Document Title: Data Sheet for Distribution Transformer
ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:
Date:7/30/2011
Rev.: 0
Page 1 of 5
MUNICIPALITY OF TEHRAN
NIAYESH TUNNEL
Document Title:
Data Sheet for Distribution Transformer
Client Doc. No.: XXXXXXXXXXXXXX Contractor Doc No.: XXXXXXXXXXXXXXXXX
0 Rev
7/30/2011 Date dd.mm.yy
A.Ghafouri TABLIEH Prepared
S.BAYANI TABLIEH Checked P.O.R
For review
Purpose of Issue
Approved
To
Set
Distributed
File Name: xxxxxxxxxxxxxxxxxxxxxxxxx
Contractor J.V.
Client
Consultant J.V.
Document Title: Data Sheet for Distribution Transformer
ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:
Date:7/30/2011
Rev.: 0
Page 2 of 5
Tabulation of Revised Pages
Page 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 00 X X X X X 01 02 03 04 05 06 07 Page 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 00 01 02 03 04 05 06 07
File Name: xxxxxxxxxxxxxxxxxxxxxxxxx
Contractor J.V.
Client
Consultant J.V.
Document Title: Data Sheet for Distribution Transformer
ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:
Date:7/30/2011
Rev.: 0
Page 3 of 5
No.
1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2..2 2.3 2.4 2.5 2.6 2.7
Description
GENERAL Application Type Rated output Quantity required Installation No load transformer ratio Number of phases Rated frequency Type of cooling WINDING Type of transformer Material of conductor Method of connection Method of connection Vector group LV Neutral Insulation of Windings H.V and L.V. One minute power Frequency withstand voltage (dry and wet) 1.2/50 micro second full wave impulse withstand TAP CHANGER Tap changer Tapping on winding HV/LV Type of Tap Changer Tap range Tap step SYSTEM DATA Nominal System Voltage On HV Side Highest System Voltage on HV side Nominal System Voltage on LV side Highest System Voltage On LV Side Fault level on HV side Fault level on LV side System Neutral on HV side
Unit
Technical Particulars Specification
Distribution Transformer Cast Resin 250 KVA Two Indoor 30/0.420 Three 50 AN 2 winding Electrolytic Cu conductor Delta Star Dyn 11 Solidly earthed H.V L.V Xx 2.5 75
Bidders configuration
Insulation KVA Nos. Indoor/Outdoor kV/kV Nos. Hz AN 2-wdg/ 3-wdg/ Auto
HV winding LV winding
kV (r.m.s)
2.8 3.0 3.1 3.2 3.3 3.4 3.5 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7
kV (Peak)
OLTC/ OCTC/ Off-Circuit link % 2.5% kV kV kV kV kA kA
By means of links HV Off Circuit links +5% t o - 5 % 2.5% 30 33 0.420 0.5 25 kA for l sec 50 kA for lsec -
File Name: xxxxxxxxxxxxxxxxxxxxxxxxx
Contractor J.V.
Client
Consultant J.V.
Document Title: Data Sheet for Distribution Transformer
ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:
Date:7/30/2011
Rev.: 0
Page 4 of 5
No.
4.8 5.0 5.1 5.2 5.3
Description
System Neutral on LV side TERMINATIONS Terminal connection HV termination Entry Termination size
Unit
Technical Particulars Specification
Solidly Earthed
Bidders configuration
Busduct/Cable Box Top/Bottom
In-built cable box Bottom Suitable for 30 kV (E) grade cable, 3x1Cx 95 sq.mm busduct Top Suitable for 1.1 kV (E) Grade busduct Solidly Earthed
5.4 5.5 5.6 6.0 6.1 6.2 6.3 6.3.1 6.3.2 7.0 7.1 7.2 8.0 8.1 8.2 9.0 9.1 9.2 9.3 10.0 10. l 10.2 10.3 10.4 11.0
LV termination Entry Termination size NEUTRAL Transformer Neutral on HV Side Transformer Neutral on LV side EARTH BUS Material Size TEMPERATURE RISE Ambient temperature End Temperature after rise PAINTING Paint type Paint Shade MOVEMENT Type of Wheels Wheel gauge Direction of Wheels Miscellaneous Accessories Spares Configuration of HV/LV Routine tests to be carried out No Load Loss
Busduct/Cable Box Top/ Bottom
Electrolytic Cu 2 no 50x6 mm strip Deg C Deg C 40 90 Deg C Class F. Epoxy Siemens grey RAL 7032 Plain/ Flanged Unidirectional/ Bidirectional Reqd/ Not Reqd Reqd/ Not Reqd degrees Yes/No KW Plain As per site requirement Bidirectional
Epoxy/ Synthetic enamel
Required Required As per site requirement Yes BY bidder
File Name: xxxxxxxxxxxxxxxxxxxxxxxxx
Contractor J.V.
Client
Consultant J.V.
Document Title: Data Sheet for Distribution Transformer
ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:
Date:7/30/2011
Rev.: 0
Page 5 of 5
No.
11.1 12.0 13.0
Description
Full Load Loss % impedance Degree of protection for enclosure
Unit
KW As per IS
Technical Particulars Specification
By Bidder 5 % at 75 deg C IP23
Bidders configuration
File Name: xxxxxxxxxxxxxxxxxxxxxxxxx