Lecture 6 Differential Protection
Lecture 6 Differential Protection
Introduction
Differential protection is based on the fact that any fault within
an electrical equipment would cause the current entering it, to be
different, from that leaving it.
Comparing the two currents either in magnitude or in phase or both and issue
a trip output if the difference exceeds a predetermined set value. This method
of detecting faults is very attractive when both ends of the apparatus are
physically located near each other. i.e.,
transformer,
generator
busbar.
Used where:
• Protection co-ordination is difficult / not
possible using time delayed elements
• Fast fault clearance is critical
Can be used on all items of plant in one form or
another (i.e. Generators, transformers, lines,
cables, busbars, motors) to form a defined zone
of protection dictated by current transformer
location.
Dot Markings (polarity marks)
Thus, during internal faults the spill current will be two times the circulating current, a, giving a slope of
2, which is expressed as 200%.
The minimum internal fault current below which the scheme will not respond is seen . , to be If,min,int and
the maximum 'through fault' current above which the scheme will maloperate is seen to be If,max,ext as
shown in Figure 3.14. Thus, the stability ratio is given by