High Speed NCM (HS-NCM)
HS-NCM Overview
Supports 200 nodes
No limitations when using a DVC to page over the
network
Two node addresses per HS-NCM
Compatible only with Onyx series panels (8th and
9th edition)
8th edition products can only be used in retrofit
applications
HS-NCM
Overview
NFN on IP based VDSL Network (Very High Data Rate
Subscriber Line)
• Does not use ARCnet protocol
The HS-NCM is NOT compatible with the standard
NCM Noti-Fire-Net Network.
Supports NUP (Notifier Universal Protocol)
Can be configured as a network repeater by setting
address to 0
Installs in same single module bay as NCM
HS-NCM
Overview
Each HS-NCM has:
• Two NUP Ports
ONYX FACP, NCA-2, DVC, Veri-Fire Tools and/or Gateway
• Two USB Connections
One Host Standard A and One On-The-Go Mini AB
Veri-Fire Tools
• External Power Connection (Remote
Repeater)
• Ethernet Port for Future Diagnostics
HS-NCM Part
Numbers
High Speed NCM (HS-NCM)
• HS-NCM-MF Multimode Fiber
• HS-NCM-MFSF Multimode/Singlemode Fiber
• HS-NCM-SF Singlemode Fiber
• HS-NCM-W Wire
• HS-NCM-WMF Wire/Multimode Fiber
• HS-NCM-WSF Wire/Singlemode Fiber
• HS-GW-EM Embedded Gateways
BACNET-GW-3
NWS-3
NFN-GW-EM-3
HS-NCM-W
VDSL Data Rate 12Mb
(Variable 3Mb-24Mb Future)
Supports twisted pair wire
• 18AWG- 14AWG
• Maximum Distance 3,000 ft.
NFPA Style 4 (Class B) or Style
7 (Class A)
Data is regenerated at each
node
HS-NCM-W
Channel A Channel B
Connection Connection
USB
Connections
Ground Fault
Detection NUP
Switches Ports
S1 = CH A
S2 = CH B
External
Power
Connection
HS-NCM-W Wire Requirements
MUST be Twisted Pair
Prefer a Data Grade Cable (Belden)
Non-Shielded Wire for High Speed Communications
200 Nodes at 3,000’
• Belden 5320UJ 18/2 FPL
• Belden 5320UM 18/2 FPLR
• Genesis 4050 18/2 FPL
• Genesis 4631 18/2 FPLP
• Genesis 4433 14/2 FPLR
• Genesis 4633 14/2 FPLP
HS-NCM-W Wire Requirements
200 Nodes at 2,000’
• Genesis 4431 18/2 FPLR
200 Nodes at 1,000’
• Genesis 5500 18/2 FPLR
• Genesis 5502 16/2 FPLR
• Belden 5220UM 16/2 FPLR
200 Nodes at <1,000’
• Genesis 5504 14/2 FPLP
This cable did not pass the test for 200 nodes at distances
even less than 1,000’ and therefore should not be used as
a network segment cable
HS-NCM-MF (Multi-Mode
Fiber)
Data Rate of 100Mb
Supports Fiber Optic Cable
• 62.5/125 10dB Limit
• 50.0/125 6.5 dB Limit
NFPA Style 4 (Class B) or
Style 7 (Class A)
Data is regenerated at each
node
Fiber Connectors: LC Style
HS-NCM-SF (Single-Mode
Fiber)
Data Rate of 100Mb
Supports Fiber Optic Cable
• 9/125 30dB Limit
NFPA Style 4 (Class B) or
Style 7 (Class A)
Data is regenerated at each
node
Fiber Connectors: LC Style
HS-NCM-SF (Single-Mode
Fiber)
NO CONVERTERS REQUIRED !!!
Previous singlemode fiber segment required two NCM-F, two
14507714-001 singlemode converters and mounting kit.
HS-NCM Hybrids (Wire to
Fiber)
HS-NCM-WSF HS-NCM-WMF
Multi-Mode fiber to Single-Mode fiber converter not shown
ONYXWorks™
Intel 2.0 GHz Pentium IV
microprocessor
1 GB RAM
80 GB hard drive
1.44 MB floppy drive
24/10/40X CD-RW drive
19” Flatscreen LCD
monitor
Microsoft Windows XP
HS-NCS
High Speed ONYXWorks
• ONYXWORKS-HNMF (High Speed NFN Multi-mode
Fiber)
• ONYXWORKS-HNSF
• ONYXWORKS-HNW
High Speed card for ONYXWorks Add-On (Upgrade
current ONYXWorks)
• NFN-GW-PC-HNMF
• NFN-GW-PC-HNSF
• NFN-GW-PC-HNW
HS-NCS Cards for ONYXWorks
HS-NCS-MF
HS-NCS-SF
• NOT compatible with the NCS Workstation
For ONYXWorks
HS-NCS-W only
HS-NCM Applications
DVC,NCA-2,Gateway
or another FACP
NUP NUP
HS-NCM
USB 2 Node USB
Addresses
NFN NFN
Veri-Fire Tools
100
HS-NCM HS-NCM
HS-NCM Applications
Veri-Fire Tools
NUP NUP (either/or connection)
HS-NCM
USB 1 Node USB
Address
NFN NFN
200 Veri-Fire Tools
HS-NCM HS-NCM
HS-NCM USB Limitations
USB connection for the HS-NCM is NOT supported
on the fire panels until the following releases:
• NFS2-3030 Release 14.1
• NFS2-640/NFS-320 Release 15.0
USB Connections not supported on NFS-640 or
NFS-3030
Do not use the USB Mini On-The-Go connection on
the fire panel