OBJECTIVES, METHODS & TESTING
PROCEDURES FOR RLA OF ELECTRICAL
           EQUIPMENT
              BY
       DR. CHANNAKESHAVA
• Importance of Electrical Power & Status
• Generation, Transmission & Distribution
Supply Chain & Substation
• Major Power Equipment
• Objectives of RLA
• Conv. Tests
• Condition Monitoring & Diagnostics Tests
• Interpretation
• Conclusions
  Percapita Consumption
          In India
year      kWh
1950      15.60
1966      61.40
1974      97.50
1980     130.50
1990     238.00
1997     334.30
2002     559.20
2005     606.20
     Percapita Consumption
 HDI-Composite of long.,know.,&income
 Country        kWh           HDI
 Canada        15129          0.96
  USA          11796          0.94
Australia      8086           0.93
Singapore      7196           0.90
  Korea        4453           0.89
Malaysia       2078           0.83
  China        1200           0.65
  India          606          0.45
INSTALLED CAPACITY(MW)
                     India
Resource   Central    State   Private   Total
 Coal      24337.5   37627     4682      68308
 Gas        4419.0    3260     4160      12430
Diesel         -      598.6     597       1202
 Total     28756.5   41486     8999      81940
Hydro        5449    23300     876.2     32135
 Wind          -     64.96    1804.7      6158
Nuclear      2720       -        -        3310
 Total      36975    64851    11680     121543
               Demand Forecast
• Forecasts for demand made by CEA Electric Power
  Surveys (EPS) . 16th EPS latest.
• Partial end-use method used.
                       Peak Demand)     Energy
                            (MW)      requirement
                                         (BU)
   End    of    10th     1,15,700       719
     Plan
   End    of    12th     2,12,700       1319
     Plan
• Forecast by CEA
REGION-WISE/TYPE-WISE BREAK UP OF
   CAPACITY ADDITION REQUIRED
     DURING 11th PLAN (2007-12) -
           TENTATIVE (Figures in MW)
      VARIOUS RESOURCES & USAGE
                TREND
•   Coal
•   Natural Gas
•   Oil
•   Hydro
•   Nuclear
•   Wind,Solar,Biomass,Fuel Cell,Hydrogen
ECONOMIC VOLTAGE LEVEL AS A FUNCTION OF
           POWER & DISTANCE
 Typical 400 kV
Transmission Line
                     POWERGRID
+ 500 kV DC Transmission Line
Typical Power System–Generation, Transmission, Switchyard
Single line diagram of a SS (Typical)
     POWER EQUIPMENT (Electrical)
• Turbo and Hydro generators
• Transformers
        * Generator transformers
        * Auxiliary transformers
        * Station service transformers
        * Transmission transformers
•   Switchyard equipment---- CTs, CVTs & PTs
•   Bus insulation and the like
•   HV Motors
•   Power cables
•   Lightning arresters
•   Isolators
•   Insulators
♣ Important Aspects In Power Sector
        * Power Availability
 * Reliability
 * Quality
* Affordable Cost
Benefits of Condition Monitoring
 
1. Economic
 Adaptive Maintenance
 Reduction of Maintenance personnel
 Minimum period of outage
 Minimum cost of outage
 
2. Safety
   Reduction of risk by early warning
   Timely technical input
   Less stress on service personnel
 
3. Technical
   Optimum use of operation
   Optimum use of systems
   Registration of system problems for future action
   Better correlation of testing & symptoms
   Upgradation of standards for tests
   Life extension & planned replacement
                Why Life Assessment?
•   Estimates the Probable Life
•   Helps in Planning
•   Evaluates the Condition
•   Identifies the Problems-Input for Remedial
    Action & Timing
•   Reduces Blind Risks
•   Avoids Catastrophic Failures & Provides
    Safety
           Testing
 *    Routine
 *    Type
 *    Special
 *    Acceptance
*    Commissioning
*    Diagnostic & Condition Monitoring
Condition Monitoring Techniques and Plant Monitored
  Condition Monitoring Technique   Plant/Equipment Monitored
  Vibration Monitoring             All Rotating Machinery
  Oil Analysis                     Lubricant systems
                                   Hydraulic Systems
                                   Transformers
                                   Bushings
  Acoustic Emissions               Rotating Machinery
                                   Leak detection
                                   Transformers
                                   Switchgear
  Thermography                     Electrical Equipment
  Electrical Tests                 Electrical Equipments
  Pressure Monitoring              Switchgear
  Visual Inspection                All Equipments
          Rotating Machinery
•   High Voltage Generator is the heart of the
    Generating station. Reliability of generators
    depends to a large extent of the quality of
    their insulation systems. During normal
    operation various stresses like electrical ,
    thermal,mechanical, environmental,
    deteriorate the insulation. By carrying out
    certain diagnostic tests on the generator , it
    is possible to assess extent of deterioration
    or ageing of the insulation
• Vibration monitoring is an important
  sub set of condition monitoring of any
  rotating machinery or Power Pant
  equipment. The vibration & noise
  characteristics define the mechanical
  condition of an equipment and is an
  indicator of incipient failure.
GENERATORS / MOTORS
              Rotating Machine (Generators/Motors)
Problems                           Diagnostic Techniques                        Service Conditions
                                                                                of the Equipment
Detection of major external        Visual inspection                            OFF
changes in condition (loose
parts, corona discharge or over
heating
Influence of moisture and          Insulation resistance/PI measurement,        OFF
contamination                      winding to earth resistance
Inhomogenities in the stator       Insulation leakage current measurement       OFF
Winding, e.g. cracks in the        as a function of DC-Voltage to earth (upto
insulation of surface tracking     2.4 * Un)
Detection of local weak – points   Voltage test, winding to eath at 1.5 * Un    OFF
in the insulation                  for 1 min.
Evaluation of dielectric losses    Capacitance & Loss angle measurement         OFF
& capacity                         (usually up to 0.6 or 1.2 * Un)
Evaluation of insulation           PD measurement as a function of voltage      OFF
                                   to earth                                     ON
                                                                                (monitoring)
Evaluation of the mechanical       Check of stator slot wedging (mechanical     OFF
fixation of winding bars           and electrical method)
Evaluation of the insulation to    Voltage Surge test by means of oscillating   OFF
ground & between turns             voltages surge
                      Generators/Motors
                             Diagnostic tests
                               Stator winding
Sl. No                 Tests                     Detection capability
  1      Polarisation index test            Index of dryness,cleanliness
  2      Tan delta & capacitance test       Dielectric losses
  3      Partial discharge test             Incipient faults, slot & end
                                            winding discharges
  4      Wedge mapping                      Loose wedges & Loose stator
                                            bars
  5      DC leakage current                 Discontinuities & cracks
  6      Winding resistance measurement     Loose or bad conductor
                                            joints
  7      Surge comparison test              Inter turn faults
              ELECTRICAL TESTS
          ON STATOR AND ROTORS OF
            GENERATORS /MOTORS
•Insulation resistance / Polarisation index
•Dielectric loss angle test at various voltages
•Capacitance measurement at diff voltages
•Integrated partial discharge energy
•Partial discharge magnitude, Vi, Ve
•Surge comparison test
•Tan delta tip in %
•Capacitance tip up in %
•Inter laminar Insulation test
•High Voltage & High Current Tests
    SIGNIFICANCE OF TESTS
• Insulation resistance:
• It indicates the status of insulation. However
  it fails to detect cracks and voids. Its
  absolute value is less important than
  continues steep fall
• Polarisation Index: It indicates dryness of
  insulation
• Tan delta and tip up test: It detects loss component of
  current in dielectric as a factor of capacitance current.
  It indicates losses in solids and voids of insulation and
  gives a general health and detiroation of winding with
  age. High tan delta indicates poor insulation
    DIELECTRIC LOSS
• A dielectric (insulation) subjected
  to a varying electric field
  produced by an alternating
  voltage applied to it, absorbs
  some of the electric energy which
  is transformed into heat in the
  dielectric. This loss of energy is
  called dielectric loss
  Dielectric Loss & Power- Factor
               Test
• This is a diagnostic test & the parameters
  measured are the fundamental properties
  of the insulation
• If any change occurs due to the physical
  movement of conductors,insulation
  deformation,deterioration or
  contamination then one or more of the
  measurable fundamental characteristics
  also changes
       POWER TRANSFORMER
 Major Insulation – paper (cellulose) & oil.
 Cellulose - kraft paper, board, spacers, etc.
 Oil - mineral oil
 STRESSES
 Dielectric
 Thermal
 Mechanical
                            CPRI
FIELD TESTING IN PROGRESS
   Most important diagnostic techniques for surge arresters
             PROBLEMS                  DIAGNOSTIC TECHNIQUES                    SERVICE CONDITIONS OF THE
                                                                                       EQUIPMENT
                                   CONVENTIONAL SURGE ARRESTERS
External pollution                  - Visual Inspection                     ON
                                    - Mesurement of external leakage        ON
                                    current                                  
Heating of grading resistors        Thermovision                            ON
Deterioration of grading system     - Leakage current under controlled      OFF
                                    voltages                                 
                                    - Watt loss under controlled voltages   OFF
                                    - 50 Hz sparkover voltage                
                                                                            OFF
                                   METAL OXIDE SURGE ARRESTERS
External pollution                  - visual inspection                     ON
                                    - Measurement of external leakage       ON
                                    current                                  
                                    - Integral charge                       ON
Deterioration of varistor blocks    - Leakage current                       ON
                                    - Harmonic decomposition of leakage     ON
                                    - Peak resistive current                ON
                                    - 3rd Harmonic of resistive current     ON
                                    - Reference voltage                      OFF-L
        Important Diagnostic Techniques used for Power Transformers
        Problems                    Diagnostic Techniques                        Service Conditions
                                                                                 of the Equipment
        Mechanical                   Excitation current                          OFF-S
                                     Low voltage impulse                         OFF-S
                                     Frequency response analysis                 OFF-S
                                     Leakage inductance measurement              OFF-S
                                     Turns ratio                                  
        Thermal                      Gas-in-oil analysis by Gas Chrmotography    ON
                                     Oil-paper deterioration by Liquid           ON
                                     Chromotography-DP method                     
                                     Surge comparison test                       OFF
                                     Recovery voltage measurements               OFF-S
                                     Insulation resistance & PI                  OFF-S
                                     Loss Angle measurement                      OFF-S
                                     Hot-spot detection by built in sensors       
                                     Moisture, electric strength, resistivity,    
                                     etc., of Oil…………..                          ON
                                     Turns ratio                                  OFF-S
                                     PD MEASUREMENT
                                           Ultrasonic method                     ON
                                           Electrical method                     OFF
OFF-S       :           Equipment out of service & test at site
OFF-L       :           Equipment out of service & test at laboratory
 ON     :          Equipment in service
    INSTRUMENT TRANSFORMERS
CONDITION MONITORING TESTS
 IR/PI Test
 Tan Delta & Capacitance Test
 Partial discharge test
 D.C Recovery Voltage Test
 Physico- Chemical Analysis of Oil
   BDV, Water content, Tan  at 90°
   DGA
   Furan Analysis
 Infrared Thermography
Most important diagnostic techniques used for bushing
           PROBLEMS                   DIAGNOSTIC               SERVICE CONDITIONS OF
                                      TECHNIQUES                  THE EQUIPMENT
  Moisture                     Capacitance / loss angle        OFF-S
                               Tap voltage
                               DC resistance
  Corona                       Partial discharge (PD)          OFF-S
                               Radio Influence voltage (RIV)   ON
  Ageing                       Capacitors / loss angle         OFF-S
                               DC resistance                   OFF-S
  Short circuited condensers   Capacitance / loss angle        OFF-S
                               Tap voltage                     ON/OFF-S
  Internal surface leakage     PD/RIV                          OFF-S
                               Capacitance / loss angle        OFF-S
                               AC dielectric loss              OFF-S
  Poor connections             Infrared scanning               ON
Most important Diagnostic Techniques used for Circuit Breakers
  Problems                  Diagnostic Techniques     Service Conditions of the
                                                      Equipment
  Insulation defects        Measurement of             
                            - gas density             ON
                            - Partial Discharge       ON
                               HF current probe       ON
                                HF capacitive probe   ON
                               Ultrasonic             ON
  Dielectric Gas Quality    SF6 quality                
                            - dielectric check        ON
                            - gas analysis            ON
  Wear of Circuit Breaker   Measurement by             
                            - potentimeter on         OFF-S
                              moving contact           
                            - optical markers on      OFF-S
                              moving parts             
                            - tripping time           ON
  Over Heating              Measurement by             
                            - infrared camera         ON
                            - contact resistance      OFF-S
    Most important Diagnostic Techniques used for Gas
                Insulated Systems (GIS)
    PROBLEMS                          DIAGNOSTIC        SERVICE CONDITIOS
                                      TECHNIQUES        OF THE EQUIPMENT
Metallic particles             Partial discharge      ON
                               Mechanical vibration   ON
Imperfection in epoxy spacer   Partial discharge      ON
Loose bolt                     Mechanical vibration   ON
Bad contact                    Partial discharge      ON
                               Mechanical vibration   ON
Internal fault                 Gas analysis           ON / OFF - S
Most important diagnostic techniques used for capacitors
             PROBLEMS                         DIAGNOSTIC            TECHNIQUES   SERVICE CONDITIONS OF THE
                                                                                         EQUIPMENT
                                         POWER FACTOR CORRECTION CAPACITORS
Breakdown of parallel fused element          Decrease of capacitance             ON
Deterioration of dielectric in paper         Increase of power factor            ON
capacitors
Deterioration of dielectric in both paper    Increase of PD level                OFF-S
and film capacitors
Breakdown of series elements                 Increase of capacitance             ON
Ionisation in metallised paper of film       Decrease of capacitance             ON
capacitors
                            OIL IMPREGNATED COUPLING AND VOLTAGE TRANSFORMERS
Breakdown of series elements                 Increase of capacitance             OFF-S
Ionisation                                   Analysis of liquid impregnant       ON
   Most important diagnostic techniques for surge arresters
             PROBLEMS                  DIAGNOSTIC TECHNIQUES                    SERVICE CONDITIONS OF THE
                                                                                       EQUIPMENT
                                   CONVENTIONAL SURGE ARRESTERS
External pollution                  - Visual Inspection                     ON
                                    - Mesurement of external leakage        ON
                                    current                                  
Heating of grading resistors        Thermovision                            ON
Deterioration of grading system     - Leakage current under controlled      OFF
                                    voltages                                 
                                    - Watt loss under controlled voltages   OFF
                                    - 50 Hz sparkover voltage                
                                                                            OFF
                                   METAL OXIDE SURGE ARRESTERS
External pollution                  - visual inspection                     ON
                                    - Measurement of external leakage       ON
                                    current                                  
                                    - Integral charge                       ON
Deterioration of varistor blocks    - Leakage current                       ON
                                    - Harmonic decomposition of leakage     ON
                                    - Peak resistive current                ON
                                    - 3rd Harmonic of resistive current     ON
                                    - Reference voltage                      OFF-L
•Construction of an Arrester
           HIGH VOLTAGE DIVISION
MEASUREMENT CIRCUIT
                              A Components at service voltage
Sub Assembly failure rate        1.Interrupting unit
                                 2.Auxiliary inter resistor
        12 13 1                 3.Main Insulation to earth
                              B Electrical Control & Aux.Ckts.
             7%14.0% 2
     11 3.8%                     4.Trip/Close circuits
                                 5.Auxiliary Switches
       8.9%          1% 3       6.Contactors, heaters etc.
                    5.7%         7.Gas Density monitor
                              C Operating mechanism.
  10 9.0%           10.0% 4     8.Compressors,pumps etc.
                                 9.Energy Storage.
       8%                      10. Control elements.
                    7.4%       11.Actuators, dampers etc.
     9 13.6% 7.6% 5            12.Mechanical transmission
               4.0%             13.Others
           8         6
              7
CIRCUIT
BREAKER
CONTACT RESISTANCE
MEASUREMENT OF
CLOSING
/OPENING TIME
    PARAMETERS TO BE MONITORED
                                                  Contd..
Due point of SF6 Gas              As per norms
 Dew point of
                                - 45 deg C at Atm. Pr.
  operating Air
Operating Timings              220kV          400k
                                               V
  Closing Time (max) -ms          200           150
  Trip      Time (max) -ms        035            025
  Close / Trip Time (max) –ms
  Pole discrepancy Ph to Ph..     3.33          3.33
    PARAMETERS TO BE MONITORED
                                           CONTD..
Tan Delta of Grading
                           0.007 at 20 deg C
 Capacitors
  Capacitance of         Within +10% of the
 Grading                  rated
   Capacitors                     - 5%   value
Contact Resistance         150 micro ohms
 Contact Resistance       10 micro ohms per
 of                            connector
    Terminal connectors
                MONITORING
•      INFRARED THERMOVISION-
Thermovision cameras, used to map the hot            spots at
 the terminals,clamps and internal portion of the equipment
            SWITCHING PARAMETERS
 Operating timings,                    Contact resistance
                      Travel
                      timings,
                  Capacitors
•   Capacitors are used in power system to improve
    the power factor. Due to improved materials,
    design, construction and processing , phenomenal
    growth in capacitor industry has taken place.
•   Due to availability of low loss materials such as
    polypropylene and new synthetic oil, the power
    rating of shunt capacitors has reached 1000 KVAR
    per unit, globally and 750 kvar in our country.
•   Premature failure of power capacitors may be due
    to several reasons.
•   They can be broadly classified as failure due to
•   (1)    faulty capacitors
•   (2)    System disturbance
•   System disturbance are caused due to over voltage ,
    switching transients, harmonics etc.
• On Capacitor bank on-line pd monitoring is done by
  Acoustic emission technique
POWER CABLES
Diagnostic Tests
IR/PI
DC leakage current test (PILC cable)
Tan delta & capacitance
   50 Hz0.1 Hz
PD Test
HVdielectric spectroscopy (Frequency domain analysis)
Oil analysis (Oil filled cables)
PROTECTION RELAYS
   Diagnostic Tests
   Operating value test
   Operating Time test
   DC sequence checking
   Scheme testing
•   Automated relay testing is very useful for
    testing any type, any brand, or make of
    relays using Laptop computers. This
    method automates all manuals testing of
    relaying and repetitive testing. In an
    average there are 5000/6000 relays in
    grid like 220KV / 400KV sub station and
    large power station of size 60MW /
    110MW / 210MW along with distribution
    network. Using software and computers it
    reduces testing time by 1 / 3rd, brings
    accuracy, generate database of test
    methods and thus brings the reliability of
    power supply
       FLOW CHART FOR LIFE EXTENSION OF
              INSUALTION SYSTEM
Condition assessment using existing off line / on line diagnostic
   techniques and recently developed advanced techniques
                       Data evaluation
        Trend evaluation followed by visual inspection
                         Interpretation
                        Recommendation
       TEST INSTRUMENTS REQUIRED FOR
            CONDUCTING THE TESTS
•   Insulation analyser
•   Tan delta & capacitance bridge
•   Partial discharge detection analysing system
•   Discharge free transformer
•   Wedge tightness detection system
•   Recurring surge tester
•   Conductor resistance meters
•   Frequency response analyser
•   Dielectric spectroscopy