Lecture 8
Conservation of Complex
Power Law
Learning Outcomes
After completing this unit you will be able to:
1. Apply complex power conservation law to compute active and
reactive power consumption in a circuit
2. Apply complex power conservation law to determine the value of
the capacitance needed to correct the power factor of a circuit.
Conservation of Complex Power in Parallel Circuit
Consider the parallel connected circuit shown below. The complex
power supplied to the circuit is given by the expression
1
S V I*
2
where I* is the conjugate of the input
current I. For the circuit given, the
input current I is related to the branch
currents I1 and I2 via the equatian
I I1 I 2 S
Hence
* * *
I I1 I 2
Conservation of Complex Power in Parallel Circuit
Thus we can write
1 1
S V I V I 1* I 2*
*
2 2
1 1
V I 1* V I 2*
2 2
S 1 S 2
S
This result shows that for a parallel-connected circuit the complex
power supplied by a voltage source is equal to the sum of the
complex power consumed by the load impedances.
Conservation of Complex Power in Parallel Circuit
Alternatively, we can rewrite the previous expression as follows:
S S 1 S 2 0
In words, this result tells us the sum of complex power absorbed by
all the elements of the circuit (i.e., voltage source and impedances) is
zero. This statement is the complex power conservation law.
Conservation of Complex Power in Series Circuit
Consider next the series-connected circuit shown below. Complex
power supplied by voltage source V to the circuit is given by the
expression
1
S V I*
2
Now, for the series-connected
impedances, their voltage drops V1
and V2 are related to the source
voltage V via the expression
S
V V 1 V 2
Hence,
V * V1 * V2*
Conservation of Complex Power in Series Circuit
Therefore, we can write
1 *
1
S V I *
2
V1 V2* I *
2
1 1
V1 I * V2 I *
2 2
S 1 S 2
This can be written as S S 1 S 2 0 S
Thus, like the parallel circuit discussed earlier, this results tells us
that the sum of complex power absorbed by all the elements of the
series circuit (voltage source V and impedances Z1 and Z2) is zero.
Conservation of Complex Power in General
Consider a closed circuit consisting of n elements. If the current
flowing through the kth circuit element is Ik and Vk is the voltage drop
across it, then, we can write
* * +
Ik
VI
Sk
all elements
k k
all elements 2
0 Vk
-
Now, the complex power is conserved implies that both average
power and reactive power are conserved. That is,
all
Pk 0 and all
Qk 0
elements elements
Worked Example
Find the total complex power supplied by the source to the three
loads.
Load 1
I
100 W, 0 VAR
+ Load 2 Load 3
E 1000 V 700 VAR (L), 200 W 1500 VAR (C), 300 W
_
Solution
Complex power consumed by load 1,
S1 P jQ 100 j 0 VA
Complex power consumed by load 2,
S 2 P jQ 200 j 700 VA
Complex power consumed by load 3,
S3 P jQ 300 j1500 VA
Load 1
I
100 W, 0 VAR
+ Load 2 Load 3
E 1000 V 700 VAR (L), 200 W 1500 VAR (C), 300 W
_
Solution
Total complex power consumed by the loads,
S P jQ S1 S 2 ( P1 P2 ) j (Q1 Q2 )
(100 200 300) j (700 1500) VA
600 j800 1000 53.13o VA
Worked Example
The 60 resistor absorbs 240 Watt of average power. Calculate V
and the complex power of each branch. What is the total complex
power?
Solution
Phasor domain circuit:
Let I 2 be the current through the 60-Ω resistor. Now P I 2 R ,
2
therefore
240 60 I 22
240
Solving for I2, we obtain I 2 2A
60
Solution
Let I 2 be the reference phasor. Therefore, we can write
I 2 2 j 0 20 o A (rms)
Application of Ohm’s law to the right branch impedance gives us the
voltage drop
Vo 60 j 20 20 o 120 j 40 V (rms)
Application of Ohm’s law to the left branch impedance gives us the
branch current
Vo
I1 3.2 j 2.4 A (rms)
30 j10
Next, KCL gives us the current equation
I I1 I 2 3.2 j 2.4 2 5.2 j 2.4 A
Solution
V 20 I Vo 104 j 48 120 j 40 V
224 j88 240.6721.45o V
For the 20-Ω resistor,
V3 20 I 204 j 48 114 .54.8o V
I * 5.2 j 2.4 5.2 j 2.4 A
*
S 3 V3 I * 114 .54.8o 5.2 j 2.4
Therefore,
S 3 654 19.97 o A
Solution
For the (30 - j10) Ω impedance,
Vo 120 j 40 126.5 24.8o V
I1 3.2 j 2.4 436.87 o A
S1 Vo I1* 126.518.43o 4 36.87 o VA
Therefore,
S1 506 18.44o 480-j160 VA
Solution
o
For the (60 + j20) Ω impedance, I 2 20 A
S 2 Vo I 2* 126.518.43o 20o 25318.43 VA
Therefore,
S 2 240 j80 VA
The overall complex power supplied by the source is
ST 240.6721.45o 5.727 24.8o VA
giving
ST 1736 j80 VA
Exercise
Two loads are connected in parallel. Load 1 has 2 kW, p.f. = 0.75
leading, and Load 2 has 4 kW, p.f. = 0.95 lagging. Calculate the p.f.
of the two loads and the complex power supplied by the source.
Load 1 Load 2
Solution
Power triangle for Load 1: Therefore,
Q1 P1 tan 1
2000 tan 41.41
S1
jQ1 1764 VAR
1
P1 = 2 kW Complex power consumed by
load 1 is
1 acos0.75 41.41 S 1 P1 jQ1
From power triangle, we get 2000 j1764 VA
Q1
tan 1
P1
Solution
Power triangle for Load 2: Therefore,
Q2 P2 tan 2
P2 = 4 kW 4000 tan 18.195
2 1315 VAR
-jQ2
S2
Complex power consumed by
load 2 is
2 acos0.95 18.195
S 2 P2 jQ2
From power triangle, we get 4000 j1315 VA
Q2
tan 2
P2
Solution
Sum of complex power consumed by the two loads is
S L S1 S 2
2000 j1764 4000 j1315 Load 1 Load 2
6000 j 449 S1 S2
6017 4.28 VA
S
Power triangle for the complex power consumed by the two loads:
Power factor of the two loads,
SL
jQ P
cos
SL
P
6000
0.997
6017
Solution
By the complex power conservation law,
SL SS
where SL complex power consumed by the two loads
SS complex power suuplied by the source
Therefore, complex power supplied by the source is
SS 6000 j 449 VA
Power Factor Correction
• The objective to adjust the power factor by adding a compensating
impedance (usually a capacitive reactance) to the load.
Source compensating
current capacitor
Load with low
C power factor
• The goal of power factor correction is to deliver maximum power
to the load using the lowest source current.
Power Factor Correction
In the following worked example we will first determine the current
that the generator needs to supply to load when its power factor is
not corrected to unity. Then, we will demonstrate the advantage of
correcting the power factor of the load on the magnitude of the
current that needs to be supplied by the generator to the load.
Worked Example
For the circuit shown, calculate IS
(i) the supply current,
(ii) the reactive power that needs to be 600 V Load
supplied by a capacitor bank to
increase the power factor to unity.
P = 120 kW
(iii) the value of the supply current at
Q = 160 kVAr
unity power factor.
Solution
Let VS be the reference phasor.
Complex power supplied by the generator to the load is
S L VS I S* IS
6000 o I S* P = 120 kW
600 V Load
120,000 j160,000 Q = 160 kVAr
Therefore,
SL
* 120,000 j160,000
I
S
6000o
VS = 6000 V
333.3351.3o A (rms) 51.3
and
I S 333.33 51.3o A (rms) IS = 333.3-51.3 A
This result shows that the supply current lags behind the supply voltage
by 51.3. The power in this case is cos(51.3) = 0.625
Solution
To achieve unity power factor, we need to connect a compensating
reactive load in parallel with the original load that cancels out the
reactive power.
IS
Let S C be the complex power consumed
by the compensating load. Then, Reactive
complex power supplied by the generator
Load
600 V load
to the two loads is
SG SC S L P = 120 kW
Q = 160 kVAr
To obtain unity power factor, we need ensure that S G has no
imaginary part. Now, since
S L 120,000 j160,000
Solution
Therefore, we require
SC j160,000
so that
SG SC S L
120,000 j160,000 j160,000
120 kW
Therefore, after the deployment of the compensating capacitor, the
supply current
SG 120 kW
I S* o
200 0 o
A IS
VS 6000
Solution
Thus, by correcting the load power factor, we have managed to deliver
the active power required by the load and at the same time significantly
reduced the supply current. This reduces the size of the cable used to
supply the load current and also the required VA rating of the generator.
The VA rating of the generator for the power factor corrected load is
S = VSIS = 600 x 200 = 120 kVA
whereas the VA rating of the generator for the uncorrected load
power factor is
S 120 10 160 10
3 2 3 2
200 kVA
(A reduction of about 40% in the capacity of the generator required!)
Worked Example
Without the capacitor connected into the circuit shown below,
Vo = 450∠0 V Is = 17∠−20 A
f = 50 Hz
What is the value of C that which will
correct the power factor angle to zero,
that is, reduce Is to a minimum value in
phase with Vo? Determine the reduction
of current which resulted from
connecting the capacitor into the circuit.
Solution
Consider the case where the capacitor C is not connected to the
circuit, as shown below.
IS
Complex power supplied to the load is
*
S L V O ( rms ) I s ( rms ) ZG
VO Z
4500 17 20 VS
765020
7189 j2616 VA IS
Next, consider the case where the capacitor
C is now connected to the circuit, as shown ZG
below. By definition, reactive power of the C VO Z
compensated load is zero. That is, we VS
should have
QL QC 0 VA SL ’
Solution
This requires us to connect a capacitance C whose capacitive
reactance – jQC will cancel out the inductive reactance of the load.
That is we require
j QL QC 0
IS
Thus, we require that IC
ZG
jQC j 2616 VA C VO Z
* VS
Now, SC V I C
Therefore,
SL’
* S C 2616 90
IC 5.81 90 A
V 4500
and
I C 5.8190 A
Solution
Reactance of capacitor is
Vo 450
XC 77.4
I C 5.81
1
Since XC , therefore the value of capacitance required is
C
1 1
C 40.7 F
X C 2 50 77.4
Since S L V o I S ' , the new value of supply current is
S L 7189
I S ' 15.97 A
Vo 450
Summary
In this study unit we have looked at
1. Complex power
2. Conservation of complex power
3. Power factor correction.