly (see Appendix A) and Hardware Definition Code must be correct (see Appendix B).
FIGURE 2-10 Volt, mV Input Make volt and millivolt connections as shown below. Terminal 5 is positive and terminal 4 is negative. Input conditioning jumper must be positioned correctly (see Appendix A) and Hardware Definition Code must be correct (see Appendix B). mADC Input Make mADC connections as shown below. Terminal 4 is positive and terminal 6 is negative. Input conditioning jumper must be positioned correctly (see Appendix A) and Hardware Definition Code must be correct (see Appendix B).
11
FIGURE 2-11 Remote Digital Communications - RS485 Make digital communication connections as illustrated below.
FIGURE 2-12 Remote Reset Connections are made as illustrated below for remote reset.
12
FIGURE 2-14 Relay Output 2 (Alarm or Annunciator) Connections are made to Output 2 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC.
FIGURE 2-15 Relay Output 3 (Alarm or Annunciator) Connections are made to Output 3 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC.
13
FIGURE 2-16 mADC Output 3 (Recorder Output Only) Make connections for DC output 3 as illustrated below.
14
SECTION 3: OPERATION
3.1 Power Up Procedure
Verify all electrical connections have been properly made before applying power to the instrument. During power up, a self-test procedure is initiated during which all LED segments in the two front panel displays appear and all LED indicators are ON. When the self-test procedure is complete, the instrument reverts to normal operation. Note: When power is first applied, a delay of about 3 seconds will be seen before the LEDs will light.
15
3.3 Displays
During configuration the upper display shows the parameter setting. The lower display shows the parameter code (tag name) for the currently selected parameter. During operation, the upper display shows the value of the process variable. The lower display shows the setpoint value. The operation display can be altered by the Display parameter in the Setup mode.
NOTE: This display is available only if one or more of the alarms is/are active.
16
If the process variable attains a value lower than the input scale minimum, the upper display will show:
If a break is detected in the sensor circuit, the upper display will show:
17
In order to reset the limit relay, the process value must not exceed the limit setpoint. Pressing the RESET key with the control in this state will reset the limit relay, and the OUT indicator will turn off. NOTE: The hysteresis limit value in the setup mode affects the value at which the control will reset. In the event of a high limit condition, the high limit setpoint must be higher than the sum of the process value and the hysteresis value. In the event of a low limit condition, the process value must be higher than the sum of the low limit setpoint and the hysteresis value.
3.6 Annunciator
An additional (optional) annunciator output is available. If selected in Program mode (either for USE2 or USE3) the annunciator output operates as follows: If the limit is, or has been, exceeded AND the Reset key has NOT been pressed since the limit was exceeded, then the annunciator output will be active. If the Reset key is pressed while the limit is exceeded, the annunciator output will be deactivated, even if the limit remains being exceeded.
18
If a mode is not enabled it will be skipped over by the routine. The Setpoint Change mode is used to adjust the limit setpoint(s). The Configuration mode is used to configure or re-configure the instrument. The input and output selections are made in the Configuration mode (see Section 6). All possible parameters are illustrated in Table 6-1. Only those parameters that are applicable to the hardware options chosen will be displayed. The Set-Up mode is used to adjust the displays, make alarm settings and retransmit scaling as needed for proper operation of the instrument. See Section 7 for the Set-up mode. Only those parameters that are applicable will be displayed. The Enable mode provides a means of enabling or disabling access to the Program and Set-Up modes, and enables the Setpoint Change parameter. See Section 8 for Enable Mode operation.
19
SEt HiHd LoHd tLE iCor Filt Hyst PoU PoL PHA1 PLA1 PHA2 PLA2 dPoS Euu EuL CCon diSP
= SCROLL key
ALA1
= DOWN key
ALA2 USE2
Press UP key with upper display blank to exit mode. In Configuration Mode, the RESET key must be pressed to store any changed values.
20
21
22
SECTION 6: CONFIGURATION
All configurable parameters are provided in Table 6-1. This table illustrates the display sequence, parameter adjustment and factory setting for each step. Depression of the SCROLL key will cycle the display. To enter the Configuration mode, press and release the SCROLL key until ConF is displayed. Use the DOWN key to enter the Configuration mode. Depress and release the SCROLL key to sequence through the parameters and their values, alternately showing the parameter code in the lower display with the upper display blank, then the parameter code with the parameter value in the upper display. Use the UP and DOWN keys to adjust the parameter values. After adjusting a parameter, the upper display will flash, indicating that the new setting has yet to be confirmed. When the setting is as required, it may be confirmed by pressing the RESET key, and the upper display will stop flashing. After confirming a change, press the SCROLL key to proceed to the next parameter. The DOWN key may also be used to advance to the next parameter when a parameter code is showing in the lower display and the upper display is blank. This is a faster way of scrolling through the parameter list. To exit the Configuration mode, press the UP key whenever a parameter code is displayed in the lower display and the upper display is blank. The instrument will automatically exit the Configuration mode if no key is pressed in one minute. DEFAULT PARAMETER INDICATION If a parameter value, such as Input Select, was changed while in the Configuration mode, a decimal point after each digit will be lit when returning to the Control mode. This display indicates all Setup mode parameters have been set to their default condition. To clear this condition, enter the Setup mode and make a parameter value change and review each parameter for its proper setting.
23
Table 6-1
STEP 1 2 3 4 5
DESCRIPTION Input Range Select Limit Action Limit Maximum Limit Minimum Alarm 1 Type
6 7
9 10 11 12 1 2 3
Hi/Lo/Both +/- SPAN +/- SPAN nonE = No Alarm P_hi = Process High P_Lo = Process Low LiHi = High Limit LiLo = Low Limit Alarm 2 Type ALA2 Same selection as ALA1 Output 2 Usage2 USE2 AL_d = Alm1 Direct LA_r = Annunc. Reverse LA_d = Annunc. Direct Ad_r =Rev Logic AND Ad_d=Dir Logic AND Or_r =Rev Logic OR Or_d=Dir Logic OR A2_r = Alm Rev A2_d = Alm Dir Al_r = Alm1 Rev Output 3 Usage2 USE3 Al-d =Alm Dir rEcP = Rcdr Out P.V. LA_r = Annunc. Reverse LA_d = Annunc. Direct Ad_r = Rev Logic AND Ad_d = Dir Logic AND Or_r = Rev Logic OR Or _d = Dir Logic OR A2_r = Alm2Rev A2_d = Alm2Dir Al_r = Alm Rev Com Bit Rate3 CbS 1200, 2400, 4800, 9600 Com Parity3 CPAr nonE, EvEn, odd 3 Com Address CAd 1 - 32 CJC Enable CJC EnAb diSA Does not appear unless Output 3 is configured as 4-20 mA. Does not appear unless additional output has been selected. Does not appear unless communications option has been selected.
P_hi Al_d
*The Hardware Definition Code and input jumper configuration may need to be changed. See Appendices A and B.
24
LOGICAL COMBINATION OF ALARMS Two alarms may be combined logically to create an AND/OR situation. They may be configured for Reverse-acting or Direct-acting. Either Output 2 or Output 3 may be assigned as Logical Outputs. Example: Logical OR of Alarm 1 with Alarm 2 Direct-Acting AL1 OFF, AL2 OFF: Relay OFF AL1 ON, AL2 OFF: Relay ON AL1 OFF, AL2 ON: Relay ON AL1 ON, AL2 ON: Relay ON Example: Logical AND of Alarm 1 with Alarm 2 Direct-Acting AL1 OFF, AL2 OFF: Relay OFF AL1ON, AL2 OFF: Relay OFF AL1 OFF, AL2 ON: Relay OFF AL1 ON, AL2 ON: Relay ON
Reverse-Acting AL1 OFF, AL2 OFF: Relay ON AL1 ON, AL2 OFF: Relay OFF AL1 OFF, AL2 ON: Relay OFF AL1 ON, AL2 ON: Relay OFF
Reverse-Acting AL1 OFF, AL2 OFF: Relay ON AL1 ON, AL2 OFF: Relay ON AL1 OFF, AL2 ON: Relay ON AL1 ON, AL2 ON: Relay OFF
25
26
DESCRIPTION Alarm Status3 Maximum Hold Minimum Hold Time Exceeded Input Correction Input Filter Hysteresis Limit Process Output Upper Process Output Lower Process High Alarm 11 Process Low Alarm 11 Process High Alarm 21 Process Low Alarm 21 Decimal Position 2 Engineering Units Upper Engineering Units 2 Lower Comm. Enable
+/-Span 0.0 to 100.0 seconds in .5 sec. Increments 0 to 10.0% of span -1999 to 9999 - 1999 to 9999 Span Span Span Span 0, 1, 2, 3 -1999 to 9999 - 1999 to 9999 O=Disable 1 =Enable
27
STEP 18
AVAILABLE SETTINGS 1 = Display Setpoint* 2 = Display Process Variable 3 = Display Process Variable** and Setpoint 4 = Display Blank * If configured for both high and low limit ,the high limit setpoint will be in the upper display and the low limit in the lower display. ** If configured for both high and low limit, pressing the up key while in control mode will display high limit setpoint. Pressing the down key will display the low limit setpoint.
FACTORY SETTING 3
1 2 3
Applies only if process alarm is selected in Configuration mode. Applies only if a linear input has been specified. Only if an alarm is active.
NOTE: Euu and EuL parameters can not be adjusted within the range of the SPhi and SPlo parameters of the Setpoint Change Mode. SPhi and SPlo may need to be changed before properly setting Euu and EuL.
MAXIMUM/MINIMUM HOLD A parameter is available that tracks and saves the maximum (high limit) or minimum (low limit) excursions of the process variable. This parameter is a read only parameter and is viewed in the Set-Up mode, display code HiHd (maximum hold) and LoHd (minimum hold). To reset this parameter, select the parameter and with the numeric value in the upper display, press and hold the UP or DOWN keys. After about 5 seconds, the upper display will indicate ---- for about another 2 seconds, then change to 0.00. Release the key. The value will be held through a supply power down/power up cycle.
28
TIME EXCEED This parameter is available to measure the amount of time that the limit is exceeded. This parameter is a read only parameter and is viewed in the Set-Up mode, display code tLE. The parameter will time in minutes and seconds from 0 to 99 minutes and 59 seconds. After this time the display will change automatically to indicate minutes and tens of seconds from 100.0 to 999.5. For times greater than 999.5 the display will be HH. The value viewed is the cumulative time that the instrument has been out of limit. To reset this parameter, select the parameter and with the numeric value in the upper display, press and hold the UP or DOWN keys. After about 5 seconds, the upper display will indicate ---- for another 2 seconds, then change to 0.00. Release the key. The value will be held through a supply power down/power up cycle.
29
30
31
32
SECTION 9: CALIBRATION
NOTE: Calibration should be attempted only on instruments on which calibration errors have been encountered (see calibration check). EQUIPMENT REQUIRED: 1. Input source with accuracy better than +/- 0.05% of reading. a. b. Thermocouple: DC: T/C simulator, K type with compensated leads 0 to 50 mV 0 to 10 V 0 to 20 mA OR OR
c. 2.
RTD:
MIC1162 case wired for appropriate input voltage supply (90 to 264 VAC, 50/60 Hz)
PROCEDURE: 1. Before applying power, position the input conditioning jumpers on the CPU PWA as appropriate. See Figure A-1 and A-2 in Appendix A. Connect the appropriate input from the Input Source. Set the Input Source as follows: INPUT TYPE DC 0 - 50 mV DC 0 - 10 V DC 0 - 20 mA RTD T/C (Type K) 3. INPUT SOURCE 50 mVDC 10 VDC 20 mADC 200 ohms 0 C
2.
Apply power to the instrument and leave powered for five (5) minutes for RTD and DC inputs OR thirty (30) minutes for T/C inputs, then power down.
33
4.
Apply power to the instrument and within 30 seconds of power-up, press and hold the DOWN and SCROLL keys simultaneously for about 5 seconds. The upper display will show ip_1 and the lower display will show CAL. Use the UP/DOWN keys as required to change the input type number as required: CAL INPUT NO. 1 2 3 4 5 INPUT TYPE DC 0 - 50 mv DC 0 - 10 V DC 0 - 20 mA RTD Thermocouple
5.
NOTE: If required, only one input type may be calibrated. EXCEPTION: If it is required to calibrate the thermocouple input (Input Type 5), it is necessary to calibrate the DC 0 - 50 mV (Input Type 1) first. 6. 7. Press the RESET key, the upper display will show _ _ _ _. After a few seconds, the upper display will show ip_X, where X is the CAL INPUT No., if the calibration was successful. If the upper display shows FAIL, the calibration was not successful - check the jumper positions, wiring, CAL INPUT No. and try again. To calibrate all inputs, repeat steps 2 through 7 for each of the other input types. The calibration procedure is now complete. Disconnect power, remove input connections.
8. 9.
34
CALIBRATION CHECK (See Configuration Mode, Appendix A, and Appendix B.) 1. Power up the instrument and allow to stabilize for at least 5 minutes (RTD and DC) or 30 minutes for T/C input. After the stabilization period, connect the appropriate input device and check a number of input points.
2.
35
36
37
38
39
40
41
While the Hardware Definition Code is displayed, depressing the SCROLL key will cause the display to change to: nonE or OPtn r485 or OPtn rrES OPtn
Where none indicates the absence of the communications option and the remote reset option, r485 indicates the presence of the communications option, and rrES indicates the presence of the remote reset option. The code may be changed by pressing the UP and DOWN keys. The RESET key must be pressed when the correct code is displayed. NOTE: It is essential that this code is changed whenever there is a change to the instrument's hardware configuration (change of input/output type, alarm/retransmit output added/removed etc.). The instrument's software depends upon this code to ensure that the instrument operates correctly.
To exit from the Hardware Definition Code display, depress the DOWN and SCROLL keys simultaneously.
42
* Factory default For RTD Inputs Note: Input conditioning jumper JU1 needs to be changed, see Appendix A. Also, the Hardware Definition Code for the input type must be changed, see Appendix B.
INPUT RANGE 0 - 800C 32-1471F 32-572F -101.0-100.0C -149.8-212.0F 0-300C DISPLAYED CODE 7220 7221 2229 2230 2231 2251 INPUT RANGE 0.0-100.9C 32.0-213.6F -200-206C -328-403F -101.0-537.3C -149.8-999.1F DISPLAYED CODE 2295 2296 2297 2298 7222 7223
For DC Inputs Note: Input conditioning jumper JU1 needs to be changed, see Appendix A. Also, the Hardware Definition Code for the input type must be changed, see Appendix B.
INPUT RANGE 0-2OmA 4-2OmA 0-5OmV 10-5OmV DISPLAYED CODE 3413 3414 4443 4499 INPUT RANGE 0-5V 1-5V 0-10V 2-10V DISPLAYED CODE 4445 4434 4446 4450
43
44
APPENDIX D: SPECIFICATIONS
INPUT SPECIFICATIONS General Input Sample Rate: Input Resolution: Input Impedance: Isolation: Four per second 14 bits approximately Greater than 100M ohm resistive (except for DC mA and V inputs) Universal input isolated from all outputs except SSR at 240 VAC.
Thermocouple Types: Calibration: Sensor Break Protection: R, S, J, T, K, L, B and N Complies with BS4937, NBS125 and IEC584. Break detected within 2 seconds. Limit Relay set to OFF; alarms operate as if the process variable has gone over-range.
RTD and DC mV Type and Connection: Calibration: Lead Compensation: Sensor Break Protection:
Three-wire Pt100 Complies with BS 1904 and DIN43760. Automatic Break detected within 2 seconds. Limit Relay set to OFF (0% power); alarms operate as if the process variable has gone under-range.
DC mA and DC V Scale Range Maximum: Scale Range Minimum: Minimum Span: Sensor Break Protection:
-1999 to 9999 -1999 to 9999 1 display LSD Applicable to 4-20mA, 1-5V, and 2-10V ranges only. Break detected within 2 seconds. Limit Relay set to OFF; alarms operate as if the process variable has gone under-range.
45
OUTPUT SPECIFICATIONS OUTPUT 1 (Limit Relay) Relay Contact Type: Rating: Lifetime: Isolation:
OUTPUT 3 (Alarm, Annunciator, or Retransmit) General Types Available: Relay Contact Type: Rating: Lifetime: Isolation: DC Resolution: Update Rate: Ranges: Load Impedance:
Eight bits in 250mS (10 bits in 1 second typical, >10 bits in >1 second typical). 4 per second 0-20mA, 4-20mA, 0-10V, and 0-5V* 0-20mA: 500 ohm maximum 4-20mA: 500 ohm maximum 0- 10V: 500 ohm minimum 0-5V: 500 ohm minimum Isolated from all other inputs and outputs.
Isolation:
46
Two "soft" alarms Up to 2 outputs can be used for alarm purposes Logical OR or AND of alarms to an individual hardware output is available.
PERFORMANCE Reference Conditions Ambient Temperature: Relative Humidity: Supply Voltage: Source Resistance: Lead Resistance: Common Mode Rejection Series Mode Rejection: DC Linear Inputs Measurement Accuracy:
20C 2C 60-70% 90-264V AC 50Hz 1% <10 ohm for T/C input <0.1 ohm/lead balanced (Pt100) >120dB at 50/60Hz giving negligible effect at up to 264V 50/60Hz >500% of span (at 50/6OHz) causes negligible effect
RTD/Thermocouple Inputs Measurement Accuracy: 0.25% of span -1 LSD Note: Reduced performance with Type B T/C between 100-600 C (212 - 1112 F) Linearization Better than 0.2 C any point, any 0.1 C range ( 0.05 C typical). Better than 0.5 C any point, any 1 C range. Cold Junction Compensation: Better than 0.7C
47
Operating Conditions Ambient Operating Temperature: Ambient Storage Temperature: Relative Humidity: Supply Voltage: Source Resistance: Lead Resistance: Temperature Stability:
0 to 55C -20 to 80C 20% - 95% non-condensing 90 - 264 VAC 50/60 Hz 1000 ohm maximum (thermocouple) 50 ohm per lead maximum balanced (Pt 100) 0.01% of Span/C change in ambient
PHYSICAL Dimensions: Mounting: Terminals: Power Consumption: Weight: Front Panel Sealing: Display Character Height: Agency Approvals: 1/16 DIN front panel (48mm x 48mm) 4.33 inches deep Plug-in with panel mounting fixing strap. Panel cut-out 45mm x 45mm. Screw type (combination head) Approximately 4 watts 8 ounces maximum IP65/NEMA4 Top - .36", bottom -.28" FM pending
48
1162
OUTPUT 1 1 Relay OUTPUT 2 0 None 1 Relay* OUTPUT 3 0 None 1 Relay 3 4-20 mA** OPTIONS 0 None 1 RS-485 2 Remote Reset SUFFIX Blank 02
49
50
Hardware Definition HDW DEF OPTION Configuration Mode inPS ACt SPUL SPLL ALA1 ALA2 USE2 USE3 CbS CPAr CAd CJC Enable Mode ENAB ESP ECon ESEt
Setting
Setting
Setting
51
Setup Mode HiHd LoHd tLE iCOR Filt Hyst Pou PoL PHAI PLAI PHA2 PLA2 dPoS Euu EuL CCon diSP Setpoint Change Mode SP SPHi SPLo
Setting
Setting
52
Exclusions
This Warranty DOES NOT cover: 1. damage or malfunctions, or expenses incurred in the process of diagnosing and/or repairing damage or malfunctions, resulting from any of the following: operator error, misuse, abuse, inadequate preventive maintenance, normal wear and tear, service or modifications by other than Despatch authorized technicians, use of the covered product that is inconsistent with the operation manual or labeling, acts of nature (including, without limitation, floods, fire, earthquake, or acts of war or civil emergency), internal or external corrosion, or non-conforming utilities (including, without limitation, electrical, fuel supply, environmental and intake/exhaust installations); 2. repair or replacement of parts or materials designed and intended to be expendable or consumable; 3. routine maintenance; or 4. labor costs incurred for troubleshooting, diagnostics, or testing (except for testing required to verify that a covered defective part or material has been repaired).
Limitations of Liability
Despatch shall not, in any event, be liable for indirect, special, consequential, incidental, or punitive damages or penalties of any kind, including, without limitation loss of revenue, profits or business opportunities resulting from interruption of process or production. In no event shall Despatch be liable for damages in excess of the amounts paid by Customer to Despatch with respect to the applicable product(s). This Warranty does not cover, and Despatch shall not be liable for any losses, costs, damages or expenses resulting from delays in diagnosing or repairing the products, supplying or obtaining replacement parts or materials, strikes, labor stoppages or shortages, fires, accidents, government acts or regulations, or any other causes beyond the control of Despatch.
Non-Compliance By Customer
Despatch reserves the right to suspend and withhold service under this Warranty in the event of non-compliance by the Customer to any terms and conditions of this Warranty or the applicable purchase order or invoice. Further, Despatch shall not be liable for any loss of production, expenses, and inconveniences incurred due to such suspension.
Performance Commitment
Despatch provides no guarantee of process performance or fitness for purpose, unless specifically noted otherwise in Despatch written order acceptance confirmation. Despatch is providing equipment with design parameters specific only to its equipment.
Transportation Costs
All transportation costs to transport defective parts or materials to Despatch, and to transport repaired or replacement parts or materials to Customer, shall be the responsibility of the Customer.
THE REPRESENTATION AND WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND IN LIEU OF, AND CUSTOMER HEREBY WAIVES AND DISCLAIMS RELIANCE UPON, ALL OTHER REPRESENTATIONS AND WARRANTIES OF EVERY KIND WHATSOEVER, WHETHER EXPRESS OR IMPLIED, OR ARISING BY OPERATION OF LAW OR IN EQUITY, OR BY COURSE OF PERFORMANCE OR DEALING OR USAGE OF TRADE, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE. THIS WARRANTY IS PERSONAL TO THE CUSTOMER AND MAY NOT BE TRANSFERRED OR ASSIGNED. ALL LIMITATIONS HEREUNDER, HOWEVER, SHALL BE BINDING ON ALL SUCCESSORS AND ASSIGNS OF CUSTOMER.
Service Worldwide Phone 612-781-5356; Worldwide Fax 612-781-5485; North American Phone 800-473-7373 www.despatch.com
BB5 (12/01)
Despatch continues to deliver exceptional products backed by a strong sense of responsibility and drive for long term customer satisfaction. Your partnership with Despatch can offer even higher value through your subscription to one of Despatch's Advantage Service Assurance Program (ASAP).
Warranty
Despatch's exclusive, comprehensive service programs start with the 1 year parts only warranty which is described on the other side of this document. This warranty can be expanded immediately to meet your most stringent service needs. Despatch Service Products Group will be able to answer your service questions and provide a quotation for the immediate expansion of your product warranty. Call 800-473-7373.