Course T315 Chapter 5
AC 800M Hardware
Extended Automation System 800xA
© ABB University - 1
Revision A
AC 800M
Hardware AC 800M Hardware
CPU
Communication Interfaces
I/O Connections
Hardware Redundancy
© ABB University - 2
Revision A
CPU
CPU PM8xx
Fuses for
Modulebus and
CEX-bus
CPU Baseplate
© ABB University - 3
Revision A
CPU
Different Processor Units
Unit Description On-line replacement Redundancy
PM860 48 MHz 8 Mbytes RAM 2 Ethernet ports, 1 Serial Port and 1 tool No No
port. Electrical and Optical ModuleBus for S800 I/O
PM856 48 MHz 8 Mbytes RAM No No
2 Ethernet ports, 1 Serial Port and 1 tool port. Electrical and
Optical ModuleBus for S800 I/O. Application speed is half of
PM860.
PM851 48 MHz 8 Mbytes RAM 1 Ethernet port, 1 Serial Port and 1 tool No No
port. Electrical and Optical ModuleBus for S800 I/O (only one
cluster). Application speed is half of PM860.
PM861 singular or redundant. 48 Mhz 16 Mbytes RAM 2 Ethernet ports, 1 Yes Yes
Serial Port and 1 tool port. Electrical and Optical ModuleBus for
S800 I/O
PM861A Same as PM861 but can use redundant communication unit Yes Yes
CI854A and BC810.
PM864 singular or redundant. 96 Mhz 32 Mbytes RAM 2 Ethernet ports, 1 Yes Yes
Serial Port and 1 tool port. Electrical and Optical ModuleBus for
S800 I/O. PM864 is 50% faster than PM861 in executing an
application.
PM864A Same as PM864 but can use redundant communication unit Yes Yes
CI854A and BC810.
PM865 (PA/HI) singular or redundant. 96 Mhz 32 Mbytes RAM 2 Ethernet ports, 1 No Yes
Serial Port and 1 tool port. Electrical and Optical ModuleBus for
S800 I/O. Supports S800 high integrity.
© ABB University - 4
Revision A
© ABB University - 5
Revision A
CPU
Internal
Battery
External
CPU
AC 800M Ports
Communication expansion
(CEX bus)
CPU
Electrical Modulebus
Optical Modulebus
port
Ethernet ports COM3/4 ports
© ABB University - 6
Revision A
AC 800M
Hardware AC 800M Hardware
CPU
Communication Interfaces
I/O Connections
Hardware Redundancy
© ABB University - 7
Revision A
Communication
Interfaces Communication Interface Units
Unit Description On-line Redundancy
replacement
CI851 The CI851 unit is the communication interface for PROFIBUS DP-V0. No No
Only to use with S200 I/O.
CI853 The CI853 is the RS-232C serial communication interface unit. No No
CI854 The CI854 unit is the communication interface for PROFIBUS DP-V1. Redundant Profibus No No
lines.
CI854A The CI854A unit is the communication interface for PROFIBUS DP-V1. Redundant Profibus Yes Yes
lines and redundant interface cards.
CI855 The CI855 unit is the communication interface for MasterBus 300 for the AC 800M. Yes No
CI856 The CI856 is a communication interface for the S100 I/O system. Yes No
Up to five S100 I/O racks can be connected to one CI856 where each I/O rack can hold up to
20 I/O boards.
CI857 The CI857 unit is the communication interface for INSUM Yes No
CI858 The CI858 unit is the communication interface for ABB Drives using DriveBus No No
CI860 The CI860 unit is the communication interface for Fieldbus Foundation HSE Yes No
© ABB University - 8
Revision A
Communication
Interfaces Communication Exchange Bus - CEX Bus
TB850
TK850 with DB25P and TB851
or
© ABB University - 9
Revision A
AC 800M
Hardware AC 800M Hardware
CPU
Communication Interfaces
I/O Connections
Hardware Redundancy
© ABB University - 10
Revision A
I/O
Connections I/O Connection Possibilities
© ABB University - 11
Revision A
I/O
Connections S800 I/O Connected with Modulebus
max. 2.5 meters
Base cluster
Modulebus
extension
Termination
TB807
I/O cluster 1
TB820
Optical modem
I/O cluster 2 I/O cluster 3 I/O cluster 4
© ABB University - 12
Duplex
Revision A
Simplex max. 15 or 200m
max. 15 or 200m
I/O
Connections S800 I/O Connected with Profibus
CI830
Profibus slave
with CI851
TB810 Profibus
master
Base cluster
Max. 2.5 meters
TB820 I/O cluster 1
Optical modem
I/O cluster 2 I/O cluster 3 I/O cluster 4
© ABB University - 13
Revision A
Duplex
Simplex max 15 or 200m
max 15 or 200m
I/O
Connections ABB Range of I/O Units
© ABB University - 14
Revision A
I/O
Connections Module Termination Units
Compact Extended
© ABB University - 15
Revision A
AC 800M
Hardware AC 800M Hardware
CPU
Communication Interfaces
I/O Connections
Hardware Redundancy
© ABB University - 16
Revision A