Diesel Generator Sets
Training Materials
Cummins Power (China) Co., Ltd.
Cummins Confidential
                                  1
Generator electrical schematic diagram
                                         2
For operation team , there are total of 4 Cummins diesel generator sets of model C1400D5, of
which 2 are container-type in the terminal building, and 2 are open-type in the central
substation. The maximum power of the four units is 1120KW for one hour, and the normal
power is 1000KW. All of them have the function of self-starting , they will provide good power
supply services
                                                                            3
The engine model is KTA50-G3, which is a V-series, water-cooled engine.
The engine is mainly composed of five systems:
1: Intake system (air filter, turbocharger, intake manifold)
2: Exhaust system (exhaust manifold, turbocharger, muffler)
3: Fuel system (fuel line, fuel filter, fuel pump)
4: Lubrication system (oil pump, oil filter, oil passage, oil pan)
5: Cooling system (radiator, fan, water pump, thermostat ,water jacket)
                                                        4
      The generator is mainly composed of stator, rotor, excitation coil,
       AVR electronic governor, bearing ,casing, etc. This is a 4-pole
       brushless rotating field alternator with class H insulation.
Cummins Confidential
                                                              5
Main functions of the controller
                            Start-stop engine
                            Keep the alternator output voltage constant
                             (400V)
                            To protect the generator set, when the water
                             temperature is high (>97°C), the oil pressure is
                             low (310kPa), and the speed is low (<1350rpm),
                             it will automatically stop.
                            Keep the engine speed constant at 1500±5rpm
Cummins Confidential
                                                       6
Control Panel and Display
                  Sealed film panel
 -
graphic display                       LED status indicator
                                             Backlight switch
                                                                                                             Line 2
                                                                                  Line 1                     Failure data
                                                   Alarm
                                                                              Controller
                                                   status/reset
                                                                           Working status
                                                                                                             Page
                                             Manual operation, start and       Line 3
                                             stop                                                            X/Page Y
                                             Switch and status indicator                                     in total
                                                                               Screen
                                                                               Name                          Data and status
                                                                                                             screen
                                             Buttons
                                             Browse buttons
                                                                                            Button options
                                                                                                                7
    Operation Instructions for Diesel
         Generator Set Control
PC3.3 Controller Panel
                                        8
Display Operation Panel
                               Genset operation-LED
                               Remote start-LED
                               Not in automatic mode-
                               LED
                               Off-LED
     Graphic display           Warning-LED
Selection buttons
(four)
                                "Lamp Test"
                                 button
  "Home" button
                                "Reset"
                                button
                             "Stop" button
                             "Auto" button
    Four switches                   "Start"
    Select button            button
                          CB close
 "ltem Select"
  button                  CB open
                          "Manual Run" button
                                              9
                          "Previous Screen" button
Buttons
          "MANUAL RUN": Supply
          power to the equipment, and
           if the "Start" button is
          pressed within ten seconds,
          the generator set will be
          started.
          "START" must be pressed
          within ten seconds after
          pressing the "Manual"
          button to start the generator
           set.
          "AUTO": The generator set
           is automatically started by
          the remote start signal.
                                     1
                                     0
Automatic Running
 In the automatic position, if the controller receives the remote start signal (the Remote
  start indicator light on the panel is on), the unit will enter the startup program to start
  operation.
 Remote signal “stop” (the Remote start indicator light on the panel is off), the unit
  shuts down after the finish shutdown procedure, and the engine operation indicator
  Gesnet Running light is off.
                                                                           1
                                                                           1
Emergency Stop Switch
 The emergency shutdown mode is allowed only in case of emergency.
 Once the "emergency stop" button is pressed (mushroom head), the LCD will have a
   fault code (1433 local emergency stop), and the "stop" light will be lit, at this time,
  the running machine group will stop directly without the cooling process.
 After pressing, the switch needs to return to original position, and then press the
  reset key to reset the system.
                                                                         1
                                                                         2
Genset Data Query-Genset Data
    Press the Home button to return to the main menu at any time.
    Press the C button to return to the previous menu. Press this button, the
    settings will not be saved.                                                 1
                                                                                3
Alternator Data Query—Alternator Data
    Press the Home button to return to the main menu at any time
    Press the C button to return to the previous menu. Press this button, the settings
    will not be saved
                                                                                  1
Mainly include generator voltage, current, frequency, power factor, load, etc.    4
Engine Data Query-Engine Data
    Press the Home button to return to the main menu at any time.
    Press the C button to return to the previous menu. Press this button, the
    settings will not be saved.
 Mainly include the engine speed (1500±5rpm), water temperature (<97℃), oil pressure
 (310~600KPa), battery voltage (24V~28V), etc.                           1
                                                                                5
Warning fault information query—Faults—Active -Warning
       Press the Home button to return to the main menu at any time.
       Press the C button to return to the previous menu. Press this button, the settings
                                                                                   1
                                                                                   22
                                                                                   6
       will not be saved.
Such as emergency stop, low battery voltage, high or low output voltage and so on.
Fault Reset
    If the fault is an alarm fault (Warning yellow indicator light is on), the unit can continue to
    start. When the fault is eliminated, press the "Reset" button, the indicator light will go out.
    If it is a shutdown fault (the Shutdown red indicator light is on), the unit is shut down and
    cannot be started. When the fault shutdown condition is eliminated, press the "Stop"
    button, and then press the reset button (Reset), the indicator light goes out. can be started
    again. Similar faults such as antifreeze temperature>103℃, low liquid level alarm, high
    speed>1650rpm lower than 1350rpm
                                                                               1
                                                                               7
Introduction to Diesel Generator Set
     Operation and Maintenance
                                  1
                                  8
Check before starting
   Check the engine oil level: verify whether the engine oil level meets the requirements;
   Check the cooling liquid level of the radiating water tank:
   ensure that the ventilation is unobstructed;
   Exhaust channel inspection: ensure that the exhaust is unblocked/no leakage/no bend/no
    looseness; no flammable products nearby
   Fuel pipeline inspection: the fuel level in the fuel tank is appropriate, the fuel valve is
    opened, the pipeline and valve has no leakage;
   check the battery terminal is in good contact, there is no impurities on the surface, the
    control panel shows that the voltage > 24V ; the positive and negative cable connections are
    correct
                                                                        1
                                                                        9
Starting and Running
  If you want to start in auto model,
 Press “AUTO” button, confirm the it’s light is on. when utility
 power is off, the generator will automatic start.
  If you want to start in manual model,
 Press the “STOP” button ,confirm the “AUTO” light is off. Press
 “MANUAL RUN” button, confirm the it’s light is on. Then press
 “START” button in 10 second, the generator will start.
                                                                   2
                                                                   0
Starting and Running
 If generator does not start after pressing the start button for 30 seconds, press the
  stop button, wait for 2 minutes, and then restart. If it fails to start three times, the
  unit will give alarm.
 Sufficient oil pressure must be reached within 15 seconds after the unit is started. If
  the panel displays an abnormal oil pressure alarm, shut down the unit immediately
  to avoid damage to the engine
 The no-load running time of the unit shall not exceed 15 minutes. Long-term idle
  speed will cause carbon deposits to form on the injector nozzles and piston rings,
  and may also lead to poor lubrication
 engine coolant temperature should between 74~91°C. Coolant temperature below
  60°C or above 100°C for long time running can damage the engine;
 Before shutting down the unit after running with load, the controller will control the
  engine to idle or run at no-load for 3 to 5 minutes before shutting down, and try to
  avoid emergency shutdown (the panel displays fault code 611)
 The frequency of the generator set should be 50Hz/1500RPM: The no-load line
  voltage should be 400±1%V, The no-load current reading should be zero, and the
  current of each phase should be roughly the same when loaded.
                                                                          2
                                                                          1
 Check list for every 3 months
 Static check
1. Check if the oil level is normal
2. Check the air filter intake resistance indicator, if it is red, it needs to be replaced.
3. Check the intake line for looseness and cracks.
4. Drain water and sediment from the diesel filter.
5. Check the ground or pipes for signs of engine oil leakage.
6. fuel tank level check
7. Fuel system leak check.
8. Check whether the connection cable of the battery terminal is tightened,
   whether it is firm, and the voltage is about 27V.
9. Check whether the automatic charger has an alarm.
10.Check coolant level
11.Visually inspect the belt and pulley for deviation and cracks.
12.Check coolant hoses and joints for leaks.
13.Cooling system leak check.
14.Check if there any cracks in the exhaust line
15.Exhaust pipe bolts check for firmness
16.Check that the air filter, piping and joints are securely connected.
                                                                             2
                                                                             2
Check list for every 3 months
 Running check
1. Check if the manual start/stop function normal
2. Whether there is abnormal sound and abnormal vibration
   in the operation of the unit
3. .Leak inspection of each system.
4. Smoke status and leak inspection, no black smoke, blue
   smoke, white smoke
5. Check the operation of the water pump and cooling fan
   for vibrations. Check if there is a sharp rise in coolant
   temperature
6. Check the three-phase voltage deviation ≯ 1%.
                                                 2
                                                 3
Check list for every 12 months
Static maintenance
    1. Change the engine oil.
    2. Change the engine oil filter.
    3. Replace fuel filter.
    4. Replace the oil-water separator
    5. Replace the cooling water filter.
    6. Check the air intake line for looseness and cracks.
    7. Check coolant level
    8. Engine oil leak check.
    9. Fuel tank level check and water drain.
    10. Fuel system leak check.
    11. Battery terminal tightness inspection.
    12. Automatic charger function check.
    13. Belt and pulley inspection.
    14. Check cooling water hoses and joints.            2
    15. Cooling system leak check.                       4
Check list for every 12 months
    16. Cooling Tank Fan Check
    17. Air filter, piping and joint inspection.
    18. Whether the exhaust pipe is leaking and fixed firmly.
    19. Exhaust line screw inspection.
    20. Check and clean the generator air inlet and outlet.
    21. Whether the connection of the output cable is firm.
    22. Generator room cleaning and inspection.
    23. External cleaning and inspection of generator.
                                                         2
                                                         5
Check list for every 12 months
 running check
1. Check if the manual start/stop function normal
2. Whether there is abnormal sound and abnormal vibration
   in the operation of the unit
3. .Leak inspection of each system.
4. Smoke status and leak inspection, no black smoke, blue
   smoke, white smoke
5. Check the operation of the water pump and cooling fan
   for vibrations. Check if there is a sharp rise in coolant
   temperature
6. Check the three-phase voltage deviation ≯ 1%.
                                                 2
                                                 6
Engine appearance/sound inspection
 Check after each startup;
 Run the engine for 8 to 10 minutes to check for abnormal noise.
 Check the engine for leakage of organic oil, coolant, fuel, intake and
  exhaust pipe.
                                                                 2
                                                                 29
                                                                 7
Check the oil level
 Wait at least 5 minutes after shutdown to check the oil level.
 After changing the oil or filter, wait for 15 minutes after the engine stop when the
  engine oil flows back to the oil pan ,and then check the engine oil level.
 When the oil level is below L or above H of the dipstick, it is not allowed to
  start the engine.
 Too high oil level will also cause engine overheating, high pressure / insufficient
  power, etc.
                                                                        2
                                                                        30
                                                                        8
Check the coolant level
                            Cylinder liner cooling system filling hole cap
                              LTA cooling system filling hole
                              cap
 The coolant level must be checked before every start up;
 When the engine temperature is below 50℃, slowly remove the radiator filler cap to release
   the system pressure
 Add coolant to the cooling system only needs to be added to the lower part of the filling
   neck of the radiator or expansion tank.
 The coolant can only be filled when the engine temperature is lower than 50°C; adding
  cold coolant to a hot engine will damage the engine castings;
                                                                             2
                                                                             9
Engine Oil Discharge before Replacement
 Note: The oil must be drained when the oil is still hot, because dirt is suspended in the oil
   at this time.
 Run the engine until the water temperature reaches 60°C. Stop the engine and drain the
  oil.
                                                                                  3
                                                                                  0
Oil Filter Replacement
 Clean around the oil filter seat and remove the filter.
 The O-ring may adhere to the filter seat and be sure to remove the O-ring.
 Add clean engine oil to the filter before installing the new filter. Apply a thin layer of oil to the
  surface of the gasket.
 Install the filter and after the gasket touches the surface of the filter head, tighten 1 / 2 to 3 /4 turns.
  Note that excessive tightening may deform the thread or damage the seal of the oil filter element.
                                                                                      3
                                                                                      1
External drive inspection
Check the belt are aligned without deviation and no abnormal noise, also no crack on it.
                                                                       3
                                                                       2
Check intake resistance (vacuum) / indicator (if matching)
 The more dust in the filter element of the air filter, the higher the red sign in the
  indicator window.
 After replacing or clean the filter, press the reset button to reset the indicator.
                                                                           3
                                                                           3
Check Exhaust System Leakage, Turbocharger
 Check leakage of installation gasket from turbocharger to exhaust
  manifold and replace the gasket if there is any.
 Check whether there is air leakage on the sealing surface of the turbine
  shell.
 Check the exhaust pipe bolts.
                                                                       3
                                                                       41
                                                                       4
Check the fuel line and joint seal
drain water and dust from the main fuel tank and fuel filter every three
 months
Check the sealing of pipelines, filter interfaces and joints for leakage.
                                                                             42
 Fuel Filter Replacement
 Remove the threaded joint sealing ring and wipe the joint surface with a clean lint-free
  cloth to remove dirt.
 Lubricate the O-ring seal with clean engine oil, and tighten the fuel filter
                                                                        3
                                                                        6
Check the Cooling System
Observe whether there is any leakage through the pump leakage observation hole.
Check the hose joints and hoses for leakage.
                                                                   3
                                                                   7
battery and cable terminal maintenance
Check whether the battery charger can charge battery normally every week;
Clean and fasten the battery terminal head.
Start the generator to check the battery status
  Check whether the terminals of the cable and the main junction box are corroded and
   firm
                                                                           3
                                                                           8
ALTERNATOR VENTILATION
 Clean the surface of the machine regularly to prevent dust and dirt from
  accumulating and adversely affecting heat dissipation.
 Ensure that the air inlet and outlet are not blocked during operation.
                                                                      3
                                                                      55
                                                                      9
Controller Check
 Panel indicators: press the Test button on the control panel once, and
  all lights should be lit for a few seconds.
 Check whether the buttons can operate normally and do not stick.
                                                                       4
                                                                       0
Troubleshooting of Diesel Generator Set
                                 4
                                 1
     Several troubleshooting methods for reference
1.Personal safety is the most important. In principle, maintenance with power off ,and do not
operate when the unit is running;
2.Routine inspection and maintenance are the best way to ensure the normal operation of
the unit;
3. When the unit fails and shuts down, the first thing is not to reset the fault;
4. Faults are often not as complicated as you think;
5. The elimination method is the most effective way to judge and locate the fault
                                                                      4
                                                                      2
Phenomenon: The unit has no response or only a "click"
Reason                                    Method:
1.Insufficient battery power;            1.Charge the battery or replace the battery;
2. Corrosion of battery terminal head;   2.Clean the battery terminal head;
3.The DC fuse in the control panel       3.Replace DC insurance;
melted down;                             4.Reset the emergency stop button and clear
4.The emergency stop button has          the alarm;
not been reset;                          5.repair the current fault, reset the fault
5.There is a fault alarm currently,      alarm;
but it has not been reset;
                                                            4
                                                            3
  Phenomenon: The starter motor can rotate, but the unit cannot start the engine
Reason:                                      Method:
1.The starting motor speed is too low;
2. No fuel supply;                           1.Refuel the tank
                                             2.Repair the leaks
3. Leakage of fuel line;
                                             3.Remove the oil pipe screw and check whether
4. The fuel filter or fuel pipe is blocked   there is fuel flowing out, if not, clean the
5. The air filter is blocked                 corresponding pipe.
                                             4.Replace air filter or fuel filter
                                                                    4
                                                                    4
    Phenomenon: black smoke from the exhaust of the unit
Reason:                             Method:
1.Overload;                         1. Reduce the load;
2.The air filter is blocked;        2. Clean or replace the air filter;
3. Poor fuel quality;               3. Change the fuel;
                                                              4
                                                              5
Phenomenon: white smoke from the exhaust of the unit
Reason                        Method
The diesel water             Check the oil-water separator (drain)
content exceeds the          and replace the diesel if necessary.
 standard;
                                                       4
                                                       6
      Phenomenon: blue smoke from the exhaust of the unit
Reason                                         Method
                                               1. Increase the load appropriately;
1.Long-term low-load operation;
                                               2. remove the excess oil;
2. Too much engine oil is added;
                                               3. Replace the engine oil
3.The engine oil grade or viscosity grade is
incorrect.
                                                                        4
                                                                        7
   Phenomenon: The water temperature of the unit is extremely high
Reason                                     Method
1.The unit is overloaded;                  1.Unload part of the load;
2. Coolant is not enough;                  2. Add the coolant
3.The fan belt is slipping or broken;      3. Re-adjust or replace the belt;
4.Too much scale in the water jacket and   4. Remove the scale;
water tank;                                5.Improve the heat dissipation conditions of
5.The engine room has poor heat            the engine room;
dissipation conditions and poor exhaust;
                                                                 4
                                                                 8
    Phenomenon: The oil pressure of the unit is too low
 Reason                                Method
1.The oil grade or viscosity
is incorrect;
                                    Replace the oil or oil filter;
2.Check whether the oil has been
used for more than 3 years ;
3. The oil filter is blocked;
4.There is water or diesel in the
oil.
                                                           4
                                                           9
Phenomenon: The engine oil pressure is too high
   Reason                            Method
   1.The oil grade or viscosity is   1.Replace the oil and oil filter;
   incorrect;                        2. Clean up the oil circuit;
   2. The oil circuit is blocked;
                                                              5
                                                              0
Safety Precautions
1. High temperature pressurized liquid: Contact with hot liquids can cause severe burns, do
not open the pressure cap while the engine is running, allow the engine to cool down before
removing the pressure cap, rotate the pressure cap slowly, and do not open it until the
pressure has been released.
2. Moving parts :Moving parts can cause serious personal injury and care should be taken
when working around moving parts.
3. Poisoning hazards: Waste oil, coolant, diesel, exhaust gas can all cause poisoning. Do not
ingest or breathe mist when checking or changing oil.
4. Power generation equipment: The generator and related equipment must be disconnected
from the power supply before overhauling. Do not operate the equipment after fatigue or
drinking or taking drugs.
5. Flammable liquids: Do not store fuel, detergent, oil, etc. in the generator room, which is
easy to cause fire and other accidents.
6. Automated machinery :Unexpected start-up of the generator set may result in serious
personal injury or death. If you need to repair and maintain the unit, it is necessary to press
the emergency stop button of the unit to ensure that the unit cannot be started.
Thank you
            5