0% found this document useful (0 votes)
342 views24 pages

1 - 7UT6 Diff - Principles - en

1) Transformer differential protection is based on Kirchhoff's current law, which states that the sum of all currents flowing into a node is equal to the sum of all currents flowing out of that node. 2) It uses current transformers to measure and compare currents flowing into and out of the protected transformer. A difference between the currents indicates an internal fault, triggering operation. 3) Several factors need to be accounted for in transformer differential protection, including angle shifting due to vector groups, different primary and secondary current values, zero sequence currents during external faults, and transient inrush currents. Restraint elements are also required to prevent operation during external faults with heavy through-currents.

Uploaded by

cacobeco
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
342 views24 pages

1 - 7UT6 Diff - Principles - en

1) Transformer differential protection is based on Kirchhoff's current law, which states that the sum of all currents flowing into a node is equal to the sum of all currents flowing out of that node. 2) It uses current transformers to measure and compare currents flowing into and out of the protected transformer. A difference between the currents indicates an internal fault, triggering operation. 3) Several factors need to be accounted for in transformer differential protection, including angle shifting due to vector groups, different primary and secondary current values, zero sequence currents during external faults, and transient inrush currents. Restraint elements are also required to prevent operation during external faults with heavy through-currents.

Uploaded by

cacobeco
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 24

Power Transmission and Distribution

Principles of system protection technology

Transformer Differential Protection


Basic principles : Kirchhoff’s knot rule

Basis for Differential-Protection:

I1
I2
I4
I3

I1 + I2 + I3 + I4 = 0  ∑ I = 0

Definition:
Currents, which flow into the node (protected object), are taken as positive.
Currents, which flow out of the node (protected object), are counted negative.

Protection objects:
Line, Transformer, Generator/Motor, Bus bar

Principles Transf. Diff 2


Basic principles: current comparison

IP1 IP2 IP1 IP2


I1F I2F IF
Protected Protected
object object
IS1 IS2 IS1 IS2
IS1 IS2
∆I IDiff =│I1 + I2│ ∆I IDiff =│I1 + I2│

internal fault external fault or load

Assumption: CT- ratio: 1/1 Assumption: CT- ratio: 1/1


IP1 = I1F IP1 = IF
IP2 = I2F IP2 = -IF
IDiff = │IP1 + IP2 │ = │I1F + I2F │ IDiff = │IP1 + IP2 │ = IF - IF = 0
 Trip  no Trip

Requirements for Differential Protection:


1) Internal faults ( faults between CT-sets )  Trip
2) External faults  no Trip

Principles Transf. Diff 3


Basic principles : restrained current comparison (1/2)
Example: external fault with linear CT-errors

Ct 1: Ct 2:
IP1 ε1= - 5% ε2 = +5% IP2 = -IP1
Protected IF
object

IS1= IS2=
0.95·IP1 IDiff = 0.1·IP1
1.05·IP2
∆I

assumption: CT- ratio: 1/1


IDiff = │IS1 + IS2 │= │(1+ε1)· IP1 + (1+ε2)·IP2 │=│0.95· IP1 – 1.05· IP1│= 0.1·IP1

-normal operation: IP1 = IN


IDiff = 0.1·IP1 = 0.1·IN

-external fault: assumption: IP1 = 10·IN


IDiff = 0.1·IP1 = 1·IN
As the setting IDiff> for usual applications
is below nominal current, Restrained characteristic necessary!
it would cause a wrong trip in case of
external faults with heavy current!

Principles Transf. Diff 4


Basic principles: restrained current comparison (2/2)

Example: external fault with linear CT- errors


CT 1: CT 2:
IP1 ε1= - 5% IP2 = -IP1
ε2 = + 5% IF
Protected
object

IRest IRest =│IS1│+│IS2│


IRest = 2·IP1

IS2=
IS1= 1.05·IP2
0.95·IP1
IDiff= │IS1+ IS2│
IDiff
IDiff = 0.1·IP1

Setting due to Linear error due to


magnetising or different
charging currents CT transformation
IDiff=
│IS1+IS2│
Resulting Under the following assumption
characteristic
IN
│ε1 │ = │ε2 │ and I1 = I2
Trip
the result for a conventional
Differential Prot. characteristic
should be:
Block IDiff = IDiff> + ε1·I1 + ε2·I2
IDiff> = IDiff> + 2·ε1 ·I1

2
with IDiff> = setting
10 IRest =│IS1│+│IS2│
Principles Transf. Diff 5
Basic principles: measuring circuit for a 3-phase system

Basic circuit for a 3- phase system:


Generator / Motor / Reactor

L1

L2

L3

Diff.

Rest. current
Conventional
Differential Protection

Principles Transf. Diff 6


Transformer Differential Protection special qualities

Angle shifting N·30° due to vector group (0 ≤ N ≤ 11)


for 3-phase transformers.

Different current values of the CT- sets on the high voltage side (HV)
and on the low voltage side (LV)

Zero sequence current in case of external faults will cause


differential current

Transformer-tap changer, magnetising current

Transient currents
Inrush
CT-saturation

Principles Transf. Diff 7


3-phase Transformer: primary values
Load: 100MVA ,vector group: Yd5
side 2: 20kV, 2887A side 1: 110kV, 525A
3000/1A 750/1A
2L1 1L1
I2L1 I1L1
I2*L1
2L2 1L2
I2L2 I1L2
I2*L2
2L3 1L3
I2L3 I1L3
I2*L3

kU = U1N/U2N = 110kV/20kV = 5.5


kWinding = w1/w2 = kU/√3

I2*L1 = -I1L1·ku /√3 + I1L2·ku /√3

I2*L3
I1L1ku/√3
I1L1

5·30°
I2*L2

I1L2ku /√3
I1L3 I1L2

-I1L1ku /√3

I2*L1
Principles Transf. Diff 8
3-phase Transformer : secondary values

SN I
I L1sec   NCT1sec
3  U N I NCTlprim

100MVA 1A
I1L1sec    0.7A
3 110kV 750A
I1L1sec= 0.7A , 0°

100MVA 1A
I2L1sec    0.96A
3  20kV 3000A

IDiff L1 = │I1L1sec+ I2L1sec│


= 0.5A

I2L1sec = 0.96A , -150°

Principles Transf. Diff 9


Vector group and current value adaptation in case of (1/2)
conventional Transformer Differential Protection
Load: 100MVA ,vector group: YNd5
side 2: 20kV side1: 110kV
3000/1A 750/1A ILoad=
525A L1
2887A
L2

L3

0.96A 0.7A

Diff. 29 23
IR Wdg. Wdg.

Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling

nominal Load (no fault): 0.70A ·23Wdg = 0.555A ·29Wdg, IR = 0.555·√3 = 0.96A

Principles Transf. Diff 10


Transformers in star-delta connection: I0-current
Vector group: YNd5 , Ratio: 1/√3
side 2: side 1:
~ L1

~ L2

~ L3

3I0
IL1(S2) = -IL1(S1) , IL3(S2) = IL1(S1)
I L1(S2) IL3(S2) IL1(S1)
1 2 3

positive No Problem for


I1
sequence Differential Protection
- 5·30°
IL1(S2) = I1 + I2 IL1(S1)= I1 + I2 + I0 = 3I0

IL2(S2) = a2·I1 + a·I2 = 0


+ + IL2(S1)= a2·I1 + a·I2 + I0 = 0

IL3(S2) = a·I1 + a2·I2 IL3(S1)= a·I1 + a2·I2 + I0 = 0


+ 5·30°
negative No Problem for
I2
sequence Differential Protection

+
Differential Protection
zero sequence I0
I0 elimination nessesary
Principles Transf. Diff 11
Vector group and current value adaptation in case of (2/2)
conventional Transformer Differential Protection
Load: 100MVA ,vector group: YNd5
side 2: 20kV side1: 110kV
3000/1A 750/1A
~ L1
13655A
~ L2

~ L3

3I0
IP=
4.55A 5.73A 4300A

Diff. 29 23
IR Wdg. Wdg.

Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling

single pole fault HV -side: 5.73A ·23Wdg = 4.550A ·29Wdg , IR = 4.55A

Principles Transf. Diff 12


Vector group and current value adaptation in case of (1/2)
numerical Transformer Differential Protection
Load: 100MVA ,vector group: YNd5
CT 2 side 2: 20kV side 1: 110kV CT 1
3000/1A 750/1A
I2L1P  I1L1P
2L1 1L1
I2L2P  I1L2P
2L2 1L2
I2L3P  I1L3P
2L3 1L3

I2L1S I2A I1A I1L1S


Current Io – Vector Io – Current
I2L2S value handling group
I2B comparison I1B
handling value
I1L2S
adaptation adaptation adaptation
CT 2
∆I CT 1
I2L3S I2C I1C I1L3S

Numerical Transformer Differential Protection

Principles Transf. Diff 13


Vector group and current value adaptation in case of (2/2)
numerical Transformer Differential Protection
Parameterisation of transformer and CT- data
in a 7UT6 Differential Protection Device

I0-Elimination

Principles Transf. Diff 14


Tripping characteristic of Transformer Differential Protection

CT-errors , Tap changer , Magnetising current

I Diff
InO
3.0 Fault
Characteristic
2.5
Trip
slope 2
Total error
2.0
Block

1.5
CT- error

1.0
slope 1 Tap changer error
0.5

IDiff>
Transf. magnetising current
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 I Rest InO

Characteristic: IDiff = f (IRest) InO = nominal current of the protected object


IRest = |I1| + |I2|

Principles Transf. Diff 15


Transient currents (with Harmonics)
- Inrush of Transformers (1 of 2)
i1 iDiff = i1
even
Inrush
2. Harm.
Y Y
t=0
i1 i2 = 0

even i1 iDiff = i1
Inrush
2. Harm.
Y

t=0
i1 I2 = 0

Connecting -T2 in parallel with -T1


(Sympathetic Inrush –T1) i1
-T1 -T1: iDiff = i1

i1 I2 = 0
-T2

t=0
Inrush -T2 t=0 t

Principles Transf. Diff 16


Inrush, cross block, over excitation [V/Hz] (2 of 2)
filter window
1 cycle
iRUSH Cross-block = No (phase separate blocking)
= iDiff Inrush current
in one phase L1-block IDiff, L1 > trip blocking

L2-block IDiff, L2 > trip blocking

L3-block IDiff, L3 > trip blocking

1P 2P 3P t

I 2har
I Diff block Cross-block = Yes (blocking of all phases)

L1-block
Setting
15 %
value L2-block OR IDiff > trip blocking
≥1 for an adjustable time
L3-block
no block
0
0 t

recognise inrush condition by evaluating the ratio 2nd harmonic I2har to basic wave IDiff.
Time limit for cross-block. Reliable reaction to the inrush condition with cross-block.
Trip of a short circuit after the set time delay.
recognise over excitation [V/Hz] by evaluating the ratio 3rd or 5th harmonic to basic wave
Principles Transf. Diff 17
Demonstration of Inrush with evolving fault

Internal
fault

IDiff>>

Inrush

IDiff>
3 cycles
Cross Blocking

Principles Transf. Diff 18


Transient currents (with harmonics) (1/2)
- Over excitation and CT- saturation
iDiff = i1 + i2
Over excitation (U/f)
UTr > UN uneven
5. Harm.

i1 i2

External fault with i1


CT-saturation at the iDiff = i1 + (-i2)
even
low voltage side and
uneven i2
HV LV

i1 i2

Internal fault with I1 (ideal CT)


CT-saturation at the iDiff = i1
high voltage side even
and
uneven i1
HV LV

i1 I2 ≈ 0

Principles Transf. Diff 19


Transient currents (with harmonics) (2/2)
- Over excitation and CT- saturation
Principle of Add-on stabilisation for external faults

I Diff Tripping characteristic 7UT6


InO
IDiff>>
7

Fault
6 Characteristic Trip
Block
5
D
C
4

3
Add-on
Stabilisation
2

1
Begin of saturation
IDiff> B
0 14 I Rest
0 2 4 6 8 10 12 16
A
InO

Principles Transf. Diff 20


Demonstration of add-on stabilisation

Fault
Characteristic

Block

Trip

Add-Stabilisation

Principles Transf. Diff 21


Differential elements IDiff> and IDiff>>
measured value Instantaneous Tripping characteristic,
pre-processing values saturation detection
( vector gr. ,Ct’s ) rectified mean value: IDiff
i1L iRest = │i1│ + │i2│
side 1 IRest = iRest
i2L fundamental wave: Trip
side 2 iDiff = i1 + i2 IDiff = rms(iDiff)50Hz
IDiff>
IRest & IDiff>
Motor start
DC off set
analysing of harmonics:
-block by 2. & 3. or 5.har
-cross block

iDiff iRest IRest IDiff


IDiff
IDiff>>
Trip
I / InO

≥1

I / InO
iDiff IDiff>>
k·IDiff>>

ms ms

IDiff> restrained (biased) differential function, IDiff> = f(IRest)


- Ct-saturation detector (add on stabilization) for external faults.
IDiff>> fast unrestrained high current differential function, it’s setting therefore should be higher then
the maximum possible through flowing current! Example Transformer: I Diff>> > (1/uk)·InO
This function will be not blocked by harmonics due to an inrush or Ct-saturation!
The IDiff>> stage evaluates the fundamental wave of the currents as well as the instantaneous values.
- Fundamental wave processing: fast tripping at the set threshold.
- Instantaneous value processing: ensures fast tripping even in case the fundamental wave
of the current is strongly reduced by Ct-saturation. Because of the possible DC offset after fault
inception, the instantaneous value stage operates only above twice the set threshold.
Principles Transf. Diff 22
Measuring Pre-processing, Example for CT Matching (1/2)

SN = 100 MVA
UN2 = 20 kV UN1 = 110 kV
3000/1A 750/1A
IP2 = 2750A IP1 = 500A
(load current) Side 2 Side 1 (load current)
InO2 = 2887A InO1 = 525A

measured
IS2 = -0.916A 7UT6 IS1 = 0.66A secondary currents
7UM62

IDiff = ?
IRest = ?

Principles Transf. Diff 23


Measuring Pre-processing, Example for CT Matching (2/2)
SN
1. Calculation of the transformer nominal current I nO 
3  USetting
I NCT
2. Correction factor kW 
I nO

3. Correction nominal current I* = kW·IS

4. Calculation of the differential and IDiff = |I1* + I2*| IRest = |I1*| + |I2*|
restraint current

Calculation example:

SN = 100MVA UN1 = 110kV UN2 = 20kV


IN1CT = 750A IN2CT = 3000A
Correction factors: kW1 = 1.428 kW2 = 1.039 IDiff = 0A

Load conditions: Ip1 = 500A Ip2 = 2750A IRest = 1.9A


Secondary currents: Is1 = 0.666A Is2 = -0.916A IDiff = 0·InO
Matched currents: IRest = 1.9·InO
I1* = 0.95A I2* = -0.95A

Principles Transf. Diff 24

You might also like