1) Current transformers and potential transformers are used to transform high currents and voltages to lower, safer levels that can be measured by instruments.
2) Current transformers have a single-turn primary winding that carries the high current, and a multi-turn secondary winding that produces a current proportional to the primary. Potential transformers work similarly for voltages.
3) Both transformer types experience ratio and phase angle errors due to load impedance and other factors that cause their outputs to differ slightly from ideal proportional transformation. Their burdens also must not exceed rated limits for accurate operation.
Download as PPTX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
239 views
Current and Voltage Transformer: Module - 6
1) Current transformers and potential transformers are used to transform high currents and voltages to lower, safer levels that can be measured by instruments.
2) Current transformers have a single-turn primary winding that carries the high current, and a multi-turn secondary winding that produces a current proportional to the primary. Potential transformers work similarly for voltages.
3) Both transformer types experience ratio and phase angle errors due to load impedance and other factors that cause their outputs to differ slightly from ideal proportional transformation. Their burdens also must not exceed rated limits for accurate operation.
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 24
MODULE – 6
CURRENT AND VOLTAGE TRANSFORMER
By-Prof. Kalyani P. Mahure
Current Transformer (CT)
Definition: A current transformer is a device that is
used for the transformation of current from a higher value into a proportionate current to a lower value. It transforms the high voltage current into the low voltage current due to which the heavy current flows through the transmission lines is safely monitored by the ammeter. 1) The current transformer is used with the AC instrument, meters or control apparatus where the current to be measured is of such magnitude that the meter or instrument coil cannot conveniently be made of sufficient current carrying capacity. The current transformer is shown in the figure below. 2) The primary and secondary current of the current transformers are proportional to each other. The current transformer is used for measuring the high voltage current because of the difficulty of inadequate insulation in the meter itself. The current transformer is used in meters for measuring the current up to 100 amperes. Construction of Current Transformers
The core of the current transformer is built up with
lamination of silicon steel. For getting a high degree of accuracy the Permalloy or Mumetal is used for the making cores. The primary windings of the current transformers carry the current which is to be measured, and it is connected to the main circuit. The secondary windings of the transformer carry the current proportional to the current to be measured, and it is connected to the current windings of the meters or the instruments. The primary and the secondary windings are insulated from the cores and each other. The primary winding is a single turn winding (also called a bar primary) and carries the full load current. The secondary winding of the transformers has a large number of turns. The ratio of the primary current and the secondary current is known as a current transformer ratio of the circuit. The current ratio of the transformer is usually high. The secondary current ratings are of the order of 5A, 1A and 0.1A. The current primary ratings vary from 10A to 3000A or more. The symbolic representation of the current transformer is shown in the figure below. • The working principle of the current transformer is slightly different from the power transformer. In a current transformer, the load’s impedance or burden on the secondary has slightly differed from the power transformers. Thus, the current transformer operates on secondary circuit conditions. Burden on a Load
• The burden of a current transformer is the value of the load
connected across the secondary transformer. It is expressed as the output in volt-amperes (VA). The rated burden is the value of the burden on the nameplate of the CT. The rated burden is the product of the voltage and current on the secondary when the CT supplies the instrument or relay with its maximum rated value of current. Phasor Diagram of Current Transformer
• The phasor diagram of the current transformer is shown in
the figure below. The main flux is taken as a reference. The primary and secondary induced voltages are lagging behind the main flux by 90º. The magnitude of the primary and secondary voltages depends on the number of turns on the windings. The excitation current induces by the components of magnetising and working current. • where, Is – secondary current Es – secondary induced voltage Ip -primary current Ep – primary induced voltage Kt – turn ratio, number of secondary turn/number of primary turn I0 – excitation current Im – magnetising current Iw – working component Φs – main flux • The secondary current lags behinds the secondary induced voltage by an angle θº. The secondary current relocates to the primary side by reversing the secondary current and multiply by the turn ratio. The current flows through the primary is the sum of the exciting current I0 and the product of the turn ratio and secondary current Kt Is. Ratio and Phase Angle Errors of CT
• The current transformer has two errors – ratio error and a
phase angle error. • Current Ratio Errors – The current transformer is mainly due to the energy component of excitation current and is given as • Where Ip is the primary current. Kt is the turn ratio and is the secondary current. • Phase Angle Error – In an ideal current transformer the vector angle between the primary and reversed secondary current is zero. But in an actual current transformer, there is a phase difference between the primary and the secondary current because the primary current has also supplied the component of exciting current. Thus, the difference between the two phases is termed as a phase angle error. Types of current Transformer • Wound Transformer – In this transformer the primary winding is composed inside the transformer. The primary winding had a single turn and connected in series with the conductor that measured the current. The wound transformer is mainly used for measuring the current from 1amps to 100 amps. • Bar-type Current Transformer – The bar type transformer has only secondary windings. The conductor on which the transformer is mounted will act as primary windings of the current transformers. • Toroidal Current Transformer – This transformer does not contain primary windings. The line through which the current flow in the network is attached through a hole or a window of the transformers. The major advantage of this transformer is that the transformer has a symmetrical shape due to which it has a low leakage flux, thus less electromagnetic interference. Potential Transformer (PT)
• Definition – The potential transformer may be defined as an
instrument transformer used for the transformation of voltage from a higher value to the lower value. This transformer step down the voltage to a safe limit value which can be easily measured by the ordinary low voltage instrument like a voltmeter, wattmeter and watt-hour meters, etc. Construction of Potential Transformer
• The potential transformer is made with high-quality core
operating at low flux density so that the magnetising current is small. The terminal of the transformer should be designed so that the variation of the voltage ratio with load is minimum and the phase shift between the input and output voltage is also minimum. • The primary winding has a large number of turns, and the secondary winding has a much small number of turns. For reducing the leakage reactance, the co-axial winding is used in the potential transformer. The insulation cost is also reduced by dividing the primary winding into the sections which reduced the insulation between the layers. Connection of Potential Transformer • The potential transformer is connected in parallel with the circuit. The primary windings of the potential transformer are directly connected to the power circuit whose voltage is to be measured. The secondary terminals of the potential transformer are connected to the measuring instrument like the voltmeter, wattmeter, etc.The secondary windings of the potential transformer are magnetically coupled through the magnetic circuit of the primary windings. Types of Potential Transformer
• The potential transformer is mainly classified into two types,
i.e., the conventional wound types (electromagnetic types) and the capacitor voltage potential transformers. • Conventional wound type transformer is very expensive because of the requirement of the insulations.Capacitor potential transformer is a combination of capacitor potential divider and a magnetic potential transformer of relatively small ratio. • The circuit diagram of the capacitor potential transformer is shown in the figure below. The stack of high voltage capacitor from the potential divider, the capacitors of two sections become C1 and C2, and the Z is the burden. • The voltage applied to the primary of the intermediate transformer is usually of the order 10kV. Both the potential divider and the intermediate transformer have the ratio and insulation requirement which are suitable for economical construction. • The intermediate transformer must be of very small ratio error, and phase angle gives the satisfactory performance of the complete unit. The secondary terminal voltage is given by the formula shown below. Ratio and Phase Angle Errors of Potential Transformer
• In an ideal potential transformer, the primary and the secondary
voltage is exactly proportional to the primary voltage and exactly in phase opposition. But this cannot be achieved practically due to the primary and secondary voltage drops. Thus, both the primary and secondary voltage is introduced in the system. • Voltage Ratio Error – The voltage ratio error is expressed in regarding measured voltage, and it is given by the formula as shown below. • Where Kn is the nominal ratio, i.e., the ratio of the rated primary voltage and the rated secondary voltage. • Phase Angle Error – The phase angle error is the error between the secondary terminal voltage which is exactly in phase opposition with the primary terminal voltage. • The increases in the number of instruments in the relay connected to the secondary of the potential transformer will increase the errors in the potential transformers. Burden of a Potential Transformer
• The burden is the total external volt-amp load on the
secondary at rated secondary voltage. The rated burden of a PT is a VA burden which must not be exceeded if the transformer is to operate with its rated accuracy. The rated burden is indicated on the nameplate. • The limiting or maximum burden is the greatest VA load at which the potential transformer will operate continuously without overheating its windings beyond the permissible limits. This burden is several times greater than the rated burden. Phasor Diagram of a Potential Transformer • Where, Is – secondary current Es – secondary induced emf Vs – secondary terminal voltage Rs – secondary winding resistance Xs – secondary winding reactance Ip – Primary current Ep – primarily induced emf Vp – primary terminal voltage Rp – primary winding resistance Xp – primary winding reactance Kt – turn ratio Io – excitation current Im – magnetising component of Io Iw – core loss component of Io Φm – main flux • The main flux is taken as a reference. In instrument transformer, the primary current is the vector sum of the excitation current Io and the current equal to the reversal secondary current Is multiplied by the ratio of 1/kt. The Vp is the voltage applied to the primary terminal of the potential transformer. • The voltage drops due to resistance and reactance of primary winding due to primary current is given by IpXp and IpRp. When the voltage drop subtracts from the primary voltage of the potential transformer, the primarily induced emf will appear across the terminals. • This primary emf of the transformer will transform into secondary winding by mutual induction and converted into secondary induced emf Es. This emf will drop by the secondary winding resistance and reactance, and the resultant voltage will appear across the secondary terminal voltage, and it is denoted by Vs. Applications of Potential Transformer
• It is used for a metering purpose.
• For the protection of the feeders. • For protecting the impedance of the generators. • For synchronising the generators and feeders. • The potential transformers are used in the protecting relaying scheme because the potential coils of the protective device are not directly connected to the system in case of the high voltage. Therefore, it is necessary to step down the voltage and also to insulate the protective equipment from the primary circuit.