Reclosures, Sectionalizers & Load Break Switches

The document discusses reclosers, sectionalizers, and load break switches which are protection devices for overhead power lines. It describes their functions and components including recloser models, load break switch features, and control cubicles. The document also covers protection, history recording, and communication capabilities.

Uploaded by

nitin369
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
218 views

Reclosures, Sectionalizers & Load Break Switches

The document discusses reclosers, sectionalizers, and load break switches which are protection devices for overhead power lines. It describes their functions and components including recloser models, load break switch features, and control cubicles. The document also covers protection, history recording, and communication capabilities.

Uploaded by

nitin369
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 20

RECLOSURES,SECTIONALIZERS

& LOAD BREAK SWITCHES


What is a Recloser ?

 A Recloser is a protection device:


 For overhead power lines
 It is a circuit breaker with more arduous
test & install conditions
 Designed to RECLOSE on to a fault.
 Terminology
 The “auto-reclose” cycle
 Will detect a fault and open for a pre-programmed time,
before closing again automatically
 This cycle can be repeated 3 times
 Lockout typically on the fourth trip

2
2
What is a Sectionaliser ?

 A Sectionaliser is a switch:
 It is used in conjunction with an upstream “recloser” or
“circuit breaker”
 It counts the interruption created by a recloser during a
fault sequence.

 On a preset count
 trips during the dead time of the up stream recloser
 Isolates a faulty network section

3
3
Products
Medium Voltage Overhead Products
• Automatic Circuit Reclosers
N, U and W series

• Load Break Switch (LBS)


RL series

• Pole Top Control Cubicle (PTCC)


Protection & Communication

• Windows Software
WSOS

4
4
Products - Recloser

Reclosers
• N series
• Vacuum interruption
• Stainless steel tank
• SF6 gas insulation

• U series
• 3 phase
• Vacuum interruption
• Epoxy resin insulation

• W series
• Vacuum interruption
• Epoxy resin insulation

5
5
N-Series recloser family
 4 models
 N12 1/15.5kV 630A 110kV 12.5kA
 N24 15.5/24kV 630A 150kV 12.5kA
 N36 27/38kV 630A 170kV 12.5kA
 N36 27/38kV 800A 170kV 16kA
 Common control and communications cubicle with
integral RTU
 Type Tested to comply with ANSI C37.60,IEC56,
IEC255

6
6
N-Series recloser
 Fully insulated bushing arrangement
 316 marine grade stainless steel tank
 Vacuum Interrupters
 SF6 Gas insulation medium
 Single pole mounting < 200 kg /440lb
 LV solenoid close and trip from stored energy
charged capacitors.
 Voltage measurement to a 2.5% accuracy on all six
bushings

7
7
U-Series three phase recloser
 15kV / 27kV Rated Maximum Voltage
 630A Rated Current
 12500A Fault Make Capacity RMS
 31500A Fault Make Capacity Peak
 12500A Fault Break Capacity
 125kV BIL
 Type Tested to ANSI C37.60

8
8
U-Series recloser features
 Simple termination using PG clamps
 316 grade Stainless steel tank
 Vacuum Interrupters
 Solid Dielectric insulation medium
 Single pole mounting 120 kg
 LV actuator close and trip from stored energy
charged capacitors.
 Voltage measurement to a 2.5% accuracy on all
three phases

9
9
Products - load break switch
Load Break Switch (LBS)
 Model 1– Manually Operated only.
 Switch only
 No CTs, CVTs fitted in the tank
 Motor pack (can be fitted on later stage)
 Model 2 – Network Automation
 CTs, CVTs fitted in the tank
 Operations Counter, Manual Lockout and Low
Pressure Interlock
 Motor pack (can be fitted on later stage)

10
10
RL-Series features
 15kV / 27kV Rated Maximum Voltage
 630A Rated Current
 12.5kA or 16kA Fault Make Capacity RMS
 31.5kA or 40kA Fault Make Capacity Peak
 125kV or 150kV BIL
 Type Tested to ANSI C37.63

11
11
RL-Series features
 Hook Stick Operated
 316 grade Stainless Steel Tank
 SF6 gas puffer interruption
 Insulation Co-ordination tested
 Single Pole Mounting < 120 kg / 265lb
 Sectonalising capability
 Remote control via common control cubicle

12
12
Common control cubicle
 Fully Range Compatible (N, U, W, and RL)

13
13
PTCC – Pole Top Control Cubicle
 Compatible with the N, U & W-Series reclosers & the
RL-Series gas switch family.
 316 Marine grade Stainless Steel.
 Three environment models.
 Tropical –10 to 50ºC.
 Moderate –15 to 45ºC.
 Temperate –30 to 40 ºC.
 Inbuilt communications.
 DNP3
 IEC and other.
 Sealed lead acid battery backup.
 Auxiliary power supply.
 Laptop power supply outlet.
 Computer communication port.
 User friendly menu driven configuration.

14
14
Operator interface
 Simple configuration.
 4 line LCD display.
 Clear menu structure.
 Quick keys to offer short cut to some features.
 No codes to look up, or remember and program.

15
15
Protection
 Overcurrent (OC), Earth Fault (EF) and Sensitive earth
fault (SEF)
 1 Amp SEF protection on N-Series
 Up to 4 reclose sequences for OC and EF.
 Up to 4 separate reclose sequences for SEF.
time [s]
 IEC255, IEEE, 42 non standard inverse curves and UDC
100 (User Defined Curves).
 Instantaneous and definite time elements.

10
Modified curve

1
100 % Setting Current

16
16
Protection
 Loss of phase protection
 Live load blocking
 High current lockout
 Inrush restraint
 Cold Load pickup
 Sequence co-ordination
 Up to 10 completely independent sets of protection
settings A,B,C - - J
 APGS (Automatic Protection Group Selection)
 Change protection group depending on power flow
 Protection settings easily loaded from the control
panel or WSOS software

17
17
History and recording
 A Demand History System is included.
 Measures and records current on all three phases.
 Measures KVA, KVAr, KW, KWh, Pf.
 Power flow is integrated over 5, 15, 30, or 60 minute
time periods.
 The data is recorded to the non-volatile memory.
 Event log recording at least the last 5000 events.
60-80  Download data to PC.
40-60
20-40
0-20

80
Sunday
60
Friday
40
20 Wednesday

0 Monday
0:00 6:00 12:00 18:00

18
18
Communications
 Built in Remote Terminal Unit (RTU)
 Most protocols including DNP3 and IEC870.
 RS232 port or inbuilt V23 FSK modem.
 Eliminates data transfer problems associated with
interfacing separate RTU by hard wiring.
 Fully tested to comply with ANSI C37.60 Clause 6.14
Control Element Surge Withstand Capability including
RTU.
 V23 FSK modem included.
 Integration into automation schemes
 Saves cost, engineering, and installation of additional
equipment.
 Internal programmable 5-15V radio power supply.
 Accessory mounting space provided for radio,
modem or IOEX installation.

19
19
WSOS Computer software

Windows Switchgear Operating System


 Measurement
 Protection
 History
 Communication
 Remote control via modem / radio
 Configurable DNP3, IEC, Modbus
 Loop Automation
 User Defined Protection curves
 Automatic Data Retrieval
 Monitoring system
 Voice annunciation
 DTMF control.