Fire Fighting Design Brief Report

This document provides a fire-fighting design brief for a large office building project. It outlines the scope of the fire-fighting system, applicable codes and standards, and proposed types of fire protection systems. These include a fire hydrant system, automatic sprinkler system, addressable fire detection and alarm system, two-way public address system, portable fire extinguishers, fire signages, and an emergency assembly point. It provides details on the proposed water storage tanks, fire pumps, wet riser system, sprinkler system, and addressable fire alarm and detection system.

Uploaded by

Ranu Agarwal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
757 views16 pages

Fire Fighting Design Brief Report

This document provides a fire-fighting design brief for a large office building project. It outlines the scope of the fire-fighting system, applicable codes and standards, and proposed types of fire protection systems. These include a fire hydrant system, automatic sprinkler system, addressable fire detection and alarm system, two-way public address system, portable fire extinguishers, fire signages, and an emergency assembly point. It provides details on the proposed water storage tanks, fire pumps, wet riser system, sprinkler system, and addressable fire alarm and detection system.

Uploaded by

Ranu Agarwal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 16

PROJECT NO - Pa ge |

14157001 1

SECTION 04 (Doc.No.A/DBR –
001)

FIRE-FIGHTING DESIGN BRIEF


REPORT

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 2

1.0 SCOPE
2.0 STANDARDS AND CODES
3.0 TYPES OF SYSTEM PROPOSED
4.0 FIRE HYDRANT SYSTEM
5.0 AUTOMATIC SPRINKLER SYSTEM
6.0 ADDRESSABLE FIRE DETEC TION AND ALARM
SYSTEM
7.0 TWO WAY PUBLIC ADDRESS SYSTEMS
8.0 PORTABLE FIRE EXTINGUISHERS
9.0 FIRE SIG N A G ES
10.0 FIRE SAFETY PLAN
11.0 EMERGENCY ASSEMBLY POINT

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 3

1.0 SCOPE
The design of Fire Fighting System in respect of fire safety as the functional usage requires office building of large number of people at a
single location and any emergency must be ensure minimum disruption in operations.

The objective of this report is to design a Fire Fighting system that shall provide:
 Life safety of occupants.
 Property protection.
 Compliance with all relevant statutory requirements.
 Minimum disruption during emergency to the operations.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 4

1. CODES AND STANDARDS


The design and planning of Fire Protection, Detection & PA system shall be done keeping in view the following codes and standards (Latest
editions):

 National Building Code: 2005 and local bylaws.

 BIS: 3844, 15105, 2189 and other relevant standards.

 Local Fire Authority.

 NFPA 13, Sprinkler System.

 NFPA 14, Hydrant System.

 NFPA 72, Fire Alarm System.

 NFPA 10, Fire Extinguishers.

Hazard Classification

As per NBC this premises is classified as Business Occupancy, Group - E, Business building, Sub - division - E1, Office Building.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 5

3.0 TYPES OF SYSTEM


PROPOSED
OCCUPANCY DESCRIPTION AREA REMARKS
Fire Hydrant / Wet riser cum down comer / Yard Hydrant /
Office Building Automatic Sprinkler / Fire Detection and Alarm / Two way All floor Area
Public addressable systems / Fire Extinguishers

FIRE WATER STORAGE


TANKS
SL, No TANK CAPACITY LOCATION SYSTEM REMARKS

1 200000 Litres Basement Hydrant & Sprinkler Combined Underground Sump

2 25000 Litres Terrace Hydrant Separate tank for tower -1 & 2

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 6

FIRE WATER PUMPS

Fire pumps should deliver water at Terrace with minimum pressure of 3.5 bars. Fire pumps shall be horizontal centrifugal type coupled
to suitable prime mover.

SL. NO. DESCRIPTION CAPACITY REMARKS

1 2 No Electrically driven main pump for Hydrant system 100 mtr @ 2850 LPM

2 2 No Diesel Engine driven standby pump for Hydrant


100 mtr @ 2850 LPM
& sprinkler system
Combined Fire Pump Room
3 2 No Electrically driven main pump for Sprinkler system 100 mtr @ 2850 LPM

4 2 No Electrically driven Jockey pump for Hydrant system 100 mtr @ 180 LPM

5 2 No Booster pump 35 mtr @ 900 LPM

2 No of Common compartmentalized Control panel located at pump house controls all pumps and further the status of pumps shall be
extended to IBMS system for monitoring through the Fire alarm panel.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 7

4.0 FIRE HYDRANT SYSTEM


Hydrant system with ring main runs at basement ceiling level with isolation valves. The yard hydrant points shall be extended from the same
mains and also the wet risers shall be connected from the mains with isolation valves.

Hydrant mains shall be G.I. heavy grade pipe with suitable type of fittings made of by same material. Underground pipes shall be treated for
anti corrosive material.

System consisting of internal hydrants for all floor levels near staircase or corridor, External hydrants at suitable locations and Fire brigade
inlet connection for emergency pumping to the system and for the fire tank.

External Hydrants

Hydrants are proposed at every 45m of periphery of the Building to


protect the building from outside with all accessories.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 8

WET RISER SYSTEM

Wet riser shall be provided for every 1000 sq.mts floor area on all floors and shall running inside the dedicated shafts. Wet risers shall be
minimum 150 mm diameter in size and shall run up to terrace and all risers to be connected to the ring main at terrace and connect to the
terrace tank.

Internal Hydrant tapped from the risers with all accessories.

5.0 AUTOMATIC SPRINKLER SYSTEM


System consisting with Sprinkler mains pipes from pump
room, piping network inside the floor area with properly
designed pipe supports, Sprinkler control valve located
outside the building and isolation valves. Sprinklers shall be
standard response pendant type, 68 deg. C temperature
rating and shall design to cover 9 to 12 sq. m.

At each floor sprinkler distribution header shall tapped off


from sprinkler riser with isolation valves and flow
switches on each distribution header and flow switch
shall be connected to fire alarm panel to monitor in case
of water flow in the event of fire.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 9

6.0 ADDRESSABLE FIRE DETECTION & ALARM SYSTEM


Complete Analogue Addressable, zoned and electrically supervised, Class A, multiple loops Fire Alarm and Detection system, including
initiating device and notification appliances shall be provided for Building.

The Fire detection and alarm system shall be consisting with the following,

 Addressable analogue Fire detection & alarm control panel.


 Smoke & heat detectors
 Manual pull stations (break glass type)
 Electronic Hooters cum strobes
 Conduits / wiring
Note: Separate Panel of Fire Alarm & PA System each tower.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 10

The main features of system shall be as under;

Interfaces

Fire Alarm System Interface with third party Systems at Fire alarm Control Panel (FACP), and programmed from Network Control Station in
Fire Control Room located at ground floor.

a. Fire Pump Status: Each fire pump shall have status indication for power failure, pump running and phase reversal. An audible trouble
signal shall sound until acknowledged and automatically restored. The running condition of pump shall be permitted to be alarm
condition whereas all other status of pumps shall be permitted to be supervisory condition.

b. The operation of Sprinkler Water flow switch, Valve supervisory switch and Pressure Switches shall c ause an alarm / supervisory
c ondition at Fire Alarm Control Panel.
c. Elevator Recall for Fire fighter servic es; Primary main floor recall shall be activated on alarm by an elevator lobby or elevator
machine
room detector. Alternate floor recall shall be activated by detector in the main floor elevator lobby.
d. Stair Pressurization: With-in a given zone, an automatic sprinkler system water flow switch, an open area smoke detector outside a
pressurized stairwell shall activate the stair pressurization systems for that zone.
e. AHU Tripping: Within a given zone, an automatic sprinkler system water flow switch, an open area smoke detector, shall switch off the
Air Handling units of affected area and simultaneously the respective fire damper.
f. External Dampers: Within a given zone, an automatic sprinkler system water flow switch, an open area smoke detector, shall switch off
associated damper of duct crossing through fire resistant wall.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 11

g. Smoke Control System: Within a given zone, an automatic sprinkler system water flow switch, an open area smoke detector or the
manual fan control at Fire Control Room shall switch OFF/ON the smoke control fan of associated Zone.
h. Building Management System (BMS): Shall interface with building management system for monitoring of fire net by BMS.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 12

7.0 PUBLIC ADDRESS SYSTEM


A public address system with a two ways
communication facility comprises with speakers
located at various strategic locations (near entry /
exit / staircases) at all floors connected to a floor
selector-switching console. The floor selector-
switching console is interconnected to an
amplifier of suitable wattage and a
microphone. The system installed close to
the fire alarm control panel. In the event of
actuation of any detector or manual call point
on a particular floor, the fire marshal or security
personnel can select the public address speaker
on the affected floor by operating the particular
floor switch on the switching console.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 13

8.0 PORTABLE FIRE EXTINGUISHERS


The portable fire extinguishers shall be provided as per NFPA 10, standards for portable fire extinguishers. However, additional fire
extinguishers shall be provided as per requirement of local Fire Services.

SL. NO TYPE OF FIRE EXTINGUISHER PROPOSED LOCATION

1. 5 kg multipurpose ABC dry chemical type fire extinguishers Staircase landing and office area

2. 4.5 kg or higher capacity CO2 fire extinguisher Electrical Rooms

3. 9 lt. Aqueous film forming foam (AFFF) stored pressure type fire Generator room and fuel pump room
extinguisher
4. 5 kg or higher capacity Clean Agent Extinguishers Fire Control room / Server and Data storage area

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 14

1. FIRE SIGNAGES
The signage’s for during evacuation for each floor level to be provided in position the following type of sign boards made out of 3mm thick
"Opaque" PVC foam board with PVC non-reflective self adhesive vinyl painted foam board.

1. Signage with printed “IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" of 1.5cm height letters in red with white back
ground. The size of the board shall be 25cm x 30 cm and shall be fixed at the height of 2mts. from finished floor near Manual call
points.
2. Floor identification signage (i.e., GROUND FLOOR …etc.) at each stair enclosure on every floor, indicating the floor number in words,
lettering size shall be 7.5 cm with contrasting colour from back ground. Size shall be 15cm x 60cm.
3. Plant rooms and equipments room signage’s need to be considered for identifications.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 15

10.0 FIRE SAFETY PLAN


A Fire safety plan for preventing and extinguishing any accidental fire in the building and action to be taken by the occupants in case of such
fire has been provided at strategic points, this shall be provided near each staircase area.

AMIN PROPERTIES
LLP FIRE-FIGHTING
PROJECT NO - Pa ge |
14157001 16

11.0 EMERGENCY ASSEMBLY POINT


An area at an appropriate place in the allowed/required setbacks shall be earmarked
with a proper board as “ASSEMBLY POINT” for the occupants to assemble after
evacuation during practice drill and in an emergency.