Reclosures, Sectionalizers & Load Break Switches
Reclosures, Sectionalizers & Load Break Switches
2
2
What is a Sectionaliser ?
A Sectionaliser is a switch:
It is used in conjunction with an upstream “recloser” or
“circuit breaker”
It counts the interruption created by a recloser during a
fault sequence.
On a preset count
trips during the dead time of the up stream recloser
Isolates a faulty network section
3
3
Products
Medium Voltage Overhead Products
• Automatic Circuit Reclosers
N, U and W series
• Windows Software
WSOS
4
4
Products - Recloser
Reclosers
• N series
• Vacuum interruption
• Stainless steel tank
• SF6 gas insulation
• U series
• 3 phase
• Vacuum interruption
• Epoxy resin insulation
• W series
• Vacuum interruption
• Epoxy resin insulation
5
5
N-Series recloser family
4 models
N12 1/15.5kV 630A 110kV 12.5kA
N24 15.5/24kV 630A 150kV 12.5kA
N36 27/38kV 630A 170kV 12.5kA
N36 27/38kV 800A 170kV 16kA
Common control and communications cubicle with
integral RTU
Type Tested to comply with ANSI C37.60,IEC56,
IEC255
6
6
N-Series recloser
Fully insulated bushing arrangement
316 marine grade stainless steel tank
Vacuum Interrupters
SF6 Gas insulation medium
Single pole mounting < 200 kg /440lb
LV solenoid close and trip from stored energy
charged capacitors.
Voltage measurement to a 2.5% accuracy on all six
bushings
7
7
U-Series three phase recloser
15kV / 27kV Rated Maximum Voltage
630A Rated Current
12500A Fault Make Capacity RMS
31500A Fault Make Capacity Peak
12500A Fault Break Capacity
125kV BIL
Type Tested to ANSI C37.60
8
8
U-Series recloser features
Simple termination using PG clamps
316 grade Stainless steel tank
Vacuum Interrupters
Solid Dielectric insulation medium
Single pole mounting 120 kg
LV actuator close and trip from stored energy
charged capacitors.
Voltage measurement to a 2.5% accuracy on all
three phases
9
9
Products - load break switch
Load Break Switch (LBS)
Model 1– Manually Operated only.
Switch only
No CTs, CVTs fitted in the tank
Motor pack (can be fitted on later stage)
Model 2 – Network Automation
CTs, CVTs fitted in the tank
Operations Counter, Manual Lockout and Low
Pressure Interlock
Motor pack (can be fitted on later stage)
10
10
RL-Series features
15kV / 27kV Rated Maximum Voltage
630A Rated Current
12.5kA or 16kA Fault Make Capacity RMS
31.5kA or 40kA Fault Make Capacity Peak
125kV or 150kV BIL
Type Tested to ANSI C37.63
11
11
RL-Series features
Hook Stick Operated
316 grade Stainless Steel Tank
SF6 gas puffer interruption
Insulation Co-ordination tested
Single Pole Mounting < 120 kg / 265lb
Sectonalising capability
Remote control via common control cubicle
12
12
Common control cubicle
Fully Range Compatible (N, U, W, and RL)
13
13
PTCC – Pole Top Control Cubicle
Compatible with the N, U & W-Series reclosers & the
RL-Series gas switch family.
316 Marine grade Stainless Steel.
Three environment models.
Tropical –10 to 50ºC.
Moderate –15 to 45ºC.
Temperate –30 to 40 ºC.
Inbuilt communications.
DNP3
IEC and other.
Sealed lead acid battery backup.
Auxiliary power supply.
Laptop power supply outlet.
Computer communication port.
User friendly menu driven configuration.
14
14
Operator interface
Simple configuration.
4 line LCD display.
Clear menu structure.
Quick keys to offer short cut to some features.
No codes to look up, or remember and program.
15
15
Protection
Overcurrent (OC), Earth Fault (EF) and Sensitive earth
fault (SEF)
1 Amp SEF protection on N-Series
Up to 4 reclose sequences for OC and EF.
Up to 4 separate reclose sequences for SEF.
time [s]
IEC255, IEEE, 42 non standard inverse curves and UDC
100 (User Defined Curves).
Instantaneous and definite time elements.
10
Modified curve
1
100 % Setting Current
16
16
Protection
Loss of phase protection
Live load blocking
High current lockout
Inrush restraint
Cold Load pickup
Sequence co-ordination
Up to 10 completely independent sets of protection
settings A,B,C - - J
APGS (Automatic Protection Group Selection)
Change protection group depending on power flow
Protection settings easily loaded from the control
panel or WSOS software
17
17
History and recording
A Demand History System is included.
Measures and records current on all three phases.
Measures KVA, KVAr, KW, KWh, Pf.
Power flow is integrated over 5, 15, 30, or 60 minute
time periods.
The data is recorded to the non-volatile memory.
Event log recording at least the last 5000 events.
60-80 Download data to PC.
40-60
20-40
0-20
80
Sunday
60
Friday
40
20 Wednesday
0 Monday
0:00 6:00 12:00 18:00
18
18
Communications
Built in Remote Terminal Unit (RTU)
Most protocols including DNP3 and IEC870.
RS232 port or inbuilt V23 FSK modem.
Eliminates data transfer problems associated with
interfacing separate RTU by hard wiring.
Fully tested to comply with ANSI C37.60 Clause 6.14
Control Element Surge Withstand Capability including
RTU.
V23 FSK modem included.
Integration into automation schemes
Saves cost, engineering, and installation of additional
equipment.
Internal programmable 5-15V radio power supply.
Accessory mounting space provided for radio,
modem or IOEX installation.
19
19
WSOS Computer software
20
20