Instrument Transformers
Instrument Transformers
Instrument Transformers
What is an Instrument Transformer ?:
1. Current transformers
2. Potential transformers
Instrument Transformers
Applications of Instrument Transformers:
Construction of C.T.:
• C.T. has a primary coil of one or more turns made of thick wire
connected in series with the line whose current is to be measured.
• The secondary consists of a large number of turns made of fine wire
and is connected across an ammeter or a relay’s terminals.
Construction Types of Current
Transformers
Window-type Bar-type
Current Transformers
Function of CT:
• The principal function of a CT is to produce a proportional current at a
level of magnitude, which is suitable for the operation of low-range
measuring or protective devices such as indicating or recording
instruments and relays.
• The primary and secondary currents are expressed as a ratio such as
100/5 or 1000/5 .
• With a 100/5 ratio CT, 100A flowing in the primary winding will result
in 5A flowing in the secondary winding, provided that the correct
rated burden is connected to the secondary winding.
Current Transformers
Specifications of CT:
CTs should be specified as follow:
RATIO : Input / output current ratio
VA: Total burden (rating) including pilot wires.
Common burden ratings are 2.5, 5, 10, 15 and 30 VA. For example:
• Moving iron ammeter is 1-2 VA
• Moving coil rectifier ammeter is 1-2.5 VA
• Electro-dynamic instrument is 2.5-5 VA
• Maximum demand ammeter is 3-6 VA
• Recording ammeter or transducer is 1-2.5 VA
Current Transformers
Current Transformers Stepping:
• These are used with low range ammeters to measure current in high
voltage alternating circuits where it is not practical to connect instrument
and meters directly to lines.
• They are step-up transformers (voltage ratio) because when we step-up
the voltage the current decreases.
• The current is a step-down in a known ratio called the current ratio .
Connections of Current Transformers
Single-Ratio CT Multi-Ratio CT
Multi-ratio CT:
• As indicated in the previous Figure, current transformers having a center tapped
secondary are referred to as a dual ratio CT.
• Dual ratio CT are used in applications where it is necessary to have available two
ratios of primary to secondary current from the same secondary winding of the CT.
• This may be accomplished by adding a tap in the secondary winding to get a
second ratio.
• The ratio obtained by the tap is usually one-half the ratio obtained by the full
secondary winding.
• A schematic example is previously shown with 200 amperes flowing in the
primary, a connection X2 – X3 will produce 5 amperes out of the secondary. As
the load grows to 400 amperes, the secondary circuit will be reconnected to X1 –
X3 to still produce 5 amperes in the secondary circuit.
Current Transformers
Working (Measurement):
• If a current transformer has primary to secondary current ratio of 100:5 then it steps
up the voltage 20 times and step down the current 1/20 times of its actual value.
• If we know the current ratio and the reading of an a.c. ammeter, the primary current
can be calculated as:
Iron Core
• The `doughnut' fits over the primary conductor, which constitutes one primary turn. If
the toroid is wound with 240 secondary turns, then the ratio of the C.T. is 240 : 1 or
1200 : 5A
• This type of `doughnut' C.T. is most commonly used in circuit breakers and power
transformers. The C.T. fits into the bushing, and the porcelain bushing fits through the
centre of the `doughnut'.
• Up to four C.T.'s of this type can be installed around each bushing of an oil circuit
breaker. This arrangement is shown in a following diagram.
Substation Class Circuit Breakers' CTs
100
___ = 100:5 or 20:1
5
Polarity
Direction of
Secondary Current
Direction of
Primary Current
X1 IEEE Secondary
IEEE H1
S1
IEC Polarity
Primary Marks
Polarity
Marks IEC P1
X1 IEEE Secondary
IEEE H1
S1
IEC Polarity
Primary Marks
Polarity
Marks IEC P1
Direction of
Primary Current
Typical window CT
Power Transformers’ CT Connections
Slip over current transformer for installation over exterior
of outdoor bushing
Vs
Relay
Connections of 1-Phase Potential Transformers
Other PT and 3-Phase Typical Connections
Y – Broken Corner VT
Connection
damping resistor R
Other PT and 3-Phase Typical Connections