Switchgear & Protection Government College of Engineering Karad (Electrical Engineering Department) Prof - Uma S.Patil
Switchgear & Protection Government College of Engineering Karad (Electrical Engineering Department) Prof - Uma S.Patil
Prof.Uma S.Patil
Switchgear & Protection
Government College Of Engineering Karad
(Electrical Engineering Department)
Introduction
1. Significance of switchgear, protection & power systems.
2. Location of switchgear in typical power system(Single line
diagram)
3. Substation equipments
4. Faults & abnormal conditions
5. Fault calculations
6. The fault clearing process
7. Protective relaying
8. Neutral grounding & equipment grounding
9. Over voltages & Insulation co-ordination.
Department of Mechanical Engineering 3
Department of Mechanical Engineering 4
Department of Mechanical Engineering 5
Department of Mechanical Engineering 6
Department of Mechanical Engineering 7
Causes of Electrical Faults
1. Weather conditions: It includes lighting strikes, heavy rains, heavy winds, salt
deposition on overhead lines and conductors, snow and ice accumulation on
transmission lines, etc. These environmental conditions interrupt the power
supply and also damage electrical installations.
2. Equipment failures: Various electrical equipments like generators, motors,
transformers, reactors, switching devices, etc causes short circuit faults due to
malfunctioning, ageing, insulation failure of cables and winding. These failures
result in high current to flow through the devices or equipment which further
damages it.
Failure of conducting path due to break in a conductor is a type of fault.
3. Human errors: Electrical faults are also caused due to human errors such as
selecting improper rating of equipment or devices, forgetting metallic or
electrical conducting parts after servicing or maintenance, switching the circuit
while it is under servicing, etc.
4. Smoke of fires: Ionization of air, due to smoke particles, surrounding the
overhead lines results in spark between the lines or between conductors to
insulator. This flashover causes insulators to lose their insulting capacity due to
high voltages.
Weather Conditions
Equipment failures
Smoke of fires
Symmetrical Faults
Unsymmetrical Faults
21
Switchgear and Protection
Switchgear:
It is a general term covering a wide range of equipment concerned with
switching and protection. All equipment associated with fault clearing
process are covered by the term switchgear. Switchgear includes switches,
fuses, circuit breaker, isolator, control panels, lighting arrestor, CT, PT and
various associated equipment
Switchgear and Protection
Control Gear:
It is used for switching and controlling power consuming devices. It is a
form of switching device capable of make and break the current in one or
more electric circuit such as relay.
30
FPGA Based Relay
https://www.nature.com/articles/s41467-021-2
2332-8
ANN
https://www.researchgate.
net/figure/Installation-diag
rams-of-protection-with-A
NN-relay-32-ANN-topology
-used-and-data-The_fig4_3
40405545
• fault cleared
• Fault interrupts is completed i.e. fault is
5
6 cleared
37
When the fault occurs
• the relay (2) connected to CT (8) and
PT (7) actuates and close its contact (6)
• Current flows from the battery (5) in
the trip circuit (4)
• Trip coil (3) is energized and CB (1)
operating mechanism is actuated.
• Auxiliary contact (a) can be used for
interlocking the CN with other
equipment to avoid enormous
operation.
Components of S/S
Components of S/S
Components of S/S
Electrical path through substation
https://www.osha.gov/SLTC/etools/electric_power/illustrated_glossary/substation.html
#Equipment
Metal Clad Switchgear
Isolator
Isolator
Isolator
Over current Relay
50
Over current Relay
A protective relay which operates when the load current exceeds a preset value, is
called an over current relay.
The value of the preset current above which the relay operates is known as its pick-up
value.
Time-Current characteristics
1. Definite-time Over current Relay-
A definite-time over current relay operates after a predetermined time, when the
current exceeds its pick-up value.
2. Instantaneous Over current Relay-
An instantaneous relay operates in a definite time when the current exceeds its
pick up value. The operating time is constant, irrespective of the magnitude of the
current.
3.Inverse-time Over current Relay-An inverse-time over current relay operates when
the current exceeds its pick-up value. The operating time depends upon the
magnitude of operating current.
4.Inverse Definite Minimum Time Over current (I.D.M.T.) Relay-
This type of relay gives an inverse-time current characteristics at lower values of
the fault current and definite-time characteristics at higher values of the fault
current.
5.Very Inverse-time Over current Relay-
6.Extremely Inverse-time over current Relay- 51
Over current Protective schemes
1.Time graded systems
54
55
Combination of both 56
57
58
59
Relay Coordination
60
61
62
https://www.electrical4u.net/relay/directional-over-current-n
on-directional-over-current-protection-working-principle/
https://electengmaterials.com/directional-over
-current-relay-67/ 64
65
https://www.gegridsolutions.com/multilin/cata
66
log/350.htm
It is a safety device used in electrical installations with high earth impedance. It detects
small stray voltages on the metal enclosures of electrical equipment. The result is to
interrupt the circuit if a dangerous voltage is detected. The EFR is protected against
tripping from transients and prevents shock.
Transformer Protection Method
No. Fault Type Protection used
Primary winding Phase-
1. Differential; Overcurrent
Phase fault
Primary winding Phase-
2. Differential; Overcurrent
Earth fault
Secondary winding Phase-
3. Differential
Phase fault
110 kV 22
132 kV 27
220 kV 35
400 kV S / C ( Single
Circuit ) 46
86
Transmission tower
Symbols Utilized in SLD
Symbols Utilized in SLD
Symbols Utilized in SLD
Single Bus bar arrangement
Single Bus bar arrangement
Key Diagram of Substation
The system architecture of the substation automation system in the 220 kV-
132 kV transmission substation. ---
Protection of Zone
Types of Circuit breaker
MCB
MCB
•Basic Principle of MCB
•Hardware circuit of MCB
•Types of MCB
Circuit breaker
•Purpose of CB
-Break the power flow
-Contain the arcing within its
chamber and extinguish it
-Animation of CB
ACB
https://www.cigreindia.org/
Fault Circuit
https://www.tina.com/tinacloud/
https://www.tina.com/circuit-design/
https://www.tina.com/current-flow-voltage-animation-in-tinacloud/
How does Arc produce
•When a fault occurs a heavy current flows through the contact of
circuit breaker.
• When the contacts begin to separate, the contacts area decreases
rapidly which causes high increases in fault current density and
hence rise in temperature.
•When the contacts are separate, a potential difference is created
between them. If the voltage between contacts is more than
dielectric strength of medium between contacts (usually the
medium is air or oil), it may sufficient to ionize the medium
between contacts.
•The ionized air or vapour act as a conducting path and hence the
arc is structed between contacts.
How does Arc produce
•The voltage that appears across the contact of circuit breaker
during arcing periods is called Arc voltage.
•The arc between contacts act as conductor and persist a
resistance value known as arc resistance. Current flowing
between the contacts depend on the earth resistance.
– Greater the arc resistance, smaller the current that flows
between contacts.
Arc resistance depend upon flowing factors
1. Degree of ionization: As the ionized particle between
contacts is decreases, the arc resistance increases.
2. Length of arc: As the separation between contact increases,
the length of arc also increases which results in increase in arc
resistance.
3. Cross section area of arc: The earth resistance increases
with the decrease in area of cross section of the arc.
Factor responsible for maintaining arc
There are two main factors responsible for maintaining arc
between the contacts. These are
1. Potential difference between contacts: When the contacts
have small separation, then the potential difference between
them is sufficient to maintain the arc.
2. The ionized particles between contacts: The ionized
particles between contacts act as charge carriers and offers
conducting the path.
First way is to separate the contacts to such a distance that
potential difference becomes insufficient to maintain the arc.
However, this method is impossible in higher voltage system
where a separation of many meters may be required.
Second way to extinguish the arc between contact may achieved
by cooling the arc by removing the arc particle from the space
between contacts.
Method of Arc extinction
High resistance method
In this method, the arc resistance is increases gradually so that current is reduced to such
a value that heat is insufficient to maintain the arc.
Consequently, the current is interrupted or the arc is extinguish. But in this method, majo
work is to increase resistance between contacts. Resistance of arc may be increased by
1. Lengthimg the arc: As length of arc increases, the arc resistance also increases. The
length of arc can be increased by increasing the gap between contacts.
2. Cooling of arc: Cooling help in de-ionisation of the medium between the contacts.
This increases the arc resistance and remove the heat from arc.
3. Reducing cross sectional area of arc: By reducing the cross section area of arc the
voltage necessary to maintain the arc is increased. This can done by allowing the arc pass
through the similar area compared to wide area.
4. Splitting of Arc: The resistance of the arc can be increased by splitting the arc into a
number arc in series. These may be split by introducing some conducting plates between
the contacts of circuit breaker.
The major disadvantages in this method is that is very high energy is dissipates in the arc
Therefore, it is the employed only in dc circuit breaker and low capacity is ac circuit
breaker.
Low resistance or zero current method
•This method is applicable only in ac circuit breaker because ac has natura
zero of current.
•As the medium (air or oil) between contacts contain ionised particles so it
has small dielectric strength.
•Therefore ionized air can easily breakdown by the contact voltage and arc
will persist for another half cycle.
•The voltage that appear across the contacts at current zero during arcing
period is called is re-striking voltage.
Low resistance or zero current method
There are following two ways to achieve this
1. Causing the ionised particles in the space between contact to
recombine into neutral molecule.Ionised particles are responsible to
carry current and reduced dielectric strength of medium. When
ionised particles are recombine, the dielectric strength of medium
increases.
2. Sweeping the ionised particles away and replace them by
unionised particles.If the ionised particles of medium between
contacts are replaced with fresh particles, the dielectric strength of
the medium between contact is increased. Therefore, the air fails to
the strikes and flow of current is interrupted.
3.The deionisation of medium can be achieved by following
methods
– Lenthing of the gap: Dielectric strength of the medium can be
increased by increasing the length of gap between contacts.
Low resistance or zero current method
– High pressure: More the pressure of medium between contacts
higher the density of particles. The increased density of the particles
causes higher rate of de-ionisation and hence the dielectric strength
of medium between contacts increases.
– Cooling: Cooling causes ionised particles in the space between
contacts to recombine into neutral molecule. This increases the
dielectric strength of the medium.
– Bast effect: In this process the ionised particle between contacts
are swept away and replaced by fresh unionised particles. This
increases the dielectric strength of the medium and hence arc fails
to re-strike.
A picture of inductance, resistance, and capacitance on a
single phase. These parameters are uniformly distributed
along the line. and Protection
Trip Circuit
Fault & its equivalent circuit
Switchgear and Protection
•One problem that is major in the power grid and not well understood
is called the Transient Recovery Voltage (TRV).
•When a short-circuit due to a fault in high voltage or medium
voltage system is switched-out by a circuit breaker, the voltage across
the breaker poles rapidly increases; as high as twice the operating
voltage.
•Although the interrupting chamber inside the breaker has enough
dielectric strength to withstand the elevated voltage, the rate at which
the recovery voltage rises (also known as RRRV) can overwhelm the
insulating medium. This leads to arc re-ignition at the poles and
eventually breaker failure.
Transient Recovery Voltage and Its Effect on a CB
Switchgear and Protection
Let’s begin with following conditions
•A solid 3-phase fault close to the circuit breaker is assumed –
produces the most severe TRV.
•Resistance R is ignored for now.
•The line to ground capacitance close to breaker is considered. This
capacitance exists due to capacitance in bushings (specifically
condenser bushing), current transformers, adjacent power
transformer, etc.
Switchgear and Protection
•At the instant a short-circuit occurs, before the breaker opens, the line
to ground capacitance is shorted-out. However as the breaker opens, it
draws an arc. As soon as it is extinguished, the source voltage starts to
charge the line to ground capacitor through the system inductance.
•The consequence? The voltage across the breaker poles is equal to the
system nominal voltage plus voltage created by the natural response of
a L-C circuit. There are two circuits at play here now. Let’s look at L-C
circuit specifically.
•In a lossless L-C circuit, the voltage oscillates indefinitely. The energy
stored in capacitor discharges and in-turn charges the inductor –
storing energy in its magnetic field. Once inductor is charged, it
discharges to charge the capacitor. This cycle looks like below.
Transient Recovery Voltage and Its Effect on a CB
What is arc?
Arc Flash is the result of a rapid release of energy due to an arcing fault between a
phase bus bar and another phase bus bar, neutral or a ground.
An electric arc is an electrical breakdown of a gas which produces an ongoing
plasma discharge, resulting from a current through normally nonconductive media
such as air.
Before 1930: CB interrupting time: 15-30 cycles; relay interrupting time: 6-120
cycles
1930: CB interrupting time: 8 cycles
1935: CB interrupting time: 3 cycles
Present days relay time becomes as small as 1-3 cycles
Switchgear and Protection
Transient in RL series circuit:
Selection of CB for the power system depends not only on the normal current
but also upon the maximum current it may have to carry momentarily and the
current it may have to interrupt at the voltage of the line in which it is placed. In
order to approach the problem for calculating the initial current when a
synchronous generator is short circuited.
Consider a RL circuit
Vm sin( ωt +α ) = Ri + Ldi/dt
Vm Vm RL t
i (t ) sin(t ) e sin( )
Z Z
ac component dc component
where Z= √{R2 + (ωL)2}; θ = tan-1(ωL/R)
Switchgear and Protection
Transient in RL series circuit:
Vm Vm RL t
i (t ) sin(t ) e sin( )
Z Z
ac component dc component
i(t) will be maximum when dc i(t) will be minimum when dc
components will be maximum at α-θ = -π components will be minimum at α = θ
Switchgear and Protection
In the case of short circuit at the terminal of a Synchronous generator.
= iac +idc
A 3-ϕ CB is rated 1250 A, 2000 MVA, 33kV, 4 sec. Find the symmetrical
breaking current, making current and short time rating
Solution:
= 2.55 X 35 = 89 kA
• Short time rating = 35 kA for 4 sec
Switchgear and Protection
Current Interruption in ac CB:
• With the increase in the natural frequency of TRV the rate of rise of TRV increases
the rate of rise of TRV across the break pole causes the voltage stress on the contact
gap tending to continue the arc with higher frequency ( say f4n ), relatively less time is
available for the building up of dielectric strength of the contact gap. Hence higher
frequency is associated with greater stress.
• the breaking capacity of a CB is related with the rate of rise of TRV and therefore
with natural frequency of TRV. The breaking capability is reduced with the increase
in natural frequency
Switchgear and Protection
Effect of Power factor on TRV:
• The voltage appearing across the CB pole at the instant of final current zero is
influenced by the power the factor of the current
• the instantaneous value of the voltage developed across the pole at the instant of
current zero ( when the arc is extinguished) depends on the phase on angle between
the voltage and current i.e. power factor.
• for unity p.f load, both current and voltage are in phase and both are zero at the
instant of current zero.
Switchgear and Protection
Effect of Power factor on TRV:
• for zero p.f current, the peak value of the voltage emax is impressed across the pole
at the instant of current zero. Suck sudden application of voltage give rise to severe
transient and has a high rate of rise of TRV. Hence interrupting current of low p.f. is a
difficult switching duty
• Rate of rise and peak value of TRV depends upon several factors such as
network configuration
type of fault
type of neutral earthing
(i.e solid grounding;
Grounding through resistor)
Switchgear and Protection
Rate of Rise of TRV (R.R.R.V) :
Consider the following circuit, when current reaches zero at final arc extinction, a
voltage e is suddenly impressed across capacitor and there across the CB contact.
The current i which would flow to the fault is now injected in the capacitor and the
inductance. Thus
1 de
i iL ic
L edt c
dt
........ (1)
di e d 2e
c 2
........ ( 2)
dt L dt
Switchgear and Protection
Derivation of Restriking Voltage:
• System voltage, e = Em cosωt
i = (Em / ωL) sinωt [since the current lags the voltage by 900 before
opening of CB]
di Em
cos t .......(3)
dt L
di Em
at t 0; ......(4)
dt L
Em e d 2e
Putting Equation (4) in equation (2) we get; c
L L dt 2
de Em t
sin 0 sin
dt LC LC
t
t LC
LC
LC
E peak Em (1 cos ) 2 Em
LC
Switchgear and Protection
Summary:
Switchgear and Protection
Mathematical Problem – 2: A 50 Hz 3ф alternator with grounded neutral has
inductance of 1.6 mH per phase and is connected to bus bar through a CB. The
capacitance to earth between the alternator and the CB is 0.003µF per phase. The
CB opens when r.m.s value of the current is 7500A. Determine:
a) Frequency of oscillation
b) The expression of T.R.V
c) Maximum R.R.R.V.
d) Time for maximum R.R.R.V.
e) Maximum voltage across the contents of the CB after the instant when arc is
formed.
f) Average rate of rise of voltage up to the first peak of the oscillation.
Switchgear and Protection
Switchgear and Protection
Mathematical Problem – 3: A 50 Hz, 66kV, 3ф generator has an earthed neutral. The
inductance and capacitance per phase of the system are 7.5mH and 0.015µF
respectively. In a short circuit test the p.f of the fault current was 0.25 and the fault
current was symmetrical and the recovery voltage was observed as 90% of the full
line voltage. Calculate the rate of rise of restriking voltage (phase to neutral
value). Assume that fault is isolated from the ground.
Solution:
Switchgear and Protection
Switchgear and Protection
Resistance Switching, Damping of T.R.V:
A deliberate connection of resistance in parallel with contact space (arc) is called resistance
switching. Resistance switching is use in CB having high post zero resistance of contact
space (Air blast CB).
It is used to
• Vanish the frequency of restriping voltage
• R.R.R.V is kept within the limit
• Divert the arc current
The value of resistance at which the frequency of T.R.V becomes zero is called the critical
damping resistance.
Switchgear and Protection
Mathematical Problem – 4: In a system of 132 kV, the phase to ground
capacitance is 0.01µF. the inductance is 6H. Calculate the voltage appearing
across the pole of CB if magnetizing current of 10 A is interrupted. Calculate
the value of the resistance to be used across the contact gap to eliminate the
restriping voltage transient. Consider equal power distribution.
Switchgear and Protection
Advantages of Air blast Circuit Breaker:
Ø Air which is free of cost can be used at high pressure.
Ø Reliable operation due to external source of extinguishing energy.
Ø Air is free from decomposition.
Ø Air is clear and non-inflammable.
Ø Fresh medium is used every time.
Ø At high pressure, small contact travel is enough.
Ø The same air serves the purpose of moving the contact and arc extinction.
Ø High speed operation.
Ø It is very easy to incorporate the rapid auto-reclosing facility.
Ø Less maintenance is required compared to Oil Circuit Breaker.
Ø Better stability.
During opening of a capacitor bank the reignition and restriking can occur in an interrupter. The current
drawn or supplied to the capacitor is generally of small order and the CB can interrupt such small
current invariably at first current zero. Due to 90° phase difference, the voltage across the capacitor is at
maximum value (ec) at this instant t1 and the capacitor remains charged at this voltage till t2. After
another cycle t2, the recovery voltage of approximate magnitude er (max) appears across the CB and the total
voltage across the contact gap is the sum of the two voltages.
Switchgear and Protection
Thus the transient recovery voltage of the order of 2 Emax might appear across the CB
at the instant of t2, after the cycle from current zero. Therefore, a restrike may occur
and this can cause damage to the system.
Switchgear and Protection
Auto Reclosure:
It is a special type of CB in which a mechanism is provided so that the contacts of
the CB will open when there is a fault on the system and will automatically try to
close after a short delay. If the fault is removed within this delay time, the contact
will be able to close by itself, otherwise it will be opened again. In this way the
CB will try to close its contact three times. If the fault still persists, the CB will
remain opened.
162