1
Classroom Rules:
1. I talk, you listen
2. I dont allow:
A. Heads on desk
B. Feet on desk
C. Going to sleep in class
D. MP3 players
3. Mobile phones are to be off, or on silent unless
OKd with me, and in you bag (not on desk)
4. Should they be OKd, and you receive a call, you
will answer it outside the classroom
5. No SMS-ing in class
6. Keith Butlers number is: 0417 637 909
Topics (from Learning Outcomes)
10. Three-phase synchronous machines
operating principles
construction feature
application
11. Three-phase synchronous machines
effects of load changes
effects of excitation change
load/current characteristics
12. Single phase synchronous machines
alternators
motors
applications
Assessment
(a)All pracs must be completed
A final written exam will be given on the
learning outcomes covered. Should a
student fail, they will be allowed one
further attempt during block. Should
they fail this they will be allowed one
further attempt within six weeks of
completing the block. Should they fail this
they will be in a Show Cause situation.
500 KW Genset / Generator Set, powered with a Cummins VTA28G1 Engine
2 x 14MW Synchronous Motors
apparently, they use permanent magnets!
9
10
3 phase Dunlite machine
11
12
Synchronous machines are not
just the big units, but they can
be small also.
13
14
AC Supply
V
I
Time->
Current is in phase
with voltage.
15
AC supply
V
I
V
I
Current lags the
Voltage by 90o
16
AC Supply
Current appears to pass through the capacitor.
In reality, it is charging in one direction, and then
discharging and recharging in the other direction.
But if an ammeter were placed in series it would
most definitely read a current.
17
AC Supply
Current leads the
Voltage by 90o
18
Both Inductors and Capacitors oppose, or resist
current flow when connected to AC supplies.
This opposition to current flow is called:
Inductive reactance, in inductors. (XL)
Capacitive reactance in capacitors. (XC)
While it opposes current flow, it is NOT called resistance.
Current flow through resistance produces HEAT.
Current flow in inductors and capacitors doesnt!
19
20
Generator / Transformer / Motor
21
Motor
N
B
C
?????
A
B
Why isnt a neutral run to a balanced
three phase Star connected load?
22
Motor
A
0A
N
B
C
0V
0V
A
B
Because the Star point is at 0V
And the neutral is at zero volts also.
So if they were joined no current would flow.
So why join it?
23
Motor
A
C
B
C
A
B
The neutral is not connected to a balanced
three phase star connected load.
Only connected to unbalanced loads!!!
24
Transformer
S
A
B
F
F
Generator / Transformer / Motor
25
Swapped
Transformer
F
A
B
S
S
Generator / Transformer / Motor
26
3-phase Transformer Secondary
Note that all windings are connected in series, with the two
ends joined together.
27
If we did that with three batteries, there would be major
problems!
28
Transformer
F
S
VC
VB
VA
The voltmeter should read the sum of the three voltages?
Right?
The voltmeter reads the phasor sum of the voltages.
29
Transformer
F
S
VC
VB
VA
The voltmeter reads, in effect, the distance between the
beginning of VA and the end of VC. ie. 0V
We can connect the two ends together because the
phasor sum adds up to zero!
30
Transformer
No Arc!
VC
VB
VA
The voltmeter reads, in effect, the distance between the
beginning of VA and the end of VC. ie. 0V
We can connect the two ends together because the
phasor sum adds up to zero!
31
32
STAR
VL = 3 VPH
IL = IPH
Generator
P = 3 x VPH x IPH x Cos
= 3 x VL/3 x IL x Cos
= 3/3 x VL x IL x Cos
= 3 VL x IL x Cos
DELTA
IL = 3 IPH
VL = VPH
Load
P = 3 x VPH x IPH x Cos
= 3 x VLx IL/3 x Cos
= 3/3 x VL x IL x Cos
= 3 VL x IL x Cos 33
NOT:
P = 415 x I x pf.
P = 3 VL x IL x Cos
34
Three Single Phase Power Equations:
True Power = Watts = V x I x Cos
Apparent Power = VA = V x I
Reactive Power = VARs = V x I x Sin
Power Factor = Cos
where Cos = Cosine of the angle
between Voltage
and Current
35
This can be put as a triangle:
VA
Vars
Phase angle
between current
and volts
Watts
VA2 = Watts2 + Vars2
36
Alternators, where the windings are limited by the
current through them, are rated in VA.
To rate them in watts, (ie. watts delivered to the load)
would give no idea of the current through them.
Load 3 = 14.14A at 45
P = V x I x Cos 45
= 240 x 14.14 x 0.707
= 2.4kW
V=240V
Load 1 = 10A
P = V x I x Cos 0
= 240 x 10 x 1
= 2.4kW
Load 2 = 20A at 60
P = V x I x Cos 60
= 240 x 20 x 0.5
= 2.4kW
37
Q What dictates the phase angle of the current
supplied by a single alternator supplying a single load?
A The load
Load 3 = 14.14A at 45
P = V x I x Cos 45
= 240 x 14.14 x 0.707
= 2.4kW
V=240V
Load 1 = 10A
P = V x I x Cos 0
= 240 x 10 x 1
= 2.4kW
Load 2 = 20A at 60
P = V x I x Cos 60
= 240 x 20 x 0.5
= 2.4kW
38
Al currents here take the same power
Constant power line
39
Al currents here take the same power
Higher power
40
Al currents here take the same power
Constant power line
41
Al currents here take the same power
Lower power
42
43
44
Lo
ss
es
Alternator
Prime
Mover
Mechanical Energy
- Diesel Engine
- Steam Turbine
- Small petrol engine
Alternator
Electrical Energy
Alternator:
Pin = Pout + Losses
Alternator:
Pout
Eff% =
x 100
Pin
45
Lo
s
se
Synchronous Motor
Electrical
Energy
MSB
Motor
Pin = Pout + Losses
Motor
Mechanical Energy
Load
Motor:
Pout
Eff% =
x 100
Pin
46
Synchronous Machine
Electrical
Power
Stator
- Identically wound
to an induction motor.
- Connected to supply.
DC
Supply
Rotor
- Constant DC field
- Connected to supply
via sliprings.
47
SYNCHRONOUS
MOTOR
The stator produces a rotating magnetic field
exactly the same as an induction motor.
The rotor is a magnet and locks in to the RMF
Rotor travels at SYNCHRONOUS SPEED.
48
Synchronous Machine
Electrical
Power
DC
Supply
If a synchronous motor is OVER driven by the load
(eg electric train going down a hill), then it will
generate power, still at synchronous speed.
If an alternator coupled to the grid is UNDER driven
by the prime mover (eg steam stops), then it will
motor, and drive the turbine at synchronous speed. 49
Synchronous Machine
Electrical
Power
DC
Supply
In other words, the two machines are identical in
construction.
50
51
Characteristic of WEG Induction Motors.
3000RPM
1500RPM
1000RPM
4kw
7.8A, .87pf
8.2A, .82pf
9A, .74pf
11A, .63pf
22kw
39A, .87pf
41A, .83pf
42A, .80pf
47A, .74pf
110kw
182A, .90pf
200A, .84pf
205A, .80pf
203A, .81pf
150kw
242A, .90pf
265A, .87pf
279A, .80pf
278A, .77pf
185kw
310A, .88pf
315A, .86pf
343A, .80pf
348A, .78pf
220kw
362A, .89pf
375A, .86pf
408A, .78pf
412A, .78pf
What is the
tendency as RPM
gets lower?
750RPM
Lower the RPM,
Larger value IS
More lagging IS
52
So why use a Synchronous Motor?
Uses:
Low Speed Drives. Low speed induction motors
draw very large currents at poor power factors.
This cannot be altered or corrected. In
synchronous motors, the p.f. can be altered to
cause the motor to draw minimum current. (The
alternative is to use a high speed induction
motor through a gearbox.)
Power Factor Correction
Constant Speed drives
53
54
55
56
2 basic types:
Cylindrical rotor
Salient Pole
Salient Pole Rotor
-Low speed
-Diesel Prime Mover
-Hydro systems
Cylindrical Rotor
-High speed
-Steam Turbine
57
58
59
60
61
62
63
Small salient pole synchronous machine rotor
www.tecowestinghouse.com
64
65
66
67
68
69
70
71
72
73
74
Lo
s
se
Synchronous Motor
Electrical
Energy
MSB
Motor
Pin = Pout + Losses
Motor
Mechanical Energy
Load
Motor:
Pout
Eff% =
x 100
Pin
75
Same as an induction motor.
76
A1
2-Pole Machine
ie. 3000RPM
A2
77
78
A1
2-Pole Machine
ie. 3000RPM
C2
B2
In reality, the coils
span more slots in
a 2-pole motor.
B1
C1
A2
Notice that for a
two pole stator we
have a 2-pole rotor
79
N
S
C
4-pole machine
A four pole stator
must have a four
pole rotor
80
N
S
S
N
+
Flux
-
Time->
Resultant flux =
1.5 x flux of one phase
81
+
Flux
-
Time->
S
Resultant flux =
1.5 x flux of one phase
82
3 4 5 6
+
Flux
-
Time->
83
1 2 3 4 5 6
+
Flux
-
Time->
So the flux rotates one full rev in one cycle,
for our two pole machine.
84
1 2 3 4 5 6
+
Flux
-
Time->
Because the flux is a constant value, it gives:
1. Very quiet operation
2. Constant torque as the rotor rotates.
85
1 2 3 4 5 6
+
Flux
-
This rotating magnetic field rotates at:
3000RPM for a 2-pole motor
1500RPM for a 4-pole motor
Time->
86
1 2 3 4 5 6
+
Flux
-
Time->
To reverse the direction of rotation:
reverse any two phases to the motor.
87
N = 120f/P
where N = RPM
f = frequency
P = Number of poles (per phase).
So the speed of the rotating magnetic field is
affected by:
Frequency, and
Number of poles.
88
As the rotating magnetic field rotates, the
rotor is locked in synchronism with it and is
dragged along for the ride.
89
As the rotating magnetic field rotates, the
rotor is locked in synchronism with it and is
dragged along for the ride.
90
What will happen as a load is put on the shaft?
91
What will happen as a load is put on the shaft?
92
The load tries to slow it down.
But it must do synchronous speed!
So it stretches the lines of flux.
93
C/L of Rotor Field
Torque Angle
C/L of RMF
94
If the lines stretch to breaking point (ie too
much load), then the rotor stalls
This is referred to as Pull Out Torque.
95
What would the Torque Curve look like?
Torque
Torque Curve for an
induction motor
0
RPM
Ns
96
What would the Torque Curve look like?
Pull out
Torque
Torque Curve for a
Synchronous Motor
Torque
Zero Torque below
synchronous speed
0
RPM
Ns
97
Starting a Synchronous Motor?
1. Amortisseur winding
98
99
Rotor Construction
Squirrel Cage
100
101
102
Starting a Synchronous Motor?
1. Amortisseur winding
This gets the motor up to speed as an
induction motor. When it is close to
synchronous speed it will lock in.
2. Shorting the rotor DC winding and
starting it as a wound rotor motor.
When it is close to synchronous speed,
the short is removed and DC is applied
to the rotor. It will (hopefully) lock
in.
103
Starting a Synchronous Motor?
3. Using a pony motor to get the
synchronous motor up to speed, then
applying AC to the stator and DC to
the rotor.
(Not applicable if there is a high
starting torque load connected)
Note that these starting methods will only
work if the load on the motor at start can be
reduced or eliminated.
104
Hunting is rhythmic fluctuations of the
RPM around an average value.
If not subdued, hunting can cause
the rotor to swing out of synchronism.
Amortisseur windings also reduce hunting.
105
Revs
Time
106
SS
N N
And all this while it is whizzing
around at synchronous speed!
107
And all this while it is whizzing
around at synchronous speed!
108
109
Phasor Diagram of Synchronous Motor
Vinduced
Vsupply
Induced in the
stator from
the rotor
110
Phasor Diagram of Synchronous Motor
Vinduced
VR
Vsupply
Isupply
Torque angle
111
Phasor diagram for increased load:
(Excitation current held constant)
VR
Vinduced
Vinduced
Vsupply
Isupply
Increased load = Increased Torque Angle
Increasing the load increases the power taken from supply
112
Phasor diagram for increased excitation:
(Constant Load)
Constant load = Constant Power line
Vinduced
Vinduced
Vsupply
113
Phasor diagram for increased excitation:
(Constant Load)
Constant load = Constant Power line
Vinduced
Vsupply
114
Phasor diagram for increased excitation:
(Constant Load)
Constant load = Constant Power line
Vinduced
Isupply
VR
Vsupply
So to force the supply current leading,
we INCREASE excitation
115
Phasor diagram for decreased excitation:
(Constant Load)
Constant load = Constant Power line
VR
Vinduced
Vsupply
Isupply
116
Phasor diagram for decreased excitation:
(Constant Load)
Constant load = Constant Power line
Vinduced
VR
Vsupply
Isupply
So to force the supply current lagging,
we DECREASE excitation
117
Constant load = Constant Power line
VR
Vinduced
Isupply
Vsupply
VR
Vinduced
Vsupply
Isupply
Vinduced
VR
Vsupply
118
With a constant load, changing excitation changes
the phase angle and value of supply current.
Constant load = Constant Power line
Vsupply
Isupply
By increasing the DC excitation current to the rotor,
the synchronous motor can act as a capacitor
It can be used for power factor correction.
119
Lag
50
%
lo
ad
Stator Current
Unity pf
Lead
Excitation Current
120
Deductions From Vee Curves
At any particular load there is a certain value of rotor
current which gives a minimum value of stator current and
unity pf.
If the rotor current is altered either way, the stator
current will increase, and pf will decrease away from 1.
For any given load there is a certain value of rotor current
below which the rotor will fall out of synchronism.
For any given load there are two values of rotor current that
will give identical values of stator current. The lower value
gives a lagging pf, and the higher value gives a leading pf.
121
ad
lo
50
%
lo
ad
pf=1
75
%
Stator Current
Stability
limit
Lead
Lag
Excitation Current
122
Per unit
Power output
0.8 pf lag
Unity
0.8 pf lead
123
124
125
Points:
At a set load there is a value of excitation that
will give minimum line current.
Reducing OR increasing excitation from this value
will only increase line current.
At any other value of line current, there are two
values of excitation current that can produce this.
If a synchronous motor is heavily loaded, supply
current may not be able to be driven highly
leading.
If a synchronous motor is lightly loaded, supply
current can be driven highly leading.
126
Single Phase Synchronous Motors
Used when constant speed is critical, with low torque
requirements. They have low efficiency, hence made in small sizes.
Application:
clocks
record players
timers
recorders
communications
servo installations
Two main types:
Reluctance motor
Hysteresis motor
127
Reluctance Motor
Stator
Stator same as a single phase, split
phase motor.
Centrifugal Switch operates at 75%
synchronous speed to open circuit the
start winding.
Two pole, 3000 RPM
rotor
Rotor
Assembled from laminated sheets
with defined teeth cut away. This
forms salient poles.
Windings are of the squirrel-cage
type.
Number of rotor poles equals the
number of stator poles.
128
Reluctance Motor
Operation
Starts as an induction motor, with slip.
A single phase stator has a Start and Run winding. At
75% centrifugal the centrifugal switch operates.
As the load is light there is small slip
The salient poles become permanently magnetised by the
stator field
The salient poles will then lock to the stator field.
Once locked into synchronism the motor will continue to
operate at synchronous speed.
Not as much power output as a similar physical size 1-phase
motor.
129
Hysteresis Motor
Rotor
Constructed from hardened steel rings, instead of thin,
magnetically soft, silicon steel laminations.
Hysteresis opposes any change once the flux is created,
so the rotor will lock into the RMF like a permanent magnet.
Stator
Often a shaded pole stator principle is used.
If the shaded pole principle is used then the motor is self
starting.
Magnetic poles are established in the rotor.
These poles lock to the stator poles.
The rotor runs at synchronous speed determined by the
poles and frequency.
130
131
Why generate AC? Why not DC?
Large brushless DC generators are not possible
Large brushless AC alternators are!
DC cant be transformed through a transformer.
AC can go through a transformer.
Why do we want to transform it?
It is easier to transmit to distant places
at higher voltages as the current
will be lower. (P=V x I)
Induction motors are simpler and cheaper than
DC motors
132
133
Generating an AC Voltage
N
S
134
Generating an AC Voltage
+
Volts
Time->
135
Generating an AC Voltage
N
S
+
Volts
Time->
136
Generating an AC Voltage
+
Volts
Time->
137
Generating an AC Voltage
+
Volts
Time->
138
Generating an AC Voltage
+
Volts
Time->
139
Generating an AC Voltage
N
S
+
Volts
Time->
140
3-Phase
Generating a AC Voltage
N
S
141
3-Phase
Generating a AC Voltage
Require:
Three sets of coils
physically displaced
from each other by
120 electrical.
+
Volts
Time->
142
3-Phase
Generating a AC Voltage
VC
N
VA
VB
143
3-Phase
Generating a AC Voltage
A1
A2
144
3-Phase
Generating a AC Voltage
A1
B2
C2
C1
B1
A2
145
3-Phase
Generating a AC Voltage
N
S
C
4-pole machine
A four pole stator
must have a four
pole rotor
146
Alternator
Reasons for having the three phase winding on the
stator rather than the rotor:
More space on the stator for the three phase
winding.
Only one, low voltage winding on the rotor.
Easier to insulate.
Less problems with centrifugal force.
Only two sliprings required rather than four
(3-ph + N)
147
Electrical
Power
Stator
- Connected to load.
Magnetic Field
Alternator
Mechanical
Power
Rotor
- Constant DC field
- Connected to its own DC
supply via sliprings.
148
Alternator
Alternator
Petrol
Engine
Q: What keeps an alternator producing 50Hz under all
load conditions?
A: The governor on the prime mover. It detects any
drop in speed, and tries to speed the unit up.
149
150
Alternator Excitation Curve
VOUT
(No Load)
IFIELD
151
Alternator
Internal
Impedance
XL
R
Load
Alt
152
Resistive Load
VGEN
VZ
ILOAD
VOUT
VL
VR
VR = Internal Resistance of the alternator
VL = Internal Reactance of the alternator
VZ = Internal Impedance of the alternator
153
Resistive Load
VGEN
VZ
ILOAD
VOUT
VL
VR
Notice that terminal volts DROP as load increases
Load current and p.f. are dictated by the LOAD!
154
Inductive Load
V
VGEN
VOUT VR
ILOAD
Parallel
155
Inductive Load
V
VOUT VR
VGEN
V
ILOAD
Now there is a greater voltage drop under load
156
Capacitive Load
VGEN
ILOAD
VOUT
Parallel
Now there is a voltage RISE under load
Because of the voltage rise under load, it is
not desirable to run alternators at a
leading power factor.
157
Effect of Power Factor on
Output Voltage
Leading pf
Output
Voltage
Unity pf
Lagging pf
Load Current
158
Voltage Regulation
%Voltage Regulation =
(VNL VFL)
VFL
x 100
eg An alternator output falls from 240V to 200V
with constant excitation.
Calculate the % voltage regulation.
(Ans: 20%)
159
Alternators - stand alone
Summary:
When an alternator is standing by itself with a single load:
Output voltage is affected by excitation current
Output frequency is affected by input power to the
alternator.
160
Alternators tied to the Grid
When an alternator is tied to the grid, you cannot change:
Grid voltage
Grid frequency
So the output voltage of the alternator will not change, and
the output frequency of the alternator will not change.
Notice that, for a stand alone alternator with stand alone
load, these are the two things that changed when:
(a) the excitation was altered, and
(b) the power input to the alternator was increased
(ie. Put the foot down on the prime mover)
161
Alternators tied to the Grid
1. Altering Excitation.
VGEN
VZ
ILOAD
VL
VOUT VR
If excitation is increased, and VOUT cannot alter, VGEN
will increase and push the triangle over.
162
Alternators tied to the Grid
1. Altering Excitation.
Constant Power Line
(Output power of the
alternator has not
Changed)
ILOAD
VOUT VR
VGEN
V
If excitation is increased, and VOUT cannot alter, VGEN
will increase and push the triangle over.
Note that input power to the alternator is not changing,
so output power does not change either.
163
Alternators tied to the Grid
1. Altering Excitation.
ILOAD
VOUT VR
VGEN
V
If excitation is reduced, and VOUT cannot alter, VGEN
will reduce and pull the triangle back.
This drives the load current lagging
164
Alternators tied to the Grid
1. Altering Excitation.
VGEN
ILOAD
VL
VZ
VOUT
VR
If excitation is reduced, and VOUT cannot alter, VGEN
will reduce and pull the triangle back.
This will drive the load current leading
165
Alternators tied to the Grid
2. Altering input power to the alternator.
VGEN
VZ
ILOAD
VL
VOUT VR
If input power is reduced, and frequency and VOUT
cannot alter, output power will reduce.
166
Alternators tied to the Grid
2. Altering input power to the alternator.
VGEN
VZ
ILOAD
VL
VOUT VR
If input power is reduced, and frequency and VOUT
cannot alter, output power will reduce.
167
Alternators tied to the Grid
2. Altering input power to the alternator.
VGEN
VZ
ILOAD
VOUT VR
VL
Size of triangle
reduces
If input power is reduced, and frequency and VOUT
cannot alter, output power will reduce.
168
Alternators tied to the Grid
2. Altering input power to the alternator.
VGEN
VZ
VL
VR
ILOAD
VOUT
Size of triangle
reduces
If input power is reduced, and frequency and VOUT
cannot alter, output power will reduce.
169
Alternators tied to the Grid
2. Altering input power to the alternator.
VGEN
VZ
ILOAD
VL
VOUT VR
If input power is increased, and frequency and VOUT
cannot alter, output power will increase.
170
Alternators tied to the Grid
2. Altering input power to the alternator.
VGEN
VZ
ILOAD
VL
VOUT VR
If input power is increased, and frequency and VOUT
cannot alter, output power will increase.
171
Alternators tied to the Grid
2. Altering input power to the alternator.
VGEN
VZ
ILOAD
VL
VOUT VR
If input power is increased, and frequency and VOUT
cannot alter, output power will increase.
172
Alternators tied to the Grid
2. Altering input power to the alternator.
VGEN
VL
VZ
ILOAD
VOUT
VR
If input power is increased, and frequency and VOUT
cannot alter, output power will increase.
173
Alternators - tied to the Grid
Summary:
Changing excitation changes the pf of output current.
Changing input power changes output power
Increasing excitation drives load current lagging
Reducing excitation drives load current leading
Increasing input power increases output power
Reducing input power reduces output power
Output frequency and voltage do not change.
174
Alternators stand alone
Summary:
Changing excitation changes output voltage.
Changing input power changes RPM, which changes
output frequency.
Here, output frequency and voltage do change
175
Paralleling Alternators
To parallel alternators (or parallel one onto the
grid), the following criteria must be met:
Output voltage must be the same
Output frequency must be the same
Phase rotation must be the same
Supply voltage must be in phase
It is understood that they must both produce the
same waveform a sine wave!
176
Alternator Rating
Alternators are rated according to:
Frequency
Voltage
Current
kVA
The frequency dictates the RPM (3000, 1500, etc).
Voltage and Current give the kVA rating.
177
Efficiency
Losses:
By far the main loss in an alternator is HEAT loss.
If an alternator can be kept cool, more power can
be obtained from it. ie. Instead of a 300MW
machine, it will become a 500MW machine.
More power must be put into it to get this
increased output power.
Cooling large alternators is a big deal! They are
often cooled using hydrogen.
178
Efficiency
Losses:
Copper Losses:
I2R losses in the stator winding
I2R losses in the rotor winding
Iron Losses:
Hysteresis loss in stator
Eddy current Loss in stator
Friction and windage
179
Magnetic Field
Electrical
Power
Stator
Single Phase Alternators
Mechanical
Power
Regulator
180
181
Single Phase Alternators
These are usually low rated units for portable use.
Prime mover is usually a small petrol or diesel engine.
The engine speed is kept constant by a governor.
This speed will usually be either 3000RPM or 1500RPM
Output voltage is kept constant using an automatic voltage
regulator. This senses the output voltage and adjusts the
rotor excitation current automatically.
They are usually self exciting, so if the load is left on at
start, they may not build up output voltage.
Many small alternators are brushless.
Usually, neither side is earthed. This is called a FLOATING
system.
182
183
Brushless Alternators
3-phase
out
AC is
sampled
Rotor
Field P.S.
Regulator
DC
Note: Self Excited
184
Brushless Alternators
3-phase
out
Rotor
Regulator
3-phase
out
Prime
Mover
185
Small Alternators
-Factors when choosing:
Voltage: 240V / 415V (1-phase or 3-phase)
kVA rating
RPM (3000RPM or 1500RPM)
Petrol or Diesel
Brushless or brushes
Ability to start loads such as motors
Extras: Soundproofing, starting, power outlets,
mounting holes, 12VDC / welding output
186
187
188
189
190
191
192
193
194
195
196
197
198
199