Differential Protection
Differential Protection
Differential Protection
Used where:
Can be used on all items of plant in one form or another (i.e. Generators, transformers, lines, cables, busbars, motors) to form a defined zone of protection dictated by current transformer location.
Protected Circuit
Protected Circuit
Requires matched current transformers of low reactance design, typically class X or equivalent Equal CT ratios Typically current operated relay with an external stabilising resistor Non-linear resistor may be required to limit voltage across relay circuit during internal faults Suitable for zones up to 200 - 300 metres (typically)
ZM
RCT
RL IS IF RL
RCT
ZM
VS
RL
R RL
Maximum voltage across relay circuit, Vs = If (RCT + 2RL) To limit current through relay to < Is the relay impedance Rrelay > Vs/Is
Stabilising Resistor
Where relay impedance alone is too low to ensure stability then the relay circuit impedance can be increased through the addition of an external resistor connected in series with the relay Required circuit impedance > Vs/Is RSTAB > (Vs/Is) - Rrelay
Current transformers must have sufficient output to ensure fast operation of relay during internal fault conditions Required Vk > 2 Vs (typically - depends on actual relay type)
During internal faults the high impedance relay circuit constitutes an excessive burden to the CTs. A very high voltage develops across the relay circuit and the CTs which can damage the insulation of CTs, secondary wiring and relay.
RST VM VS RR
Metrosil Characteristic V = CI
High Impedance protection limits the spill current to a value less then relay setting Low Impedance principle provides no such limit on spill but instead artificially raises the setting of the relay The higher the through current, the higher the potential spill and hence the greater the increase in setting Required The increase in setting is therefore normally based on a percentage of the through current
Spill Current
Low Imp.
Trip
No Trip
Is
Through Current
High Imp.
Differential Current
I1
BIAS
BIAS I1 - I2
I1 - I2 I2
OPERATE
OPERATE
RESTRAIN
I1 + I2 2
Biased Characteristic
Differential Current
5.0
30% Bias
4.0
OPERATE
3.0
RESTRAIN
2.0
1.0
0.2 2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
Through Current
Does not rely on equal ratio CTs (ratio correction can be done via external interposing CTs or internally to the relay) Limit on allowable spill dictated by percentage of bias used - practical limit to give sufficient sensitivity to internal faults Amount of spill related to CT size - stability limits and CT requirements are therefore dependant on each other
Relaying Point
R Trip B
Trip A
Relaying Point
Trip B
B I V
OP
OP
Circulating Current
Summation Transformers
3
IN Let output for operation = K
(1)
IB (1 + 3) > K
(3)
IC x (3) > K
(4)
(5)
(6)
IAC (1 + 1) > K
Ks is a setting multiplier, variable from 0.5 to 2.0 In is the relay rated current 1 Amp or 5 Amps
Line charging current produce certain amount of unbalancing ATs under normal steady state conditions when balanced 3 charging current flows. Unbalancing ATs = 3 IC ATs of most sensitive fault setting = (2 + N) IA where IA = setting for A-E fault
A 0.35 C
IA
> IC
Note: For EHV cables, one relay per phase is sometimes used to avoid lack of sensitivity for phase faults.
Pilot Characteristics
Pilot Wire
Resistance and shunt capacitance of pilots introduce magnitude and phase differences in pilot terminal currents. Pilot Resistance Attenuates the signal and affects effective minimum operating levels. To maintain constant operating levels for wide range of pilot resistance, padding resistor used.
Rp/2
Rp/2
Pilot Capacitance
Circulating current systems : Pilot capacitance effectively in parallel with relay operating coil. Capacitance at centre of pilots has zero volts across them.
Pilot Isolation
Electromagnetic Induction Field of any adjacent conductor may induce a voltage in the pilot circuit. Induced voltage can be severe when : (1) Pilot wire laid in parallel to a power circuit.
Danger to personnel
Danger to equipment Difference in Station Earth Potentials
De =
Pilot circuits and all directly connected equipment should be insulated to earth and other circuits to an adequate voltage level. Two levels are recognised as standard : 5kV & 15kV
Relay Case 5kV Relay Input Pilot Terminal Relay Circuit Pilot Wire 2kV 5kV 15kV
Pilot circuits are subject to a number of hazards, such as : - Manual Interference - Acts of Nature (storms, subsidence, etc.) - Mechanical Damage (excavators, impacts) Therefore supervision of the pilots is felt to be necessary. Two types exist : - Signal injection type - Wheatstone Bridge type
Maloperation occurs even under normal loading conditions if 3-phase setting < ILOAD. Overcurrent check may be used to prevent maloperation. Overcurrent element set above maximum load current.
50C
50 G
50A-1
+
50C-1
50G-1
Isoc > Ifl 0.9 Isef > 1.2 IZ Isef < 0.8 x Ief
Source
Feeder Protection Busbar Protection
PILOT WIRES
TRIP
TRANSFORMER PROTECTION
TRIP
End A
End B
A/D
OPGW
interface unit
850nm multimode optical fibre
Multiplexer
G.703 or V.35 electrical
interface unit
ISDN
X.21 electrical
Multiplexer
34 Mbit/s
64k bits/s Telephone Telecontrol
Multiplexer
End A
Teleprotection
End B
PCM Multiplexer
End A
Teleprotection
End B
Receiver Sensitivity
Optical Budget Less Safety Margin (3dB)* Typical Cable Loss Max. Transmission Distance
-25.4dBm
5.6dB 2.6dB 2.6dB/km 1km
-38.2dBm
30.0dB 27.0dB 0.8dB/km 33.7km
-38.2dBm
30.0dB 27.0dB 0.4dB/km 67.5km
-38.2dBm
30.0dB 27.0dB 0.3dB/km 90km
Short Haul
Key: * 3dB allowance for joint loss/ageing
Long Haul
Relay B
Propagation delay
MiCOM-P540-52
IR
IchL
VL
IchR
VR
Conventional current differential protection needs to be set above Ich to avoid tripping for 50/60Hz line charging current Modern relays can extract Ich to allow more sensitive current settings to be applied
Power transformer
Ratio correction
Direct Intertrip
Relay A
DTT=1
Relay B
Transformer Protection
Data Message +
The channel could alternatively be used along with the distance elements and PSL to configure permissive or blocking distance aided schemes
Permissive Intertrip
IB F Relay A Relay B Busbar Relay
PIT=1
Data Message
+ +
Example shows interlocked overcurrent protection Feeder fault seen within busbar zone Remote end trip after set delay for PIT & current > Is1