TECOF
STORAGE TANKS
CATHODIC PROTECTION
PREPERED AND PRESENTED
BY
M.Y.EL SHAZLY
TECOF
SACRIFICIAL ANODE SYSTEM
CURRENT
C
A
A
T
N
H CURRENT
O
O
D
D
E
E
TECOF
IMPRESSED CURRENT
SYSTEM
CURRENT
- +
C
A
A
T
N
H CURRENT
O
O
D
D
E
E
TECOF
INTERNAL & EXTERNAL
PROTECTED AREA
INTERNAL INTERNAL
PROTECTION PROTECTION
EXTERNAL
PROTECTION
EXTERNAL PROTECTION
INTERNAL PROTECTION
INTERNAL PROTECTED AREA = AREA CONTACTING ELECTROLYTE
PROTECTION (SOIL AND OR CONDUCTIVE LIQUID)
TANK INTERNAL CATHODIC
PROTECTION
IMPRESSED CURRENT SYSTEM
h1
Transformer rectifier Anode
automatic control
DC output
volt/current V A
Set point 000
Ref. protection Reference
h 2
level electrode
Protected area = bottom area + shell wetted area
shell wetted area = II x tank diameter x height
bottom area II x (tank diameter) 2
4
Protection current = protected area x current intencity
TECOF
TANK INTERNAL CATHODIC
PROTECTION
SACRIFICIAL ANODE SYSTEM
Welded anodes
h1
Anode
Suspended
anodes
h 2
Protected area = bottom area + shell wetted area
shell wetted area = II x tank diameter x height
bottom area II x (tank diameter) 2
4
Protection current = protected area x current intencity
TECOF
STORAGE TANKS EXTERNAL
CATHODIC PROTECTION
UNDER BASE ANODE INSTALLATION
RODE ANODE TYPE
-950 mv
-850 mv
50 cm
Rod anodes
TECOF
STORAGE TANKS EXTERNAL CATHODIC
PROTECTION
UNDER BASE ANODE TYPE •
INSTALLATION •
-900 mv
-850 mv
50 cm
RIBBON ANODE
TECOF
STORAGE TANKS EXTERNAL CATHODIC
PROTECTION
DISTREBUTED ANODE INESTALLATION •
-850 mv
-850 mv
5 -10 m
Rod anode
vertical or horizontal
m
0
-1
5
Min. potential point
RIM POTENTIAL = 1100 TO 1200 BS STANDERED
OR TECOF
ADD 1mv per one foot of tank diameter to the min. protection level (-850 mv)
STORAGE TANKS EXTERNAL CATHODIC
PROTECTION
DEEP WELL GROUND BED INESTALLATION
Tank-1 Tank-2 Tank-3 Tank-4
Deep well ground
bed
Tank Farm
Tank Tank Tank Tank
1 2 3 4
Deep well
GB
Tank Tank Tank Tank
5 6 7 7
TECOF
STORAGE TANKS EXTERNAL CATHODIC
PROTECTION
REMOTE GROUND BED INESTALLATION
-2500 mv
-850 mv
-450 mv
Remote GB
TANK FARM
Tank Tank Tank
1 2 3
Tank Tank Tank
4 5 6
Tank Tank Tank
7 8 9 REMOTE GB
TECOF
CURRENT REQUIREMENT
SURFACE AREA TO BE PROTECTED - 1
EXTERNAL = BOTTOM AREA (BARE) •
INTERNAL = BASE AREA + WETTED SHELL AREA (BARE)
IF COATED A COATING DEFFECT PERCENTAGE MUST BE APPLAYED
TECOF
CURRENT REQUIREMENT
CURRENT INTENSITY – 2
:INTERNAL
FRESH WATER = 20 ma/m2
SALT WATER = 100 ma/m2
:EXTERNAL
DEPEND ON SOIL RESISTIVITY
RANGES FROM 5 TO 0.5 ma/m2
TECOF
CURRENT REQUIREMENT
= CURRENT CALCULATION – 3
SURFACE AREA TO BE PROTECTED X CURRENT INTENCITY
COATING DEFFECT PERCENTAGE TO BE TAKEN INTO -1
CONSEDIRATION
IF THE TANK IS USED TO STORE WATER, THIS MEENS -2
THAT SHELL WETTED AREA WILL CHANGE WITH HIGHT, .
HEIGHER CURRENT VALUE MUST BE TAKEN IN SIZING
TECOF
ELECTRICAL EQUIVALENT CIRCUIT
CURRENT = VOLTAGE DIVIDED BY RESISTANCE
OHMS LOW R2 R1
EQUIVALENT CIRCUIT RESISTANCE = R1+R2+R3+R4
WHERE:
R1 = NEGATIVE CABLE RESISTANCE ohm
R2 = TANK STEEL RESISTANCE ohm CURRENT
R3 = GROUND BED RESISTANCE ohm V
R4 = POSITIVE CABLE RESISTANCE ohm OUTPUT
CURRENT = PROTECTION CURRENT DEMAND in ampere
VOLTAGE = DRIVING POTENTIAL in volt R3 R4
TECOF
SAMPLES OF TANK CORROSION
CELLS
WELD CORROSION BATCH CORROSION
+ NEW METAL
- OLD METAL OLD METAL
- + -
- RING BEAM CORROSION
+ +
ANNUAL PLAT WELD CORROSION Tank bottom
Concrete ring CP current
CORROSION beam
AREA
Bottom pla
tes DEBARY
5 deg.
CORROSION
PRODUCTS