2*25 KV SYSTEM
Technology Advancements: OHE
2 X 25 KV AT SYSTEM
TRANSFORMERS: SCOTT & AUTO
New
Technologies AUTO FAULT LOCATOR
Adopted
AUTOMATIC POWER FACTOR
CORRECTION EQUIPMENT
MECHANIZED OHE FOUNDATION-
FIRST TIME IN INDIA
2
EMP 4: 2 X 25 KV HIGH RISE OHE
(Comparison:
(Comparison: Conventional
Conventional && DFC)
DFC)
Conventional 25 kV OHE 2X25 kV High Rise OHE
Catenary wire
Feeder wire
1.40 mtr
Catenary wire Earth wire
1.40 mtr Contact wire
Contact wire
7.54m
5.4m
Buried Earth Conductor
Items Conventional 25 kV 2 x25 kV High Rise
Mast heights ~ 9.5 mtr ~ 11.6 mtr with Larger Cross Sections
Contact wire 107 Sqmm 150 Sqmm
Catenary wire 65 Sqmm 125 Sqmm
Feeder Wire, AEC, BEC Not required Required
Foundations Conventional RDSO design Designed for higher/heavier masts
3
SCOTT CONNECTED TRANSFORMER AUTO TRANSFORMER
1. Drives 2-Phase electric power from a 3-Phase
2. Combination of two single phase transformers
Scott Connected 3. Has two 27 KV winding secondary windings at each
1
Transformer Main and Teaser Phase.
4. O&M are almost same as traction transformer of
conventional system
1. Transforms feeder to catenary voltage to catenary to
rail voltage.
2. Results in a system with lower voltage drop along the
2 Auto Transformer
alignment than is possible with 25 kV direct‐fed system,
resulting in an improved train voltage profi le along the
line.
4
2X25 KV AUTO TRANSFORMER FEEDING SYSTEM
ADVANTAGES:
1. Utilization of 54 KV traction
power instead of 25 KV with the
help of AT and feeder.
2. Less voltage drop in feeder
circuit.
3.Large spacing of traction
substations.
4. Less telecommunication
interferences.
4. Suitable for heavy haul and
high speed operation.
5
AUTO FAULT LOCATOR
1. Faulty sub-sector is identified with provision of "Auto Fault
1. The fault is accurately located by
Segregation Scheme" through the SCADA system
sensing auto-transformer current.
2. The fault locating technique is cumbersome and time consuming. 2. Fast Power supply restoration
6
AUTOMATIC POWER FACTOR POWER CORRECTION EQUIPMENT AT DFCC TSS:
PFC FOR IR – STATIC COMPENSATOR PFC FOR DFCC – STATIC & DYNAMIC COMPENSATOR
ADVANTAGE::
Power factor improvement: Conventional system improves power factor normally from .75
to .85, whereas APF improves power factor from .85 to .95
Avoids leading power factor (PF>1): To safeguard supply source
Reduction in maximum demand : Direct saving in Electricity Bill
7
Differences in Equipment:: DFCC SP and IR SP
Item 2x25 KV AT Feeding System 25 KV Conventional Traction System
Size of contact and catenary wire are 150 sq. mm & 129
Size of contact and catenary wire are 107 sq. mm & 65 sq. mm
Conductors sq. mm respectively and OHE current carrying capacity
respectively and OHE current carrying capacity is 600 Amp.
is 1000 Amp.
Feeder Wire 288 sq. mm AAAC Not reqd.
1250 A Double Pole, with distance between the Pole-
Isolator 800 A Double Pole with Distance between the Pole- 550 mm
1500 mm
Iterrupter 1600 A Double Pole 800 A Single Pole
Cross-Feeder Double run of 150 sq. mm Single run 150 sq. mm
Auto Transformer 8 MVA Not Provided
Circuit Breaker 1600 A Double Pole Single Pole 800/1250 A
8
MECHANIZED OHE FOUNDATION
First time in India
STEP 1: AUGER BORING BY
AUTOMATED AUGER BORER
STEP 2: CONCRETING TRAIN
FOR CONCRETING, CONSISTS
OF: UTV, BFR, Mixer Machine,
Water tanks
STEP 3: Mast Erection (contd.)
9
MECHANIZED OHE FOUNDATION
First time in India
STEP 3: Mast Erection (contd.) STEP 5: OHE Inspection
STEP 4: Wiring train
1