Substation Automation System

The document provides an overview of the CSC2000 substation automation system, including: 1. The system architecture uses a distributed structure with gateways, bay controller units (BCUs), and protection intelligent electronic devices (IEDs) communicating over Ethernet. 2. The local SCADA (HMI) software runs on multiple operating systems and hardware, supports IEC 61850, and provides functions like single line diagrams, alarm handling, control, and automated voltage/reactive power control. 3. The CSC-1320 gateway is an embedded device that connects the station level network to remote control centers and integrates 3rd party IEDs using various protocols including IEC 61850 and I

Uploaded by

KASHIF
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views44 pages

Substation Automation System

The document provides an overview of the CSC2000 substation automation system, including: 1. The system architecture uses a distributed structure with gateways, bay controller units (BCUs), and protection intelligent electronic devices (IEDs) communicating over Ethernet. 2. The local SCADA (HMI) software runs on multiple operating systems and hardware, supports IEC 61850, and provides functions like single line diagrams, alarm handling, control, and automated voltage/reactive power control. 3. The CSC-1320 gateway is an embedded device that connects the station level network to remote control centers and integrates 3rd party IEDs using various protocols including IEC 61850 and I

Uploaded by

KASHIF
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 44

CSC-2000(V2)

Substation Automation System


Main Content
1 Overview of SAS CSC2000
2 Local SCADA(HMI)
3 Gateway CSC-1320
4 BCU CSI-200E
5 Protection IED and network
1 Overview of CSC2000 SAS
 System Architecture
 System Feature
 Communication Network and Protocol
http://www.sifang-electric.com
1 Overview of CSC2000 SAS
1.1 System Architecture
Satellite
Remote Control
Center
Network/
PLC/
Microwave

GPS Clock
Operator Operator Engineer
Workstation 1 Workstation 2 Workstation
PPS/ SNTP Printer
IRIG-B

Gateway1 Gateway2

Ethernet 1
 Station level IEC61850 Ethernet 2

 HMI
 Engineer WS
 Gateway Protection
Gateway

 Bay level HV/MV Line Transformer LV Line


 Protection IED
Bus
HV/MV BCU Protection Protection Protection IEC103,DNP,MODBUS
Protection

 BCU: Measurement/Control
 Network and communication standard
 Fast industry Ethernet(100/1000M) Protection from other venders

 IEC61850 and non- IEC61850 protocol


1 Overview of CSC2000 SAS

1.2 System Feature (1)


 The first distributed SAS in China.
 Over 3000 CSC2000 systems installed and running in
China and other countries, the voltage level range from
35kV to 1000kV.
 It was awarded Chinese SSTPA (State Scientific and
Technological Progress Award, the highest award by
Chinese government) in 2003.
 All the IED get the IEC 61850 certificate of KEMA in Jan.
2008. include CSI-200EA, CSC-101, CSC-161, CSC-326, CSC-
150, CSC-211.
1 Overview of CSC2000 SAS
1.2 System Feature (2)

Medal of SSTPA
1 Overview of CSC2000 SAS
1.2 System Feature (3)

CSI-200EA
CSC- 101
CSC-161
CSC-326
CSC-150
CSC-211

IEC 61850 certificate of KEMA


Products & Solutions
1 Overview of CSC2000 SAS

1.2 System Feature (4)


 Distributed system, bay oriented
 Maintain conveniently, high reliability, easy to extend
 Support IEC61850 and non-IEC61850 at the same time
 Gateway of station level based on embedded hardware
and real-time OS
 HMI on station level can support Windows/LINUX/UNIX
OS and 32/64 bit hardware
 Device of bay level based on common modular hardware
which can be configured freely according to the
requirement
 Redundancy technology is used in the system:
mainframe (SCADA server, gateway), network,
 Advanced application: Sequence control, AVQC
1 Overview of CSC2000 SAS

1.3 Communication Network and Protocol


 Fast Industry Ethernet 100/1000M
 Double bus (star) topology for electronic and optical
Ethernet
 IEC 61850 and CSC 2000 protocol
 Other protocol (IEC 60870-5-103, DNP, Modbus/TCP,
Modbus/RTU) connect to SAS via gateway
2 Local SCADA (HMI)
 Composition of Local SCADA
 Multiple Platform (OS, hardware)
 IEC 61850
 SCADA
 Protection Relay Management
 AVQC
CSC-2000 Substation Automation
Scada system(V2)
2 Local SCADA (HMI)

 Composition of Local SCADA


 Data Server
 Operation Workstation
 Engineer Workstation
 Protection Engineer Workstation
 Advanced Application Workstation: AVQC
2 Local SCADA (HMI)

 Support multiple OS
 UNIX(Solaris/AIX)
 Linux(RedHat/Suse/RedFlag, etc)
 Windows
 Support multiple hardware platform
 SUN/IBM 64 bit UNIX workstation /server
 DELL 、HP、IBM 32 bit PC workstation/server
 Advantech、SIEMENS 32bit Industrial computer
 Support multiple database
 Oracle, MS SQL Server, PostgreSQL
2 Local SCADA (HMI)

 Support IEC61850 and compatible with non-IEC61850 protocol


 CSC2000
 Single line diagram (SLD)
 Topology analysis and dynamic color
 Distributed real time database
 Event and alarm
 alarm text (flash)
 human voice
 printing
 beep or ring
 sending short message (SMS) to cell phone
 Report and trend
 Printing report automatically
 Real time trend
2 Local SCADA (HMI)

 Control
 Authorized operation
 Select before operate (SBO)
 Interlocking function (Station level and bay level)
 Sequence control
 Two-seat control mode: monitor and operator
 Card verifying mode
 Finger print verifying mode (must record 2 finger’s print at least)
 Protection relay management
 Relay setting
 Disturbance recording analysis (COMTRADE file)
2 Local SCADA (HMI)

 AVQC: voltage and reactive power control.


 No restriction to the number of controllable equipment
 Automatic topology
 Configurable parameter
Database
drawing
History report
3 Gateway CSC-1320

 Main Feature
 Hardware
 Scope of Application
 Other Type of Gateway
3 Gateway CSC-1320
3 Gateway CSC-1320
3.1 Main Feature
 4U, 19 inches device / IEC60297-3 standard.
 Based on 32-bit CPU, embedded hardware platform, no
hard disk, no cooling fan, low power consumption.
 Based on embedded real time OS.
 Distributed architecture, multiple plug-in, connected with
industry Ethernet and CAN field bus.
 Communication interfaces can be expanded with plug-in.
 Class 4 of EMC for main items of IEC 61000-4.
 IEC 61850 standard as the station level protocol, also
support private protocol of CSC2000
 Friendly HMI with key and LCD, tools for configuration
and debug.
3 Gateway CSC-1320
3.2 Hardware
 Main CPU, 32 bit CPU
 Ethernet, 32 bit CPU
 Serial port, 32 bit CPU
 DIO, 16 bit CPU
 Synchronize, 16 bit CPU MMI

 Extend, switch Ethernet

 MMI, 16 bit CPU, 4 arrow CAN

key, 3 function key, LCD,


5 indication lamp

synchronize
Main CPU

Serial Port
Ethernet

Extend
DIO
 Networked
 Distributed
 Modularized
Block diagram of system hardware
 Extensible and open
3 Gateway CSC-1320
3.3 Scope of application
 The goal of the CSC-1320 serial product: general protocol
process.
 Gateway of station level: CSC-1321, data exchange with
RCC (Remote Control Center), protocol: IEC 60870-5-101,
IEC 60870-5-104, SC 1801, DNP. Typical Configuration:
 1 main CPU
 1 Ethernet for IEC 61850 to connect IED
 1 Ethernet for IEC 60870-5-104 to RCC
 1 Serial port for IEC 60870-5-101 to RCC
 1 Synchronize for GPS
 Gateway of bay level: CSC-1322, integrate IED from 3rd
part, we can also use other type of gateway include: CSC
1312B, CSM320E, protocol: IEC 60870-5-103, Modbus,
IEC 60870-5-101, IEC 60870-5-104.
3 Gateway CSC-1320
3.4 Other type of bay level gateway

CSC 1312B

CSM 320E
4 BCU CSI-200E
 Hardware
 Main Function
4 BCU CSI-200E
Sifang CSI-200E
4 BCU CSI-200E
4.1 Hardware architecture
 Modular design
 Intelligent HMI

 Data bus within device MASTER COM


Data Bus

CPU CPU
DI DO
A/D A/D

PT/CT signal trip


4 BCU CSI-200E
4.2 Main Function
 Data acquisition: AI, DI, Tap Position
 Remote control and Local control: DO
 Hardware module can be configured freely
 PLC: Interlock, CB synchronization
 Large LCD MMI with bay diagram
 Communication with HMI and Gateway, support
IEC61850, IEC60870-5-103 and CSC2000 protocol.
5 CSC Serial Protection IED
5 CSC Serial Protection IED

 CSC-100 Series High Voltage Line Protection Relay


 CSC-160 Series M/L Voltage Line Protection Relay
 CSC-326 Series Transformer Protection Relay
 CSC-150 Series Bus bar Protection Relay
 CSC-330 Series Reactor Protection Relay
 CSC-300 Series Generation Protection Relay

 Communication with HMI and Gateway, support


IEC61850, IEC60870-5-103, CSC2000 protocol
overcurrent protection
protection backboard of map
6 Typical Configuration of SAS
 Concentric Configuration
 Distributed Configuration
6 Typical Configuration of SAS
6.1 Concentric Configuration

RCC

satellite
WAN

Channel Switch
GPS
OWS 1 OWS 2 Protection WS VQC Fail Safe WS
Station Level
Gateway

Ethernet 1
PPM/ IEC 61850 / CSC2000
PPM/
Ethernet 2
IRIG-B

Gateway Gateway Gateway

IEC60870-5-103 IEC60870-5-103 IEC60870-5-103


BCU Protection BCU BCU BCU & Protection BCU & Protection BCU
Protection Protection IED from 3rd part
Protection from 3rd part from 3rd part
Bay Level

Bay 1 Bay 2 Bay 3 Bay 1 Bay 2 Bay 3 Common Bay …

H/MV Bay LV Bay Common Bay

Concentrical SAS Configuration


6 Typical Configuration of SAS
6.2 Distributed Configuration

RCC
satellite
WAN

Channel Switch
GPS Control Room
OWS1 OWS2 Protection WS Engineer WS M/B SCADA Server VQC Fail Safe
Station Level Gateway

Ethernet 1
Ethernet 2 IEC 61850 / CSC2000

E/O E/O

Fiber Fiber Fiber Fiber

E/O E/O
GPS Extend GPS Extend

Ethernet 1 Ethernet 1
PPM/
Ethernet 2 Ethernet 2 PPS/
IRIG-B

Gateway Gateway Gateway

PPM/ IEC60870-5-103 IEC60870-5-103


PPS/ BCU Protection BCU Protection BCU Protection
IEC60870-5-103 BCU & Protection BCU & Protection
IRIG-B from 3rd part from 3rd part
Protection PPM/
from 3rd part PPS/
Bay Level IRIG-B

Bay 1 Bay 2 Bay 1 Bay 2 Bay 3 Common Bay …

H/MV room LV room Common Bay

Distributed SAS Configuration


7 Network Topology Compare
 Double Bus (Star) Topology
 Double Ring Topology
 Single Ring with Double Net in Station Level
7 Network Topology Compare
7.1 Double Bus (Star) Topology

HMI

Gateway

IED (BCU & Protection)

Double Bus (Star) Topology


7 Network Topology Compare
7.2 Double Ring Topology

HMI
Gateway

IED (BCU & Protection)

Double Ring Topology


7 Network Topology Compare
7.3 Single Ring with Double Net in Station Level

HMI
Gateway

IED (BCU & Protection)

Single Ring with Double Net in Station Level


Thank you,best wishes