F & G and ESD Interface

• The F&G system is used to initiate


alarm, initiate protective actions,
shutdown equipment and alert
personnel.
• The F&G system processes input
signals from the field mounted
detectors, addressable detectors and
manual call points.
• The F&G System is controlled and
monitored from the Operator
Stations in (CCR).
The F&G CAAP in CCR

1
The safety system will have one dedicated
safety OS, but the system may use all other OS
as well.

The safety Field Stations (FS) are located in Safety OS Other OS


ITR.

Safety systems are usually designed as 1oo2


redundant systems. Network A

The KM 1oo2 architecture consists of two


RCU’s connected in parallel, where both RCU: Network B
Read the input cards.
Contain the same software.
Perform the same actions and set
the output cards. ESD FS PSD FS F&G FS Other FS
Are able to perform a shutdown
independently of each other. (RCU & (RCU & (RCU & (RCU &
Only one RCU is displaying information on RIO) RIO) RIO) RIO)
the VDU, Display Active (DA), the other RCU is
Display Passive (DP).
 Fail situations:
 If the two RCU have different alarm or module status, a redundancy deviation
alarm will be activated.
 If one of the two elements fails (RCU or IO card), the element is isolated, and
the other element will keep control.
 If both elements fail (RCU or IO card), then the output will go to the failsafe
state.
Identification of the
Fire Zone, ESD level The F will open a list
or PSD level. of the instrument tag
connected to the
effect line.

The note field is a


text field
This may include Description of the
C&E revision, effect line.
important notes for
the C&E, etc.

Name of the Fire


Zone, ESD level or
PSD level.

This is a timer, that


will start to count
Level buttons down the time delay
when the effect (or
cause) is activated.

The unique ID for a The unique ID for an


cause line. effect line.

Description of the
cause line.

The X indicates that


the cause will
The F will open a list
activate the
of all detector tags
corresponding effect.
connected to the
cause line.
Legend
Eg. MF1
Confirmed Fire
Scenario